DATOS INSTALACIN
CONTROLES Y CHEQUEOS
18. CONTROLES Y CHEQUEOS GAMA Mr. SLIM SOLO FRO - CONTROL PK-FL 157 ~ 167
19. CONTROLES Y CHEQUEOS GAMA Mr. SLIM SOLO FRO - CONTROL J 169 ~ 176
20. CONTROLES Y CHEQUEOS GAMA Mr. SLIM SOLO FRO - CONTROL AJ (Anterior ao 1997) 177 ~ 180
21. CONTROLES Y CHEQUEOS GAMA Mr. SLIM BOMBA DE CALOR - CONTROL K 181 ~ 209
22. CONTROLES Y CHEQUEOS GAMA Mr. SLIM BOMBA DE CALOR - CONTROL K (Anterior ao 1997) 211 ~ 220
23. CONTROLES Y CHEQUEOS GAMA Mr. SLIM BOMBA DE CALOR - CONTROL AG 221~ 227
25. CONTROLES Y CHEQUEOS GAMA INDUSTRIAL BOMBA DE CALOR (YD) 231~ 243
28. ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL Mr. SLIM 309 ~ 351
CERTIFICADOS AO 2000
EJEMPLO
MODELO
UNIDAD INTERIOR
AIR-CONDITIONER ALLOWABLE VOLTAGE: 10 % FAN MOTOR: 0,08 kW HEATER: 1.8/1.9/2.1 kW
(INDOOR UNIT) CONTROL RATING: 12 V REFRIGERANT: R-22 UNIT WEIGHT: 34 kg
MODEL PCH-3EKH1 JOINT OUTDOOR UNIT: PUH-3VK, 3YK
OPERATE COOLING HEATING (WITHOUT HEATER) HEATING (WITH HEATER)
UNIT RATING V 220 230 240 220 230 240 220 230 240
1 PHASE Hz 50 50 50 50 50 50 50 50 50
W 7700 7800 7900 8400 8500 8600 10200 10400 10700
CAPACITY kcal/h 6650 6750 6800 7250 7300 7400 8760 8960 9210
BTU/h 26400 26800 27000 28800 29000 29400 34800 35600 36500
TOTAL (IN+OUT)
INPUT kW 3.20 3.26 3.32 3.22 3.28 3.34 4.99 5.21 5.44
INPUT kW 0.12 0.13 0.14 0.12 0.13 0.14 1.89 2.06 2.24
CURRENT A 0.58 0.60 0.62 0.58 0.60 0.62 8.63 8.99 9.37
POWER FACTOR % 94 94 94 94 94 94 100 100 100
START CURRENT A 1.2 1.2 1.2 1.2 1.2 1.2 9.2 9.6 10.0
RATING CONDITIONSINDOOR
DB/WB C
27/19.5
OUTDOOR 35/24 [ JIS B8616]
JIS B8615 INDOOR
OUTDOOR
21/-
7/6 [JIS B8616]
JIS B8615
MADE IN JAPAN
DWG.NO.BC79F273H02 SERIAL No. 32000477
NUMERO
DE SERIE
1
CONSEJOS DE INSTALACION
1. NO EMPLEE SIFONES 5. FILTROS SECADORES
La utilizacin de sifones en nuestras unidades, No emplee filtros secadores en el circuito
slo conduce a una prdida de rendimiento del frigorfico de las Unidades de Aire
sistema. Algunas unidades MITSUBISHI ELEC- Acondicionado MITSUBISHI ELECTRIC.
TRIC pueden alcanzar distancias verticales de
instalacin de hasta 50 mts de altura. En este
6. VISOR DE LIQUIDO
manual viene descrita, para cada unidad, la
relacin de trazado de tubera frigorfica. No realize nunca la carga frigorfica observando
el visor de lquido.
2. MAGNETOTERMICOS CURVA M
Es necesario el uso de magnetotrmicos de 7. NO RECALCULE LINEAS FRIGORIFICAS
curva retardada, ya que estos, son capaces
de absorber las puntas de consumo produci- No recalcule lneas frigorficas y respete las
das en el arranque de las unidades. distancias de instalacin de tuberas. Las uni-
dades MITSUBISHI ELECTRIC preexpansio-
3. AISLE LOS DOS TUBOS POR SEPARADO nan en la unidad exterior.
Es muy importante en las unidades MITSU-
BISHI ELECTRIC, un buen aislamiento de las 8. CONTROL DE CONDENSACION
tuberas frigorficas, debido a que estas unida-
En caso de ser necesario acoplar un control
des expansionan en la unidad exterior.
de condensacin, se recomienda el uso de
Un mal aislamiento producira, condensacio- regulacin a travs de temperatura, ya que
nes, goteos y una prdida de rendimiento del las unidades MITSUBISHI ELECTRIC preex-
sistema. pansionan en la condensadora.
4. NO PULSE EL CONTACTOR
9. SELECTORES DE TENSION
Las unidades MITSUBISHI ELECTRIC TRIFA-
SICAS, que utilizan compresores rotativos, Las unidades Mr. Slim y Gama Industrial,
poseen un control de sentido de rotacin del incorporan un selector o microrruptor que
compresor. Si al intentar arrancar la unidad, permite ajustar la tensin de alimentacin al
sta, no se pone en marcha, cambie dos de transformador de los circuitos electrnicos
las fases para que el compresor gire en el sen- (tanto interiores como exteriores), y a los
tido correcto. motores del ventilador.
La manipulacin indebida del contactor del Escoja el valor ms cercano a la tensin de
compresor y fases de alimentacin invertidas, red de toma de corriente, o entre los mrge-
comporta en todos los casos el deterioro ins- nes que indiquen las etiquetas en los conec-
tantneo del compresor. tores.
COMPRESOR ROTATIVO
2
10. HAGA UN VACIO EFICAZ 13. TUBOS DE REFRIGERANTE
Elimine cualquier resto de humedad del cir- Pares de apriete especificados (utilice una
cuito frigorfico, con una bomba adecuada, y llave con limitador del par de apriete)
a ser posible por ambas lneas.
Especificaciones del par
11. PRUEBA DE ESTANQUEIDAD
Dimetro exterior del Par de apriete
Realice siempre la prueba de estanqueidad tubo de cobre (mm) (kg/cm)
de las lneas frigorficas con nitrgeno seco.
6,35 - 1/4 140 - 180
MITSUBISHI ELECTRIC no es ajeno a la pro-
blemtica existente con los refrigerantes, y 9,52 - 3/8 350 - 420
recordamos que se han de evitar fugas inne-
cesarias a la atmsfera; esto es posible com- 12,7 - 1/2 500 - 575
probando que el circuito no fugue por poros 15,88 - 5/8 750 - 800
o juntas.
19,05 - 3/4 1000 - 1400
12. UNIDADES INVERTER GAMA DOMESTICA
Si no dispone de una llave de apriete,
Las unidades de Sistema Inverter Gama
puede utilizar este mtodo.
Domstica, requieren de un mnimo de uni-
Deje de apretar la tuerca con la llave cuando
dades interiores conectadas frigorfica y elc-
el par de apriete aumente de repente.
tricamente.
Entonces gire la llave el ngulo especifica-
MXZ-18RV (Inverter 2 x 1) 2 unidades.
do en la tabla que sigue.
MXZ-32RV (Inverter 4 x 1) 3 unidades.
Angulo de apriete adicional aproximado:
3
14. PRECAUCIONES PARA APARATOS QUE UTILIZAN REFRIGERANTE R407C/R410A
No utilice las tuberas actuales Utilice bombas de vaco con vlvula de control de
flujo reversible.
El refrigerante y el aceite lubricante existentes actual-
El aceite de la bomba de vaco puede pasar al circuito
mente contienen una gran cantidad de cloro lo que
refrigerante y provocar el deterioro del refrigerante.
provocara el deterioro del lubricante utilizado en la
nueva unidad.
Si suciedad o agua entra en el circuito de refrigerante el Sea especialmente cuidadoso con las herramientas.
aceite se deteriorar.
Si suciedad o agua entrase en el circuito el refrigerante
se deteriorara.
4
DATOS DE INSTALACION GAMA DOMESTICA
DATOS DE INSTALACIN
5
DATOS DE INSTALACION GAMA DOMESTICA
GAMA DOMESTICA
* Las secciones de cable y protecciones han sido calculadas para distancias inferiores a 30 metros. Para distancia
superior se deben recalcular.
* Todas las lneas deben disponer de protecciones de diferencial y magnetotrmico adecuados.
POTENCIA MANIOBRA
6
DATOS DE INSTALACION GAMA DOMESTICA
IMPORTANTE SERIE RV
INTERRUPTORES DE SELECCIN SOLO FRO O BOMBA DE CALOR Y FUNCIN AUTO RESTART
DATOS DE INSTALACIN
1. SELECCIONE SOLO FRO O BOMBA DE CALOR SW2- Selecciona la funcin AUTO RESTART ON / OFF.
Las unidades interiores MSC 07/09/12 RV son las SW2- Selecciona SOLO FRO / BOMBA DE CALOR.
mismas tanto para las unidades exteriores SOLO FRO SELECCIONADO DE FBRICA
como para las unidades exteriores BOMBA DE CALOR. y
SW2-
SW2-1: FUNCIN AUTOFUNCTION
RESTARTOFFOFF
SW2-
AUTO RESTART
SW2-2: BOMBA
MUH typeDE CALOR MUH/MXZ }
COMO SELECCIONAR MU & MUX / MUH & MXZ
C111
C11
! Quitar alimentacin elctrica a las unidades.
@ Seleccionar a travs del microrruptor SW2 ubicado CN201
en la placa electrnica de la unidad interior, tal y
CN211
como aparece en los dibujos. LA UNIDAD INTERIOR TAB12
EST CONFIGURADA DE FBRICA EN BOMBA.
CN202
CN111
SW2
CN121
IC101
SOLO FRO BOMBA DE CALOR
CN112
MU & MUX MUH & MXZ
1 2
Mover hacia arriba Mover hacia abajo 1 2
IC152
SW1 SW2
CN151
1 2
SW2
1 2 1 2
1 2 1 2 PLACA ELECTRNICA UNIDAD INTERIOR
SW2 SW2
NOTA:Una mala conexin puede comportar un mal funcionamiento
o el deterioro de los componentes.
Es necesaria la conexin a tierra. El no hacerlo puede
ocasionar un shock elctrico.
2. FUNCIN AUTO RESTART
Cuando la unidad interior es controlada con el control remoto, el modo de operacin, la temperatura seleccionada y la
velocidad del ventilador son memorizadas por la placa electrnica de la unidad interior. La funcin AUTO RESTART arranca
AUTOMATICAMENTE la unidad en las mismas condiciones memorizadas despus de un fallo de suministro elctrico. Sin
embargo, si la unidad se encuentra funcionando en I FEEL antes del fallo de suministro elctrico la operacin no es
memorizada. En funcionamiento I FEEL la operacin de fro / calor es decidida automticamente solo en el primer
arranque mediante la temperatura ambiente interior detectada. De fbrica se encuentra desactivado.
1 2 1 2
1 2 1 2
SW2 SW2
OPERACIN
! Si el suministro elctrico (220/240V AC) ha sido cortado mientras la unidad funcionaba, la unidad arranca de nuevo
despus de restablecerse el suministro elctrico, segn la memorizacin. La unidad tardar 3 minutos en restablecer el
funcionamiento normal.
NOTA
Las selecciones son memorizadas 10 segundos despus de operar el control remoto.
Si el suministro elctrico es cortado mientras la funcin AUTO START/STOP est activada sta temporizacin ser cancelada
Si la unidad est parada antes que ocurra el corte de suministro elctrico, la unidad no arrancar automticamente.En este
caso solo arrancar cuando sea pulsado el botn ON sobre el control remoto.
Cuando esta operacin sea seleccionada en varias unidades, deberan de tomarse medidas especiales de secuenciacin
de arranque para evitar caidas de tensin o el salto de la proteccin (magnetotrmico).
7
DATOS DE INSTALACION GAMA DOMESTICA
NOTA: Diferencial
Configurar placa electrnica
Ver pg. anterior.
Haga la configuracin sin
alimentacin elctrica
I.C.P. I.C.P.
3 N 1 2
B A
N
MITSUBISHI
ELECTRIC
L
C
2
1
U. EXTERIOR
I.C.P. I.C.P.
3 N 1 2
B A
N
MITSUBISHI
ELECTRIC
L
C
N
3
U. EXTERIOR
8
DATOS DE INSTALACION GAMA DOMESTICA
SOLO FRIO
DATOS DE INSTALACIN
Para distancias frigorficas superiores a 7 m aadir 15 gr/m adicional de R-22
* Este modelo tiene 3 cables de interconexin + tierra (Ver esquema Bomba de Calor)
BOMBA DE CALOR
Para distancias frigorficas superiores a 7 m aadir 50 gr/m adicional de R-22 y para la MSH-24 aadir 65 gr/m.
9
DATOS DE INSTALACION GAMA DOMESTICA
SOLO FRIO
DATOS DE INSTALACIN
* Este modelo tiene 3 cables de interconexin + tierra. (ver esquema Bomba de Calor)
BOMBA DE CALOR
Para distancia frigorficas superiores a 7 m aadir 50 gr/m de R-22 y para la MCFH-24 aadir 65 gr/m de R-22
10
DATOS DE INSTALACION GAMA DOMESTICA
SOLO FRIO
DATOS DE INSTALACIN
(CABLE-MANGUERA
SUMINISTRADO)
Para distancias frigorficas superiores a 7 m aadir 15 gr/m adicional de R-22
BOMBA DE CALOR
(CABLE-MANGUERA
SUMINISTRADO)
SEH 1.6 - SEH 2 - Para distancias frigorficas superiores a 7 m aadir 50 gr/m adicional de R-22
SEH 2.5 - Para distancias frigorficas superiores a 7 m aadir 65 gr/m adicional de R-22
11
DATOS DE INSTALACION GAMA DOMESTICA
SOLO FRIO
DATOS DE INSTALACIN
NOTA:
Configurar placa electrnica
Ver pg. 7
Haga la configuracin sin
alimentacin elctrica
SOLO FRIO
NOTA:
Configurar placa electrnica
Ver pg. 7
Haga la configuracin sin
alimentacin elctrica
12
DATOS DE INSTALACION GAMA DOMESTICA
SOLO FRIO
NOTA:
DATOS DE INSTALACIN
Configurar placa electrnica
Ver pg. 7
Haga la configuracin sin
alimentacin elctrica
Permite conectar
1 2 unidades
interiores por compresor Para distancias frigorficas superiores a 7 m aadir 15 gr/m adicional de R-22
* Cuando es usado un solo comp. con una sola Unidad Interior, la distancia total vertical+horizontal se amplia a 20 m, siendo la mxima
vertical de 5 m.
N de unidades interiores: 1 ~ 2
Longitud total de tubera: mx. 30 mts. Este sistema requiere un mnimo de 2 unidades interiores conectadas
para dos unidades interiores frigorfica y elctricamente SIEMPRE (no es necesario que funcionen de
Conexin longitud de tubera: mx. 20 mts. forma simultnea).
para una unidad interior
Diferencia de altura (int. ~ ext.): mx. 7 mts.
PRECARGA DE GAS: 1,32 kg
UNIDAD PRECARGADA
N de curvas (mx por Unidad): 15 curvas NO AADA CARGA ADICIONAL
N de curvas (mx Total Unidades): 30 curvas
INTENSIDAD
MODELO
SECCION SECCION SECCION NOMINAL (A)
PUNTA DE
ARRANQUE
I.C.P.
(A)
*
TUB. FRIGOR. MSC 07/09 *
TUB. FRIGOR. MSC 12
A mm2 B mm2 C mm2 LIQUIDO GAS LIQUIDO GAS
FRIO CALOR (A) CURVA C mm (in) mm (in) mm (in) mm (in)
MXZ-18 2x4+T 2x1,5+T 2x1,5 10,5 9,4 10,5 15 5 6,35 (1/4) 9,52 (3/8) 6,35 (1/4) 12,7 (1/2)
13
DATOS DE INSTALACION GAMA DOMESTICA
BOMBA DE CALOR
DATOS DE INSTALACIN
Este sistema requiere un mnimo de 3 unidades interiores conectadas frigorfica y elctricamente SIEMPRE (no es
necesario que funcionen de forma simultnea).
1) El dimetro del tubo frigorfico entre unidades ha de ser el mismo que el de la unidad interior. Las reducciones, si
son necesarias, se harn en la entrada de la unidad exterior.
2) Las unidades interiores de mayor potencia (12 - 13 - 18 - 1,6 ) se deben conectar en las posiciones A y B (conexin
1/2 lnea de gas).
3) En caso de ser de potencias iguales, las de mayor distancia se conectarn en A y B.
CONEXION FRIGORIFICA
MODELOS LIQUIDO GAS
MSC-07 6,35 mm (1/4) 9,52 mm (3/8)
MSC-09 6,35 mm (1/4) 9,52 mm (3/8)
MSC-12 6,35 mm (1/4) 12,7 mm (1/2)
MSH-18 6,35 mm (1/4) 15,88 mm (5/8)
MCFH-13 6,35 mm (1/4) 12,7 mm (1/2)
MCFH-18 6,35 mm (1/4) 15,88 mm (5/8)
SEH-1,6AR 6,35 mm (1/4) 12,7 mm (1/2)
INTENSIDAD PUNTA DE
SECCION SECCION SECCION NOMINAL (A) ARRANQUE I.C.P.
MODELO (A) (A)
A mm2 B mm2 C mm2 ESCALONADA CURVA C
FRIO CALOR HASTA
MXZ-32 2x6+T 2x1,5 2x1,5+T 5,05~16,31 6,06~14,04 16,31/14,04 mx. 25
14
DATOS DE INSTALACION GAMA COMERCIAL
DATOS DE INSTALACIN
15
DATOS DE INSTALACION GAMA COMERCIAL
Y PRECARGAS DE GAS
{
* INTERIOR L Fase.
220V N Neutro.
E Tierra. Todas las unidades con L y N son monofsicas 220V.
* ENTRE UNIDADES: Maniobra (no conectar nunca alimentacin elctrica a 220V o 380V).
{
1
12V DC 2 1-2 Slo Fro.
3 1-2-3 Bomba de Calor.
* UNIDADES EXTERIORES
{
L1
Trifsica
380V
L2
L3
Monofsica
220-I { L
Las secciones de cableado de potencia y protecciones han sido calculadas para distancias inferiores a 30 m.
Para distancias superiores se deben recalcular.
16
DATOS DE INSTALACION GAMA COMERCIAL
DATOS DE INSTALACIN
MODELO A (mm) B (mm)
PL-2/2,5/3FJ 420 870
PL-4/5/6FJ 420 1.397
PLH-3GK 530 785
PLH-2/3FK(H) 420 870
PLH-4/5/6FK(H) 420 1.390
PLH-4/5/6GK 530 1.305
PL-1,6/2/2,5KJ 507 640
PL-3GJ 530 785
PL-4/5/6GJ 530 1.305
PLH-1,6/2/2,5KK 507 640
17
DATOS DE INSTALACION GAMA COMERCIAL
PL - SPLIT CASETTE
PS - SPLIT VERTICAL SUELO
PED - SPLIT CONDUCTOS
MODELOS
PK
* El control remoto se suministra junto con el cable-manguera de 12 hilos, para todas las uni-
dades excepto para los modelos PS, que se incorporan en el propio mueble de la unidad
interior y los modelos PK, que son inhalmbricos.
DISTANCIAS
INTENSIDAD I.C.P. TUB. FRIGOR.
SECCION PUNTA DE FRIGORIFICAS NUMERO PRECARGA
MODELO SECCION SECCION NOMINAL (A) (A) CARGA
ARRANQUE TOTAL DE DE GAS
CV A mm2 B mm2 C mm2 (A)
CURVA MAXIMA VERTICAL + CURVAS HASTA
ADICIONAL
FRIO CALOR C LIQUIDO GAS VERTICAL HORIZONTAL
1,6 2x2,5+T 2x1,5+T 2x1,5 7,6 30 10 3/8 5/8 15 20 12 20
Vea pg. 22
18
DATOS DE INSTALACION GAMA COMERCIAL
DATOS DE INSTALACIN
PL - SPLIT CASETTE
PS - SPLIT VERTICAL SUELO
PED - SPLIT CONDUCTOS
MODELOS
PK
* El control remoto se suministra junto con el cable-manguera de 12 hilos, para todas las
unidades excepto para los modelos PS, que se incorporan en el propio mueble de la
unidad interior y los modelos PK, que son inhalmbricos.
DISTANCIAS
INTENSIDAD I.C.P. TUB. FRIGOR. FRIGORIFICAS
SECCION SECCION SECCION NOMINAL (A) PUNTA DE NUMERO PRECARGA CARGA
MODELO (A)
ARRANQUE TOTAL DE DE GAS ADICIONAL
CV A mm2 B mm2 C mm2 (A)
CURVA MAXIMA
C LIQUIDO GAS VERTICAL + CURVAS HASTA
FRIO CALOR VERTICAL
HORIZONTAL
3 3x2,5+N+T 2x1,5+T 2x1,5 6 36 10 3/8 5/8 20 30 12 20
Vea pg. 22
19
DATOS DE INSTALACION GAMA COMERCIAL
(ver tabla) 5A
DISTANCIAS
INTENSIDAD I.C.P. TUB. FRIGOR. FRIGORIFICAS
SECCION SECCION SECCION NOMINAL (A) PUNTA DE NUMERO PRECARGA CARGA
MODELO (A)
ARRANQUE TOTAL DE DE GAS ADICIONAL
CV A mm2 B mm2 C mm2 CURVA MAXIMA
(A)
C LIQUIDO GAS VERTICAL + CURVAS HASTA gr/m
FRIO CALOR VERTICAL
HORIZONTAL
7,16
1,6 2x2,5+T 2x1,5+T 3x1,5 7,2 33 10 3/8 5/8 40 40 9 30
[6,63]
11,11
2 2x4+T 2x1,5+T 3x1,5 11,3 45 15 3/8 5/8 40 40 12 30
Vea pg. 22
[6,63]
11,23
2,5 2x4+T 2x1,5+T 3x1,5 12,72 52 15 3/8 5/8 50 50 12 30
[9,5]
15,04
3 2x4+T 2x1,5+T 3x1,5 14,96 58 20 3/8 5/8 50 50 15 30
[9,8]
16,3
4 2x6+T 2x1,5+T 3x1,5 16,3 [12,3] 79 25 3/8 3/4 50 50 15 30
20
DATOS DE INSTALACION GAMA COMERCIAL
DATOS DE INSTALACIN
PLH - SPLIT CASETTE
PSH - SPLIT VERTICAL SUELO
PEHD - SPLIT CONDUCTOS
5A
DISTANCIAS
INTENSIDAD I.C.P. TUB. FRIGOR. FRIGORIFICAS
SECCION SECCION SECCION NOMINAL (A) PUNTA DE NUMERO PRECARGA CARGA
MODELO (A)
ARRANQUE TOTAL DE DE GAS ADICIONAL
CV A mm2 B mm2 C mm2 CURVA MAXIMA gr/m
(A)
C LIQUIDO GAS VERTICAL + CURVAS HASTA
FRIO CALOR VERTICAL
HORIZONTAL
5,61
3 3x2,5+N+T 2x1,5+T 3x1,5 5,58 37 10 3/8 5/8 50 50 15 30
[9,8]
Vea pg. 22
6,01
4 3x2,5+N+T 2x1,5+T 3x1,5 6,07 40 10 3/8 3/4 50 50 15 30
[12,3]
7,34
5 3x2,5+N+T 2x1,5+T 3x1,5 6,99 53 10 3/8 3/4 50 50 15 30
[13,8]
7,83
6 3x4+N+T 2x1,5+T 3x1,5 8,03 58 15 3/8 3/4 50 50 15 30
[13,9]
21
DATOS DE INSTALACION GAMA COMERCIAL
22
DATOS DE INSTALACION GAMA INDUSTRIAL
DATOS DE INSTALACIN
23
DATOS DE INSTALACION GAMA INDUSTRIAL
Y PRECARGAS DE GAS
CONEXIONADO UNIDADES
* UNIDADES INTERIORES
L1 R
L2 S
L3 T
PEH-YD PE, PF
* ENTRE UNIDADES: Maniobra (no conecte nunca alimentacin elctrica a 220V en los modelos PEH).
}
1 1
2 2
12V DC 220 V
3 3
PEH-YD 4
PE, PF
* UNIDADES EXTERIORES
L1 R
L2 S
Trifsica
380V L3 T
N N
Las secciones de cableado de potencia y protecciones han sido calculadas para distancias inferiores a 30 m.
Para distancias superiores se deben recalcular.
24
DATOS DE INSTALACION GAMA INDUSTRIAL
DATOS DE INSTALACIN
DE FABRICA CARGA ADICIONAL
(KG) R-22 (KG) R-22
PEH-8YD 6,5 0,05 x L x 0,5
PEH-10YD 7,0 0,08 x L x 0,5
BOMBA DE CALOR
25
DATOS DE INSTALACION GAMA INDUSTRIAL
SOLO FRIO
DATOS DE INSTALACIN
Ver pg.31/32
CARGA DE GAS R-22: ver pgina 30 para su conexin
BOMBA DE CALOR
26
DATOS DE INSTALACION GAMA INDUSTRIAL
SOLO FRIO
DATOS DE INSTALACIN
CARGA DE GAS R-22: ver pgina 30
Ver pg. 31/32
MX. VERTICAL A: Unidad interior por encima de la exterior para su conexin
MX. VERTICAL B: Unidad exterior por encima de la interior
BOMBA DE CALOR
27
DATOS DE INSTALACION GAMA INDUSTRIAL
SOLO FRIO
DATOS DE INSTALACIN
BOMBA DE CALOR
28
DATOS DE INSTALACION GAMA INDUSTRIAL
BOMBA DE CALOR
DATOS DE INSTALACIN
Ver pg. 31/32
para su conexin
INTENSIDAD
SECCION PUNTA DE NOMINAL (A) I.C.P. CAUDAL PRESIN
SECCION
MODELO ARRANQUE (A) m3 / h ESTTICA dA Kg
A mm2 B mm2 (A) CURVA C mmcda
FRIO CALOR
PRH-8YA 3x6+N+T 1,5 87 20,6 20,6 32 5.040 10 75 393
PRH-10YA 3x10+N+T 1,5 100 25,7 25,7 40 6.000 10 75 413
PRH-15YA 3x25+N+T 1,5 115 37,9 37,9 50 10.080 20 79 698
PRH-20YA 3x25+N+T 1,5 135 50,9 50,9 63 11.400 20 79 729
29
DATOS DE INSTALACION GAMA INDUSTRIAL
Altura A (m) 20 20 20 20 20
Altura B (m) 30 30 30 30 30
n de curvas 15 15 15 15 15
Longitud total (m) 50 50 50 50 50
Lquido (mm) 15,88 - 5/8 15,88 - 5/8 15,88 - 5/8 2x15,88 - 5/8 2x15,88 - 5/8
Tuberias Gas (mm) 25,4 - 1 25,4 - 1 28,6 - 11/8 2x25,4 - 2x1 2x28,6 - 2x11/8
30
DATOS DE INSTALACION GAMA INDUSTRIAL
DATOS DE INSTALACIN
GRIS TB4 1 GRIS TB3 1
24VAC(L)
F
24VAC(L)
(3.15A) (3.15A)
Tr Tr
24VAC(N)
COMP1
24VAC(N)
FAN HI
COMP1
COMP2
FAN HI
AC AC
220~ AC24V 220~ AC24V
240V TB4 2 3 240V TB4 2 3 4
GRIS GRIS
4 5
24VAC(L)
F
(3.15A) (3.15A)
Tr Tr
24VAC(N)
24VAC(N)
COMP1
COMP1
COMP2
FAN HI
FAN HI
4WV
4WV
AC AC
220~ AC24V 220~ AC24V
240V TB4 2 3 4 240V TB3 2 3 4 5
GRIS GRIS
5 6
1 TB4 1 TB5
24VAC(L)
24VAC(L)
F F
(3.15A) (3.15A)
COMP1
24VAC(N)
COMP1
COMP2
24VAC(N)
Tr
FAN HI
Tr
FAN HI
Error
Error
AC AC
220~ AC24V 2 4 5 6 7 220~ AC24V TB5 2 3 5 6 7 8 9
240V 240V
FZO FZO
30 30
30
8 CZ 10 CZ1-1 CZ2-1
1 TB4 1 TB5
COMP1 24VAC(L)
24VAC(L)
F F
(3.15A) (3.15A)
24VAC(N)
COMP1
COMP2
24VAC(N)
FAN HI
Tr
FAN HI
Tr
4WV
Error
4WV
Error
30
8 CZ 30 30
10 CZ1-1 CZ2-1
ON/OFF
31
DATOS DE INSTALACION GAMA INDUSTRIAL
MICRORRUPTOR
SELECTOR: (Ver tabla superior)
SONDA EN
CONTROL
O
SONDA
REMOTA
CONEXIN DE
SONDA DE
TEMPERATURA
DE RETORNO
DE AIRE
REMOTA
(
*)
(
* ) LA UTILIZACIN DE ESTA CONEXIN A UNA SONDA REMOTA PERMITE DETECTAR LA
TEMPERATURA EN OTRO LUGAR QUE NO SEA EL PROPIO CONTROL REMOTO.
32
DATOS DE INSTALACIN GAMA COMERCIAL
DATOS DE INSTALACIN
COMPO MULTI
FRO/ BOMBA DE CALOR
33
DATOS DE INSTALACIN GAMA COMERCIAL
INSTALACIN ELCTRICA
COMPO MULTI
SOLO FRIO
DATOS DE INSTALACIN
UNIDAD EXTERIOR
MONOFSICA
(2x1) I.C.P.
ROJO
2 hilos
(12 m de fbrica)
BLANCO
Control
remoto
INSTALACIN ELCTRICA
COMPO MULTI
SOLO FRIO
UNIDAD EXTERIOR
TRIFSICA
I.C.P.
(2x1)
ROJO
2 hilos
(12 m de fbrica)
BLANCO
Control
remoto
34
DATOS DE INSTALACIN GAMA COMERCIAL
DATOS DE INSTALACIN
SW1 El Microrruptor SW1 est ubicado en la placa electrnica de la Unidad Interior.
ON 2
Unidad (1) Slo conmutar los microrruptores N 2 y N 3 tal como se indica en cada caso
OFF 3
para cada unidad.
ON 2 3
Unidad (2) Los dems microrruptores no tocar.
OFF
IMPORTANTE:
Siempre funcionarn las dos unidades interiores a la vez con un solo control remoto. Bajo ningn
concepto se instalarn dos controles remotos.
Las unidades interiores (Slo Fro) deben ser del mismo modelo y por lo tanto de la misma
capacidad frigorfica.
INSTALACIN FRIGORFICA
COMPO MULTI
SOLO FRIO
UNIDAD INTERIOR
UNIDAD INTERIOR h
B C
H
DISTRIBUIDOR
UNIDAD A
EXTERIOR
35
DATOS DE INSTALACIN GAMA COMERCIAL / INDUSTRIAL
INSTALACIN ELCTRICA
COMPO MULTI
BOMBA DE CALOR
DATOS DE INSTALACIN
UNIDAD EXTERIOR
MONOFSICA
(2x1) Aplicar I.C.P. en funcin de las resistencias
elctricas de apoyo seleccionadas
2 cables
CONTROL
REMOTO
INSTALACIN ELCTRICA
COMPO MULTI
BOMBA DE CALOR
UNIDAD EXTERIOR
TRIFSICA
Aplicar I.C.P. en funcin de las resistencias
(2x1) elctricas de apoyo seleccionadas 2 cables
(3x1)
2 cables
CONTROL
REMOTO
MODELO kW (A) Consumo elctrico recomendado de las resistencias elctricas de apoyo para 1 sola unidad interior.
1,6 1,4 6,36
2 1,4 6,36
2,5 2,1 9,54 NOTA: Aumente la seccin de cableado SECCIN B cuando la unidad interior
3 2,1 9,80 incorpore resistencias elctricas de apoyo o en caso de que ustedes deseen
4 2,6 11,81 acoplarlas fabricando una batera de resistencias (del mercado) en las
5 3,0 13,63 unidades de conductos. Tenga presente que la seccin de cable B est
6 3,0 13,63 calculada sin tener presente, este consumo adicional.
36
DATOS DE INSTALACIN GAMA COMERCIAL / INDUSTRIAL
DATOS DE INSTALACIN
IMPORTANTE: Siempre funcionarn las dos ( o tres ) (2x1)
unidades interiores a la vez con un solo control
remoto. Bajo ningn concepto instale dos o tres (3x1)
controles.
INSTALACIN FRIGORFICA
MULTIPLES
BOMBA DE CALOR (2x1)
(3x1)
C h
B D
H
DISTRIBUIDOR
UNIDAD A
EXTERIOR
37
DATOS DE INSTALACIN GAMA COMERCIAL / INDUSTRIAL
MULTIPLES
BOMBA DE CALOR
DATOS DE INSTALACIN
Solo para 3 / 4 / 5 / 6 CV
LONGITUD DE TUBERIA DIFERENCIA DE ALTURA
DIFERENCIA N DE
LONGITUD MXIMA LONGITUD MXIMA EXTERIOR ~ INTERIOR INTERIOR ~ INTERIOR
ENTRE UNIDADES CURVAS
A + B : Mx. 40 m A+B+C: B-C: MAXIMO 15
DOBLE H: 40 m h: 1 m
A + C : Mx. 40 m Mximo 50 m Mximo 8 m (NOTA: 1)
A + B : Mx. 40 m A+B+C+D: B - C : Mximo 8 m
MAXIMO 15
TRIPLE A + C : Mx. 40 m Mximo 50 m B - D : Mximo 8 m H: 40 m h: 1 m
(NOTA: 1)
A + D : Mx. 40 m C - D : Mximo 8 m
Solo para 8 CV / 10 CV
LONGITUD DE TUBERIA DIFERENCIA DE ALTURA
DIFERENCIA N DE
LONGITUD MXIMA LONGITUD MXIMA EXTERIOR ~ INTERIOR INTERIOR ~ INTERIOR
ENTRE INTERIORES CURVAS
A + B : Mx. 50 m A+B+C: B-C: MAXIMO 15
DOBLE H: Mximo 40 m h : Mximo 1 m
A + C : Mx. 50 m Mximo 70 m Mximo 8 m (NOTA: 1)
A + B : Mx. 50 m A+B+C+D: B - C : Mximo 8 m
MAXIMO 15
TRIPLE A + C : Mx. 50 m Mximo 70 m B - D : Mximo 8 m H: Mximo 40 m h : Mximo 1 m
(NOTA: 1)
A + D : Mx. 50 m C - D : Mximo 8 m
Distribuidores frigorficos
DOBLE TRIPLE
RATIO 50:50 33:33:33 25:25:50 20:40:40
DISTRIBUIDOR SDD-50W SDT-111 SDT-112 SDT-122
38
DATOS DE INSTALACIN GAMA INDUSTRIAL
DATOS DE INSTALACIN
DATOS DE INSTALACIN-MULTIS
MULTI MYA
(ELECTROMECNICAS)
39
DATOS DE INSTALACIN GAMA INDUSTRIAL
MULTIPLES ELECTROMECNICAS
Serie PE / PEH - MYA
DATOS DE INSTALACIN
COMBINACIONES
PEH-8MYA x 2 PUH-15MYC x 1
PEH-10MYA x 2 PUH-20MYC x 1
PEH-15MYA x 1 PUH-8MYC x 2
PEH-20MYA x 1 PUH-10MYC x 2
PE-8MYA x 2 PU-15MYC x 1
PE-10MYA x 2 PU-20MYC x 1
PE-15MYA x 1 PU-8MYC x 2
PE-20MYA x 1 PU-10MYC x 2
CIRCUITO FRIGORFICO
( PE - 8 x 2 ) + PU - 15
( PE - 10 x 2 ) + PU - 20
( PEH - 8 x 2 ) + PUH - 15
( PEH - 10 x 2 ) + PUH - 20
PE - 15 + ( PU-8 x 2 )
PE - 20 + ( PU-10 x 2 )
PEH - 15 + ( PUH-8 x 2 )
PEH - 20 + ( PUH-10 x 2 )
40
DATOS DE INSTALACIN GAMA INDUSTRIAL
BOMBA DE CALOR
CIRCUITO ELCTRICO
DATOS DE INSTALACIN
Ver pg.31/32
para su conexin Ver pg. 31/32
13 para su conexin
14 13
15 14
15
11 11
12 12
13 13
14 14
13
14
15 Ver pg.31/32
para su conexin
SOLO FRO
41
DATOS DE INSTALACIN GAMA COMERCIAL
DATOS DE INSTALACIN
CONTROL DE GRUPO
Mr. SLIM - BOMBA DE CALOR
43
DATOS DE INSTALACIN GAMA COMERCIAL
Para controlar un grupo de unidades a travs de un solo mando a distancia siga las instrucciones siguientes en cada uni-
DATOS DE INSTALACIN
44
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
45
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
PLFY-P3240506380100125 VKM
PUHY-200 100 a 260 1 a 13 PLFY-P20253240506380100125 VLMD
PEFY-P20253240506380100125 VM
PCFY-P4063100125 VGM
PKFY-P2025 VAM
PKFY-P324050 VGM
PUHY-250 125 a 325 1 a 16
PFFY-P2532405063 VLEM
PFFY-P2532405063 VLRM
Nota:
1. La capacidad total de modelos de unidades interiores conectables representa el total de la suma de las cifras expresadas
en el nombre del modelo de interior.
2. Las combinaciones en las que la capacidad total de las unidades interiores conectadas excede la capacidad nominal de la
unidad exterior reducir la capacidad de cada unidad interior por debajo de las capacidades indicadas durante un funciona-
miento simultneo. Por ello, si las circunstancias lo permiten, combine unidades interiores dentro de la capacidad nominal de
las unidades exteriores.
Nota:
1. La capacidad total de modelos de unidades interiores conectables representa la suma total de las cifras expresadas en el
nombre del modelo de interior.
2. Debe observarse la cifra en ( ) para la longitud actual de los conductos de refrigeracin de 90 m o ms para PURY-200,250.
3. Las combinaciones en las que la capacidad total de las unidades interiores conectadas excede la capacidad nominal de la
unidad exterior reducir la capacidad de cada unidad interior por debajo de las capacidades indicadas durante un funciona-
miento simultneo. Por ello, si las circunstancias lo permiten, combine unidades interiores dentro de la capacidad nominal de
las unidades exteriores.
46
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
47
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
48
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
49
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
50
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
51
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
52
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
53
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
54
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
55
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
56
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
57
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
58
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
59
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
60
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
Prueba de estanqueidad
El test de hermetismo debe llevarse a cabo mediante la presurizacin de gas nitrgeno a 30 kg/cm2. Observe cmo reslizar el test en la
DATOS DE INSTALACIN
siguiente figura. (Efectue una prueba con la vlvula de bola cerrada y asegrese de presurizar la tubera de lquido y de gas).
El resultado de la prueba se considerar satisfactorio cuando la presin no haya disminuido una vez transcurrido aproximadamente un
da despus de haber finalizado la presurizacin de gas nitrgeno.
Vaciado
La evacuacin debe realizarse desde la altura de servicio situada en la vlvula de bola de la unidad exterior hasta la bomba de vaco que
normalmente se utiliza para la tubera de lquido y de gas. (Efecte la evacuacin de la tubera de lquido y de gas teniendo cerrada la
vlvula de bola).
* No realice nunca un purgado de aire con refrigerante.
Cuando se instale o desplace el aire acondicionado a otro lugar, no lo cargue con un refrigerante distinto al especificado en la unidad (R22)
- Si se mezcla un refrigerante distinto o aire con el refrigerante original, el ciclo de refrigeracin funcionar mal y la unidad puede quedar daada.
61
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
62
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
63
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
64
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
R2
DATOS DE INSTALACIN
65
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
R2
DATOS DE INSTALACIN
66
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
R2
DATOS DE INSTALACIN
67
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
R2
DATOS DE INSTALACIN
68
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y
DATOS DE INSTALACIN
69
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y
DATOS DE INSTALACIN
70
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y
DATOS DE INSTALACIN
71
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y
DATOS DE INSTALACIN
72
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Y & R2
DATOS DE INSTALACIN
73
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Todos los equipos que componen el sistema CITY MULTI unidades exteriores, unidades interiores, controlador BC y controles
remotos disponen de un microprocesador.
DATOS DE INSTALACIN
Para su identificacin a travs del sistema de transmisin deben codificarse dichos equipos individualmente mediante los
selectores de asignacin de direccin.
Acabados los trabajos anteriores de instalacin y montaje, asegrese de establecer correctamente las direcciones de los
componentes.
Tipos de selectores
Para llevar a cabo las operaciones de transmisin y control de una instalacin de CITY MULTI es necesario establecer las
direcciones de los componentes del sistema.
Ponga el mximo cuidado cuando realice esta operacin, puesto que asignaciones incorrectas no permitirn desarrollar un
buen funcionamiento.
(1) Direccin de la unidad (unidad exterior, unidad interior, controlador BC, control remoto)
Para configurar los sistemas CITY MULTI, establezca las direcciones de las unidades exteriores e interiores, controlador BC
y controles remotos con los selectores rotativos que se encuentran en cada uno de los componentes del sistema.
74
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
DATOS DE INSTALACIN
(2) No deben existir en un mismo sistema ms de una unidad con la misma direccin.
(3) El control remoto no puede conectarse a la unidad de tratamiento de aire exterior si sta funciona en interconexin con las
unidades interiores
Diferentes configuraciones del sistema
Funcionamiento individual y funcionamiento por grupos de unidades interiores dentro del mismo sistema
frigorfico. (Cuando no est conectado a ningn controlador de tipo superior)
Si los cdigos de direcciones se establecen como se descubre a continuacin, no se necesita registrar las unidades a travs
del control remoto. De todos modos, en el caso de tener una unidad de tratamiento de aire exterior en interconexin con la
unidad interior, si se requiere registrarla a travs del control remoto.
75
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
76
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Para el funcionamiento en grupo de unidades interiores conectadas a un mismo sistema de refrigerante, no se necesita registro
DATOS DE INSTALACIN
especial a travs del control remoto. Pero si el funcionamiento en grupo es para unidades interiores de sistemas frigorficos
distintos s hace falta haberlas registrado especficamente con el control remoto.
Cableado elctrico
A la hora de tender la lnea de transmisin es necesario conectar las unidades exteriores de los sistemas que tengan
unidades interiores en el mismo grupo de control. Proceda a la conexin de las unidades exteriores a travs de una
manguera de dos almas con apantallamiento en el conector TB7 adems de cableado estndar de transmisin.
Sustituya el cortocircuto practicado en el conector CN41 de una de las unidades exteriores y pselo al conector CN40.
Como las unidades interiores [ (001), (002), (003), (004) ], [ (007), (008), y (009) ], funcionan dentro de un grupo en el mismo
sistema de refrigerante, no es necesario proceder al registro por el control remoto.
Por otro lado, s es necesario este registro para las unidades, (005) y (006), puesto que pertenecen a un grupo siendo de
sistemas frigorficos distintos.
Tambin se requiere registro a travs del control remoto para el funcionamiento en interconexin de la unidad de tratamiento
de aire exterior, (010) con las unidades interiores, (006), (007), (008) y (009).
Registro de grupos
Registre las unidades interiores, (005) y (006) en el control remoto.
Nota: Con un control remoto se pueden registrar hasta 16 unidades de unidades interiores.
(Se pueden agrupar en combinaciones de hasta 16 unidades por grupo)
Para la interconexin con una unidad de tratamiento de aire exterior se pueden agrupar hasta 9
unidades interiores.
Para el funcionamiento en grupos mixtos con sistemas de la series Y y R2, utilice exclusivamente el
control remoto de la serie Y.
77
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Unidad exterior
DATOS DE INSTALACIN
Lnea de transmisin
Unidad interior
Lnea de transmisin
Control
remoto
Unidad exterior
Lnea de transmisin
Unidad interior
Unidad de tratamiento
de aire exterior Control remoto
Control remoto
Principal Secundario
GA=1 GA=5
78
DATOS DE INSTALACIN CAUDAL VARIABLE DE REFRIGERANTE
Para conectar el control centralizado MJ-103, debe hacerse el registro de grupos a travs de este control MJ-103. Por lo tanto,
es necesario cambiar el selector para control centralizado de la unidad exterior a la posicin ON.
DATOS DE INSTALACIN
Cableado elctrico
Para establecer la lnea de transmisin, conecte el MJ-103 y el bloque de terminales para control centralizado (TB-7) de la
unidad exterior con una manguera de dos almas con apantallamiento adems del cableado estndar. No se necesita ningn
cambio en el cable en cortocircuito del conector CN41.
Asignacin de direcciones
El mtodo de asignacin de direcciones es el mismo que para el tipo (1) de sistemas frigorficos. Con el control MJ-103 se
registran los grupos y la posible interconexin con una unidad de tratamiento de aire exterior.
Si, por error, se procede al registro de grupos con un control remoto en un sistema de control centralizado el sistema no
funcionar con normalidad.
Unidad exterior NOTA: Recuerde que Ud., solo dispone de SW11 y SW12.
El primer 0 en las unidades interiores, exteriores y BC
controller y el 1 en los controles remotos no estn
disponibles fsicamente, de modo que seleccionaremos
como 01 - 51- etc.
Lnea de transmisin
Unidad interior
Lnea de transmisin
Control
remoto
Unidad exterior
Conducto
Lnea de transmisin
Unidad interior
Unidad de tratamiento
de aire exterior Control remoto
Control remoto
Principal Secundario
79
DATOS DE INSTALACIN RECUPERADORES ENTLPICOS
DATOS DE INSTALACIN
RECUPERADORES ENTALPICOS
81
DATOS DE INSTALACIN RECUPERADORES ENTLPICOS
CONEXIONADO ELECTRICO
Para utilizar este equipo se necesita un interruptor de control (accesorio opcional o parte adquirida en su suministrador de mate-
DATOS DE INSTALACIN
rial elctrico). El diagrama del cableado cambia segn el modelo correspondiente. Consulte el diagrama aplicable y empiece a
realizar el trabajo elctrico. Cuando utilice un interruptor de control oprcional, consulte sus instrucciones de funcionamiento
para realizar el trabajo elctrico.
UNIDAD NEGRO
RELE X
ANARANJADO ROSADO
EA
ALIMENTACION 5 (aire de escape)
ALTO AZUL
220-240V 50Hz M1
VERDE/
AMARILLO BLANCO
DIFERENCIAL 1
EXTRA ALTO NEGRO
4 ROSADO
ICP 6
ENCENDIDO/APAGADO
L ROJO ALTO AZUL
1 M2
ALTA 2 BLANCO
BLANCO 8
2 EXTRA ALTO SA
N N X (suministro
VERDE de aire)
3 7
ALTA-BAJA
BAJA
LOSSNAY ROJO Interuptor
4 BLANCO
/BY-PASS limitador
REGISTRO MG GM
Transformador
220-240 V 100 V
LGH-150RS2-E y LGH-200RS2-E
Diagrama de cableado
* Conecte los cables indicados por las lnea en negrita.
Alimentacin
3~ 380-415V 50Hz
DIFERENCIAL
ICP
UNIDAD
R Y B
ROJO 100 V F ENCENDIDO/APAGADO
ROJO
1
AMARILLO MARRON
2
BLANCO X1 52F BY PASS
AMARILLO
52F X2 3
X2
AMARILLO 51F
51F
U V W
NEGRO
BLANCO
ROJO
AZUL AZUL Terminal para opciones
de control externo
Interruptor
M1 M2 limitador Lmpara Lmpara Lmpara Lmpara
indicadora indicadora indicadora indicadora
MG GM de de de de
NEGRO parada funciona- error ventilacin
BLANCO miento
Interruptor
ROJO limitador 5 7 9 11
MG GM
M1 M2 52F 52F X1 X2
6 8 10 12
82
DATOS DE INSTALACIN RECUPERADORES ENTLPICOS
ESPECIFICACIONES
Volumen
Frecuencia Presin Eficiencia de intercambio (%) Nivel
DATOS DE INSTALACIN
Nombre Tensin Corriente Consumo de aire
de lnea esttica Entalpia sonoro
del modelo (V) (A) (W) (mmH2O) Temperatura
(Hz) (m3/h) L/S (dB(A))
Calefaccin Refrigeracin
LGH- Monofsico
50 0,35-0,36 75-86 150 42 5,5 74 64 58 26,5-27,5 19
15RS2-E 220 - 240
LGH- Monofsico
50 0,42-0,44 92-105 250 69 4,5 72 64 58 27-28 23
25RS2-E 220 - 240
LGH- Monofsico
50 0,57-0,57 125-134 350 99 6,0 75 65 61 29-31 33
35RS2-E 220 - 240
LGH- Monofsico
50 0,78-0,78 170-183 500 138 4,7 74 62 58 32-33 38
50RS2-E 220 - 240
LGH- Monofsico
50 1,9-1,9 415-445 800 222 10,0 74 65 60 35-36 73
80RS2-E 220 - 240
LGH- Monofsico
50 2,2-2,2 475-525 1.000 278 7,4 75 66 61 35,5-36,5 83
100RS2-E 220 - 240
LGH- Trifsico
50 1,6-1,6 840-855 1.500 417 13,0 75 66 61 38-39 175
150RS2-E 380 - 415
LGH- Trifsico
50 1,9-1,9 1020-1050 2.000 556 15,0 75 66 61 39,5-40,5 194
200RS2-E 380 - 415
* Los valores dados en la tabla para el nivel sonoro reflejan los niveles medidos en una posicin ubicada a 1,5 metros inme-
diatamente debajo de la unidad en una cmara anecoica.
* El nivel sonoro en las salidas de aire (a un ngulo de 45 y a 1,5 metros frente a ellas) es aproximadamente 8-11 dB (A)
superior al de los valores dados en la tabla.
* Los valores de arriba se aplican durante la ventilacin LOSSNAY cuando la velocidad del ventilador est en el ajuste de alta
velocidad.
* En los modelos LGH-150 y LGH-200 se recomienda especialmente el empleo de silenciadores en impulsin y retorno al local.
83
DATOS DE INSTALACIN RECUPERADORES ENTLPICOS
Alimentacin
Adaptador del
Control remoto Control
(PAC-SA88HA-E) remoto
Interruptor de control LOSSNAY (PZ-05SLB2-E) Interruptor de control LOSSNAY
(PZ-05SLB2-E)
BAJA ROJO
Aislamiento Caja de rel ALTA BLAN
necesario (PZ-12RB-E) Mr. SLIM
AMAR CN51 N ROJO
NARA 12V DC
DAMPER NARA
Cable de conexin ROJO
mnimo 0,13 mm2 BLAN Alimentacin DAMPER BLAN
Cable de conexin ROJO 220~240V AC
cable slido ALTA
1,6 o 2,0
(de fbrica)
BLAN
ICP de fbrica
Alimentacin
elctrica
50Hz LOSSNAY
220~240V
Bloque
terminal
NOTA: Para mayor informacin,
NARA
consulte el manual tcnico
LOW ROJO
HIGH BLAN
y de servicio de LOSSNAY.
N ROJO
DAMPER NARA
DAMPER BLAN
Interruptor de
control LOSSNAY Caja de empalmar
(PZ-05SLB2-E) (de fbrica)
84
DATOS DE INSTALACION CORTINAS DE AIRE
DATOS DE INSTALACIN
SERIE
GK
85
DATOS DE INSTALACION CORTINAS DE AIRE
AVISOS
DATOS DE INSTALACIN
Nunca utilice el producto en un bao ni en otra ubicacin donde la humedad sea excesiva (ms del
90% de humedad relativa).
(Esto puede causar una sacudida elctrica o un incendio.)
Si va a funcionar ms de una unidad al mismo tiempo, asegrese de que el valor de las corrientes
combinadas que fluyen a travs del panel de terminales al que estn conectadas las unidades no
sobrepase 5 A.
(Si no se toma esta precaucin podr producirse una sacudida elctrica o un incendio.)
Si el producto no va a ser utilizado durante un largo periodo de tiempo, asegrese de poner el dis-
yuntor del tablero de energa en la posicin OFF.
(El deterioro del aislamiento puede causar una sacudida elctrica, fugas de energa o incendios.)
Notas
Los dgitos del nmero del modelo indican la distancia de la barrera estndar y la anchura de instalacin. (En el caso del
GK- 2509YS, la distancia de la barrrera estndar es de 2,5 m y la anchura de instalacin es de 90 cm.) La cortina de aire
no ser eficaz si la circulacin del aire es demasiado dbil o demasiado fuerte.
Asegrese de confirmar la altura de instalacin y el modelo.
Cuando instale la cortina de aire a la entrada de una tienda u oficina, la abertura de salida de aire deber orientarse hacia
el interior. Sin embargo, podr orientarse hacia el exterior siempre que la unidad est instalada bajo aleros o toldos que
eviten que el agua de lluvia caiga sobre la unidad y sea succionada al interior de la unidad por la abertura de entrada.
Adems, la unidad deber instalarse en el exterior si sta va a montarse sobre una cmara de congelacin.
Si la unidad va a empotrarse en el techo, asegrese de proporcionar una abertura de inspeccin (de unos 450 mm de
anchura como mnimo) en el techo para permitir realizar inspecciones de mantenimiento.
Si se produce un fallo de alimentacin, asegrese de desconectarla con el interruptor de alimentacin. (De lo contrario,
existe el peligro de que se produzca una avera si el ventilador de la unidad empieza a funcionar de repentinamente cuan-
do se reanude la alimentacin.)
Utilice un disyuntor o similar con el sitema de cableado.
Medida correctiva:
Resulta necesario desconectar la alimentacin, remediar la causa del problema y reemplazar los motores, capacitores y
resistores.
86
DATOS DE INSTALACION CORTINAS DE AIRE
DATOS DE INSTALACIN
de los agujeros de montaje de la placa de montaje en la pared, y
luego asegure la placa de montaje en la pared utilizando las aran-
delas, arandelas de resorte y tuercas que hayan sido quitadas.
El aparato puede instalarse verticalmente. Tenga cuidado en la orientacin del cuerpo de la unidad y siga las instruciones para
el montaje en la pared.
NOTA
Alinee los agujeros de los tornillos del cuerpo de la unidad con el
ngulo de los tornillos de ajuste de ngulo, y luego apritelos. De
lo contrario, las cabezas de los tornillos podran ser aplastadas
imposibilitando el ajuste.
Trabajo elctrico
87
DATOS DE INSTALACION CORTINAS DE AIRE
Cableado
Haga las conexiones de cableado para las partes indicadas por lneas negras en el diagrama de conexiones.
Si el viento del exterior afecta a la eficacia de la cortina de aire podrn realizarse los ajustes de velocidad y ngulo siguientes:
LIMPIEZA
La cortina de aire deber limpiarse cuando est sucia. Asegrese tambin de limpiar y hacer el funcionamiento de prueba de
la cortina de aire antes de empezar a utilizarla en verano y en invierno.
Desconecte siempre la alimentacin antes de limpiar la unidad.
No cuelgue nunca de la unidad ni la empuje hacia abajo a la fuerza porque podra producirse un serio accidente.
DESMONTAJE DE LA UNIDAD
NOTA
Tenga en cuenta que el ventilador se ajusta en el eje con una
orientacin especfica.
88
DATOS DE INSTALACION CORTINAS DE AIRE
MONTAJE DE LA UNIDAD
Cuando termine, siga a la inversa los pasos de desmontaje para volver a montar la unidad. Inspeccione los tems siguientes al
volver a montar la unidad.
DATOS DE INSTALACIN
1. El ventilador se ajusta en el eje con una orientacin especfica. Asegrese de no instalarlo al revs.
2. Est araado el cableado del interior del cuerpo de la unidad?
3. Han sido montados firmemente el cuerpo de la unidad, las arandelas, los ventiladores, las tuercas y las protecciones?
4. Conecte la alimentacin y confirme que la cortina de aire funcione correctamente.
ESPECIFICACIONES
Dimensiones (mm)
Modelo A B C D
GK-2509YS 900 750 870 5
GK-2512AS 1.194 1.044 1.164 6
Toma de corriente
Agujeros de anclaje
89
CONTROLES Y CHEQUEOS
CONTROLES Y CHEQUEOS
CONTROLES
Y CHEQUEOS
91
92
CONTROLES Y CHEQUEOS DESHUMIDIFICADORES
CONTROLES Y CHEQUEOS
93
CONTROLES Y CHEQUEOS DESHUMIDIFICADORES
[MJ-101MW]
[MJ-101MWX]
Descongelacin visual
Indica que la descongelacin es
progresiva.
94
CONTROLES Y CHEQUEOS DESHUMIDIFICADORES
95
CONTROLES Y CHEQUEOS DESHUMIDIFICADORES
Normal Anormal
C-R 26.5 ~ 28.7 Circuito abierto
C-S o corto-circuito
96
CONTROLES Y CHEQUEOS DESHUMIDIFICADORES
DESCONECTADO
:Luces encendidas
CORTOCIRCUITADO
:Luces apagadas
Auto diagnsis
Descripcin de anormalidad (fallo) Accin correctiva
<Seccin de temporizador> <Modo operacin>
Fallo de Microordenador
Sustituir placa principal.
Error RAM
:Luces encendidas
:Luces apagadas
97
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
SERIE RV
99
CONTROLES Y CHEQUEOS GAMA DOMSTICA
En caso de Multisplit debe asegurarse que las maniobras elctricas corresponden a las tuberas frigorficas
entre mquinas.
Ponga una unidad n 1 en marcha y comprobar si sale aire fro.
Ponga la unidad n 2 u otras unidades en ventilacin y asegurarse que no dan aire fro. En caso de darlo, alguna
de las maniobras es incorrecta.
100
CONTROLES Y CHEQUEOS GAMA DOMSTICA
SOLO FRIO
Pantalla de funcionamiento
AM CLOCK PM
FUNCIONAMIENTO/PARO
FAN VANE
VELOCIDAD DEL VENTILADOR Angulo del botn del DEFLECTOR
CONTROLES Y CHEQUEOS
ECONO COOL
FUNCIONAMIENTO ECONO COOL
START STOP
Botn de ARRANQUE PROGRAMADOR Botn de PARO DEL PROGRAMADOR
HR. MIN.
CLOCK
Botn del BARREDOR
RESET
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
MITSUBISHI ELECTRIC
BOMBA DE CALOR
Pantalla de funcionamiento
AM CLOCK PM
FUNCIONAMIENTO/PARO
Botn de TEMPERATURA
Seleccin de MODO MODE I FEEL COOL DRY HEAT
DE FUNCIONAMIENTO
FAN VANE
VELOCIDAD DEL VENTILADOR Angulo del botn del DEFLECTOR
ECONO COOL
FUNCIONAMIENTO ECONO COOL
START STOP
Botn de ARRANQUE PROGRAMADOR Botn de PARO DEL PROGRAMADOR
HR. MIN.
CLOCK
Botn del BARREDOR
RESET
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
MITSUBISHI ELECTRIC
101
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Serie RV
102
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
NO
SI NO
ESTAN LOS CABLES LOS PUNTOS DE SOLDADU-
CONECTADOS? RA SON NORMALES?
SI
RECONECTAR RESOLDAR
103
CONTROLES Y CHEQUEOS GAMA DOMSTICA
NO
SE ENCIENDE LA PANTALLA DEL CONTROL REMOTO?
SI
SI
SI
EXISTEN LUCES FLUORESCENTES
REINSTALE LA UNIDAD MAS LEJOS
A MENOS DE 1 METRO?
NO
104
CONTROLES Y CHEQUEOS GAMA DOMSTICA
(A)
COMPROBAR VISUALMENTE
TODAS LAS CONEXIONES Y SI
CONECTORES. EXISTE ALI-
CONTROLES Y CHEQUEOS
MENTACIN ELCTRICA?
SI
NO
LA RESISTENCIA OHMICA DEL MOTOR
FUSIBLE?
VENTILADOR ES "0" OHMIOS? NO
105
CONTROLES Y CHEQUEOS GAMA DOMSTICA
SI
CONTROLES Y CHEQUEOS
SI
NO
SI
COMPRUEBE LA PLACA
ELECTRONICA DE CONTROL
SI
COMPROBAR EL CONTACTOR
LA UNIDAD EXTERIOR NO LAS CONEXIONES
52C .MOTOR VENTILADOR Y
FUNCIONA. SON INCORRECTAS?
COMPRESOR.
NO
NO
RECONECTAR EL
FUNCIONA?
CABLEADO
O.K.
SI
SI
COMPROBAR
ESTA EL COMPRESOR EL COMPRESOR
EL COMPRESOR NO CORRECTAMENTE NO
FUNCIONA CONECTADO?
FUNCIONA?
SI O.K.
NO
RECONECTAR EL
CABLEADO
A LA SIGUIENTE HOJA
106
CONTROLES Y CHEQUEOS GAMA DOMSTICA
SUSTITUIR EL
FUSIBLE
SI
SI
COMPROBAR
MOTOR VENTILADOR
LAS CONEXIONES
SON CORRECTAS?
NO
NO
CONTROLES Y CHEQUEOS
RECONECTAR EL FUNCIONA?
CABLEADO
VIENE DE LA HOJA ANTERIOR
O.K.
107
CONTROLES Y CHEQUEOS GAMA DOMSTICA
EL SW2 SE ENCUENTRA EN
LA UNIDAD EXTERIOR NO
LA POSICION DE BOMBA MUH?
FUNCIONA
(EN LA UNIDAD INTERIOR)
SI
NO
NO
NO
FUNCIONA?
SI
COMPROBAR COMPRESOR
O.K. Y MOTOR VENTILADOR
A LA SIGUIENTE HOJA
108
CONTROLES Y CHEQUEOS GAMA DOMSTICA
NO SI
COMPROBAR EL
CONTROLES Y CHEQUEOS
RECONECTAR COMPRESOR
ESTA BIEN?
NO NO
FUNCIONA?
SI
SI
COMPROBAR SUSTITUIR EL
O.K.
LA P.C.B. COMPRESOR
NO SI
NO
NO SI
FUNCIONA?
SI
109
CONTROLES Y CHEQUEOS GAMA DOMSTICA
NO
LA UNIDAD ES BOMBA DE CALOR? COMPROBAR EL SW2 DE LA
UNIDAD INTERIOR
SI
SI NO
CONTROLES Y CHEQUEOS
FUNCIONA?
-.QUITAR ALIMENTACION ELECTRICA
(INTERIOR-EXTERIOR)
-.PRESIONAR UNA VEZ EL INTERRUPTOR
DE "EMERGENCY OPERATION"
COMPROBAR LA UNIDAD
O.K.
EXTERIOR
SI
EXISTE MAL CONTACTO O DESCONEXION
DEL CABLEADO?
NO RECONECTAR
NO
HAY 20V DC ENTRE LAS DOS PATAS DEL COMPONENTE SUSTITUIR LA
R132? (SITUADO EN LA PLACA ELECTRONICA INTERIOR) P.C.B.
SI A LA SIGUIENTE HOJA
A LA SIGUIENTE HOJA
110
CONTROLES Y CHEQUEOS GAMA DOMSTICA
SI
SI
CONTROLES Y CHEQUEOS
HA Y 5V DC ENTRE J8(-) Y J9(+)? NO SUSTITUIR LA PLACA
(DE LA PLACA EXTERIOR) ELECTRONICA EXTERIOR
DURANTE EL FUNCIONAMIENTO EN
COMPROBAR EL
"EMERGENCY OPERATION" HAY 10V DC NO
CONECTOR
ENTRE LAS PATAS DEL COMPONENTE
CN730
R601? (PLACA ELECTRONICA UNIDAD
EXTERIOR)
SI
111
CONTROLES Y CHEQUEOS GAMA DOMSTICA
UNIDAD INTERIOR
Comprobacin de las partes principales
MSC-07RV
MSC-09RV
MSC-12RV
Componente Criterio y mtodo de deteccin Esquemas
Termistor Mediciones de resistencia mediante un tester.
temperatura (Temperatura 10C ~ 30C)
ambiente Normal Anormal
Termistor MSC-07/09/12RV Abierto o
batera
8k ~ 20k cortocircuitado
interior
Mediciones de resistencia mediante un tester.
(Temperatura del bobinado 10C ~ 30C)
Normal
Anormal
Motor
MSC-07/09/12RV
CONTROLES Y CHEQUEOS
Motor Fusible
Ventilador
interior Medir con suministro elctrico.
NEGRO ROJO BLANCO
Normal
Anormal
MSC-07/09/12RV
Sensor
MARRON
BRN
MSC-07/09/12RV
Abierto o cortocircuitado NARANJA
ORN VERDE
GRN
282 ~ 306
112
CONTROLES Y CHEQUEOS GAMA DOMSTICA
UNIDAD EXTERIOR
Comprobacin de las partes principales
MU-07RV MUH-07RV
MU-09RV MUH-09RV
MU-12RV MUH-12RV
Part name Criterio de mtodo de deteccin Esquemas
Mediciones de resistencia mediante un tester.
(Temperatura 10C ~ 40C)
Termistor de
desescarche Normal Anormal
MUH-07/09/12RV
<MUH-07/09/12RV> Abierto o cortocircuitado
5k ~ 60k
CONTROLES Y CHEQUEOS
C-R 3.68~4.51 3.55~4.35 1.87~2.30 BLANCO
Abierto o cortocircuitado WHT C
Compresor C-S 5.08~6.22 5.03~6.16 3.44~4.22 P
AUX. MAIN
Normal S
Anormal R NEGRO
BLK
MUH-07RV MUH-09RV MUH-12RV RED
ROJO
Normal
Anormal
MU-07/09RV MU-12RV MAIN
MUH-07/09RV MUH-12RV
BLANCO-NEGRO 227~279 155 ~ 191
Abierto o cortocircuitado
NEGRO-ROJO 339~416 363 ~ 445
P CLIXON INTERNO
113
CONTROLES Y CHEQUEOS GAMA DOMSTICA
}
Motor ventilador
interior
220~240V AC
R132
} Entrada de
CONTROLES Y CHEQUEOS
alimentacin elctrica
220-240V AC
Termistor
12V DC
{ +-- temperatura ambiente
(RT11)
Punto de ciclo
corto
Termistor batera
interior (RT12)
Pulsador de operacin
de emergencia
+
-- } 5V DC
30
')
Resistencia (k'
20
SW2 (Ver pg. 7)
10
0
0 10 20 30 40 50 60
;)
Temperatura (;
114
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MUH-09RV - E1
MUH-12RV - E1
Resistencia
CONTROLES Y CHEQUEOS
Temperatura
Vlvula de R601
Motor ventilador 5~10V DC Entrada de alimentacin
inversin de ciclo
}
}
}
}
Fusible 2A/250V
Ciclo corto de
desescarche
+ J9
J8 } 5V DC
+
+
}
12V DC
52C Puente para cambio
12V DC de configuracin del
desescarche (JPC, JPE)
(Ver pg. ...... )
115
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES
CONTROLES Y CHEQUEOS
Serie NV
117
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Pantalla de funcionamiento
FUNCIONAMIENTO/PARO
Botn de TEMPERATURA
Seleccin de MODO
DE FUNCIONAMIENTO
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
BOMBA DE CALOR
Pantalla de funcionamiento
FUNCIONAMIENTO/PARO
Botn de TEMPERATURA
Seleccin de MODO
DE FUNCIONAMIENTO
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
118
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
CONDUCTOS
119
CONTROLES Y CHEQUEOS GAMA DOMSTICA
11 28
MODE
10 27 DRY
SELECT
Seleccin de funcin
9 26 FAN
Este botn sirve para cambiar
8 25 UP HIGH FAN entre los modos de fro,
7 24
Las luces indican el LOW SPEED ventilacin y deshumectacin.
6 23
tiempo de temporizado DOWN Cada una de las luces verdes
5 22
o la temperatura. indica el modo operativo.
4 21
3 20 AUTO
Indicador tiempo de STOP TIMER
2 19
temporizacin. START MODE
1 18
Las luces marcan el lapso
de tiempo que se ha Velocidad ventilador
programado. Cada luz verde MITSUBISHI ELECTRIC
Este pulsador vara la
que est encendida determina
velocidad del ventilador de
una cantidad de horas.
baja a alta. cada una se
Indicador temperatura indica mediante una luz verde.
de ambiente
Las luces indican la
temperatura ambiente y de
consigna.
Temperatura consigna: Pulsadores de subir y bajar
Luz verde fija. Control de temperatura (mientras las luces
Temperatura ambiente: verdes TEMP estn encendidas).
Luz verde destellante. Use UP y DOWN para consignar la temperatura
deseada entre 18 and 29C.
Temporizador (Siempre que las luces verdes Funcin temporizador
TIMER estn encendidas).
Se usa para seleccionar el
Use UP y DOWN para seleccionar el tiempo
tiempo de encendido o
deseado entre 2 y 12 horas.
apagado. Se indica con las
luces verdes.
Atencin :
Apretando UP y DOWN juntos por ms de dos segundos iniciar el funcionamiento de emergencia o inspeccin. Evite
pulsar estos botones simultneamente durante el funcionamiento normal. Pulse ON/OFF para cancelar el funcionamiento
de emergencia o inspeccin.
Todas las luces verdes se apagarn cuando apague el aire acondicionado.
Evite presionar los botones con las uas u objetos cortantes. Estos pueden estropear el panel de control.
120
CONTROLES Y CHEQUEOS GAMA DOMSTICA
(3) Las luces del control ensean el ltimo problema. Este queda memorizado hasta el prximo problema, excepto si se
desconecta el suministro elctrico. para limpiar la memoria pulse UP and DOWN simultneamente por ms de dos
segundos durante el proceso de auto diagnsis .
(4) Durante el proceso de auto diagnsis todos los pulsadores se desactivan excepto el de ON/OFF.
(5) Para dejar el proceso de auto diagnsis, pulse el boton ON/OFF.
TIMER TEMP.
CONTROLES Y CHEQUEOS
12 29 Interfase del control remoto averiada
11 28
10 27 Termistor anormal
9 26
8 25
7 24
6 23
5 22
4 21
3 20
2 19
1 18
121
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Unidad interior funciona y Cableado entre la unidad interior y la Compruebe el cableado entre las unidades.
exterior no arranca exterior desconectados.
Diferente polaridad entre la unidad
interior y la exterior.
Problemas en el contacto (52C) Cambie el contactor.
122
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Normal C
WHT
BLANCO
Anormal
1.6 2 2.5
Compresor NR VR NR VR NR VR
S R NEG.
1.52~ 1.87~ 0.81~ 0.94~ 0.73~ 0.84~ BLK
C-R Abierto o
1.87 2.30 1.00 1.16 0.90 1.04
ROJO
RED
CONTROLES Y CHEQUEOS
cortocircuitado
2.41~ 3.44~ 1.70~ 1.99~ 1.61~ 1.82~
C-S
2.96 4.22 2.09 2.44 1.98 2.24
Motor Normal P
Anormal AMA.
ventilador 1.6AR 2AR 2.5AR GRN
VERDE
YLW
interior Blanco-Negro 241.4~261.2 155.5~168.2 97.0~105
Negro-Azul 19.0~20.6 48.3~52.3 53.8~58.3 Abierto o BLKAZU.
NEG. YLW
BLU AMA. RED NAR.
ROJO ORN
WHT
BLANCO
1.6/2NR
1.6/2VR
Principal
MAIN
Auxiliar
AUX
P
Mediciones de resistencia mediante un tester.
(Temperatura -10C ~ 40C)
ventilador Anormal
1.6NR/1.6VR 2NR/2VR 2.5NR/2.5VR 2.5NR
exterior
Blanco-Negro 115 ~ 141 102 ~ 126 71.5 ~ 87.5 2.5VR
Abierto o
Negro-Rojo 118 ~ 146 97.9 ~ 120 90.1 ~ 110.2 Principal
MAIN
cortocircuitado AUX.1
Aux. 1 Aux. 2
AUX.2
AMAR. NEGRO
YLW BLK ROJO
REDNARAN.
ORN BLANCO
WHT
p :protector interno
123
CONTROLES Y CHEQUEOS GAMA DOMSTICA
11 28
MODE
10 27 DRY
SELECT
Seleccin de funcin
9 26 FAN
Este botn sirve para cambiar
8 25 UP HIGH FAN entre los modos de fro,
7 24
Las luces indican el LOW SPEED ventilacin y deshumectacin.
6 23
tiempo de temporizado DOWN Cada una de las luces verdes
5 22
o la temperatura. indica el modo operativo.
4 21
3 20 AUTO
Indicador tiempo de STOP TIMER
2 19
temporizacin. START MODE
1 18
Las luces marcan el lapso
de tiempo que se ha Velocidad ventilador
programado. Cada luz verde MITSUBISHI ELECTRIC
Este pulsador vara la
que est encendida determina velocidad del ventilador de
una cantidad de horas. baja a alta. cada una se indica
mediante una luz verde.
Indicador temperatura
de ambiente
Las luces indican la
temperatura ambiente y de
consigna.
Temperatura consigna: Pulsadores de subir y bajar
Luz verde fija. Control de temperatura (mientras las luces
Temperatura ambiente:
verdes TEMP estn encendidas).
Luz verde destellante. Use UP y DOWN para consignar la temperatura
deseada entre 18 and 29C.
Temporizador (Siempre que las luces verdes Funcin temporizador
TIMER estn encendidas).
Se usa para seleccionar el
Use UP y DOWN para seleccionar el tiempo
tiempo de encendido o
deseado entre 2 y 12 horas.
apagado. Se indica con las
luces verdes.
Atencin :
Apretando UP y DOWN juntos por ms de dos segundos iniciar el funcionamiento de emergencia o inspeccin. Evite
pulsar estos botones simultneamente durante el funcionamiento normal. Pulse ON/OFF para cancelar el funcionamiento
de emergencia o inspeccin.
Todas las luces verdes se apagarn cuando apague el aire acondicionado.
Evite presionar los botones con las uas u objetos cortantes. Estos pueden estropear el panel de control.
124
CONTROLES Y CHEQUEOS GAMA DOMSTICA
(3) Las luces del control ensean el ltimo problema. Este queda memorizado hasta el prximo problema, excepto si se
desconecta el suministro elctrico. para limpiar la memoria pulse UP and DOWN simultneamente por ms de dos
segundos durante el proceso de auto diagnsis .
(4) Durante el proceso de auto diagnsis todos los pulsadores se desactivan excepto el de ON/OFF.
(5) Para dejar el proceso de auto diagnsis, pulse el boton ON/OFF.
TIMER TEMP.
CONTROLES Y CHEQUEOS
12 29 Interfase del control remoto averiada
11 28 Perdida de conexin entre unidades
6 23
5 22
4 21
3 20
2 19
1 18
125
CONTROLES Y CHEQUEOS GAMA DOMSTICA
28 Mala conexin del Falsos contactos en el cableado Chequee el cableado entre ambas unidades.
cableado. la unidad exterior se apaga.
Diferencia polaridad en la conexin
entre interior y exterior.
Error de seal entre interior Problemas en la placa de la Compruebe la placa de la unidad exterior.
y exterior. exterior.
CONTROLES Y CHEQUEOS
126
CONTROLES Y CHEQUEOS GAMA DOMSTICA
La unidad interior funciona Cableado entre la unidad interior y la Compruebe el cableado entre la unidad interior y
CONTROLES Y CHEQUEOS
pero la unidad exterior no exterior en mal estado. la exterior.
arranca. Diferencia de polaridad en el cableado
entre la interior y la exterior.
Problemas con la placa exterior. Compruebe la placa exterior.
127
CONTROLES Y CHEQUEOS GAMA DOMSTICA
WHT
BLANCO
C
Normal
Compresor Anormal
1.6VR 2VR 2.5VR
S R NEG.
BLK
C-R 1.87~2.30 0.94~1.16 0.84~1.04 Abierto o RED
ROJO
Normal
Anormal
1.6AR 2AR 2.5AR
Motor
ventilador Blanco-Negro 241.4~261.2 155.5~168.2 97.0~105 P
1.6/2VR
MAIN
Principal
AUX
Auxiliar
P
Medidas de resistencia con tester.
(Temperatura -10C ~ 40C)
NEGRO
BLK AMARILLO
YLW RED WHT
ORN BLANCO
ROJO NARANJA
p :protector interior
128
CONTROLES Y CHEQUEOS GAMA DOMSTICA
VLo Lo Lo Hi
50Hz 60Hz
7 5 6 4 3 2 1 8
CONTROLES Y CHEQUEOS
REntrada alimentacin elctrica
220-240V AC
+
12V DC
+
5V DC
Termistor bateria
Indoor coil interior
thermistor (RT12)
(RT12)
Termistor temperatura
Room temperature ambiente
thermistor (RT11)
(RT11)
40
30
Resistance (K')
Temperatura
20
10
0
0 10 20 30 40 50 60
Temperature ( C)
Temperatura
129
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Al
CONTROL REMOTO
A la
CONTROLES Y CHEQUEOS
JP15= 0V
+ JP16=12V DC
+ JP17= 5V DC
Funcin de
AUTO-ARRANQUE
Aumento de 4 grados
(solo SEH Bomba de Calor)
130
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Resistencia
CONTROLES Y CHEQUEOS
Temperatura C
R601
5~10V DC ENTRADA
Motor ventilador Bobina Solenoide
}
Fusible 2A/250V
Ciclo corto de
desescarche
+ J9
J8 } 5V DC
+
+
}
12V DC
52C Intrvalo de desescarche
12V DC cambio de temperatura
del final de desescarche
Puente JPC y JPE
131
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Serie SUELO-TECHO
CONTROLES Y CHEQUEOS
133
CONTROLES Y CHEQUEOS GAMA DOMSTICA
SOLO FRIO
Pantalla de funcionamiento
FUNCIONAMIENTO/PARO
Botn de TEMPERATURA
Seleccin de MODO
DE FUNCIONAMIENTO
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
BOMBA DE CALOR
Pantalla de funcionamiento
FUNCIONAMIENTO/PARO
Botn de TEMPERATURA
Seleccin de MODO
DE FUNCIONAMIENTO
Botn de HORA
Botn de MINUTOS
(Seleccin HORARIA)
134
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Salida
CONTROLES Y CHEQUEOS
Comprobar el
motor ventilador
Comprobar interno
la sonda Segn D Causa: Unidad interna
de la Comprobar 2-veces-Temperatura ambiente/Problema en la
temperatura la unidad sonda de bateria interior.
ambiente.
LAMPARA DEL
INDICADOR
DE OPERACIN
Antes de tomar medidas, asegrese que el indicio reaparece, para una correcta localizacin de averas.
Comprobar la tabla adjunta
Corriente
NO. anormal Indicacin Indicio Mtodo deteccin Check point
135
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Sonda de
Medida de la resistencia con un tester.
temperatura
(intervalo temperatura 10C ~ 30C)
ambiente
C
Normal
Anormal
13NV 18NV 24NV
Compresor
C-R 1.86~2.28 1.05~1.3 0.84~1.04 Circuito abierto S R
13/18NV
MAIN
AUX
P
ventilador Anormal
13NV 18NV 24NV
exterior 24NV
BLA-NEG 115 ~ 141 102 ~ 126 71.5 ~ 87.5
Circuito abierto MAIN
NEG-ROJO 118 ~ 146 97.9 ~ 120 90.1 ~ 111
o Corto-circuito AUX
BLA-AMAR ___ ___ 81.3~ 99.5 MAIN P
NARAN.
Circuito abierto
Resistencia/fase 329~357
o Corto-circuito AMAR MAR AZUL
P : Protector interno
136
CONTROLES Y CHEQUEOS GAMA DOMSTICA
No Si No
Est la toma de corriente
Los cables estn conectados?
soldada?
Si
Volver a conectar los
Volver a soldarla
cables.
Desconectar los cables del conector (Motor ventilador) en el cuadro PC del control electrnico interno.
Medir la resistencia entre n 1 y n 4 y luego n 3 y n 4 del motor ventilador
CONTROLES Y CHEQUEOS
Yes ( 0 or ) (otros)
Si
Si
No
OK Se percibe ruido de radio? Sustituir el control remoto.
Si
Si
Hay algn fluorescente en el Volver a instalar la unidad fuera de
radio de 1 m.? las luces.
No
No(5V DC 0V)
Sustituir el receptor.
137
CONTROLES Y CHEQUEOS GAMA DOMSTICA
No
Ha saltado el fusible
(F11)?
Problemas de la placa PC
Comprobar las partes y el Asegrese de comprobar el
control electrnico interior.
esquema de la placa PC del control fusible y el varistor en todos
electrnico interior, visualmente. los casos.
(NR11? No
Si
Sustituir el varistor.
MCF-13NV- E1 , E2 MCF-24NV- E1 , E2
MCF-18NV- E1 , E2
Salida Salida
No
Si Comprobar voltaje unidad Comprobar voltaje unidad Comprobar la continuidad de la
externa si hay 220/240V AC externa si hay 220/240V AC conexin de la unidad interna y
en terminal entre 2 - N ? en la terminal entre 2 - N ? externa.
138
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MCF-13NV - E1 MCF-13NV - E2
MCF-18NV - E1 MCF-18NV - E2
MCF-24NV - E1 MCF-24NV - E2
PLACA ELECTRNICA UNIDAD INTERIOR
CONTROLES Y CHEQUEOS
Potencia suministrada a
220-240V CA
+
12V CC
+
5V CC
Corriente de corto-circuito
Sonda de temperatura de batera (RT12)
30
GILMS
Resistencia (K')
RT11
TH113
CH313
En el cuadro
PC del control 20
electrnico
DE00R697B interno CN113
10
Sonda de
temperatura 12
ambiente (RT11) 0
0 10 20 30 40 50 60
Temperatura ( C)
Sonda de temperatura ambiente (RT11)
139
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Comprobar Segn D
sonda de Comprobar
temperatura la unidad Motivo:conexin unidades 6-destello
ambiente. externa interna/externa
Motivo:Unidad interna 2.5-segundos OFF
(
Problema de interconexin
Problema de la serie de 2-veces-Problema
Cuando el control remoto seales sondas
Motivo: Unidad externa
est pulsado cuando el 6-instante-Sustituir la
interruptor de OPERACION resistencia
DE EMERGENCIA est trmica externa
pulsado, el ventilador no gira
con la lmpara encendida Segn E
del indicador de operacin. Como comprobar
el mal
conexionado y el Comprobar sonda de Comprobar sonda
Segn A Comprobar el error de seal batera interior. ambiente.
motor del ventilador interno
Lmpara
INDICADOR
OPERACIN
wAntes de tomar medidas, asegurarse que el indicio reaparece, para una correcta solucin.
Comprobar esta misma tabla
Bobina resist.
Comprobar calibracin de la resistencia
trm. interna 2-destellos
trmica.
Resistencia Unidad externa Comprobar sondas de
2 Volver a conectar el conector
trmica de no funciona. temperatura.
2.5-segundos OFF Comprobar el cuadro PC del control
la temp.
electrnico interno.
ambiente
6-destellos
Resistencia Comprobar el cuadro PC del
Unidad externa Sonda de temperatura
3 trmica
no funciona. exterior.
descongelador externo.
externa Comprobar calibracin Resist. trmica.
2.5-segundos OFF
140
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Normal
Compresor Anormal
CONTROLES Y CHEQUEOS
13NV 18NV 24NV
S R
1.86~2.28 1.05~1.3 0.84~1.04
NEG
C-R Circuito abierto ROJO
13/18NV
MAIN
AUX
P
Medida de la resistencia entre los terminales con un tester.
(Temperatura bobina -10C ~ 40C)
ventilador Anormal
13NV 18NV 24NV
exterior 24NV
BLA-NEG 115 ~ 141 102 ~ 126 55.3 ~ 67.7
NEG-ROJO 118 ~ 146 97.9 ~ 120 Circuito MAIN
Circuito abierto
Resistencia/fase 329~357
o corto-circuito YLW BRN BLU
p :Protector interno
141
CONTROLES Y CHEQUEOS GAMA DOMSTICA
No Si No
Est la toma de corriente
Los cables estn conectados?
soldada?
Si
Volver a conectar los
Volver a soldarla
cables.
Desconectar los cables del conector (Motor ventilador) en el cuadro PC del control electrnico interno.
Medir la resistencia entre N.1 y N.4 y luego N.3 y N.4 del motor ventilador
Si ( 0 or ) (otra)
Si
Si
No
OK Se percibe ruido de radio? Sustituir el control remoto.
Si
No
No(DC5V or 0V)
Sustituir el receptor.
142
CONTROLES Y CHEQUEOS GAMA DOMSTICA
No
Ha saltado el fusible
(F11)?
Problemas de la placa PC
Comprobar las partes y el Asegrese de comprobar el control electrnico interior.
esquema la placa PC del control fusible y el varistor en todos
electrnico interior, visualmente. los casos.
CONTROLES Y CHEQUEOS
No
Yes
Sustituir el varistor.
Salida
13/18NV
Comprobar la continuidad de la conexin de
24NV
la unidad interna y externa. No
Comprobar continuidad
Comprobar placa electrnica.
entre terminal L - 2, y
entre terminal N - N.
143
CONTROLES Y CHEQUEOS GAMA DOMSTICA
E Como comprobar el cableado defectuoso y los errores de seal (cuando la unidad externa no
funciona)
Salida
Si
Reparar cables. Existe mal bobinado, contacto pobre o desconexin del cable?
No
1. Parar OFF la potencia de suministro y desconectar in-out del rel de conexin de la cara interna.
CONTROLES Y CHEQUEOS
2. Cortocircuito entre N y 3.
3. Encender la potencia de suministro y pulsar el interruptor de OPERACIN EMERGENCIA.
Si
Apagar alimentacin.
Empalmar los hilos de la conexin interior-exterior.
Encender alimentacin.
Si
3 minutos mas tarde cuando el interruptor de OPERACION DE No Comprobar y verificar el fusible y varistor
EMERGENCIA est pulsado y el rel 52C se enciende ON, hay en la placa electrnica de la unidad
5VDC entre J8 + -J7 ? exterior.
Si
Si
144
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MCFH-13NV - E1 , MCFH-13NV - E2
MCFH-18NV - E1 , MCFH-18NV - E2
MCFH-24NV - E1 , MCFH-24NV - E2
PLACA ELECTRNICA INTERIOR
VLo Me Lo Hi
7 5 6 4 3 2 1 8
CONTROLES Y CHEQUEOS
Potencia suministrada a
220-240V CA
+
12V CC
+
5V CC
Corriente de corto-circuito
Sonda de temperatura de batera (RT12)
40
30
20
10
Sonda de
temperatura
ambiente (RT11) 0
0 10 20 30 40 50 60
145
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MUCFH-13NV - E1 , MUCFH-13NV - E2
MUCFH-18NV - E1 , MUCFH-18NV - E2 Sonda de desescarche
MUCFH-24NV - E1 , MUCFH-24NV - E2
PLACA ELECTRNICA EXTERIOR
Resistencia
CONTROLES Y CHEQUEOS
Temperatura
R601
Motor ventilador exterior Vlvula DC5~10V INTRODUCIR
}
(RT61)
}
Fusible
2A/250V
Intervalo de
descongelacin
Pin del inst. del
corto-circuito
+ J9
J8 } 5V CC
+
+
}
12V CC
52C Intervalo de descongelacin
12V CC Punto de descongelacin
Temperatura de cambio
Camisa del cable JPC y JPE
146
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
INVERTER
MXZ-18/32
147
CONTROLES Y CHEQUEOS GAMA DOMSTICA
No hay 4~10VDC entre los ter- Comprobar la conexin de maniobra entre unidad
minales N y 3 . interior y exterior.
Fusible Fusible cortocircuitado. Comprobar la vlvula de 2 vas, vlvula de 4 vas,
CONTROLES Y CHEQUEOS
Circuito principal No hay 310~340VDC entre los Comprobar los componentes principales (diode
terminales TAB62 y TAB63 del stack, electrolytic capacitor, y resistor) y cableados.
mdulo de potencia, para
MXZ-32NV/RV y 280VDC para la
MXZ-18NV/RV.
Salida de inverter La salida de voltaje entre los Reemplace la placa electrnica de control.
cables es diferente durante el
funcionamiento con inverter y
compresor desconectado.
CODIGOS DE COMPROBACION
Sntoma La unidad exterior no funciona
148
CONTROLES Y CHEQUEOS GAMA DOMSTICA
Termistor de temperatura El compresor se detiene cuando el termistor de evapo- Resistencia ohmica del
de evaporacin anormal. racin est cortado o abierto durante el funcionamien- termistor.
to del compresor. Conector del termistor
en la placa electrnica.
Termistor de temperatura El compresor se detiene cuando el termistor de desca- Resistencia ohmica del
de descarga anormal. ga est cortado o abierto durante el funcionamiento del termistor.
compresor. Conector del termistor
en la placa electrnica.
Termistor de temperatura El compresor se detiene cuando el termistor de alerta Resistencia ohmica del
de aleta anormal. est cortado o abierto durante el funcionamiento del termistor.
compresor. Conector del termistor
en la placa electrnica.
CONTROLES Y CHEQUEOS
Proteccin de sobrein- Cuando una intensidad de 30A para MXZ-18NV o 40A Salida de inverter.
tensidad. para MXZ-32NV o ms, es aplicada sobre el mdulo de Carga de gas.
potencia, el compresor para y arranca al transcurrir 3 Cortocircuito de aire
minutos. (unidad int. o ext.).
Filtros de aire sucios.
Compresor.
Proteccin de temperatu- Cuando el termistor de temperatura de descarga Carga de gas.
ra de descarga. detecta por encima de 120 C, el compresor se detie- Cortocircuito de aire en
ne y arranca en un perodo de 3 minutos. la unidad exterior.
La funcin se rearma a 80 C o menos. Sistema frigorfico.
Proteccin de temperatu- Cuando el termistor de temperatura de alerta detecta, Cortocircuito de aire en
ra de aleta. por encima de 28 C, el compresor se detiene y arran- la unidad exterior.
ca en un perodo de 3 minutos. Mdulo de potencia.
Motor ventilador de la
unidad exterior.
Proteccin de presin de Cuando la presin de baja disminuye a 0,05 Mpa (0,5 Vlvula de servicio.
baja. kgf/cm2G) durante 5 minutos o ms, el compresor se Tubera frigorfica con cur-
detiene y arranca en un perodo de 3 minutos. vas demasiado cerradas
o tubera taponada.
LEV.
Placa electrnica de con-
trol de la unidad exterior.
Proteccin de baja tem- Cuando la temperatura de descarga disminuye a 35 C Carga de gas.
peratura de descarga. o menos durante 50 minutos o ms, el compresor se Conector de la LEV en
detiene y arranca en un perodo de 3 minutos. la placa electrnica de
la unidad exterior.
Sustituir placa electrni-
ca en la unidad exterior.
Proteccin por clixn Cuando el clixn interno del compresor detecta por Salida del inverter.
interno del compresor. encima de 130 C el compresor se detiene y arranca en Compresor.
un perodo de 3 minutos. Carga de gas
Filtros de aire sucios
Cortocircuito de aire en la
unidad interior o exterior
149
CONTROLES Y CHEQUEOS GAMA DOMSTICA
cambian.
Reduccin de frecuencia Cuando la presin de baja disminuye a 0,05 MPa (0,5 Vlvula de servicio.
por proteccin de baja pre- kgf/cm2G) o menos, la frecuencia de operacin del Tubera frigorfica con cur-
sin. compresor se reduce, adems la vlvula de 2 vas abre. vas demasiado cerradas o
tubera taponada.
LEV.
Placa electrnica de con-
trol de la unidad exterior.
Proteccin contra seque- Cuando existen 5 C de diferencia o ms entre la tem- El sntoma no indica
dad. peratura de la unidad interior y la de la batera interior anomala en la unidad,
durante 10 minutos, la temperatura a conseguir de des- compruebe la siguiente.
carga de aire se reduce. Cantidad de gas.
Longitud de tubera.
Proteccin contra tem- Cuando la temperatura de descarga alcanza 95 C o Recircula el aire en la
peratura excesiva en el ms en una unidad funcionando en fro, la velocidd del unidad exterior.
cuerpo del compresor. ventilador exterior falla. Longitud de tubera.
150
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
BuP EuP BvP EvP BwP EwP x1
(+) V 22
x1
U V W W 22
x1
BuN 2k
x100
(-) BuN EuN BvN EvN BwN EwN
EuN 22
x1
BvN 2k
x100
EvN 22
x1
BwN 2k
x100
EwN 22
x1
V
U
W
V
W
V
151
CONTROLES Y CHEQUEOS GAMA DOMSTICA
4
3
CONTROLES Y CHEQUEOS
4
3
RESISTOR DETECTOR DE
CORRIENTE (DS 63)
MXZ-18NV/RV
M21.U48.362
152
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
PILA DE DIODOS (DS62)
MXZ-32NV/RV
M21.17 A.447
+ - (A)
(K)
K
- + (A)
A (K) x1 22
RESISTOR (R)
MXZ-32NV/RV
M21.17 A.362
153
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MUY IMPORTANTE
Para que estas mediciones coincidan cuando usted realice las comprobaciones que aparecen a continuacin,
CONTROLES Y CHEQUEOS
debe usted utilizar un elemento de medicin de iguales prestaciones al indicado ya que el valor especfico de la
resistencia, depende del tipo de tester que se use ya que el diodo del transistor no es lineal, por lo que las distin-
tas impedancias y voltajes del tester resultan de influencia.
154
CONTROLES Y CHEQUEOS GAMA DOMSTICA
CONTROLES Y CHEQUEOS
5
Temperatura de
aleta
Temperatura de aleta 90 C,
compresor para y rearranca a los
Comprobar unidad exterior.
Comprobar recirculacin de aire.
3 min. Comprobar ventilador exterior.
6 Se repite que
compresor para
y rearranca a los
Temperatura de
descarga.
Temp. descarga > 120 C, compresor
para y rearranca 3 min. despus. Pro-
Comprobar temp. de descarga
Comprobar circuito refrigerante.
teccin se elimina si T < 80 C o menos Comprobar carga de refrigerante.
3 min.
7
Corriente de
salida.
Si I ext. > 22,5 A frec. para a
40 Hz compresor para y rearranca
Comprobar mdulo transist.
Comprobar placa elect. exterior.
3 min. Comprobar compresor.
8
Presostato de
descarga.
Cuando presostato se conecta
debido al aumento de presin y frec,
el compresor para.
9
Corriente de
salida.
Cuando la corriente supera 22,5 A
frecuencia del compresor baja. Comprobar si los filtros estn
10
Unidad exterior
funciona a baja
frecuencia
Sobrecarga de
compresor.
Cuando se excede la carga lmite la
frecuencia se reduce.
sucios.
Comprobar si existe obstruccin en
circuito frigorfico.
11
Alta presin. Temperatura de tubo supera 50 C
en calor, frecuencia se reduce.
Comprobar si existen
recirculaciones de aire en batera
12
Temperatura
descarga
Cuando temperatura descarga
> 115 C frecuencia se reduce.
exterior.
tubera.
13
Presostato de
descarga.
Cuando se conecta el presostato la
frecuencia se reduce.
14
Termistor de
desescarche.
Termistor de desescarche de aire o
cortocircuito, compresor funciona
Comprobar termistor desescarche.
Comprobar placa electrnica
siempre. exterior.
ENCENDIDO FIJO
APAGADO
PARPADEO
155
CONTROLES Y CHEQUEOS GAMA DOMSTICA
MXZ-18LV Y MXZ-32AV
LEDS EN LA PLACA DEL INTERFACE EXTERIOR INVERTER DOMESTICO
N MXZ-18 LE854 LE855 Punto
Mtodo de deteccin Puntos a comprobar
MXZ-32 LE971 LE972 de anomala
1 Normal
Normal Leds lucen con la unidad en marcha
o paro.
2
Seal grave. Interface no recibe seal de placa de
control ext. durante 4 segundos.
Comprobar placa de control exterior.
3
Unidad exterior
Vlvula expans.
microprocesador.
Interface no puede recibir seal de
microprocesador a vlvula de
Comprobar interface de la placa
electrnica.
expansin.
no funciona
4
Termistores temperat. Cuando termistor de temperatura de
evaporacin/aspiracin. evaporacin se abre o cortocircuita,
Comprobar termistor aspiracin.
Comprobar termistor de temp.
compresor para y rearranca 3 min. evaporacin.
despus. Comprobar placa del interface.
5 Se repite que la
unidad exterior Correccin de
supercalent de
Cuando recalent es 2 C o menos y
temp. descarga 60 C o menos
Comprobar vlvulas de expans.
Comprobar carga de refrig.
para y rearranca aspiracin. 30 min., compresor para y rearranca
6 min. despus a los 3 min.
6
Vlvula de expansin. Modo fro, tubo lq. 10 C o menos en Comprobar placa electr. interface.
CONTROLES Y CHEQUEOS
8
Termistor de tubera de
lquido.
Cuando termistor de tubo de lquido Comprobar termistores de tubera
se cortocircuita o se abre el de lquido.
compresor para en modo fro. En Comprobar placa del Interface.
calor el compresor funciona de modo
continuo.
ENCENDIDO FIJO
APAGADO
PARPADEO
156
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
PK-FL
CONTROLES Y CHEQUEOS
Solo Fro
157
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Pantalla
Muestra cuando no ha batera. Pantalla RELOJ
CONTROLES Y CHEQUEOS
158
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL REMOTO
ENTRADA al control remoto SALIDA al control remoto
Unidad interior
CONTROLES Y CHEQUEOS
ENTRADA desde la unidad interior PLACA ELECTRONICA DE LA UNIDAD INTERIOR
Ventilador MARCHA-PARO.
Velocidad del ventilador: ALTA-BAJA.
Seleccin del ngulo del barredor.
Paro de emergencia. 2 cables de hilos polarizados
Unidad exterior
159
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Pulse el botn POWER ON/OFF.
Pulse el botn de MODO para seleccionar el funcionamiento de REFRIGE-
RACION.
Seleccione la temperatura deseada con el botn o .
Termostato
Ventilador interior
Autobarredor
Compresor
MIN. 3 minutos 1
1 Aunque la temperatura ambiente sea superior a la temperatura seleccionada durante este perodo, el compresor no empezar a
funcionar hasta que el perodo haya concluido.
160
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL FL
Proteccin contra escarcha en la batera.
Cuando la temperatura de la batera interior es de 15 C o inferior, la proteccin contra escarcha proceder de
modo siguiente:
<Condicin inicial>
Tras el funcionamiento continuo del compresor durante un mnimo de 3 minutos y con una lectura de la sonda de
tubo interior es de 15 C o inferior durante 3 minutos, se iniciar la proteccin contra escarcha.
<Proteccin contra escarcha en la batera>
El compresor se para durante 6 minutos y vuelve a ponerse en marcha.
Si se cumple la condicin inicial de nuevo durante los 10 primeros minutos de funcionamiento del compresor, se
parar la unidad interior y la exterior, apareciendo en el control remoto el cdigo de comprobacin.
<Condiciones finales>
La proteccin contra escarcha de la batera se interrumpir cuando no se vuelva a cumplir la condicin inicial durante
el perodo autorizado, o cuando se detenga el modo de refrigeracin o cambie a otro modo.
(2) Control del ventilador interior
La velocidad del ventilador interior depender del ajuste en el control remoto.
Sin embargo, si se detecta una anomala en la unidad exterior, la velocidad del ventilador ser baja, independientemente
del ajuste en el control remoto.
(3) Control del deflector
La posicin del deflector depender del ajuste en el control remoto.
CONTROLES Y CHEQUEOS
(4) Deteccin de anomalas en la unidad exterior
Tras el funcionamiento continuo del compresor durante un mnimo de 3 minutos, y si la diferencia entre la temperatura de
la batera interior y la ambiental queda fuera del rango C durante 1 minuto, la velocidad del ventilador interior pasar a ser
baja. Cinco minutos despus, si la diferencia contina estando fuera del rango C, se considerar que la unidad exterior tiene
una anomala. Por tanto, el compresor se detendr y aparecer el cdigo de comprobacin en el control remoto.
El cdigo de comprobacin en el control remoto
Rango A: La temperatura de la batera interior es como mnimo 5 superior a la ambiental.
Rango B: La temperatura de la batera interior es 5 la temperatura ambiental.
Rango C: La temperatura de la batera interior es como mnimo 5 inferior a la ambiental.
161
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Pulse el botn de encendido MARCHA/PARO
Pulse el botn de MODO para seleccionar el modo de funcionamiento en
DESHUMECTACION.
Seleccione la temperatura deseada con el botn o .
La temperatura La temperatura
El funcionamiento El funcionamiento
ambiental ambiental supe-
se inicia con pul- concluye con el
iguala a la ra la selecciona-
sador en marcha. pulsador en paro.
seleccionada. da.
Termostato
Ventilador interior
Autodeflector
Compresor
MIN. 3 minutos 2
2 Aunque la temperatura ambiental sea superior a la temperatura de ajuste durante este perodo, el compresor no empezar a funcionar hasta
que el perodo haya concluido.
162
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Pulse el botn POWER ON/OFF.
Pulse el botn de MODO para seleccionar el funcionamiento de modo
VENTILACION.
(1) Control del ventilador interior
Pulse el botn POWER ON/OFF.
CONTROLES Y CHEQUEOS
(2) Control del autobarredor
La posicin del autobarredor depende del ajuste en el control remo-
to.
<Funcionamiento>
Pulse el botn POWER ON/OFF.
Compruebe si la hora actual est correcta o no.
Pulse el botn de PARO o MARCHA y seleccione el temporizador
deseado.
Seleccione la hora del temporizador usando los botones de hora y
minuto.
163
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL FL
2-5 Funcionamiento de prueba
*(1) Conecte el encendido principal de la Control remoto con cubierta de la batera en la parte posterior
unidad. extrada. La pantalla continuar parpadeando.
(2) Cambie el interruptor de ajuste en la
parte posterior del control remoto a Cambie el interruptor de ajuste La pantalla continuar
SET CHECK y TEST RUN a SET parpadeando
empezarn a parpadear.
*(3) Pulse el botn MINUTO y el modo
modo de funcionamiento aparecer
en la pantalla. (Vea el ejemplo ilus-
trado de pantalla en la izquierda).
*(4) Pulse el botn MODO, cambie el
modo a ventilacin y asegrese de
que no est bloqueada la salida del
caudal de aire.
*(5) Pulse el botn MODO, cambie el
modo a refrigeracin y asegrese de
que abre la salida del caudal de aire
fro.
*(6) Pulse el botn ventilacin y aseg-
CONTROLES Y CHEQUEOS
164
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL FL
2-7 Funcin de puente y microrruptor en la placa electrnica interior
1. Puente
JR01... Puente para los autodeflectores
JR01 cortado para unidades sin autodeflectores.
JR02... Puente para temperatura para iniciar la prevencin antiescarcha
Cortando JR02 cambia la temperatura de + 1 C a 3 C.
JR03... Puente para ajuste de temperatura seleccionada en modo calefaccin
En modo calefaccin, el aire caliente se concentra en la parte superior de la habitacin. La unidad interior
instalada en la parte superior de la habitacin detecta la temperatura de aire ms alta que la temperatura
actual en la habitacin. Esta diferencia es aproximadamente de 4 C. Por lo tanto, la temperatura detectada
por el termistor de temperatura ambiente deber corregirse bajando 4 C.
La unidad con el JR04 adjunto har este ajuste.
JR04... Puente para velocidad del ventilador interior durante paro del termostato en modo CALEFACCION.
Cortando JR04 cambia la velocidad de extrabaja a baja.
JR05... Puente para deteccin de anomalas en la unidad exterior
Cortando JR05 hace imposible la deteccin (casos de anomala no pueden detectarse).
JR06... Puente para autoreinicio de funcionamiento
CONTROLES Y CHEQUEOS
Cortando JR06 hace posible el reinicio automtico.
2. Microrruptor
SW1 (Funcin del interruptor)
PK-1.6FL
PK-2.5FL PK-4FL PK-2FL
PK-3FL
0 1 2 3
165
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL FL
SW2 (Interruptor de unidad)
PK-1.6/2FL PK-2.5/4FL
CONTROLES Y CHEQUEOS
166
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
4 Sensor de drenaje irregular
5 Bomba de drenaje irregular
6 Proteccin congelacin
8 Unidad exterior irregular
9 Ninguna
La unidad se detiene
despus de funcionar La funcin de proteccin est funcionando. Vea cdigo de comprobacin en el panel
de 5 a 20 segundos del control remoto. Vea pg. 18.
167
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
CONTROLES Y CHEQUEOS
J
Solo Fro
169
CONTROLES Y CHEQUEOS GAMA COMERCIAL
DISPLAY SELECT
MODE
SELECT
TEMP Pulsador eleccin
proceso:
Escala de (COOL) = Fro.
temperaturas. (FAN) = Ventilador.
La luz intermitente
indica la 12 29
temperatura 11 28
ambiente. 10 27
Luz fija la FAN SPEED
9 26
temperatura
deseada. 8 25
7 24
Selector de
6 23 velocidad aire
5 22 tratado unidad
4 21 interior.
3 20 HIGH = Velocidad
2 19
alta.
DOWN LOW = Velocidad
1 18
baja.
Bajar.
Presionando
hacemos descender
SWING
la temperatura o la
diferencia horaria, LOUVER
segn la escala que
utilicemos. Funcionamiento
en abanico.
UP TIMER MODE
170
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Interruptor temporizador. 11
10
28
27
Escala temperatura. 9
8
26
25
Escala tiempo. 7
6
24
23
Autodiagnosis de averas. 5
4
22
21
Test de funcionamiento.
3 20
2 19
1 18
Unidad interior
CONTROLES Y CHEQUEOS
Cable de 12 hilos con polaridad.
Mxima longitud 50m (164ft).
Ventilador: ON-OFF/MARCHA-PARO.
Velocidad del ventilador: HIGH-LOW/ALTA-BAJA.
Barredores: ON-OFF/MARCHA-PARO. Cable de 2 hilos sin polaridad
Bomba de drenaje: ON-OFF.
<Opcional>.
Paro de emergencia.
Unidad exterior
Trabaja el mecanismo de
proteccin del compresor. Recibe rdenes del
microprocesador interior.
Paro de emergencia.
SALIDA de la unidad exterior
171
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Pulse el botn de encendido MARCHA-PARO (POWER ON-OFF)
Pulse el botn de seleccin de modo para seleccionar el modo de funcio-
namiento de REFRIGERACION (COOL)
Compruebe lmpara TEMP
est encendida y seleccione la temperatura
deseada con el botn arriba y abajo (UP o DOWN).
NOTAS: 1. Cuando la lmpara TIMER est encendida, pulse el botn de
seleccin de pantalla (SELECT DISPLAY) para cambiar la pan-
talla a modo temperatura.
2. La temperatura seleccionada cambia en 1 C en el rango
18~29 C, cada vez que se pulsa el botn arriba o abajo.
3. La lmpara encendida muestra la temperatura elegida, y la luz
Fija Parpadeante OFF parpadeante muestra la temperatura ambiente.
Cuando la temperatura ambiente es igual a la temperatura selec-
cionada, la lmpara se mantiene encendida, 0,5 segundos de
CONTROLES Y CHEQUEOS
MARCHA (ON)
Termostato PARO (OFF)
MARCHA (ON)
Compresor PARO (OFF)
Mnimo 3 minutos 1
1 Aunque la temperatura ambiente sea superior a la temperatura de ajuste durante este perodo, el compresor no empezar a funcionar hasta que el perodo
haya concluido.
172
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
(4) Deteccin de anomalas en la unidad exterior
Tras el funcionamiento continuo del compresor durante un mnimo de 3 minutos y si la diferencia entre la temperatura de la
batera interior y la ambiental queda fuera del rango C durante 1 minuto, la velocidad del ventilador interior pasar a ser baja.
Cinco minutos despus, si la diferencia contina estando fuera del rango C, se considera que la unidad exterior sufre una
anomala. Por tanto, el compresor se detiene y la localizacin del problema se indica en el control remoto.
RANGO A: La temperatura de la batera interior es como mnimo 5 superior a la ambiental.
RANGO B: La temperatura de la batera interior es 5 la temperatura ambiental.
RANGO C: La temperatura de la batera interior es como mnimo 5 inferior a la ambiental.
(6) Control de la bomba de drenaje (opcin)
La bomba de drenaje funciona en modo refrigeracin. Cuando se detiene la refrigeracin o cambia a otro modo, la bomba
de drenaje contina su funcionamiento durante 3 minutos ms. Aun cuando el modo de comprobacin inicia su funciona-
miento durante la refrigeracin, la bomba de drenaje seguir funcionando durante 3 minutos ms.
<Sensor de drenaje>
Cuando funcionan a la vez la unidad y la bomba de drenaje, la sonda de drenaje detecta la temperatura. Esta temperatura
indica si el nivel del agua de drenaje est por encima o por debajo del sensor.
Si el nivel del agua se eleva por encima de la sonda debido a un mal funcionamiento, la unidad iniciar el modo de com-
probacin. El funcionamiento se detendr y slo la bomba de drenaje seguir funcionando durante 3 minutos ms. Cuando
cualquiera de las siguientes condiciones se cumpla, se considera que el sensor de drenaje est bajo agua.
A pesar que el sensor de drenaje haya sido calentado por la resistencia de la sonda durante ms de 40 segundos, su incre-
mento de temperatura es inferior a 20 grados.
La temperatura del sensor de drenaje es inferior a 63 C.
173
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Para eliminar el calor remanente, el ventilador interior contina su funcionamiento en velocidad BAJA (LOW) durante
ms de 1 minuto despus de que se haya detenido el funcionamiento de calefaccin.
2.4 Funcionamiento de TEMPORIZADOR
<Funcin temporizador>
PARO AUTOMATICO (AUTO STOP)... El acondicionador de aire se detiene
al finalizar el tiempo fijado.
ARRANQUE AUTOMATICO (AUTO START)... El acondicionador de aire arranca al
finalizar el tiempo fijado.
<Funcionamiento de paro automtico del temporizador>
Mientras la lmpara POWER est encendida, pulse el botn del modo
174
CONTROLES Y CHEQUEOS GAMA COMERCIAL
5. Funcin autodiagnstico
(1) Cuando hay algn problema durante el funcionamiento, la unidad se detiene y aparece la localizacin del problema
mediante las luces del temporizador en el control remoto. Todas las otras luces permanecern apagadas.
(2) Para activar el funcionamiento de autodiagnstico, pulse simultneamente los botones de arriba y abajo (UP-DOWN)
durante ms de dos segundos durante el funcionamiento con la lmpara TEMP
. encendida (ON).
(3) Las luces del temporizador muestran el ltimo problema. Los datos del problema permanecern memorizados hasta que
aparezca un nuevo problema, hasta cuando el interruptor se apague.
(4) Todos los botones excepto el de encendido MARCHA/PARO (POWER ON/OFF) son inutilizables durante el modo de
autodiagnstico.
(5) Para detener el modo autodiagnstico, pulse el botn de encendido MARCHA/PARO (POWER ON/OFF).
CONTROLES Y CHEQUEOS
interior/exterior.
Compruebe el cableado.
Deteccin de anomala en la
Compruebe la unidad exterior.
Unidad exterior unidad exterior.
Compruebe la sonda de batera
Mal funcionamiento de la sonda
interior.
de batera interior.
Detectada fase reversible.
Unidad
N 1
Sonda
temperatura Falso contacto del conector.
Compruebe el conector.
Compruebe la sonda. }
Si no hay avera cambie la
ambiente Mal funcionamiento de la sonda.
Unidad placa electr-
(RT1)
N 2 nica interior.
Unidad
N 1
Sonda
batera Falso contacto del conector.
Compruebe el conector.
Compruebe la sonda. }
Si no hay avera cambie la
interior Mal funcionamiento de la sonda.
Unidad placa electr-
(RT2)
N 2 nica interior.
Unidad
N 1 Sensor
Falso contacto del conector.
Compruebe el conector.
Compruebe la sonda. }
drenaje Si no hay avera cambie la
Mal funcionamiento de la sonda.
Unidad (DS) placa electr-
N 2 nica interior.
Unidad
N 1
Proteccin
desbor-
Compruebe la bomba de drenaje.
Mal funcionamiento de la bomba Compruebe el sensor de drenaje. }
de drenaje. Si no hay avera cambie la
damiento
Unidad Sensor de drenaje mal montado. placa electr-
de drenaje
N 2 nica interior.
Unidad
Prevencin de Recirculacin de aire.
N 1 Extraiga obstculo.
sobrecorriente Filtro obstruido.
Compruebe filtro del aire.
o hielo Mal funcionamiento del
Unidad Compruebe ventilador interior.
en batera ventilador interior.
N 2
175
CONTROLES Y CHEQUEOS GAMA COMERCIAL
1. Microrruptor
CONTROLES Y CHEQUEOS
176
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
AJ
CONTROLES Y CHEQUEOS
(UNIDADES ANTERIORES AL AO 1997)
Solo Fro
177
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Durante el funcionamiento del control remoto o del temporizador semanal, el botn OFF/ON se desconecta invalidando el
botn TIMER MODE y la puesta en mrcha/paro automtico se detiene si en la unidad se cambia a control remoto durante el
funcionamiento de AUTO STOP/AUTO START la unidad permite el funcionamiento del temporizador.
1) Seccin Temperatura/Temporizador.
I) Cuando la unidad est en AUTO STOP es posible cambiar de la pantalla de tiempo a la de temperatura, pulsando el
interruptor DISPLAY SELEC.
II) Cuando la unidad no est en AUTO START no es posible cambiar de pantalla y sta siempre mostrar el tiempo.
III) Cuando la unidad no est en modo temporizador, la seleccin de la pantalla no es posible y sta permanecer en la
escala de temperatura. Cuando la unidad deja de funcionar la pantalla se apaga.
CONTROLES Y CHEQUEOS
2) Escala de temperaturas.
Test
La unidad pone en funcionamiento el test cuando se pulsan simultneamente los botones UP y DOWN, durante dos
segundos cuando la luz del temporizador (TIMER) est encendida y la unidad parada.
Durante el test la funcin AUTO STOP trabajar automticamente y se parar al cabo de 2 horas.
La temperatura programada no aparecer durante el test.
La temperatura de la habitacin aparecer en pantalla pulsando el botn selector de pantalla, DISPLAY SELECT.
El test se puede interrumpir pulsando ON/OFF o TIMER MODE.
178
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
Sensor del tubo
(TH2) termistor. problema, cambiar cuadro
microprocesador interior).
179
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL AJ-EJ
Funcin de emergencia
Cuando el control remoto o el microprocesador estn averiados, es posible poner en marcha la refrigeracin de emergencia, si
no hay otra avera.
1) Funcin refrigeracin es posible cuando sobre los interruptores (SW1 <1.B>) 1, 2 y 3 en ON y el 4 en OFF. Estn
situados en la carta electrnica interior (ver figura).
CONTROLES Y CHEQUEOS
2) Asegurarse de accionar el interruptor manual hacia ON primero el de la unidad exterior y luego el de la interior.
3) Durante la refrigeracin de emergencia el ventilador trabaja en velocidad alta, el compresor funciona continuamente y
el difusor se detiene. En las unidades que incorporen sistema de bombeo del agua de condensacin, ste funcionar.
180
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
K
CONTROLES Y CHEQUEOS
Bomba de Calor
181
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ON (Marcha)
STAND-BY
PANTALLA
Se visualiza desde el inicilo del ciclo de
calefaccin hasta que el aire caliente es
propulsado por la turbina.
DEFROST (Desescarche)
PULSADORES
HEAT, COOL, AUTO, DRY
CONTROLES Y CHEQUEOS
Visualizacin del modo de
funcionamiento.
NOTA:
Al pulsar el botn de puesta en marcha ON OFF, se visualiza
CENTRALLY CONTROLLED durante 2 segundos.
182
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ENTRADA SALIDA
Placa electrnica del control
remoto
Desconexin-conexin. Control remoto
Seleccin de modo Procesa y transmite rdenes Pantalla de cristal lquido (LCD).
REFRIGERACION/DESHUMECTACION-
AUTOMATICO/CALEFACCION.
Ajuste del termostato.
Seleccin de modo de funcionamiento
por TEMPORIZADOR y ajuste del
Temporizador.
Seleccin de velocidad del ventilador:
ALTA-BAJA.
Seleccin del deflector automtico AIR
DISCHARGE (Descarga de aire).
Conexin del funcionamiento de test.
Conexin del modo de comprobacin.
(Autodiagnstico de averas).
CONTROLES Y CHEQUEOS
Cable de dos hilos no polarizados
distancia mxima 500 metros
Seal
PLACA ELECTRONICA
ENTRADA de la Unidad Interior
Recibe las rdenes del mando a distancia y
los datos de temperatura de la unidad
Sonda de temperatura ambiente (RT1). interior.
Sonda de batera interior (RT2). Procesa las rdenes y los datos .
Sensor de drenaje. Control del funcionamiento Interior y Exterior.
Funcin de autodiagnstico.
* Funcionamiento del control del sistema.
* Funcionamiento de emergencia.
* Ajustado mediante los interruptores de la
placa electrnica interior.
SALIDA a la unidad interior
Transmite alimentacin al mando a distancia.
Control independiente
Cambio del modo de
funcionamiento
de la unidad exterior Unidad exterior
REFRIGERACION-
CALEFACCION.
Funcionamiento del
dispositivo de proteccin
del compresor.
Desescarche:
MARCHA-PARO.
Control de velocidad del
ventilador.
Control ON-OFF de la
resistencia del crter.
Funcin de autodiagnstico.
183
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Presione el botn POWER ON/OFF.
Presione el botn para visualizar .
Presione el botn TEMP para seleccionar la temperatura deseada.
NOTA: La temperatura seleccionada vara 1 C cada vez que se pulsa
el botn o .
ON
Termostato OFF
ON
OFF
Resistencia elctrica OFF
ON
Compresor OFF
Mnimo 3 minutos 1
1 Aunque la temperatura ambiente supere la temperatura seleccionada durante este perodo, el compresor no empezar a funcionar hasta que el perodo haya concluido.
184
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Cuando la deteccin de anomalas de la unidad exterior se libera y la velocidad del ventilador vueve a ser la seleccionada,
el control de ciclo silencioso funcionar.
(a) Control normal.
CONTROLES Y CHEQUEOS
(i) La velocidad del ventilador BAJA/ALTA depende de la seleccin en el control remoto independientemente del funciona-
miento ON/OFF del termostato.
(ii) La velocidad del ventilador continuar siendo baja si se detecta alguna anomala en la unidad exterior. (5 minutos).
Cuando se libera la deteccin de anomalas, la velocidad del ventilador vuelve a ser la seleccionada.
5 minutos 5 minutos
185
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<RETORNO AUTOMATICO>
Velocidad del VENTILADOR: BAJA.
descarga 40 60
horizontal descarga descarga
descarga 20 40 60
horizontal descarga descarga descarga
Cuando se selecciona una descarga de 40 o 60 grados con velocidad de ventilador BAJA en funcionamiento de REFRIGERA-
CION, aparecer AUTO RETURN bajo la visualizacin de la temperatura. Una hora despus, la direccin de la descarga vol-
ver automticamente a la posicin horizontal y AUTO RETURN desaparecer. Si la direccin de descarga se seleccio-
na horizontal durante la indicacin AUTO RETURN, se cancela el tiempo de recuento del retorno automtico.
186
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Deflector automtico>
(a) El deflector funciona con un motor DC12V.
(b) La direccin de descarga se selecciona dependiendo del nmero de pulsaciones enviadas.
(c) Antes de iniciar el manejo del deflector automtico, detecta primero la posicin, y produce el nmero de pulsacio-
nes para cada descarga de aire.
(d) La velocidad del funcionamiento del deflector automtico de abertura y cierre est seleccionado en 200 pulsaciones/seg.
(e) Mtodo de funcionamiento del deflector automtico.
Deteccin de posicin inicial:
Salida 1448 (2~3CV), 1498 (4~6CV).
Posicin seleccionada:
Produccin del nmero de pulsaciones indicadas en grfico inferior a la direccin cerrada.
CONTROLES Y CHEQUEOS
Descendente C 813 817
RANGO B
RANGO C
187
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Presione el botn POWER ON/OFF.
Presione el botn para visualizar .
ON
Termostato OFF
ON
OFF
Resistencia elctrica OFF
ON
Compresor OFF
Mnimo 3 minutos 1
1 Aunque la temperatura ambiente supere la seleccionada durante este perodo, el compresor no empezar a funcionar hasta que el perodo haya concluido.
188
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
(3) Control del deflector automtico y bomba de drenaje
Es el mismo que en el modo REFRIGERACION.
(4) Deteccin de anomalas en la unidad exterior
No se podrn detectar anomalas en la unidad exterior durante el funcionamiento de DESHUMECTACION.
189
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Presione el botn POWER ON/OFF.
Presione el botn para visualizar .
Presione el botn TEMP para seleccionar la temperatura deseada.
NOTA: La temperatura seleccionada vara 1 C cada vez que se pulsa
el botn o .
Calefaccin entre 17 y 28 C.
<Visualizacin en modo CALEFACCION>
[DESESCARCHE]
El smbolo [DEFROST] slo se visualiza durante el funcionamiento de
desescarche [STANDBY] se visualiza desde el inicio del modo calefaccin
hasta que el aire caliente comienza a surgir.
ON
Termostato OFF
Extra BAJA 1 BAJA Extra BAJA 1
1 Cambiable con
ON resistencias
BAJA o ALTA BAJA o ALTA
Ventilador interior OFF interiores J1-7
y J1-8.
Depende del ajuste Depende del ajuste
en el control remoto en el control remoto
ON
Deflector automti- OFF Horizontal Horizontal
ON
OFF
Bomba de drenaje OFF
OFF... durante:
ON Paro del termostato
Resistencia elctrica OFF Ajuste de calor
Ajuste de calor Ajuste de calor Desescarche
ON
Compresor OFF
Mnimo 3 minutos 2
ON
Indicador power ON OFF
2 Aunque la temperatura ambiente sea superior a la de seleccin durante este perodo, el compresor no empezar a funcionar hasta que el perodo haya concluido.
190
CONTROLES Y CHEQUEOS GAMA COMERCIAL
En los casos siguientes, la direccin de descarga ser horizontal independientemente del ajuste del control remoto.
Durante el ajuste de calor con velocidad de ventilador EXTRA-BAJA.
Durante el desescarche con el ventilador interior en OFF.
Durante el termostato OFF.
(b) Modo OSCILANTE (SWING).
(i) El motor del vane se pone en marcha cuando se selecciona el modo SWING.
El motor del vane est continuamente ON durante el modo SWING.
(ii) En los siguientes casos, la direccin de descarga es horizontal independientemente del ajuste del control remoto.
Durante el ajuste de calor con velocidad de ventilador EXTRA-BAJA.
Durante el desescarche con el ventilador interior en OFF.
Durante el termostato OFF.
(4) Control de la resistencia elctrica
CONTROLES Y CHEQUEOS
Cuando la temperatura ambiental sea 3 grados inferior a la de ajuste la resistencia elctrica se pondr en marcha.
Cuando la temperatura ambiental sea igual a la de ajuste, la resistencia elctrica se apagar.
Durante el ajuste de calor, la resistencia elctrica no funcionar.
<Prevencin de sobrecalentamiento>
Si la sonda de batera inferior se eleva a 60 C o los sobrepasa, no podr funcionar la resistencia elctrica.
Si la sonda de batera inferior alcanza 55 C o desciende ms podr funcionar la resistencia elctrica.
191
CONTROLES Y CHEQUEOS GAMA COMERCIAL
(grados) RANGO A
RANGO B
RANGO C
192
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Presione el botn POWER ON/OFF.
Presione el botn para visualizar .
Presione el botn TEMP para seleccionar la temperatura deseada.
NOTA: La temperatura seleccionada vara 1 C cada vez que se pulsa
el botn o .
Automtico entre 19 y 28 C.
El funcionamiento automtico cambia el modo refrigeracin
o calefaccin, segn la temperatura ambiente.
CONTROLES Y CHEQUEOS
Si la temperatura ambiente es superior a la seleccionada, el funcionamiento se inicia en modo REFRIGERACION.
Si la temperatura ambiente es igual o inferior a la seleccionada, el funcionamiento se inicia en modo CALEFACCION.
Cuando el funcionamiento AUTO se inicia despus de la REFRIGERACION o la CALEFACCION, contina el modo previo.
(2) Cambio de modo
El modo calefaccin cambia a REFRIGERACION cuando han pasado 15 minutos desde que la temperatura ambiente
supera 2 grados a la seleccionada.
El modo de REFRIGERACION cambia a calefaccin cuando han pasado 15 minutos desde que la temperatura ambiente es
2 grados inferior a la temperatura seleccionada.
To + 1
To
To 1
To 2
15 minutos Cambio de modo
Inicio 15 minutos (REFRIGERACION CALEFACCION)
Mnimo 3 minutos
Modo CALEFACCION Modo REFRIGERACION Modo CALEFACCION
ON
Compresor
OFF
Mnimo 3 minutos
5 C
Rango calefaccin
193
CONTROLES Y CHEQUEOS GAMA COMERCIAL
<Funcionamiento>
Para cambiar la direccin del caudal de aire, pulse el botn AIR DIS-
CHARGE UP/DOWN.
NOTA: El ngulo del deflector puede cambiarse a un ngulo superior
desconectando J5-3.
(Resistencia de unidades interiores).
horizontal 20 40 60
Descarga
Descarga descendente
OSCILACION
Cambia pulsando el
botn AIR DISCHARGE
UP/DOWN
194
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
<Ejemplo de seleccin del temporizador> ON/OFF.
Control remoto
Encienda el interruptor principal, 12 horas antes de proceder al paso 2 tenga
1
en cuenta el funcionamiento de la resistencia del crter.
Cuando se inicia un funcionamiento de prueba, el temporizado debera seleccionar en 2 horas. La unidad se detendr automticamente
despus de 2 horas.
195
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Cdigo 1 2 3 4 5 6 7 8
Temperatura
40 ~ 1 C ~ 10 C ~ 15 C ~ 20 C ~ 25 C ~ 30 C ~ 35 C ~ 40 C
batera interior
Cdigo 9 10 11 12 13 14 15
Temperatura Anomala
45 C ~ 50 C ~ 55 C ~ 60 C ~ 70 C
batera interior de la sonda
Si existiese un mal funcionamiento del control remoto o del microprocesador pero el resto es normal, se inicia el funcio-
namiento de emergencia ajustando el microrruptor SW3 de la placa electrnica interior.
<Previo al funcionamiento de emergencia>
1. Asegrese que el compresor y el ventilador interior funcionan con normalidad.
2. Localice la avera con la funcin de autodiagnosis. Cuando la funcin de autodiagnstico indica protective function
is working libere la funcin de proteccin antes de iniciarse el funcionamiento de emergencia.
PRECAUCION: Cuando la funcin de autodiagnstico indica un cdigo de comprobacin P5 (mal funcionamiento
de bomba de drenaje), no inicie el funcionamiento de emergencia porque el drenaje podra inundarse.
<Funcionamiento>
1. Para refrigeracin de emergencia, seleccione el microrruptor SW3-1 en ON y SW3-2 en OFF.
Para calefaccin de emergencia, seleccione el microrruptor SW3-1, 2 en ON.
NOTA: El botn POWER ON/OFF del control remoto no puede poner en marcha ni detener el funcionamiento de emergencia.
PRECAUCION: No utilice la refrigeracin de emergencia durante ms de 10 horas, porque podra congelarse la batera
interior.
196
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
3 CV 230 1360
240 1370
220 1150
4 CV 250 1160
240 1170
220 1150
5 CV 230 1170
240 1190
220 1160
6 CV 230 1180
240 1200
197
CONTROLES Y CHEQUEOS GAMA COMERCIAL
198
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
Control individual Control doble Control triple
SW6-1 OFF ON (Doble N 1) ON (Triple N 1)
SW6-2 OFF ON (Doble N 2) ON (Triple N 2)
SW6-3 OFF OFF ON (Triple N 3)
SW6-4 OFF OFF ON
(6) SW7
SW7-1, 7-3, 7-4): Seleccin de capacidad
SWA
SWB
3 : Techo alto
2 : Estndar 4 - direccin de descarga 2,4 2,7 3,0
1 : Silencioso 3 - direccin de descarga 2,7 3,0 3,3
(8) SWB (Selector del nmero de salida de descarga) (9) SWC (Selector de opcin)
Opcin
2 : (No utilizado)
Para montar el filtro de alta eficiencia opcional,
3 : Direccin de descarga coloque este interruptor en opcin.
4 : Direccin de descarga Standard
(Estndar)
199
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ON
Termostato
OFF
ON
Compresor
OFF
Resistencia del crter ON 60 minutos 60 minutos 60 minutos 60 minutos 60 minutos Repite 60 minutos
(sin cable puente J3) OFF ON/OFF
Vlvula de 4 vas ON
(REFRIGERACION) OFF
10 minutos 10 minutos 1
Vlvula de 4 vas ON
(CALEFACCION) OFF
3 minutos 3 minutos
ON
Vlvula Bypass
OFF
ON
Ventilador exterior
OFF
200
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ON
Ventilador interior
OFF
35 grados (SW5-3 OFF) o 20 grados (SW5-3: ON) de direccin de descarga
ON Seleccin Seleccin
de direccin (El control remoto todava visualiza la direccin seleccionada) de direccin
OFF
Unidad exterior
ON
Vlvula de 4 vas
OFF
CONTROLES Y CHEQUEOS
ON
Vlvula bypass
OFF
ON
Ventilador exterior
OFF
ON
Compresor
OFF
201
CONTROLES Y CHEQUEOS GAMA COMERCIAL
NOTA 1: Si se detiene la unidad durante el desescarche, el intervalo de escarche siguiente ser de 50 minutos.
NOTA 2: Si est en marcha una funcin de proteccin durante el desescarche, se detendr el compresor.
Despus del retraso de 3 minutos, volver a arrancar el desescarche. En este caso, se incluye un retraso de 3 minutos
en el tiempo de desescarche.
Si se pone en por segunda vez la funcin de proteccin, la unidad dejar de funcionar y se visualizar el cdigo de
CONTROLES Y CHEQUEOS
comprobacin.
El intervalo de desescarche siguiente ser de 30 minutos.
NOTA 3: Cuando concluye el desescarche, se borra el tiempo total de funcionamiento del compresor.
(4) Condiciones finales
El desescarche se detiene cuando se cumple alguna de las condiciones siguientes:
El desescarche ha continuado durante 15 minutos.
La lectura de la sonda de batera exterior es de 22 o superior durante los primeros 75 segundos del inicio del desescarche.
La lectura de la sonda de batera exterior es de 8 C o superior despus de 75 segundos de desescarche.
El botn de encendido POWER ON/OFF se pulsa OFF durante el desescarche.
3.6.
(1) Control de la vlvula de Bypass
<Modo refrigeracin>
Cuando se detiene la unidad debido a la prevencin contra el escarche de la batera, se conecta la vlvula de Bypass (ON).
Pasada una hora desde la parada del compresor, la vlvula de Bypass se detiene (OFF).
Cuando el compresor funciona con la vlvula de Bypass en ON durante ms de 30 minutos, sta se desconecta (OFF).
Cuando el compresor se detiene con la vlvula de Bypass en OFF, sta se pone en marcha (ON) y permanece as
durante 3 minutos.
<Modo calefaccin>
Cuando la unidad arranca (ON) por primera vez tras conectar el ICP, o cuando arranca con el compresor en OFF durante
30 minutos o ms, si la lectura de la sonda de batera exterior es de 12 C o superior, se pondr en marcha la vlvula de
bypass (ON).
Cuando funciona el presostato de alta presin (63H1), la vlvula de Bypass tambin funcionar.
Cuando la vlvula de Bypass ha estado en ON durante 30 minutos:
Si el presostato de alta presin ya ha desconectado, la vlvula de Bypass pasar a estar en OFF.
Si no es as, el paso de potencia til del ventilador se mantiene en 70 durante 3 minutos. Mientras tanto, si regresa el
presostato de alta presin, la vlvula de bypass pasar a estar en OFF.
De otro modo se iniciar el control normal del ventilador.
Cuando vara o se detiene el modo de funcionamiento, la vlvula de bypass estar en ON y se mantendr as duran-
te 3 minutos.
<Funcionamiento del desescarche>
La vlvula de bypass est en OFF.
(2) Control de la resistencia de crter
Con el cable puente J3.
La resistencia de crter est en ON desde el encendido (POWER ON) hasta que arranca el compresor, y volver a
ponerse en ON una hora despus de la parada del compresor.
Sin el cable puente J3.
La resistencia del crter est en ON desde el encendido (POWER ON) hasta que arranca el compresor, y despus
repetir una hora en ON y otra en OFF.
202
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
SW2 (pulsador): Indicacin del estado de salida y del cdigo de comprobacin.
SW3-1,2 (microrruptor): Indicacin de informacin sobre el estado de salida.
Para mayor informacin, consultar la pg. 50.
(4) Potencia til del ventilador del 100%
La potencia til se fija en el 100% uniendo los terminales en el conector CN22. Sin embargo el ventilador se detiene cuan-
do el compresor est en OFF o desescarcha. CN22 en circuito abierto restaura el control normal del ventilador.
(5) Ajuste del tiempo
El cortocircuito del conector CN21 acorta el tiempo de la siguiente manera:
Perodo de control del ventilador: 30 segundos-3 segundos.
Funcin de 3 minutos de retraso: 3 minutos-3 segundos.
Desescarche mximo: 15 minutos-15 segundos.
Intervalo de desescarche: 30~120 minutos-3~12 segundos.
Tiempo de compresor ON/OFF para vlvula de bypass ON/OFF: 30 minutos-3 segundos.
Tiempo de compresor ON para iniciar otras funciones: x minutos-x segundos.
Funcionamiento de la resistencia de crter: 1 hora-6 segundos.
203
CONTROLES Y CHEQUEOS GAMA COMERCIAL
LOCALIZACION DE AVERIAS
1. AVERIAS EN EL FUNCIONAMIENTO DE PRUEBA
No se visualiza nada en el 1) Control remoto averiado. 1) Mida el voltaje entre los terminales del control
control remoto a pesar de 2) Cortocircuito del cable de transmisin. remoto, si no hubiera, retire los terminales y
haberse pulsado POWER 3) Falso contacto del CN40 interior. mida el voltaje entre cables. Si el voltaje est
ON. 4) CN40 unido a una subunidad. comprendido entre 6V DC y 12V, sustituya el
5) Transformador averiado. control remoto.
6) Falso contacto del CN45. 2)~8) Compruebe cada punto.
7) Fusible fundido. Si no es defectuoso, sustituya la placa
8) ICP en OFF. electrnica interior.
204
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
(3) Para cancelar el modo comprobacin, pulse POWER ON/OFF.
En control remoto ON/OFF, pulse ON/OFF del control remoto.
En control centralizado, pulse OFF en el pulsador ON/OFF del
control centralizado.
NOTA: Se memoriza el ltimo cdigo de comprobacin, aunque se cancele el modo comprobacin en la forma arriba
indicada. Se tarda como mximo 60 segundos en visualizar el cdigo de comprobacin memorizado.
205
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Cdigo
comprobacin Diagnosis de la avera Causa Solucin
P6 Funcionamiento del 1) Ciclo corto del ciclo de aire. 1) Retire posibles obstrucciones del ciclo de
protector de escarcha o de 2) Filtro de aire sucio. aire.
sobreintensidad. 3) Ventilador averiado. 2) Limpie el filtro de aire.
4) Refrigerante no normal. 3) Compruebe el ventilador.
206
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL K
3. FUNCION DE AUTODIAGNOSTICO Y DATOS DE SERVICIO DE LA UNIDAD EXTERIOR
3.1 Funcin de autodiagnstico y localizacin de averas.
Pulsando SW2 alternativamente, LD1 a LD8 indican la Salida activada (Output State), o el Cdigo de comprobacin.
Con la condicin de que SW3-1 y SW3-2 estn en OFF.
CONTROLES Y CHEQUEOS
LD7 Vlvula bypass ON Protec. sobrecalentamiento termistor (TH3)
LD8 Resistencia del crter ON Entrada defectuosa
Parpadeo
Diagnosis de la avera Causa Solucin
del LED
LD4 Funcionamiento del presostato Fallo en el motor del ventilador Compruebe la presin de
de alta (63H2) exterior. aspiracin y de la lnea de
(slo en PUH-5/6YK). Sobrecarga de funcionamiento. descarga.
Limpie el intercambiador de
condensacin.
Cambie el motor del ventilador
LD5 Funcionamiento del rel de Funcionamiento en baja tensin. Compruebe la tensin de la red
sobrecarga de corriente Fallo en el compresor. elctrica.
(51CM). Vlvula de paro cerrada. Compruebe el cableado de
alrededor del compresor.
Cambie el compresor.
LD6 Funcionamiento del interruptor Fuga de gas. Compruebe si hay una fuga de
trmico (26C). gas. Reparar y recargar de gas.
LD7 Termistor de proteccin de Fallo en el motor del ventilador Compruebe y cambie el motor del
sobrecalentamiento (TH3). exterior. ventilador exterior.
LD8 Entrada defectuosa. Fallo de la placa electrnica exterior. Cambie la placa electrnica exterior.
207
CONTROLES Y CHEQUEOS GAMA COMERCIAL
LD7 64 64 16384
LD8 128 128 32768
(Abierto 8 bits)
Nmero de bits
<50Hz>
Velocidad (rpm)
Velocidad (rpm)
208
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
OFF Parada del funcionamiento.
CALOR
Parada del funcionamiento. 27 minutos despus, aparece en el
ON
control remoto el cdigo de comprobacin P8.
209
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
K
CONTROLES Y CHEQUEOS
( ANTERIOR AO 1997 )
211
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ON (Marcha)
STAND-BY
DEFROST (Desescarche)
CHECK
LOW, HIGH
(Comprobacin).
(Velocidad de la turbina: BAJA, ALTA).
Aparece en la pantalla cuando
Visualizacin de la velocidad de la turbina (Baja;
entra en funcionamiento el
Alta).
autodiagnstico;
Simultneamente se visualiza
el cdigo de comprobacin en
AUTO RETURN la casilla de la temperatura de
ajuste.
(Retorno automtico).
(Direccin del caudal de aire de una hora).
Aparece en la pantalla cuando la unidad est en el modo de
Refrigeracin o Deshumectacin, con la velocidad del ventilador baja
y las lamas deflectoras en la poblacin de salida de aire descendente. NOTA:
Se anula su visualizacin una hora despus conjuntamente con el Al pulsar el pulsador de puesta en marcha
retorno de las lamas deflectoras a su posicin horizontal. ON OFF, se visualiza CENTRALLY
CONTROLLED durante 2 segundos.
212
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ADVERTENCIA 1.
El pulsador TEST RUN no funcionar si tenemos
conectado un interruptor PARO/MARCHA en el mando.
ADVERTENCIA 2.
Si cuando pulsamos el pulsador TEST RUN por segun-
CONTROLES Y CHEQUEOS
da vez nos equivocamos y pulsamos otros pulsador, el
modo de funcionamiento de prueba ser anulado.
ADVERTENCIA 1.
El cdigo de temperatura va de 1 a 15 ( 15 C a 80 C),
durante el funcionamiento de refrigeracin debe decrecer
(durante la calefaccin debe crecer). Uselo para compro-
bar el funcionamiento del compresor.
Cdigo 1 2 3 4 5 6 7 8
Temperatura
15 ~ 2 C ~ 10 C ~ 15 C ~ 20 C ~ 25 C ~ 30 C ~ 35 C ~ 40 C
intercambiador
Cdigo 9 10 11 12 13 14 15
213
CONTROLES Y CHEQUEOS GAMA COMERCIAL
EJEMPLO
Nmero de Cdigo de
unidad comprobacin
A-1 Ajustamos la unidad al modo de comprobacin pulsando dos veces seguidas el pulsa-
dor CHECK.
A-2 Cuando el modo de comprobacin queda activado, aparece la palabra CHECK (com-
probacin) en la pantalla, y se visualizar CHECK y UNIT ADDRESS (nmero de la
unidad) en la parte de visualizacin del ajuste de temperatura. Luego (al cabo de 10 seg.
mx.) aparece el ltimo modo de comprobacin ocurrido y memorizado, y muestra alter-
nativamente UNIT ADDRESS (nmero de la unidad) y CHECK (comprobacin)
durante 1 seg. cada uno.
A-3 Se debera realizar la comprobacin de servicio de acuerdo con el cdigo de compro-
bacin.
214
CONTROLES Y CHEQUEOS GAMA COMERCIAL
Cdigo
de Diagnosis
Mtodo de deteccin Causa Solucin
compro- de la avera
bacin
EO. Error en la seal de Se activa cuando el Avera en el circuito de Vuelva a la explicacin de:
Transmisin/Recepc mando a distancia no reci- transmisin/recepcin de Funcionamiento de Test
in. be 6 veces y de manera seales del mando a dis- (TEST RUN).
continuada la seal de tancia. 1 Cuando se controla una
comprobacin enviada Avera en el circuito de sola unidad.
por la placa electrnica transmisin/recepcin 2 Cuando se controlan
interior. de seales de la unidad varias unidades mediante
interior. un solo mando.
P1: Sonda de la toma Cuando se detecta que el Avera en el termistor. Compruebe la resistencia
de aire del local circuito est abierto Mal contacto del conec- del termistor. Valores de
defectuosa. (menos de 50 C o, cuan- tor. resistencia:
do se detecta un cortocir- Avera del circuito detec- 0 C 15 kilo ohms.
P2: Sonda de tempera- cuito (ms de 90 C). tor (placa electrnica). 10 C 9,6 kilo ohms.
tura de los tubos 20 C 6,3 kilo ohms.
CONTROLES Y CHEQUEOS
defectuosa. 30 C 4,3 kilo ohms.
40 C 3,0 kilo ohms.
P4: Sonda de drenaje (En el caso de la sonda de
defectuosa. drenaje el valor de la resis-
tencia est entre (4) - (5) en
el conector).
Compruebe si el conector
hace buen contacto.
Si no se encuentra ninguna
avera, cambie la placa
electrnica de la unidad
interior.
P5 Avera en el meca- Se activa el P5, si durante El mecanismo de eleva- Tome el valor de resisten-
nismo de proteccin los 40 seg. posteriores a cin de drenaje se ha ave- cia del calentador del sen-
de desbordamiento que se conecte la resis- riado, ha subido el nivel sor de drenaje (entre los
del drenaje. tencia, la temperatura del agua y la sonda de puntos (1) - (3) en el
detectada (temperatura drenaje ha quedado conector). El valor correcto
anterior a que se conecte sumergida bajo el agua. de resistencia suele ser de
la resistencia) no sube Mal contacto en la resis- 82 ohms.
ms de 20 grados. tencia del sensor de dre- Compruebe el funciona-
naje. miento del elevador de
Avera en el circuito detec- drenaje.
tor. Si los dos mecanismos
funcionan correctamente
cambie la placa electr-
nica de la unidad interior.
P3 Error de sistema Se activa cuando el La longitud del cable del Compruebe la longitud y la
(Transmisin/Recep mando a distancia no recibe mando a distancia es de seccin del cable del
cin de seales). 6 veces y de manera con- ms de 500 m. mando a distancia.
tinuada la seal de com- El cableado de conexin Compruebe el cableado
probacin enviada por la entre el mando a distancia de conexin.
placa electrnica interior. y la placa electrnica es
defectuoso.
215
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL K
Cdigo
de Diagnosis
Mtodo de deteccin Causa Solucin
compro- de la avera
bacin
P7 * Error de sistema Se activa cuando es reci- Error en el mando a dis- Compruebe el nmero de
(Nmero de orden bido el mismo dato de la tancia o en la placa elec- orden (Address) ajusta-
de la unidad unidad. trnica del ajuste del do en el mando a distancia
Address Se activa cuando el nmero de orden de la y el ajustado en la placa
mando a distancia no reci- unidad (Address). electrnica de la unidad
be 6 veces y de manera Avera en el circuito de interior.
continuada la seal de transmisin/recepcin Compruebe la tensin de
comprobacin enviada de seales. los terminales del mando a
por la placa electrnica Falla la alimentacin del distancia, la cual debera
interior. mando a distancia. ser de 12V DC.
Si los 2 componentes
anteriores funcionan
correctamente, cambie
la placa electrnica.
CONTROLES Y CHEQUEOS
216
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL K
3. FUNCION DE AUTODIAGNOSTICO Y DATOS DE SERVICIO DE LA UNIDAD EXTERIOR
3.1 Funcin de autodiagnstico y localizacin de averas.
Pulsando SW2 alternativamente, LD1 a LD8 indican la Salida activada (Output State), o el Cdigo de comprobacin.
Con la condicin de que SW3-1 y SW3-2 estn en OFF.
CONTROLES Y CHEQUEOS
LD7 Vlvula bypass ON Protec. sobrecalentamiento termistor (TH3)
LD8 Resistencia del crter ON Entrada defectuosa
Parpadeo
Diagnosis de la avera Causa Solucin
del LED
LD4 Funcionamiento del presostato Fallo en el motor del ventilador Compruebe la presin de
de alta (63H2) exterior. aspiracin y de la lnea de
(slo en PUH-5/6YK). Sobrecarga de funcionamiento. descarga.
Limpie el intercambiador de
condensacin.
Cambie el motor del ventilador
LD5 Funcionamiento del rel de Funcionamiento en baja tensin. Compruebe la tensin de la red
sobrecarga de corriente Fallo en el compresor. elctrica.
(51CM). Vlvula de paro cerrada. Compruebe el cableado de
alrededor del compresor.
Cambie el compresor.
LD6 Funcionamiento del interruptor Fuga de gas. Compruebe si hay una fuga de
trmico (26C). gas. Reparar y recargar de gas.
LD7 Termistor de proteccin de Fallo en el motor del ventilador Compruebe y cambie el motor del
sobrecalentamiento (TH3). exterior. ventilador exterior.
LD8 Entrada defectuosa. Fallo de la placa electrnica exterior. Cambie la placa electrnica exterior.
217
CONTROLES Y CHEQUEOS GAMA COMERCIAL
LD7 64 64 16384
LD8 128 128 32768
(Abierto 8 bits)
Nmero de bits
Velocidad (rpm)
218
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL K
Tiempo de funcionamiento del compresor.
El tiempo acumulado aparecer en unidades de 256 horas. Durante el modo de indicacin de tiempo las maniobras de SW2
son ignoradas.
Maniobras de SW1.
Cambiando SW1 a ON borramos el cdigo de comprobacin (vuelve a cero). Si se acciona durante el autodiagnstico, anu-
lamos el modo de autodiagnstico. Si se pulsa durante la visualizacin del cdigo de comprobacin, la visualizacin cambia y
aparece la Salida activada.
Nota: SW1 es siempre vlido sin que le afecte el ajuste del interruptor DIP SW3. Como excepcin, el SW1 es invalidado cuan-
do al poner en marcha la unidad, entra el modo de comprobacin (antifase, o fase desconectada).
CONTROLES Y CHEQUEOS
J2 Slo cuando el desescarche SV
est accionado
J3 Resistencia del crter Vaya a 12-6 (1) Vaya a 12-6 (2)
Durante la calefaccin la tensin
del ventilador llega al 100%
J4 Temperatura de condensacin Unidad con bomba de calor (30 C) Unidad slo refrigeracin (35 C)
La numeracin de las pginas de este manual corresponde a la del original TECHNICAL & SERVICE MANUAL.
219
CONTROLES Y CHEQUEOS GAMA COMERCIAL
1) Para el funcionamiento en el modo de refrigeracin cambie en DIP SW3 los interruptores 1, 2 y 3 a la posicin ON
(arriba), y el 4 a OFF (abajo).
Para el funcionamiento en el modo de calefaccin cambie 2, 3 y 4 a ON (arriba) y 1 a OFF (abajo).
2) Conecte el ICP general.
3) Durante el funcionamiento de emergencia, la turbina gira a la velocidad alta y no funciona ni el control automtico de la
lama deflectora ni la opcin SWING (abanico) para la distribucin del caudal de aire.
4) El termostato deja de funcionar. Durante la calefaccin, cuando empieza el desescarche la turbina no para y da lugar a
la salida de aire fro.
5) El tiempo mximo de funcionamiento en el modo de refrigeracin es de 10 horas.
ADVERTENCIA:
Durante la refrigeracin, si el sistema de autodiagnstico indica avera en el mecanismo de elevacin de drenaje, abs-
tngase de usar el funcionamiento de emergencia.
220
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROL
AG
CONTROLES Y CHEQUEOS
Bomba de Calor
221
CONTROLES Y CHEQUEOS GAMA COMERCIAL
ON LAMP ON/OFF
CONTROL TEMPERATURA
CONTROLES Y CHEQUEOS
WARMER = Calentar.
COOLER = Enfriar.
SELECTOR
FAN SPEED
SWING LOUVER
TEST
222
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CALOR DE EMERGENCIA
CONTROLES Y CHEQUEOS
1. Cambie CN40 a CN42 de la placa del microprocesador de la evaporadora, conecte la alimentacin de la condensadora,
luego conecte la alimentacin de la interior.
TENGA EN CUENTA
* Que el encendido y apagado del aire acondicionado slo depende del interruptor general.
* El lower no funciona.
* Slo funcionan los ventiladores en LOW.
* El compresor funciona continuamente, no se puede controlar la temperatura.
* Mximo tiempo admisible 10 h.
* El desescarche en la operacin de calor de emergencia, el aire fro tiene que estar en la interior.
N OFF ON
1 NO POSIBLE FIJO
3 FIJO NO POSIBLE
223
CONTROLES Y CHEQUEOS GAMA COMERCIAL
N 2: ON TH2 del evaporador del conector del termistor. conectores del termistor.
de la U. Interior Fallo del termistor. 2) Compruebe y cambie el
(abierto o cerrado). Fallo del detector de la placa termistor.
del microprocesador. 3) Cambie la placa del
microprocesador de la
POSICION interior (si 1 y 2 no son).
NORMAL
TODOS EN
OFF LD 4 luce Fallo en el termistor Falso contacto o desconexin 1) Compruebe y repare los
TH1 del aire de del conector del termistor. conectores del termistor.
entrada de la U. Fallo del termistor. 2) Compruebe y cambie el
Interior (abierto o Fallo del detector de la placa termistor.
cerrado). del microprocesador. 3) Cambie la placa del
microprocesador de la
interior (si 1 y 2 no son).
LD 2 luce Frio/sobrecarga Ausentes los cables entre la Compruebe y repare los cables
CONTROLES Y CHEQUEOS
ha entrado en evaporadora y la condensadora. entre la condensadora y la
marcha el evaporadora (para detalles ver
mecanismo de El aire de descarga de la la prxima pgina).
SW1 proteccin del evaporadora no tiene espacio
evaporador. filtro de aire sucio o atascado. Compruebe que la salida de
aire tiene el suficiente espacio
La entrada de aire fro es muy (quite obstculos).
pequea.
Limpie el filtro de aire.
Compruebe fugas de
refrigerante y si es necesario,
poner gas.
225
CONTROLES Y CHEQUEOS GAMA COMERCIAL
LED
ALL OFF N 1: ON N 2: ON
la evaporadora.
LD 3 Humidificacin* Proteccin del Fallo de detec-
ENCENDIDO exceso de agua cin del termis-
activado. tor, del tubo del
evaporador cor- * LD3 luce durante el funcionamiento en calor,
tado/abierto. excepto cuando est ajustando el calor, deses-
carche y paro del termostato.
LD 4 Fallo de la Fallo de detec. del
ENCENDIDO condensadora. termistor, de la
temp. del aire de PROCEDIMIENTO DE CHEQUEO:
entrada cortado o
PONGA SW1 A ON LUCE UN LED FALLO
abierto.
CHECK TIMER LED Compruebe que est el conector CN 23 con su cable conectado, y todas las
palanquitas estn en OFF (* en caso de control de grupo).
CHECK SW1
1 (*1) conecte CN24 a CN23 y ponga el temporizador SW a la posicin ).
CHECK TIMER LED Si ha resuelto la localizacin de los fallos, siga el grfico de seguimiento,
cuando haya terminado de repararlos ponga a OFF todas las palanquitas del
SW1 CHECK/TIMER y compruebe que LD1 no luzca en TEST-RUN.
3
(Si LD1 luce pase sobre el procedimiento 2).
* Compruebe que LD2 luce en operacin normal.
El chequeo se ha terminado.
En caso de control de grupo ponga el temporizador a la posicin , como procedimiento 1, pero recuerde la posicin original
para despus.
226
CONTROLES Y CHEQUEOS GAMA COMERCIAL
CONTROLES Y CHEQUEOS
Iluminacin LED Diagnosis de avera Causa Remedio
ALL LD luce Fallo de la placa Fallo del transformador. Compruebe el voltaje del
condensadora. transformador y cambie la placa
de la condensadora.
227
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
CONTROL
CONTROLES Y CHEQUEOS
ELECTRO MECNICO
P E - 7 / 8 / 1 0 / 1 5 / 2 0 M YA
P E H - 7 / 8 / 1 0 / 1 5 / 2 0 M YA
P R H - 8 / 1 0 / 1 5 / 2 0 YA
Solo Fro
Bomba de Calor
229
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
No funciona La visualizacin ON- Corte elctrico Presione los botones [ON-OFF] cuando se restablezca la alimentacin.
OFF no se ilumina.
La toma de corriente est desconectada. Conecte la alimentacin.
O aparece visualiza-
cin incluso cuando No hay fusible en la toma de corriente. Reemplace el fusible.
el botn [ON-OFF]
se presiona No hay interruptor de prdida a tierra. Ponga a tierra el interruptor de fugas.
Sale aire pero no La visualizacin El ajuste de la temperatura es inadecuado. Despus de comprobar la temperatura ajustada y la temperatura de en-
enfria lo suficiente de cristal lquido trada en la visualizacin del cristal lquido, rerase a (Para cambiar la
o calienta lo muestra que est temperatura de la habitacin) en la pg. ... y opere de botn de ajuste.
suficiente en estado de Limpie el filtro
El filtro est lleno de polvo y suciedad.
operacin
Hay algunos obstculos en la entrada de aire y
Remover
la salida de las unidades interior y exterior.
Las ventanas y las puertas estn abiertas. Cerrar
No sale el aire fro La visualizacin El circuito que impide volver a ponerlo Espere durante un momento
o el aire caliente. de cristal lquido en marcha est en operacin durante (Para proteger el compresor, el circuito que previene volver a poner
CONTROLES Y CHEQUEOS
muestra que est 3 minutos. en marcha se encuantra en la unidad interior) Por eso hay ocasiones
funcionando en las que el compresor no comienza afuncionar inmediatamente.
(Hay casos en los que no funciona durante 3 minutos).
La operacin de la unidad interior comenz Espere durante un momento
de nuevo durante la operacin de calefaccin (La operacin de calefaccin comienza despus de que haya terminado
y descongelacin. (5-10 HP solamente). la operacin de descongelacin.)
No se puede No se puede El interruptor DIP no est correcto. Cambie el interruptor DIP de desconectado a conectado.
cambiar a modo cambiar a modo (Refirase al Manual de Instalacin)
de calefaccin de calefaccin
cuando se presio-
na la tecla MODE
Error de visualizacin
La visualizacin ER en modo de Error. (Parpadea en intervalos de 0,5 segundos).
E01 Sensor de la habitacin abierto
E02 Sensor de la habitacin en corto circuito
E03 Error de entrada de la unidad interior o la unidad exterior
Puesta a cero.
E01 / E02 : Se pone a cero automticamente para restituir el Error
E03 : Interruptor conectado/desconectado (Desconectadoconectado: Puesta a cero)
230
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
CONTROL
YD
CONTROLES Y CHEQUEOS
PEH-8 / 10YD
Bomba de Calor
231
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
232
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
2) Cuando alguno de los sistemas de proteccin detecta un problema, empezar el modo de prevencin de arranque de
3 minutos del compresor la primera vez que se detecta. La segunda vez que se detecte el problema de control se co-
locar en modo de comprobacin (check mode).
Sin embargo, en el caso del sistema de proteccin de alta presin (63H1), el modo de comprobacin (check mode)
empezar la primera vez.
3) Los detalles del fallo de proteccin detectado la segunda vez sern memorizados e indicados por LED en la placa
electrnica (incluso si el fallo detectado esta segunda vez no es el mismo que el detectado la primera vez).
4) Cuando el comando OFF del control remoto (control remoto OFF, termostato OFF) es pulsado con el compresor en
marcha, ste no se pondr en marcha hasta que hayan transcurrido al menos 3 minutos.
5) El modo de chequeo se desactiva mediante el comando OFF de la unidad interior.
CONTROLES Y CHEQUEOS
(2) Compresor, vlvula de 4 vas, control de calentamiento
1) Mediante el comando de la unidad interior para poner en marcha el compresor y poner la vlvula de 4 vas en ON, se
controlar que el equipo trabaje en fro o bomba de calor (cooling/heating).
2) El control del compresor incluye la funcin de retardo de 3 minutos, contados a partir de la ltima parada del compre-
sor.
3) Cuando el comando para poner la vlvula de 4 vas en ON est activado, la vlvula de 4 vas estar siempre en ON ex-
cepto en el caso de realizar un desescarche en modo bomba de calor (heating).
4) Con compresor parado, la resistencia del crter estar en posicin ON (mientras que estar en OFF con el compresor
en marcha).
5) Cuando el comando de la vlvula de 4 vas cambia con el compresor en marcha, el compresor se parar introducin-
dose un retardo de 3 minutos, y luego arrancar el nuevo modo (fro / bomba) de operacin.
N=5 H H
N=4 x H x H
N=3 x L x x H
N=2 x x H x x L
N=1 x x L x x x H
N=0 x x x x x x x
233
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
Temperatura de la batera.
Nota: 1. T1 habr transcurrido cuando haya terminado el desescarche o se haya activado el comando COOLING ON.
2. Cuando el compresor se detenga durante la operacin de desescarche, T1 = 30 minutos estar seleccionado
reconociendo la parada como final del desescarche.
3) Durante la operacin de desescarche, todos los ventiladores de la unidad exterior se detendrn (N=0), la vlvula de
byspass (SV1) se abrir (ON), y la vlvula de 4 vas (21S4) se pondr en OFF.
4) La operacin de desescarche finalizar cuando las siguientes condiciones sean satisfechas:
En caso de T2 2 minutos Tp 20C
En caso de 2 < T2 < 15 minutos TP 8C
234
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
En caso de T2 = 15 minutos
5) Despus de la operacin de desescarche, el modo bomba de calor (heating mode) ser restaurado ponindose el ven-
tilador y la vlvula de cuatro vas en ON. 2 minutos despus de terminar el desescarche, la vlvula de bypass (SV1) se
cierra (OFF).
CONTROLES Y CHEQUEOS
Si 63H2 ha vuelto despus de 15 minutos sin detectarse, la vlvula se vuelve en OFF.
La vlvula est abierta (ON) durante el desescarche.
Nota: Para el modo de control de temperatura de bateras y el modo de salida del ventilador ver pgina siguiente.
235
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
Tabla de detalle
CONTROLES Y CHEQUEOS
1 OFF OFF ON ON
SW03
2 OFF ON OFF ON
60
Temperatura (C)
40
20
20
40
(Open 129-bit)
236
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
El controlador de la unidad LED08 no se ilumina en el in- 1) Mal conectada la placa a la ali- Compruebe cada una de las cone-
exterior no funciona. dicador de la unidad exte- mentacin elctrica. xiones.
rior. 2) Mal contacto en el conector del Compruebe la tensin que llega a
transformador. la unidad exterior.
3) Fusible (10A) fundido. Compruebe si est fundido el fusi-
ble y en caso afirmativo cmbielo.
CONTROLES Y CHEQUEOS
Unidad exterior no trabaja a 1) Cableado errneo o conexin in- 1) Compruebe el cableado y que las
pesar de las indicaciones del correcta entre la unidad interior y conexiones son las correctas.
control. la exterior. 2) Compruebe la tensin en la lnea
2) No se recibe el comando ON de la entre la unidad interior y exterior
unidad interior. (lneas 1 y 2).
3) Compruebe que los LED04~7 es-
tn iluminados
(4) Autodiagnstico
LED
Significado Mtodo de deteccin Motivo Medidas
parpadeante
Problema en el sensor Cuando detecta abierto (40 C Fallo del sensor Compruebe el valor de la resisten-
de batera o menos) o cerrado (sobre 90 C). Conexin incorrecta del sensor cia del sensor, o el nmero de bits
Fallo en la placa electrnica detectados por el miniordenador
LED03 La deteccin no es efectiva
Asegrese de que el conector hace
dentro de los 7 minutos des-
buen contacto
pus de arrancar el compresor.
Sensor de proteccin Cuando el conector (63H1) est Fallo en el ventilador (motor) de la Compruebe cada uno de los puntos
de alta presin abierto unidad exterior, o cortocircuito de de la izquierda
63H1 aire en fro
+0
30 1.5 kg/cm2 Fallo en el ventilador (motor) de la
LED04
unidad interior o cortocircuito de ai-
re en bomba de calor
Vlvula de solenoide (SV1) averiada
Rel de proteccin por Cuando el conector (49C) est Arranque con vlvula de servicio cerrada Compruebe cada uno de los puntos
sobrecorriente (compre- abierto Trabajo anormal del compresor de la izquierda
LED05 sor) Tensin anormal en la alimentacin
51CM de la mquina
Fallo de suministro elctrico
Proteccin de tempera- Cuando el conector (49C) est Compresor sobrecalentado debido Compruebe el sobrecalentamiento
tura (compresor) abierto a una insuficiente refrigeracin en la aspiracin
LED06 49C Compruebe que no hay fuga de re-
frigerante
Compruebe si el aparato necesita
una carga adicional de refrigerante
Proteccin por subida Cuando el sensor de tubera de- Fallo del ventilador (motor) de la Compruebe el ventilador (motor) de
anormal del sensor de tecta 67,5 C (incluyendo un cor- unidad exterior trabajando en fro la unidad exterior
LED07 tubera (termistor) te) Lo mismo que cuando el LED03 Lo mismo que cuando el LED03
parpadea parpadea
Fallo en la placa elec- Cuando el pulso de entrada de Fallo de la parte funcional (fotosensor) Cambio de la placa electrnica
LED08 trnica potencia est siempre en HI del circuito electrnico
237
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
3. Datos de referencia
(1) PUH-8YD, 10YD Tabla de caractersticas del termistor de tubera
2 13,67 172
4 12,48 169
6 11,40 165
8 10,43 161
10 9,56 157
12 8,77 153
14 8,05 149
16 7,41 145
18 6,82 141
20 6,28 137
22 5,80 132
24 5,35 128
26 4,95 124
28 4,58 122
30 4,25 116
32 3,94 112
34 3,66 108
36 3,40 104
38 3,16 100
40 2,94 96
42 2,74 93
44 2,56 89
46 2,39 86
48 2,23 82
50 2,09 79
52 1,95 76
54 1,83 73
56 1,71 70
58 1,61 67
60 1,51 65
Nota: Los valores de la tabla son valores medios. Existirn pequeas diferencias con los
valores medios sobre una mquina en concreto.
238
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
OFF ON Efecto
SW1-1 Control del ventilador Modo automtico fro/bomba de El modo de trabajo del ventilador (*)
calor
SW1-2 Indicador de obertura/izq. y de- Indicador obertura/girando Mtodo de pantalla de cristal lquido (**)
recha cuando el indicador de obertura pasa a ON
SW1-3 Control de Lama/sin lama Control automtico de lama/su- Seleccin del modelo con lama (**)
ministrado automtica y sin lama
CONTROLES Y CHEQUEOS
SW1-4 Ordinariamente Fro/bomba de calor Aplicado en modelos especiales (**)
SW1-6 Resta 4 C a la temperatura medi- Sin correccin de temperatura Corrige problemas de estratificacin
da por la sonda de retorno del aire
SW1-7 Velocidad del ventilador muy baja Velocidad del ventilador baja Caudal de aire en bomba de calor con (**)
(extralow) (low) el termostato OFF
SW1-8 Termostato de calor muy bajo Para funciones especiales. Seleccin (**)
de funcin del ventilador
SW1-9 Problemas en la unidad exterior: Problemas en la unidad exterior: Para modelos especiales (**)
S NINGUNO
SW1-10 Marcha/paro de corriente no su- Marcha/paro de corriente sumi- Seleccin de marcha paro de corriente
ministrado nistrado
OFF ON
SW2-1 0 20(1)
SW2-2 0 21(2)
SW2-3 0 22(4)
SW2-4 0 23(8)
SW2-5 0 24(16)
SW2-6 0 25(32)
239
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
OFF ON Notas
SW5-1 Modelos corrientes Modelos con autoswing Modelos con mecanismo de autoswing
240
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
El indicador CENTRALLY CONTRO- Avera de recepcin del control remo- (1) Comprobar la correcta seleccin del DIP SW17 del
LLED no desaparece, y el switch no to, o avera en el circuito de transmi- control remoto.
responde. sin de la unidad interior. (2)
a) Ponga el DIP SW17-7 del control remoto ON (ac-
La direccin est siendo selecciona- tuando como subordinado del control remoto), y
da al DIP-SW17 del control remoto, o conctelo al terminal del control remoto.
a DIP-SW2 de la unidad interior. b) Ponga el control remoto en ON y compruebe si
CENTRALLY CONTROLLED ha desaparecido.
A El control remoto est siendo conec-
tado con adaptador de tiempo. Sustituya el control remoto si ha desaparecido el
problema.
Cuando no ha desaparecido, compruebe el DIP-
SW2 y sustituya la placa electrnica de la unidad
interior si est correctamente configurado.
CONTROLES Y CHEQUEOS
Volviendo la operacin del control re- Avera en el circuito de recepcin/ (1) Ponga el DIP SW17-7 del control remoto en ON (ac-
moto en ON, EO aparece entre transmisin del control remoto, o ave- tuando como control remoto subordinado), y conc-
2 ~ 4 segundos antes del indicador ra del circuito de recepcin/transmi- telo al control remoto terminal bed.
de operacin. sin de la placa electrnica de la uni- (2) Vuelva local switch ON, y despus de 5 segundos,
dad interior. compruebe que el indicador de cristal lquido. Si
CENTRALLY CONTROLLED aparece entonces
vuelva a A.
(3) Ponga el control remoto subordinado en marcha y
compruebe las pantallas de ambos controles remo-
tos 4 segundos despus.
Avera de comunicacin
3 Pantalla en EO
de la unidad interior
blanco
con el control remoto
Se pone en ON el switch del control Conexin errnea entre las unidades (1) Compruebe la conexin entre las unidades inte-
remoto para generar el modo de interior/exterior, o funcin de resset rior/exterior.
operacin con sonido electrnico, por deteccin de sobrecorriente de-
pero desaparece pronto. bida a cortocircuito del sensor de a)
drenaje.
interior exterior
b)
interior exterior
241
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
c)
interior exterior
d)
C
interior exterior
de 82 aprox.
Poniendo SW del control remoto en Cortocircuito del cable de control re- (1) Compruebe la tensin en los terminales del control
ON se mantienen todas las luces en- moto. remoto.
cendidas y no se genera sonido a) Si no tienen tensin, cambie el cable del termi-
electrnico. Fallo en la alimentacin elctrica de la nal del control remoto y compruebe luego la
controladora de la unidad interior, o tensin.
mala conexin de CN40. Si el voltaje es de DC6V ~ DC12V, sustituya el
control remoto al estar averiado (cortocircuito
D Transformador desconectado o con- dentro del control remoto).
tacto incorrecto en CN40. Si no se detecta tensin compruebe la tensin
en la unidad interior:
Fusible fundido (F). 380 ~ 415V comprobar.
Fusible (F).
Local Switch OFF. Conector CN4T del transformador.
Conector CN40.
Cuando no se detecta ningn problema habiendo
realizado ~ , sustituya la placa electrnica de
la unidad interior.
242
CONTROLES Y CHEQUEOS GAMA INDUSTRIAL
E0 Fallo en transmisin/recepcin Fallo en la lnea de transmisin Utilice el autodiagnstico con otro control
La unidad interior no devuel- Fallo en el circuito de recepcin/transmisin remoto
ve seal al control remoto. de la seal E0 sigue apareciendo sustituya la placa
No existencia de la direccin de la unidad electrnica de la unidad interior
designada No aparece EO sustituya el control re-
moto
P2 Sensor de problemas en tube- Termistor averiado Compruebe que el conector est bien co-
ras Mal contacto al conector nectado a la placa
Compruebe si el termistor est averiado
Si no hay problemas sustituya la placa
de la unidad interior
CONTROLES Y CHEQUEOS
P3 Fallo en la transmisin/recepcin Mala conexin de la lnea de transmisin Compruebe la lnea de transmisin
El control remoto no responde Circuito de transmisin/recepcin de seal Compruebe el circuito de transmisin/re-
a la seal de la unidad interior averiado cepcin de seal
P6 Salto de la proteccin por so- Cortocircuito de aire Elimine materias que obstruyen los con-
brecalentamiento Filtro de aire sucio ductos de aire
Avera del ventilador de la unidad interior Compruebe el filtro de aire
Compruebe el funcionamiento del ventila-
dor de la unidad interior
P7 Fallo de sistema Seleccin errnea de la direccin de la uni- Compruebe la direccin de la unidad interior
dad interior Compruebe el circuito de transmisin/recep-
Avera del circuito de transmisin del control cin
remoto Compruebe la alimentacin del control remoto
P8 Problemas en la unidad interior Conexin errnea entre la unidad interior y Compruebe el cableado y la placa electr-
la exterior nica de la unidad exterior
Deteccin de fase inversa Compruebe el sistema de proteccin de la
Ha saltado el sistema de proteccin de la unidad exterior
unidad exterior
Fallo en el sensor de tubo
Placa electrnica exterior averiada
243
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
CDIGOS Y
VISUALIZACIN DE AVERAS
CONTROLES Y CHEQUEOS
245
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
Unidad: mm
CONTROLES Y CHEQUEOS
Montura colocacin
246
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
PAC-SE51CRA
Unidad: mm
CONTROLES Y CHEQUEOS
247
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
PAC-SC32PTA
Unidad: mm
CONTROLES Y CHEQUEOS
Montura colocacin
248
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
MJ-103MTRA
Unidad: mm
CONTROLES Y CHEQUEOS
Placa instalacin
249
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
Serie Y
1 Un cdigo de comprobacin de 4 dgitos aparece en el control remoto si la unidad se para debido
a un fallo. Busque las causas de dicho problema. Tambin es posible localizar dichos cdigos
en la pantalla de la unidad exterior.
1. Unidad interior
2. Unidad exterior
CONTROLES Y CHEQUEOS
0403 Funcionamiento defectuoso de la transmisin en serie 5105 Sensor de temperatura de las tuberas (TH5)
1102 Temperatura de carga 5106 Sensor de temperatura exterior (TH6)
1111 Temperatura saturada por baja presin (detectada por 5107 Anomalas en el sensor de temperatura de salida del
el sensor de temperatura saturada) serpentn de subrefrigeracin (TH7)
1112 Temperatura saturada por baja presin (detectada por 5108 Anomalas en el sensor de temperatura de salida del
el nivel de lquido que detecta el sensor de temperatura) interruptor del serpentn de subrefrigeracin (TH8)
1113 Temperatura saturada por baja presin (detectada por el 5110 Anomalas en el sensor de temperatura de la placa de
nivel de lquido que detecta el sensor de temperatura) refrigeracin del inversor (THHS)
1302 Presin elevada 5201 Anomala del sensor de alta presin (HPS)
1500 Carga excesiva de refrigerante 5301 Funcionamiento anmalo del circuito del sensor IDC
1501 Falta de refrigerante 6600 Configuracin duplicada de la direccin de la unidad
1505 Problema de presin baja 6602 Error de transmisin (Error en el sistema del procesador
4103 Fase de inversin de transmisin)
4115 Funcionamiento anmalo de la seal simultnea de 6603 Error de transmisin (ruta de transmisin ocupada
alimentacin BUSY)
4200 Funcionamiento anmalo del circuito de deteccin 6606 Error de transmisin y recepcin (Problema de comu-
VDC/IDC nicacin con el procesador de transmisin)
4210 Interrupcin de la sobrecorriente 6607 Error de transmisin y recepcin (No es un error de
4220 Tensin baja del cable del conector inversor reconocimiento)
4230 Proteccin contra el sobrecalentamiento del panel del 6608 Error de transmisin y recepcin (No es un error de
radiador cuadro)
4240 Proteccin contra la sobrecorriente 7100 Error de capacidad total
4260 Funcionamiento anmalo del ventilador de refrigeracin 7101 Error en el cdigo de capacidad
5101 Sensor de la temperatura de carga (TH1) 7102 Error del nmero de unidad de conexin
5102 Temperatura saturada de presin baja (TH2) 7105 Error de configuracin de la direccin
5103 Superficie de lquido que detecta el sensor de 7109 Conexin incorrecta
temperatura (TH3) 7130 Configuracin incorrecta
5104 Superficie de lquido que detecta el sensor de
temperatura (TH4)
3. Remote controller
6101 Respuesta ilegible 6606 Error de transmisin (Error en el sistema del procesador
6600 Configuracin duplicada de la direccin de la unidad de transmisin
6602 Error de transmisin (Error en el sistema del procesador 6607 Error de transmisin y recepcin (No es un error de
de transmisin) reconocimiento)
6603 Error de transmisin (ruta de transmisin ocupada 6608 Error de transmisin y recepcin (No es un error de
BUSY cuadro)
250
CONTROLES Y CHEQUEOS CAUDAL VARIABLE DE REFRIGERANTE
Serie R2
Un cdigo de comprobacin de 4 dgitos aparece en el panel de visualizacin del controlador remoto si la unidad se para debido a un fallo. Busque las
causas de dicho problema.
1. Unidad interior
Cdigo de comprobacin Problemas Cdigo de comprobacin Problemas
2500 Escape de agua 6603 Error de transmisin (ruta de transmisin ocupada
BUSY)
2502 Fallo de la bomba de drenaje 6606 Error de transmisin y recepcin (problemas de
2503 Fallo del sensor de drenaje; el interruptor de comunicacin con el procesador de transmisin)
flotador est accionado 6607 Error de transmisin y recepcin (No es un error de
5101 Problemas con el sensor de entrada de aire reconocimiento)
5102 Fallo del sensor de las tuberas 6608 Error de transmisin y recepcin (No es un error de
5103 Fallo del sensor de las tuberas en el lado del gas cuadro)
6600 Configuracin duplicada de la direccin de la 7101 Error en el cdigo de capacidad
unidad
6602 Error de transmisin (Error en el sistema del 7111 Fallo del sensor del controlador remoto
procesador de transmisin)
2. Unidad exterior
Cdigo de comprobacin Problemas Cdigo de comprobacin Problemas
0403 Funcionamiento defectuoso de la transmisin en serie 5105 Sensor de temperatura de las tuberas (TH5)
1102 Temperatura de carga 5106 Sensor de temperatura exterior (TH6)
1111 Temperatura saturada por baja presin (detectada por 5107 Anomalas en el sensor de temperatura de salida del
CONTROLES Y CHEQUEOS
el sensor de temperatura saturada). serpentn de subrefrigeracin (TH7)
1112 Temperatura saturada por baja presin (detectada por 5108 Anomalas en el sensor de temperatura de salida del
el nivel de lquido que detecta el sensor de temperatura) interruptor del serpentn de subrefrigeracin (TH8)
1113 Temperatura saturada por baja presin (detectada por el 5110 Anomalas en el sensor de temperatura de la placa de
nivel de lquido que detecta el sensor de temperatura) refrigeracin del inversor (THHS)
1302 Presin elevada 5201 Anomala del sensor de alta presin (HPS)
1500 Carga excesiva de refrigerante 5301 Funionamiento anmalo del circuito del sensor IDC
1501 Falta de refrigerante 6600 Configuracin duplicada de la direccin de la unidad
1505 Problema de presin baja 6602 Error de transmisin (Error en el sistema del procesador
4103 Fase de inversin de transmisin)
4115 Funcionamiento anmalo de la seal simultnea de 6603 Error de transmisin (ruta de transmisin ocupada-
alimentacin BUSY)
4200 Funcionamiento anmalo del circuito de deteccin 6606 Error de transmisin y recepcin (Problema de comunicacin
VDC/IDC con el procesador de transmisin)
4210 Interrupcin de la sobrecorriente 6607 Error de transmisin y recepcin (No es un error de
4220 Tensin baja del cable del conector inversor reconocimiento)
4230 Proteccin contra el sobrecalentamiento del panel 6608 Error de transmisin y recepcin (No es un error de
del radiador cuadro)
4240 Proteccin contra la sobrecorriente 7100 Error de capacidad total
4260 Funcionamiento anmalo del ventilador de refrigeracin 7101 Error en el cdigo de capacidad
5101 Sensor de la temperatura de carga (TH1) 7102 Error del nmero de unidad de conexin
5102 Temperatura saturada de presin baja (TH2) 7105 Error de configuracin de la direccin
5103 Superfcie de lquido que detecta el sensor de 7109 Conexin incorrecta
temperatura (TH3) 7130 Configuracin incorrecta
3. Controlador BC
Cdigo de comprobacin Problemas Cdigo de comprobacin Problemas
1368 Presin alta (controlada por el sensor de presin del 5116 Fallo del sensor de temperatura de la seccin intermedia
lado de lquido) 5201 Fallo del sensor de presin del lado de lquido (63HS1)
1369 Presin alta (controlada por el sensor de presin del 5203 Fallo del sensor de presin intermedio (63HS3)
lado de gas) 6101 Error de recepcin por respuesta ilegible
1370 Presin alta (controlada por el sensor de presin 6600 Ajuste de la direccin de la unidad doble
intermedio) 6602 Error de transmisin (error de hardware en el procesador
2503 Interruptor de flotador activado de transmisin)
5111 Fallo del sensor de temperatura de la entrada de lquido (TH11) 6603 Error de transmisin (ruta de transmisin SATURADA)
5112 Fallo del sensor de temperatura de la salida de bypass (TH12) 6606 Error de transmisin y recepcin (problemas de comunicacin
5113 Fallo del sensor de temperatura de salida del cambiador con el procesador de transmisin)
de calor de la superficie de lquido (TH13) 6607 Error de transmisin y recepcin (no error ACK)
5114 Fallo del sensor de temperatura de entrada del 6608 Error de transmisin y recepcin (error marco de no
cambiador de calor de la superficie de lquido (TH14) respuesta)
5115 Fallo del sensor de temperatura de entrada de bypass (TH15) 7107 Error en el ajuste del nmero de conexiones.
4. Remote controller
Cdigo de comprobacin Problemas Cdigo de transmisin Problemas
6101 Respuesta ilegible 6606 Error de transmisin (Error en el sistema del procesador
6600 Configuracin duplicada de la direccin de la unidad de transmisin)
6602 Error de transmisin (Error en el sistema del procesador 6607 Error de transmisin y recepcin (No es un error de
de transmisin) reconocimiento)
6603 Error de transmisin (ruta de transmisin ocupada- 6608 Error de transmisin y recepcin (No es un error de
BUSY) cuadro)
251
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Y FRIGORFICOS
253
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
5 - WIRING DIAGRAM
MSC-07RV - E1
MSC-09RV - E1
MSC-12RV - E1 MODELS WIRING DIAGRAM
INDOOR UNIT
TO OUTDOOR
UNIT TB
L BRN TAB12 CN RT12
CONNECTING 112
FOR BRN HIC1 CN
3 CN201 RT11
MUH OR RED 111
3
MXZ TYPE BLK
2 1
12V N BLU NR11 CN 3 GRY
1 121 2
FOR BLU YLW
3
2 CN202
MU OR WHT 2
TRANS 1 BRN
4
MF
C11
MUX TYPE 2 WHT
5
1 F11 SR141
12V 1 BLK 3 RED
6
CN LD101T CN211
POWER 151
SUPPLY ELECTRONIC CONTROL P.C. BOARD
CORD
~/N 220-240V 5
50Hz 5
POWER MONITOR,
PE RECEIVER
GRN/YLW
MV P.C.BOARD
REMOTE
CIRCUIT BREAKER CONTROLLER
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servic-
ing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
254
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MU-07RV - E1
MU-09RV - E1
MU-12RV - E1 MODELS WIRING DIAGRAM
OUTDOOR UNIT
TB2
FROM 2 WHT
INDOOR UNIT
CONNECTING 52C
12V 1 BLK
DSAR
BRN
CIRCUIT BREAKER TB1 52C
L BRN WHT
C
NO COM
POWER SUPPLY WHT C1
~/N
N BLU RED MC
220-240V S R
F BLK
50Hz
PE GRN/YLW C2 WHT
WHT 1 WHT
BLU 2 BLK
RED 3 RED
MF
MUH-07RV - E1
MUH-09RV - E1
MUH-12RV - E1 MODELS WIRING DIAGRAM
OUTDOOR UNIT
FROM
INDOOR UNIT TB2 MF
3 RED
CN730
CN661 CN721
CONNECTING 1
12V N BLK 2 X62 RED
C65
3 SR61 1
BRN WHT
2
CIRCUIT BREAKER
DSAR
TB1
IC881
3
NR61
F61
L BRN BLK
4
POWER SUPPLY TRANS
N BLU CN711
~/N
220-240V TAB20 52C
X62
50Hz PE
4 3 DEICER P.C. BOARD
C
WHT
C1
GRN/YLW BLU RED S MC R
BLK
255
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MSC-07RV - E1 MU-07RV - E1
MSC-09RV - E1 Refrigerant pipe [9.52
MU-09RV - E1
(Option)
INDOOR UNIT (with heat insulator) Stop valve OUTDOOR UNIT
(with service port)
Indoor
Indoor coil
heat
exchanger thermistor Outdoor
RT12 heat
Flared connection
exchanger
Room temperature
thermistor
RT11
Compressor
Flared connection
Strainer
Capillary tube
[3.0x[1.4x600
Refrigerant pipe [6.35
Refrigerant flow in cooling
(Option)
(with heat insulator)
Unit:mm
MSC-12RV - E1 MU-12RV - E1
ESQUEMAS ELCTRICOS Y FRIGORFICOS
Indoor
Stop valve
heat Indoor coil
exchanger (with service port)
thermistor Outdoor
RT12 heat
Flared connection exchanger
Room temperature
thermistor Compressor
RT11
Flared connection
Capillary tube
[3.0x[1.6x600
Refrigerant pipe [6.35
(Option) Refrigerant flow in cooling
(with heat insulator)
256
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
MSC-07RV - E1 MUH-07RV - E1
MSC-09RV - E1 MUH-09RV - E1
INDOOR UNIT Refrigerant pipe [ Reversing valve OUTDOOR UNIT
9.52 (4-way valve)
(with heat insulator)
Muffler
Room temperature
thermistor
RT11 Capillary tube
[3.0x[1.4x800
Accumulator (2 pcs)
Compressor
Capillary tube
[3.0x[1.6x600(MUH-07RV)
Flared connection [3.0x[1.6x400(MUH-09RV)
Check valve Reversing valve coil
(4-way valve coil)
Strainer
heating ON
cooling OFF
Stop valve Capillary tube
[3.0x[1.4x600(MUH-07RV)
Refrigerant pipe [6.35 [3.0x[1.4x550(MUH-09RV)
(Option) Refrigerant flow in cooling
(with heat insulator)
Refrigerant flow in heating
Unit:mm
Room temperature
thermistor
RT11 Capillary tube
[3.0x[1.4x500(2pcs)
Accumulator
Compressor Capillary tube
[3.0x[1.8x300
Flared connection
Capillary tube Reversing valve coil
(4-way valve coil)
Strainer [3.0x[1.6x700
heating ON
cooling OFF
Stop valve
Refrigerant flow in cooling
Refrigerant pipe [6.35 Check
(Option) Refrigerant flow in heating
valve
(with heat insulator)
257
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
1 - ESQUEMA ELCTRICO
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block, : Connector
MU-09NV - E1
OUTDOOR UNIT
258
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Flared
connection
Accumulator
Room temperature Compressor
thermistor
RT11
Capillary tube
[1.6x1200
Strainer
Refrigerant pipe
[6.35 Refrigerant flow in cooling
(Option)
(with heat insulator)
Unit:mm
259
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
5 - WIRING DIAGRAM
MSH-07NV - E1 MODELS WIRING DIAGRAM
MSH-09NV - E1
INDOOR UNIT
~
~/N
OUTDOOR UNIT
260
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Room temperature
thermistor Capillary tube
RT11 [1.4x800 (2 pcs)
Accumulator
Unit:mm
MSH-09NV - E1
Indoor coil
thermistor (with heat insulator)
RT12
Flared connection
Indoor
heat Outdoor
Stop valve Strainer
exchanger heat
(with service Defrost
Room temperature thermistor exchanger
port) Capillary tube
thermistor RT61
RT11 [1.4x800 (2 pcs)
Accumulator
Capillary tube
Flared connection Check
[1.6x400
valve
261
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block, : Connector
NOTE:1. Use copper conductors only.(For field wiring) 1.Slide the sleeve.
2. show the terminals with a lock mechanism, so they cannot be removed when you pull 2.Pull the wire while
the lead wire. pushing the locking
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger. lever.
3. Symbols below indicate.
: Terminal block, : Connector
262
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Indoor
heat Indoor coil Stop valve Outdoor
exchanger thermistor (with service port) heat
RT12 exchanger
Refrigerant pipe
[6.35 Refrigerant flow in cooling
(Option)
(with heat insulator)
263
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
~/N
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block, : Connector
OUTDOOR UNIT
264
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
MSH-12NV - E1 MUH-12NV - E1
MSH-12NV - E2 Refrigerant pipe Reversing valve MUH-12NV - E2
[12.7 (4-way valve)
INDOOR UNIT OUTDOOR UNIT
(with heat insulator) Muffler
Room temperature
thermistor Accumulator
RT11 Compressor Capillary tube
[1.6x400
Flared connection
Capillary tube Reversing valve coil
Strainer [1.4x500 (4-way valve coil)
heating ON
cooling OFF
Refrigerant pipe Stop valve
(Option) [6.35
Refrigerant flow in cooling
Check
(with heat insulator) Refrigerant flow in heating
valve
265
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
NR11
TO OUTDOOR WHT BLK 1 121
YLW
UNIT CN201 3 52C
CONNECTING 3 GRY
C11
N BLK CN211
BLK 1 4
WHT MF
BLU BRN F11 RED
2
BLK
GRN/YLW
LD1 1
CN CN CN CN
101 102 151
ELECTRONIC CONTROL P.C BOARD 111 RT11
DSAR
5
POWER 3 3
SUPPLY MV
CORD
1~
RECEIVER DISPLAY
220-240V
50Hz P.C.BOARD P.C.BOARD
GRN/YLW
REMOTE
CONTROLLER
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
ESQUEMAS ELCTRICOS Y FRIGORFICOS
OUTDOOR UNIT TB
GRN / YLW
2 WHT
TO INDOOR UNIT
CONNECTING C
N BLK C1
RED MC
R
S
BLK
BLK BLK
4
WHT WHT
3
ORN ORN MF
2
C2 RED
RED 1
266
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
MS-18NV - E1 MS-18NV - E2 MU-18NV - E1 MU-18NV -
MS-18NV - E3 E2
Distributor
Flared
connection Compressor
Room temperature
thermistor
RT11 Capillary tube
Stop valve [2.0X700
Refrigerant pipe
[6.35
(Option) Refrigerant flow in cooling
(with heat insulator)
267
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
~/N
268
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
MSH-18NV - E1 MUH-18NV - E1
MSH-18NV - E2 MUH-18NV - E2
MSH-18NV - E3 MUH-18NV - E3
INDOOR UNIT Refrigerant pipe [15.88 Reversing valve OUTDOOR UNIT
(Option) (4- way valve)
Indoor coil
Indoor thermistor Strainer
heat RT12 Stop valve Outdoor
exchanger Distributor (with service port) heat
Flared connection Defrost exchanger
thermistor
RT61
Room temperature
thermistor
RT11
Accumulator
Compressor Capillary tube
[1.6x750
(2 pcs)
Flared connection
Capillary tube
[2.0X800
Strainer Reversing valve coil
(4-way valve coil)
heating ON
Refrigerant pipe Stop valve
cooling OFF
(Option) [6.35 Check
valve
(with heat insulator) Refrigerant flow in cooling
269
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
NR11
220-240V~ 2 WHT F12
BLU 4 CN 3 BRN
2 121
BRN BLU
TO OUTDOOR 1 CN201 3 52C YLW
UNIT CN211 GRY
3 TRANS
C11
CONNECTING N BLU MF
BLU 1 WHT
4
BLU F11 RED
2
WHT 1 WHT BLK
1
POWER LD1
GRN/YLW
CN
SUPPLY CN CN 151 ELECTRONIC CONTROL P.C BOARD CN
111 RT11
CORD
DSAR 101 102
~/N 220-240V
50Hz 5
3 3
MV
RECEIVER DISPLAY
CIRCUIT BREAKER P.C.BOARD P.C.BOARD
GRN/YLW
REMOTE
CONTROLLER
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate.
: Terminal block, : Connector
TB
220-240V 2 52C
WHT 2 1 WHT
RED RED
1
C2 ORN ORN
2
BLU 8 7 RED WHT WHT
X1 3 MF
3 BLK BLK
BLU 6 5 4
N YLW YLW
BLU 5 C
TO INDOOR X1 1
6
26F1
UNIT b
CONNECTING MC
52C S R
TB2
RED
GRY
BLK
3 F a
220-240V RED RED 1 RED
RED
RED
CR
GRN/YLW C1
BLU
NOTE:1. Use copper conductors only.(For field wiring) 1.Slide the sleeve.
2. show the terminals with a lock mechanism, so they cannot be removed when you pull 2.Pull the wire while
pushing the locking
the lead wire.
lever.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
270
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
Distributor
Flared
connection Compressor
271
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
CN
L NF RT11
NR11
111
TO OUTDOOR BRN BLU2 3 BLU 3
4 CN BRN
UNIT CN201 52C 121 YLW
CONNECTING N BLU 1 4 3
3 TRANS CN211 GRY
C11
BLU 1 4
WHT MF
RED
WHT F11 2 BLK
POWER 1
SUPPLY CN CN CN
151
CORD 101 102 ELECTRONIC CONTROL P.C BOARD
~/N 220-240V 5
50Hz
3 3
MV
RECEIVER DISPLAY
CIRCUIT BREAKER P.C.BOARD P.C.BOARD
GRN/YLW
REMOTE
CONTROLLER
BLK BLK
BLK
BLK
4 3
MF WHT WHT
3
ORN ORN
2
RED RED C2 CN711 1 2 3 4 CN661 CN721
1 CN730 X62
SR61
TB 3
12VDC 3 RED 2
CONNECTING
1 IC881
NR61
WHT
220-240V~2
TO INDOOR
F
F61
VLT
YLW 52C
52C1 DEICER
3 4 P.C. BOARD
GRN/YLW
DSAR WHT
CR
VLT YLW CZ
WHT WHT
52C1
WHT WHT C
1 2
BLU C1 RED S MC R
BLK
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
C1 COMPRESSOR CAPACITOR MF OUTDOOR FAN MOTOR X62 REVERSING VALVE COIL RELAY F FUSE(2A)
<INNER THERMOSTAT>
C2 OUTDOOR FAN MOTOR CAPACITOR NR61 VARISTOR 21S4 REVERSING VALVE COIL 26F1 THERMOSTAT (AIR FLOW CONTROL)
DSAR SURGE ABSORBER 1 RT61 DEFROST THERMISTOR 52C CONTACTOR IC881 DC/DC CONVERTER
F61 FUSE(2A) SR61 SOLID STATE RELAY 52C1 COMPRESSOR CONTACTOR CR SURGE ABSORBER 2
MC COMPRESSOR<INNER THERMOSTAT> TB. TB2 TERMINAL BLOCK X1 FAN MOTOR RELAY CZ SURGE ABSORBER 3
272
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit:mm
MSH-24NV - E1 MUH-24NV - E1
MSH-24NV - E2 MUH-24NV - E2
Reversing valve OUTDOOR UNIT
INDOOR UNIT Refrigerant pipe [15.88
(4- way valve)
(Option)
(with heat insulator) Muffler
Indoor coil
Indoor thermistor Ball valve Strainer
heat RT12
exchanger Distributor Outdoor
Flared connection
heat
exchanger
Room temperature
thermistor Accumulator
RT11 Defrost
Compressor thermistor
RT61
Discharge pressure
Flared connection Capillary tube
Check regurator open
[1.6X350 23.5 kgf/J
valve
Strainer
273
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MCF-18NV- E2
CIRCUIT BREAKER TB
GRN/YLW
N BLU 2 2
CN RT12
112
HIC1
L BRN
LDCOM WHT WHT
3 1
4 ORN 2 ORN
NR11
LDC11
POWER SUPPLY 2
~/N 220-240V 52C C11 LDC12 RED 3 RED
1 3 BRN
50Hz MF
CN201 TRANS LDFH BLK 7 BLK
SR144 4
LDFL BLU 6 BLU
GRN/YLW F11 SR142
LDFM YLW 5 YLW
SR143
CN CN CN CN 8
TO OUTDOOR N BLU 101 104 113 151
ELECTRONIC CONTROL P.C BOARD
UNIT GRN/YLW
CONNECTING 5 6
220-240V~ 2 WHT 5
4 6
5 MV
DISPLAY & SW/THERMO
REMOTE AUTO
RECEIVER P.C.BOARD
CONTROLLER RESTART
P.C.BOARD ASSEMBLY RT11
MODEL MCF-24NV- E2
TB
CIRCUIT BREAKER
GRN/YLW
N BLU 2 2
ESQUEMAS ELCTRICOS Y FRIGORFICOS
CN RT12
112
HIC1
L BRN
LDCOM WHT 1 WHT
3
NR11
5 MV
DISPLAY & SW/THERMO
REMOTE AUTO RESTART
RECEIVER P.C.BOARD
CONTROLLER
P.C.BOARD ASSEMBLY RT11
274
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MUCF-18NV- E1 MUCF-18NV- E2
TB
220V - 240V~ 2 WHT
C
WHT
TO BLU
C1
N RED
MC
INDOOR UNIT
CONNECTING S
R
BLK
F
GRN/YLW C2
RED RED
1
ORN ORN
2
WHT WHT
3 MF
BLU BLK
4
TB
2 52C
220-240V~ WHT 2 1 WHT
RED RED
1
C2 ORN ORN
BLU RED 2
UNIT A2/b
CONNECTING MC
52C S R
TB2
RED
GRY
BLK
3 F
220-240V~ RED 1 WHT A1/a
RED
RED
RED CR
GRN/YLW C1
BLU
275
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Refrigerant pipe
INDOOR UNIT 12.7 OUTDOOR UNIT
(option)
(With heat insulation)
Outdoor
heat
Flared exchanger
Indoor coil Distributor Compressor
thermistor connection
RT12
Room
temperature Stop valve
Capillary tube Strainer
thermistor
RT11
Refrigerant pipe 1.8 800
6.35
(option)
(With heat insulation)
MCF-18NV E1 E2 MUCF-18NV E1 E2
Refrigerant pipe
INDOOR UNIT 15.88 OUTDOOR UNIT
(option)
(With heat insulation) Accumulator
Outdoor
heat
Flared exchanger
Indoor coil Distributor Compressor
thermistor connection
ESQUEMAS ELCTRICOS Y FRIGORFICOS
RT12
Room
temperature Stop valve
Capillary tube Strainer
thermistor
RT11
Refrigerant pipe 2.0 700
6.35
(option)
(With heat insulation)
MCF-24NV E1 E2 MUCF-24NV E1 E2
Refrigerant pipe
INDOOR UNIT 15.88 OUTDOOR UNIT
(option)
(With heat insulation) Accumulator
Outdoor
heat
Flared exchanger
Indoor coil Distributor Compressor
thermistor connection
RT12
Room
temperature Stop valve Capillary tube
2.0 700 Strainer
thermistor
RT11
Refrigerant pipe
9.52 Capillary tube Discharge
(option) pressure
1.6 350
(With heat insulation) regulator
276
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MCFH-18NV-
CIRCUIT BREAKER
TB
GRN/YLW
N wBLU
CN 2 2
112 RT12
L wBRN HIC1
LDCOM WHT WHT
POWER SUPPLY 3 w LDC11 ORN
1
ORN
NR11
~/N 220-240V 4 2
2 C11 LDC12 RED RED
50Hz 1 w3 52C 3
GRN/YLW SR144
LDFH BLK 4
BLK MF
CN201 TRANS SR142
LDFL BLU 6
BLU
N wBLU LDFM YLW YLW
F11 SR143 5
TO OUTDOOR SR141
LDFVL BRN 7
BRN
UNIT 220-240V~ 2 wWHT CN CN CN CN 8
CONNECTING 101 104 113 151 ELECTRONIC CONTROL P.C BOARD GRN/YLW
12VDC 3 wRED 5 6
5
5 SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
4 6
ROOM TEMP- SW/THERMO SWITCH & ROOM TEMP-
C11 INDOOR FAN
MF INDOOR
FAN MOTOR RT11 THERMISTOR P.C. BOARD P.C.BOARD
AUTO RESTART ERATURE ERATUR THERMISTOR
FOR MULTI SYSTEM
ASSEMBLY MV CAPACITOR
INDOOR TERMINAL
N F11 FUSE(3.15A) MV VANE MOTOR RT12 COIL TB
BLOCK
TO OUTDOOR THERMISTOR
2
REMOTE DISPLAY & SW/THERMO SR141 SOLID STATE
UNIT COMPRESSOR
12VDC 3 RECEIVER P.C.BOARD HIC1 DC/DC NR11 VARISTOR 52C
~
CONNECTING CONTROLLER P.C.BOARD RT11 CONVERTER SR144 RELAY CONTACTOR
MUCFH-18NV- E2
21S4 52C
RT61
BLK
BLK
VLT
VLT
WHT 1 1
CONNECTING
w
INDOOR UNIT
220-240V~ 2 SR61
TAB21 WHT ORN
2 2
IC881
NR61
WH WHT
T 3 3
N w BLU BLK BLK
TRANS 4 4
w
TO
CN711
TAB20 X62
DSAR
277
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MCFH-13NV- E2
Reversing valve MUCFH-13NV- E2
Refrigerant pipe [12.7 (4-way valve)
INDOOR UNIT (Option) OUTDOOR UNIT
(with heat insulator) Muffler
Coil temperature
thermistor
RT12
Compressor Defrost
Capillary thermistor
Accumulator tube RT61
[1.6o350
R.V.coil
Room temperature heating ON
thermistor cooling OFF
RT11 Flared connection
Capillary tube
Strainer [2.0o250
MCFH-18NV- E1 MUCFH-18NV- E1
Coil temperature
thermistor
RT12
Compressor Defrost
Capillary thermistor
Accumulator RT61
tube Capillary
[1.6o750 tube
[1.6o750
Room temperature
thermistor
RT11 Flared connection R.V.coil
heating ON
cooling OFF
Strainer Capillary tube [2.0o600
278
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
CIRCUIT BREAKER TB
GRN/YLW
N w BLU
CN 2 2
HIC1 112 RT12
L w BRN
LDCOM WHT WHT
POWER SUPPLY 3 4 1 ORN
NR11
LDC11 ORN 2
~/N 220-240V 2 C11 LDC12 RED RED
50Hz 1 w 3 52C 3
SR144
LDFH BLK 4 BLK MF
GRN/YLW CN201 TRANS LDFL BLU BLU
SR142 6
LDFM YLW 5 YLW
Nw BLU F11 SR143
BRN
TO OUTDOOR SR141
LDFVL BRN 7
CN CN CN CN 8
UNIT 220-240~ 2 w WHT 101 104 113 151 ELECTRONIC CONTROL P.C BOARD GRN/YLW
CONNECTING
6
12VDC 3 w RED 5 5
4 6 SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
MV INDOOR FAN INDOOR ROOM TEMP- SW/THERMO SWITCH & ROOM TEMP-
5 C11 CAPACITOR MF FAN MOTOR
RT11 ERATURE
THERMISTOR
ERATURE THERMISTOR
P.C. BOARD P.C.BOARD
INDOOR COIL TERMINAL
REMOTE
DISPLAY & SW/THERMO F11 FUSE(3.15A) MV VANE MOTOR RT12 THERMISTOR TB BLOCK
RECEIVER AUTO RESTART P.C.BOARD
CONTROLLER DC/DC SR141 SOLID STATE COMPRESSOR
ASSEMBLY NR11 52C
~
P.C.BOARD RT11
HIC1 VARISTOR
CONVERTER SR144 RELAY CONTACTOR
RT61
6 X1 21S4
YLW YLW
5 BLK 1 5 BRN
BLK
BLK
BLK
MF 4
WHT WHT 3
3
ORN ORN
2 CN711 1 2 3 4 CN661 CN721
RED RED
1 C2 CN730
SR61
X62
TB 3
12VDC 3 w RED 2
CONNECTING
1 IC881
2w
TO INDOOR
NR61
WHT
F61
BLU
VLT
A2 YLW 52C
A1 52C1 3 w 4 w DEICER
P.C. BOARD
DSAR WHT
CR YLW
GRN/YLW
VLT CZ WHT
WHT 52C1
WHT CWHT
1 2
BLU C1 RED S MC R
BLK
NOTE :1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/:Terminal block, : Connector
4. w shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
279
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
MCFH-24NV- E1 MUCFH-24NV- E1
MCFH-24NV- E2 MUCFH-24NV- E2
Reversing valve
Refrigerant pipe [15.88 (4-way valve)
(Option)
(with heat insulator) Muffler
Coil temperature
thermistor
RT12
Compressor
Accumulator
Discharge pressure
regurator open
Room temperature 23.5Of/F
thermistor Capillary tube
Check [1.6o350
RT11 Flared connection valve
280
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
4 - WIRING DIAGRAM
INDOOR UNIT
SE-1.6AR.TH SE-1.6AR.TH-T
SE-2AR.TH SE-2AR.TH-T
SE-2.5AR.TH SE-2.5AR.TH-T
CIRCUIT BREAKER TB
GRN/YLW
N W BLU
HIC1
L W BRN
LDCOM WHT WHT
W
3 4 LDC11 ORN 1 ORN
NR11
POWER SUPPLY
~/N 2 C11 LDC12 RED 2 RED
220-240V 220V 1 W 3 52C 3
MF
50Hz 60Hz TB CN201 TRANS LDFH BLK 7 BLK
GRN/YLW
SR144 4
LDFL BLU YLW 5 YLW
F11 SR142
LDFM BLU 6 BLU
NW BLU
SR143
CN CN CN 8
TO OUTDOOR 104 113 112 ELECTRONIC CONTROL P.C BOARD
UNIT 220-240V 220V 2 GRN/YLW
50Hz 60Hz W WHT
CONNECTING
220-240V 220V 3 5 2 2
50Hz 60Hz W RED
12 12
CNR CN CN
120 120 104B
REMOTE
REMOTE
CONTROLLER RT11 RT12
CONTROLLER
INTERFACE
P.C BOARD P.C BOARD
C11 FAN MOTOR CAPACITOR MF FAN MOTOR RT12 INDOOR COIL THERMISTOR
SR141
F11 FUSE(3.15A) NR11 VARISTOR SOLID STATE RELAY
~
SR144
HIC1 DC/DC CONVERTER RT11 ROOM TEMPERATURE THERMISTOR TB TERMINAL BLOCK
NOTE :1. Since the indoor fan motor (MF) is connected with 50 Hz power, if 60Hz power is used,change the wiring
connection showing fig:*1 fig: *1 50 YELLOW
Indoor Fan Moter(MF) for 60Hz BLUE 60 BLUE
2. About the outdoor side electric wiring referto the outdoor unit electric wiring diagram for servicing.
3. Use copper conductors only. (For field wiring)
4. Symbols below indicate.
/:Terminal block, : Connector
How to remove the terminals shown at W mark.
W shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
281
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
OUTDOOR UNIT
TB
2 W
220V, 60Hz WHT RED RED
SU-1.6NR.TH C2
1
ORN
3 ORN 2
CONNECTING
SU-2NR.TH 220V, 60Hz W RED F RED
TB2
WHT WHT
TO INDOOR
3 MF
BLK BLU BLK
N 4
W BLU
26C
UNIT
BLK
A2 52C A1
52C
GRN/YLW WHT
CR L1/1 T1/2 C
VLT YLW
BLU C1 RED S MC R
BLU
L3/5 T3/6 BLK
SU-2.5NR.TH TB
2 W RED RED
1
220V, 60Hz WHT C2 ORN ORN
2
WHT WHT
CONNECTING
3 3 MF
220V, 60Hz W RED F RED RED RED 8 3 BLK BLK
TO INDOOR
TB2 5 4
26F1 7 X1 YLW YLW
N BLU 5
W X1 1
ORN
UNIT
BLU
A2 52C A1
GRN/YLW
52C
WHT
VLT CR YLW L1/1 T1/2 C
BLU C1 RED S MC R
BLU
L3/5 T3/6 BLK
282
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
SE-1.6AR.TH SU-1.6NR.TH
INDOOR UNIT Refrigerant pipe [12.7
(Option)
OUTDOOR UNIT
(with heat insulator)
Indoor coil
thermistor
Distributor
(With strainer) Dis pressure
regulator
Compressor
SE-2AR.TH SU-2NR.TH
INDOOR UNIT Refrigerant pipe [15.88 OUTDOOR UNIT
(Option)
(with heat insulator)
Indoor coil
thermistor
Distributor
(With strainer)
SE-2.5AR.TH SU-2.5NR.TH
INDOOR UNIT Refrigerant pipe [15.88 OUTDOOR UNIT
(Option)
(with heat insulator)
Indoor coil
thermistor
Distributor
(With strainer)
Accumulator Compressor
Dis pressure
regulator
283
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
4 - WIRING DIAGRAM
INDOOR UNIT
SEH-1.6/2/2.5AR.TH
CIRCUIT BREAKER TB
GRN/YLW
N W BLU
L W BRN HIC1
LDCOM WHT WHT
4 1
NR11
POWER SUPPLY 3 LDC11 ORN ORN
~/N 2 52C C11 LDC12 RED
2 RED
220-240V TB 1 W3 BLK
3 BLK
50Hz GRN/YLW TRANS
SR144
LDFH
4 MF
CN201 SR142
LDFL BLU YLW
5
YLW
LDFM BLU BLU
N W BLU F11 SR143 6 BRN
LDFVL BRN
TO OUTDOOR SR141 7
UNIT CN CN CN 8
220-240V~2 W WHT 104 113 112 ELECTRONIC CONTROL P.C BOARD GRN/YLW
CONNECTING
12VDC 3 W RED 5 2 2
12 12
CNR CN CN
120 120 104B
REMOTE REMOTE
CONTROLLER
RT11 RT12
CONTROLLER
INTERFACE
P.C BOARD P.C. BOARD
C11 FAN MOTOR CAPACITOR MF FAN MOTOR RT12 INDOOR COIL THERMISTOR
SR141
F11 FUSE(3.15A) NR11 VARISTOR SOLID STATE RELAY
~
SR144
HIC1 DC/DC CONVERTER RT11 ROOM TEMPERATURE THERMISTOR TB TERMINAL BLOCK
NOTE :1. Since the indoor fan motor (MF) is connected with 50 Hz power, if 60Hz power is used,change the wiring
connection showing fig:*1 fig: *1 50 YELLOW
Indoor Fan Motor(MF) for 60Hz BLUE 60 BLUE
2. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
3. Use copper conductors only. (For field wiring)
4. Symbols below indicate.
/:Terminal block, : Connector
How to remove the terminals shown at w mark.
w shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
284
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
OUTDOOR UNIT
SUH-1.6/2VR.TH
RT61
21S4
BLK BLK
BLK
BLK
4
MF WHT WHT
3
ORN
2 CN711 1 2 3 4 CN661 CN721
RED RED
1 CN730 X62
C65
SR61
TB 3
3 W 2
12VDC RED
1
IC881
2 W
NR61
CONNECTING
F61
TO INDOOR
W
N
W BLU TAB20 TRANS
UNIT
BLU
A2 YLW 52C DEICER
A1 52C1
3 W 4 W P.C. BOARD
CR
WHT
VLT YLW
52C1
WHT WHT
WHT
GRN/YLW
C
DSAR
L1/1 T1/2
W
CZ
BLU BLU C1 RED S MC R
W W BLK
WHT
L3/5 T3/6
285
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Indoor coil
thermistor Dis
RT12 Pressure
Distributor Regulator
(With strainer) Accumulator Capillary
Compressor tube
({3.0x{1.6xR550)
Defrost
Room temperature thermistor
thermistor Flared connection RT61
Capillary tube
RT11 ({3.0x{1.8xR330)
Strainer
SEH-2AR.TH SUH-2VR.TH
INDOOR UNIT OUTDOOR UNIT
Refrigerant pipe [15.88 Reversing
(Option) valve Strainer 1
(with heat insulator) Muffler
Indoor coil
thermistor Dis
RT12 Pressure
Distributor Regulator
(With strainer) Capillary
Accumulator
Compressor tube
({3.0X{1.6XR860)X2
Defrost
Room temperature thermistor
thermistor Flared connection RT61
RT11 Capillary tube
Strainer ({4.0X{2.4XR660)
286
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
OUTDOOR
SUH-2.5VR.TH
RT61
6 X1 21S4
YLW YLW 1 5 BRN
5
BLK BLK
BLK
BLK
4
MF WHT WHT 3
3
ORN ORN
2 CN711 1 2 3 4 CN661 CN721
RED RED C2
1 CN730
SR61
X62
TB 3
12VDC 3 W 2
RED
1 IC881
WHT
NR61
220-240V~ 2 W WHT F
CONNECTING
ORN RED
F61
RED 8
TO INDOOR
VLT
A2 YLW 52C
A1 52C1 DEICER
3 W 4W P.C. BOARD
WHT
CR
VLT YLW
GRN/YLW
52C1
WHT
WHT
WHT
DSAR
L1/1 T1/2 C
CZ
BLU BLU C1 MC R
RED S
WHT
L3/5 T3/6 BLK
287
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
SEH-2.5AR.TH SUH-2.5VR.TH
Indoor coil
thermistor Dis
RT12 Pressure
Distributor Regulator
(With strainer) Defrost
Accumulator Distributor thermistor
Compressor RT61
Room temperature
thermistor Flared connection
RT11 Capillary tube
Strainer 3 ({4.0x{2.0xR410)
288
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
8 - WIRING DIAGRAM
MV P.C.BOARD
REMOTE
CIRCUIT BREAKER CONTROLLER
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
289
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
TB 52C2
POWER SUPPLY L BRN NO COM WHT 1 51C WHT
~/N
BRN
WHT
220-240V
BRN
N BLU 52C1 C
50Hz WHT WHT TB3
NO COM 1
PE GRN/YLW F13 C1 RED S MC R
WHT
BLK
F12 BLU
X2 WHT WHT
YLW TB2 YLW 2 1 1
52C2 BLU BLK
C2
BRN
BRN
4 3 2 2 MF
BLU
RED RED
3
X1
RED TB2 RED 2 1
52C1
TB 4 3 1
FROM INDOOR 2 WHT1
UNIT No.A
CONNECTING X1 BLU
1
12V 21R1 BLU
BLK 2
BLU BLU
2 GRY 1
FROM INDOOR 21R2 BLU 2 21R
UNIT No.B TB3 BLU
X2
CONNECTING 1
12V ORN 2
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
290
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Flared connection
Refrigerant pipe
Indoor coil 6.35 (1/4)
Solenoid valve Compressor
thermistor (option) 21R1
(With insulation)
RT12
Indoor
heat Stop valve
UNIT B exchanger with service port
Flared connection
Solenoid valve
21R2
Indoor coil
thermistor Stop Capillary tube
RT12 valve
Refrigerant flow
Refrigerant pipe 1.4 x 400
6.35 (1/4)
(option)
(With insulation)
Outdoor unit
MUX-10RV E1
PIPING PREPARATION
1 Table below shows the specifications of pipes commercially available.
Outside diameter Insulation
UNIT No. Pipe Insulation material
mm inch thickness
For liquid 6.35 1/4 8 mm Heat resisting foam plastic
A and B UNIT
For gas 9.52 3/8 8 mm 0.045 specific gravity
2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3 Refrigerant bending radius must be 10cm or more.
291
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
5 - WIRING DIAGRAM
INDOOR UNIT MODELS MSX-05NV- E1 , MSX-09NV- E1 , MSX-12NV- E1
SR11 CN
RT12
TB 112
TO OUTDOOR
L BRN TAB12 HIC1
CN
UNIT BRN 111 RT11
F12 BLU
CONNECTING 1 CN201
BLU BLU BLK
2 1 1
12VDC 2 WHT NR11 CN 3 GRY
121 2
YLW
CN202 3
12VDC 1 BLK TRANS
3
BRN
4
MF
2 C11
WHT
1 F11 2 5
N BLU RED
1 6
BLU 1 CN LD101 CN CN211
122 151 ELECTRONIC CONTROL P.C BOARD
GRN/YLW
GUARD
POWER
GRN/YLW
PLATE
SUPPLY 5
CORD
~/N 220-240V
50Hz POWER MONITOR,
MV
RECEIVER
P.C.BOARD
CIRCUIT BREAKER
REMOTE
CONTROLLER
52C2
POWER SUPPLY L BRN NO COM WHT 1 51C WHT
BRN
WHT
ESQUEMAS ELCTRICOS Y FRIGORFICOS
BRN
WHT
BLU
BLK
X2 TB2 WHT 1 WHT
YLW 2 1
52C2 BLU
2 BLK
C2
BRN
BRN
4 3 2 YLW MF
RED
BLU
3 RED
X1
REDTB2 2
52C1
1
TB 1
2 WHT
4 3 RED
TO INDOOR
BLU
UNIT No.A 12VDC1 X1
CONNECTING 21R1 BLU
BLK
BLU BLU
2 GRY
TO INDOOR 21R2 BLU 2 21R
UNIT No.B
TB3 BLU
CONNECTING 12VDC1 X2
ORN
292
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Flared connection
Refrigerant pipe
Indoor coil 6.35 (1/4)
Solenoid valve Compressor
thermistor (option) 21R1
(With insulation)
RT12
Indoor
heat Stop valve
UNIT B exchanger with service port
Flared connection
Solenoid valve
21R2
Indoor coil
thermistor Stop Capillary tube
RT12 valve
Refrigerant flow
Refrigerant pipe 1.4 x 400
6.35 (1/4)
(option)
(With insulation)
Outdoor unit
MUX-10NV E1
PIPING PREPARATION
1 Table below shows the specifications of pipes commercially available.
Outside diameter Insulation
UNIT No. Pipe Insulation material
mm inch thickness
For liquid 6.35 1/4 6 mm Heat resisting foam plastic
A and B UNIT
For gas 9.52 3/8 6 mm 0.045 specific gravity
2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3 Refrigerant bending radius must be 10cm or more.
293
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
BLU
NO COM BRN
220-240V N BRN GRY F13 BLK R MC1 C
50Hz
BLU 3 13 1
PE
WHT
WHT
X11 X12
GRY
F12
TB3 1 BLU 8 7 5 WHT 5
CIRCUIT BREAKER X11
1 51C1
GRN/YLW BLU BLU
RED
BRN BRN
2 YLW 1 X2
FROM INDOOR RED 1 2 BLU TB2 BLU C2 S
52C2
UNIT No.A 4 3 RED TB2 1 BLU 21R
52CA
CONNECTING 1 BLU 2 MC2 C
BLK R
BLU
12V 2 BLU
WHT
21R2
RED
WHT
2 GRY 1 X1 WHT 1 51C2
FROM INDOOR YLW 1 2
52C1
UNIT No.B BRN 4 3
CONNECTING 1
X1 YLW BLU 8 7 GRY
X12
BLU
12V ORN
2 BLU 21R1 X11 4 RED RED
X12 4 RED C3 ORN
1
6 ORN
2 WHT 1 52C2 2
FROM INDOOR BRN 4 3 6 2 WHT WHT
UNIT No.C 2 3 MF
BRN
BLK
WHT
X2 BLK
CONNECTING 1 52C1 F14 4
12V 2 WHT YLW YLW YLW
5
BLK 4 3
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
294
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit : mm
MSC-09RV- E1 MUX-18RV- E1
Indoor coil
thermistor
Refrigerant pipe
Capillary tube
RT12
6.35<1/4>
1.6 1100
(option)
(With insulation)
295
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
BLU
BRN
220-240V N BLK R MC1 C
50Hz BRN GRY F13
BLU 3 1 3 1
WHT
WHT
X11
GRY
X12
F12
TB3 1 BLU 8 7 5
CIRCUIT BREAKER X11 WHT 5
1 51C1
GRN/YLW BLU BLU
RED
BRN BRN
2 YLW 1 X2
TO INDOOR RED 1 2 BLU TB2 BLU C2 S
52C2
1
UNIT No.A 52CA 4 3 RED BLU TB2 BLU 21R
12VDC1 2 BLK R MC2 C
BLU
CONNECTING
WHT
RED2 BLU 21R2
WHT
X1 1 51C2
2 GRY 1 YLW 1 2 WHT
TO INDOOR 52C1
UNIT No.B X1 BRN 4 3 YLW 8 7 GRY
12VDC1 BLU
BLU
X12
CONNECTING BLU 21R1 X11 4
ORN 2 RED RED
X12 4 RED 1
6 C3 ORN 2 ORN
2 WHT 1 BRN 4
52C2
3 6 2 WHT
TO INDOOR WHT
X2 2 3 MF
WHT
BRN
C2 COMPRESSOR CAPACITOR(B,C) X11 FAN MOTOR RELAY(A) 51C2 OVER CURRENT RELAY(B,C)INNER THERMOSTAT
C3 OUTDOOR FAN CAPACITOR X12 FAN MOTOR RELAY(B,C) 52CA COMPRESSOR CONTACTOR(A)
MC1 COMPRESSOR(A) 21R SOLENOID COIL 52C1 COMPRESSOR CONTACTOR(B)
MC2 COMPRESSOR(B,C) 21R1 SOLENOID COIL(B) 52C2 COMPRESSOR CONTACTOR(C)
MF FAN MOTOR(INNER THERMOSTAT) 21R2 SOLENOID COIL(C) X1 RELAY(B)
F12 FUSE(2A) F14 FUSE(2A) X2 RELAY(C)
F13 FUSE(2A) TB2,TB3 TERMINAL BLOCK
ESQUEMAS ELCTRICOS Y FRIGORFICOS
296
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Unit : mm
MSX-09NV- E1 MUX-18NV- E1
Indoor coil
thermistor
Refrigerant pipe
Capillary tube
RT12
6.35<1/4>
1.4 600
(option)
(With insulation)
297
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
OUTDOOR UNIT
MODEL MUX-24RV- E1
BRN BRN
~/N TB10
220-240V 4 52C2 3 2 RED
N 1 BRN 4 3 WHT MC1
50Hz C1 S
52C4
BRN WHT R
PE WHT BLK
4 52C3 3
BLU
BLU 2 BLU 1
CIRCUIT
BREAKER GRN/YLW TB8 BLU
WHT C
F
BLU BLU
BLU
1 RED
21R1 BLU 21RA MC2
BRN
2 2 C2 S
FROM INDOOR YLW2 BLU BLU
UNIT No.A X1 BLU ORN 52C1 R
TB1 X1 2 1
CONNECTING 1 4 3 1 2 2 BLU BLU BLK
12V YLW1
BLU
BLU
TB6 BLU ORN
X11
7 8
BLU BLU 1 BLU
1
21R2 BLU BRN
BRN
2 2 2
FROM INDOOR ORN 2 13 1
3
UNIT No.B X2 BLU ORN 52C2 BLU
BLU
TB2 X2 TB5 2 1 X12
CONNECTING 1 4 3 1 2 1 X11
TB7
12V ORN 1 5 WHT 5
BLU BLU
WHT
1
BLU
21R3 BLU
C11
2 GRY RED
7 1
BRN
2 3 ORN ORN
FROM INDOOR WHT 2 X12 2
WHT WHT
UNIT No.C X3 BLU ORN 52C3 BLU 8 3 MF
TB3 X3 YLW BLK
CONNECTING 1 4 3 1 2 4
BLU
BLU
12V 1 5
WHT
BLU BLU 6
1
21R4 BLU
2 1 2 3
BRN BRN
2 3
FROM INDOOR GRY 2 BLU BLU
UNIT No.D X4 BLU ORN 52C4 BLU
TB4 X4 21RB
ESQUEMAS ELCTRICOS Y FRIGORFICOS
CONNECTING 1 4 3 1 2
12V GRY 1
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
298
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Refrigerant pipe
Indoor coil {6.35 (1/4) Solenoid valve Compressor 1
(option) 21R1
thermistor (With insulation)
RT12
Indoor
heat Stop valve
UNIT B exchanger with service port
Flared connection
MSC-12RV- E1
Solenoid valve
21R2
Indoor coil
thermistor Stop Capillary tube
RT12 Refrigerant pipe valve {1.6 x 420
{6.35 (1/4)
(option)
(With insulation)
Outdoor
heat
Room Refrigerant pipe exchanger
temperature {9.52 (3/8)
thermistor (option)
(With insulation) Solenoid valve
RT11
21RB
Refrigerant pipe
Indoor coil {6.35 (1/4) Solenoid valve Compressor 2
(option) 21R3
thermistor (With insulation)
RT12
Indoor
heat Stop valve
UNIT D exchanger with service port
Flared connection
MSC-09RV- E1
Solenoid valve
21R4
Indoor coil
thermistor Stop Capillary tube Refrigerant flow
RT12 Refrigerant pipe valve {1.6 x 650
{6.35 (1/4)
(option)
(With insulation)
299
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
WHT
POWER SUPPLY TB BRN
L
WHT
52C1 WHT C
BRN
~/N WHT
1
220-240V N BRN 4 52C2 34 3 RED RED
2 MC1
50Hz C1 3 S
WHT BLK
BRN
WHT
52C4
BRN WHT R
BLK
BLU 4 3
BLU
52C3
CIRCUIT
BREAKER GRN/YLW C
BRN F
BLU BLU WHT
21RA 1
1 RED RED MC2
YLW
21R1 BLU
2 BLU BLU 2
2 2 C2 3 S
BLK
TO INDOOR X1 BLU 21 R
UNIT No.A
1TB1 X1
ORN 2 BLU BLU BLK
BLU
52C1
CONNECTING 4 3 1 2 BLU ORN
12VDC YLW 1 TB6
7 X11 8 BLU
1 BLU
BLU BLU BLU 2
BRN
21R2 BLU
1 BRN
2 2
ORN 2
TO INDOOR X2 BLU
TB5 3 1 1
BLU
ORN BLU
UNIT No.B
CONNECTING 1 TB2
X2 4 3 1
52C2
2
2 1 X12 3 X11
TB7 5
12VDC ORN 1 5
BLU BLU WHT
C11
WHT
1
BLU
21R3 BLU
2 7 GRY RED
BRN
WHT 1
2 2 3 ORN
2
ORN
TO INDOOR X3 BLU
X12
8 WHT
3
WHT
MF
TB3 X3
UNIT No.C BLU ORN 52C3 YLW BLK
CONNECTING 1 4 3 1 2 4
BLU
BLU
12VDC WHT 1 5
BLU BLU 6
21R4 BLU 1
2
BRN BRN
123
2 GRY
2 3 BLU BLU
TO INDOOR
X4 BLU ORN BLU 21RB
UNIT No.D 1 TB4 X4 52C4
CONNECTING 4 3 1 2
12VDC 1
GRY
TB10 2 RED
POWER SUPPLY N 31 BRN 4 52C2 4
WHT
S
MC1
C1
BRN
BLK
50Hz BLU 4 52C3 3 2 BLU 1
CIRCUIT GRN/YLW TB8 BLU C
WHT
F
21R1 BLU
1 21RA RED
MC2
2 YLW 2 2 C2 S
BRN
X1 BLU BLU
TO INDOOR BLU ORN R
UNIT No.A 1 TB1 X1 4 3
52C1
2 BLU 2 1 BLU BLK
BLU
CONNECTING 1 2
12VDC YLW 1
BLU
BLU BLU 1 7 8
1
BRN
C11
BLU
21R3 BLU
2 GRY RED
BRN
7 1
2 2
WHT 3 X12
ORN
2
ORN
TO INDOOR X3 BLU BLU 8 WHT
3
WHT
MF
UNIT No.C TB3 X3 ORN
52C3 YLW BLK
1 4 3 4
BLU
2
BLU
CONNECTING 1 5
12VDC WHT 1 6
BLU BLU
21R4 BLU
1
2
BRN BRN
12 3
2 GRY 2 3 BLU BLU
TO INDOOR
UNIT No.D X4 BLU ORN 52C4 BLU
1TB4 X4
21RB
CONNECTING 4 3 1 2
12VDC GRY 1
300
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Refrigerant pipe
Indoor coil {6.35 (1/4) Solenoid valve Compressor
(option) 21R1
thermistor (With insulation)
RT12
Indoor
heat Stop valve
UNIT B exchanger with service port
Flared connection
MSX-12NV- E1
Solenoid valve
21R2
Indoor coil
thermistor Stop Capillary tube
RT12 Refrigerant pipe valve {1.6 x 400
{6.35 (1/4)
(option)
(With insulation)
Outdoor
heat
Room Refrigerant pipe exchanger
temperature {9.52 (3/8)
thermistor (option)
(With insulation) Solenoid valve
RT11
21RB
Refrigerant pipe
Indoor coil {6.35 (1/4) Solenoid valve Compressor
(option) 21R3
thermistor (With insulation)
RT12
Indoor
heat Stop valve
UNIT D exchanger with service port
Flared connection
MSX-09NV- E1
Solenoid valve
21R4
Indoor coil
thermistor Stop Capillary tube Refrigerant flow
RT12 Refrigerant pipe valve {1.6 x 650
{6.35 (1/4)
(option)
(With insulation)
301
ESQUEMAS ELCTRICOS Y FRIGORFICOS
V
TB WHT L MF
PE GRN/YLW WHT WHT
2 NF62 2 NF61 U MC W
POWER SUPPLY DS63
N BLU 4 4 BLK BLK
220-240V ~ 1
+ - + WHT WHT
~/N L BRN BRN 3 3 C67 RED 2
50Hz 1 RED RED
1 ~ - 3
RED
WHT
BLK
BLK
CIRCUIT BREAKER
WHT
BLK
BLU
GRN
YLW
ORN
BRN
RED
3 TB RED BLK R65 BLU TR
OUTDOOR UNIT
BLU
RED
+ C63 P U
UNIT LD74 V
N W
CONNECTING 3 - LD72 C64 LD77 BLU BuNEuNBvNEvNBwNEwN
RED - ~+
21S4
12V INDOOR ~
RED
BLK
BLU
RED
ORN
BLU
RED
RED
WHT
BLK
ORN
YLW
RED
GRN
YLW
UNIT (A) N BLU ~ DS61 BLU
1 BRN 1 BRN
YLW CN801 1 2 1 2 CN621 1 2 CN61 4 3 2 1 TAB91 1 2 3 4 5 6 8 RED
2 2
GRN YLW 3 FUSE1 CN731 C65 CN63 7
3
BLU
CN611
YLW
TBAC2
TBAC1
CN941
4 6
T801
4 FUSE2 X67 ORN
RED 5
BLU 1 YLW
2 ELECTRONIC CONTROL X60 4
LD64
LD63 BLK
LDE1
TB62 BRN
SSR61
LD62
CN701
P.C.BOARD 3
RED 3 GRN
F62 TB61
CT61 4
CN601
BLK
BLU 5 CN761 CN771 CN682 CN661 CN683 CN681 CN641 CN671 2 BLU
X64
NR61 6 1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 2 1 2 3 4 1 2 3 4 4 3 2 1 1 2 1
LD61
AR61 3 4
MODELS MXZ-18RV-
BLU
RED
ORN
GRY
GRY
GRY
GRY
BLU
WHT
RED
BLK
BLK
BLK
BLK
ORN
YLW
GRY
GRY
GRY
GRY
YLW
GRY
GRY
RED
RED
WHT
R64
E1
RELAY P.C.BOARD
LEV A LEV B
RT62 RT63 RT64 RT65 RT66 RT67 RT61 HPS
302
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
AR61 SURGE ABSORBER L REACTOR FIN TEMPERATURE CURRENT-DETECTING
RT63 R65
CT61 CURRENT TRANSFORMER LEV A,B EXPANSION VALVE THERMISTOR RESISTOR
C61 POWER-FACTOR CAPACITOR L61 CMC COIL GAS PIPE TEMPERATURE B. SSR61 SOLID STATE RELAY
RT64
C63 CERAMIC CAPACITOR MC COMPRESSOR THERMISTOR TB TERMINAL BLOCK
C64 CERAMIC CAPACITOR INDOOR FAN MOTOR GAS PIPE TEMPERATURE A. POWER TRANSISTOR
MF RT65 TR
C65 INDOOR FAN CAPACITOR (INNER THERMOSTAT) THERMISTOR MODULE
C67 SMOOTHING CAPACITOR NF61,62 NOISE FILTER SUCTION TEMPERATURE T801 TRANSFORMER
RT66
ESQUEMAS ELCTRICOS Y FRIGORFICOS
DS61,63 DIODE MODULE NR61 VARISTOR THERMISTOR X60,67 FAN MOTOR RELAY
FUSE1 FUSE(1A) DEFROST TEMPERATURE EVAPORATION TEMPERATURE X64 RELAY
RT61 RT67
FUSE2 FUSE(3.15A) THERMISTOR THERMISTOR REVERSING VALVE
21S4
F62 FUSE(3.15A) DISCHARGE TEMPERATURE CURRENT-LIMITING SOLENOID COIL
RT62 R64
HPS HIGH PRESSURE SWITCH THERMISTOR RESISTOR
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
GAMA DOMESTICA
BRN
2 1
X65
GRY
DS62
CN552
CN553
DS61 C61 C63 C62
RED ORN A L + RED + RED BLK
+ ORN + K YLW
2 1
BLK WHT
- - WHT - - BLK
CN554
YLW
WHT
YLW WHT
X66
REDR BLK
X65
TB4 NOISE FILTER
OUTDOOR UNIT
CT
LD63
P.C.BOARD
LDB
GRN/YLW X64 4 6 BLK 61
POWER SUPPLY
V 63H2
X66
X67
LD64
LDB
TAB62
~/N 220-240V X64
TB2
CN801
CN501
1 2 34
43 21
50Hz 0 1
(1A)
F801 TAB63
PE MC
X63
X62
X61
L61 ORN
L BLK LD62
X67
2 U W
SSR61
SSR62
SSR63
CN551
N BLU LD61 ORN
F911
BLK
RED
WHT
RELAY
CN704
CN514
P.C. BOARD
GRY
CIRCUIT BRAKER LDE TAB64
BRN
T801
C65
1 2 CN913 CN912
TB3 CN720 CN901 CN902 TAB65
N BLU
1 2 34 1 2
INDOOR
RED
ORN
WHT
BLK
YLW
BLU
RED
1 2
UNIT (A) GRN/YLW CT62
CN515
BLU
3
WHT
1 2 3456
RED
RED
BLU
CN705
INDOOR N BLU TAB66
1 2 34567
7 65 43 2 1
ORN 6 4
1 2
UNIT (B)
WHT
3 21S4 21S2
INDOOR N BLU I.P.M P.C. BOARD
MF61
MODELS MXZ-32RV-
YLW CH
1 2
UNIT (C)
3
INDOOR N BLU
E1
1 2
UNIT (D) ELECTRONIC CONTROL P.C. BOARD
303
CN723
1 2 3456 1 2 3456 1 2 3456 1 2 3456 1 2 34 1 2 1 2 3456 78 1 2 3456 78
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
RED
BLK
BLK
BLK
BLK
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
BLK
BLK
GRY
GRY
GRY
GRY
DS61 DIODE MODULE RT63 FIN TEMPERATURE THERMISTOR 21S2 SOLENOID COIL
DS62 DIODE STACK RT64 EVAPORATION TEMPERATURE THERMISTOR 21S4 R.V. COIL
F801 FUSE (1A) RT65 SUCTION TEMPERATURE THERMISTOR 63H1 HIGH PRESSURE SWITCH
F911 FUSE (1A) RT66,67 GUS PIPE TEMPERATURE THERMISTOR 63H2 HIGH PRESSURE SWITCH
L REACTOR RT68,69 GUS PIPE TEMPERATURE THERMISTOR 63L LOW PRESSURE SWITCH
L61 COMMON MODE CHOKE COIL SSR61,62 SOLENOID COIL RELAY
LEV A~D EXPANSION VALVE SSR63 CRANKCASE HEATER RELAY
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
GAMA DOMESTICA
Crankcase
heater Low pressure switch
MXZ-32RV - E1 Refrigerant flow in cooling
Suction Refrigerant flow in heating
temperature
thermistor [16
Compressor
ESQUEMAS ELCTRICOS Y FRIGORFICOS
High pressure
switch 1 Discharge
High pressure temperature
thermistor Reversing valve coil
switch 2
Capillary tube heating ON
Accumulator cooling OFF
Oil
separator [2.5 [0.61000
Unit D gas pipe temperature thermistor
[9.52 Capillary tube Capillary tube
Indoor unit [3.0[2.0 500
D Ball valve with
Unit C gas pipe temperature thermistor service port [3.0[2.0500
[9.52
Indoor unit Reversing valve 2-way-valve
C Unit B gas pipe temperature
thermistor [12
Indoor unit [16
B Unit A gas pipe
temperature thermistor
[12 [16
Indoor unit
A Evaporation
temperature
thermistor
(RT67)
Outdoor
heat
exchanger
Indoor unit
A Ball valve with Capillary tube
[6
Strainer LEV Strainer service port [2.5[0.6 750
Indoor unit Capillary tube
B Defrost [4.0[2.4 400
[6
Strainer LEV Strainer thermistor
Indoor unit
C [6 Distributor
Strainer LEV Strainer Distributor Strainer
[9.52
Indoor unit
D [6
Strainer LEV Strainer
304
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
7 - WIRING DIAGRAM
V
TB WHT L MF
GRN/YLW
2 NF62 2 NF61
WHT WHT
U MC W
POWER SUPPLY N 4 4 DS63 BLK BLK
BLU ~ 1
220-240V WHT WHT
- C67 +
~/N L 3 3 + RED 2
BRN BRN RED RED
50Hz 1 1 ~ - 3
WHT
WHT
BLK
BLK
CIRCUIT BREAKER RED
GRN
ORN
YLW
RED
BRN
BLK
BLU
TB BLK R65 TR
DC24V 3 RED BLU
RED
INDOOR
BLU
TO C61 RED
LD71 L61 LD73 RED BuP EuP BvP EvP BwPEwP
INDOOR UNIT (B) N BLU P U
+ C63 LD74 V
UNIT N W
CONNECTING DC24V 3 - +
- LD72 C64 LD77 BLU
BuN EuN BvN EvN BwN EwN
RED ~ 21S4
~
WHT
INDOOR BLU
ORN
ORN
YLW
GRN
RED
RED
YLW
RED
RED
RED
BLU
BLK
BLK
BLU
~
UNIT (A) N BLU DS61
BRN
1 1 BRN
YLW CN801 1 2 1 2 CN621 1 2 CN61 4 3 2 1 TAB91 1 2 3 4 5 6 8
TBAC2
TBAC1
CN611
2 2
CN941
BRN
RED
BLU
BLK
T801
GRN 3 3 FUSE1 C65
YLW
4 4 6
FUSE2 X67 ORN
RED
LDE1
LD63
LD64
TB61
TB62
CN701
BLU
1 YLW
LD62
RED
3 3
F62
BLK
CT61 4 GRN
BLU CN761 CN771 CN682 CN661 CN683 CN681 CN641 CN671 2
X64 5 BLU
LD61
6 1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 2 1 2 3 4 1 2 3 4 4 3 2 1 1 2 1
NR61
3 4
WHT
WHT
ORN
ORN
YLW
YLW
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
RED
RED
RED
RED
BLU
BLU
BLK
BLK
BLK
BLK
AR61
R64
RELAY P.C.BOARD
LEV A LEV B
RT62 RT63 RT64 RT65 RT66 RT67 RT61 HPS
C61 POWER-FACTOR CAPACITOR LEV A,B EXPANSION VALVE RT67 EVAPORATION TEMPERATURETHERMISTOR
C65 OUTDOOR FAN CAPACITOR MF OUTDOOR FAN MOTOR(INNER THERMOSTAT) SSR61 SOLID STATE RELAY
NOTE:1. For the outdoor electric wining refer to the outdoor unit electric wining diagram for servicing. 1.Slide the sleeve.
2. Use copper conductors only.(For field wining) 2.Pull the wire while
3. Symbols below indicate. pushing the locking
: Terminal block, : Connector lever.
4. shows the terminals with a lock mechanism,so they cannnot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
305
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
BRN
X65
2 1
GRY
CN552
CN553
DS62
DS61 C61 C63 C62
RED L + RED +
+ ORN + ORN A RED BLK
CN554
2 1
K YLW
BLK WHT
-
WHT
WHT
- WHT - - BLK
X66
YLW
YLW
X65
REDR BLK
LD63
TB4 NOISE FILTER
LDB
CT
P.C.BOARD
F801 TAB63
TAB62
GRN/YLW X64 4 6 BLK 61
LD64
POWER SUPPLY
1 2 34
LDB
43 21
X66
X67
CN801
CN501
V 63H2
~/N 220-240V 50Hz X64
TB2
(1A)
X63
X62
X61
0 1
MC
SSR61
SSR62
SSR63
ORN
CN551
X67
L61
L BLK LD62 U W
2
CN704
CN514
WHT
ORN
RED
LD61
BLK
N BLU
F911 RELAY
GRY
BRN
1 2 34567
7 65 43 2 1
TB3 CN720 CN901 CN902 1 2 34 1 2 TAB65
CN515
WHT
ORN
YLW
INDOOR
RED
N
CN604 CN603 CN602 CN601
BLU
BLK
BLU
CN705
1 2
12VDC RED
WHT
UNIT (A)
BLU
RED CT62
RED
BLU
3 GRN/YLW
1 2 3456
INDOOR N BLU TAB66
1 2
WHT
UNIT (B) 12VDC ORN 6 4
3 21S4 21S2
INDOOR N BLU
MF61 I.P.M P.C. BOARD
1 2
12VDC YLW CH
UNIT (C)
3
INDOOR N BLU
1 2
CN723
12VDC BEN
1 23
UNIT (D)
3 CN791 CN792 CN793 CN794 CN722 CN663 CN662 CN661 YLW
1 2 3456 1 2 3456 1 2 3456 1 2 3456 1 2 34 1 2 1 2 3456 78 1 2 3456 78
WHT
WHT
WHT
WHT
ORN
ORN
ORN
ORN
YLW
YLW
YLW
YLW
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
RED
BRN
RED
BRN
RED
BRN
RED
BRN
RED
RED
BLU
BLU
BLU
BLU
BLK
BLK
BLK
BLK
BLK
BLK
63H1 63L RT63 RT66 RT68 RT62 RT64
LEV A LEV B LEV C LEV D
RT67 RT69 RT61 RT65
306
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA DOMESTICA
Indoor unit
A Ball valve with Capillary tube
[6
Strainer LEV Strainer service port [2.5[0.6 750
Indoor unit Capillary tube
B Defrost [4.0[2.4 400
[6
Strainer LEV Strainer thermistor
Indoor unit
C [6 Distributor
Strainer LEV Strainer Distributor Strainer
[9.52
Indoor unit
D [6
Strainer LEV Strainer
307
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Y FRIGORFICOS
309
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
5 - WIRING DIAGRAM
PU-1.6VLJA2.UK
TB1 52C
BLU R
RED L1/1 T1/2 BLU
L C RED S
C COMPRESSOR RUN CAPACITOR
POWER BLU L3/5 T3/6 WHT C CP COMPRESSOR PROTECTOR
SUPPLY N
~/N (1PHASE) 49C MC C3 FAN MOTOR CAPACITOR
220-240V 50Hz F3 FUSE(5A)
GRN/YLW BLU BLU MC COMPRESSOR
4 MF3 FAN MOTOR
RED RED
2 TB1 TERMINAL BLOCK (POWER SUPPLY)
RED
C3
BLU
ORN ORN
1 TB3 TERMINAL BLOCK (CONNECTING WIRES INDOOR/OUTDOOR)
WHT WHT
3 49C COMPRESSOR INTERNAL THERMOSTAT
49F3 MF3 49F3
A1 63H 63L FAN MOTOR INTERNAL THERMOSTAT
F3 52 52C COMPRESSOR CONTACTOR
(5A) C
A2
63H HIGH PRESSURE SWITCH
WHT
WHT
ORN
GRY
GRY
YLW
PU-2VJA2.UK,PU-2.5VJA2.UK,PU-3VJA2.UK
TB1 52C
RED L1/1 T1/2 RED BLK R
L
C
RED S
GRY
POWER
C COMPRESSOR RUN CAPACITOR
SUPPLY BLU WHT
L3/5 T3/6 C CP COMPRESSOR PROTECTOR
~/N (1PHASE) N 2
220-240V 50Hz 49C MC C3 FAN MOTOR CAPACITOR
HC F3 FUSE(5A)
GRN/YLW
BLU BLU HC CRANKCASE HEATER
1 4 MC COMPRESSOR
RED RED
RED
GRY
BLU
C3
2 MF3 FAN MOTOR
ORN ORN
EARTH 22(32) 1 TB1 TERMINAL BLOCK (POWER SUPPLY)
52C WHT WHT
21(31) 3 TB3 TERMINAL BLOCK (CONNECTING WIRES INDOOR/OUTDOOR)
GRY 49F3 MF3
A1 63L 49C INTERNAL THERMOSTAT FOR MC
ESQUEMAS ELCTRICOS Y FRIGORFICOS
63H
F3 52
52C 14
49F3 INTERNAL THERMOSTAT FOR MF3
(5A) C 13
A2
52C COMPRESSOR CONTACTOR
WHT
WHT
ORN
GRY
GRY
YLW
VLT
PU-3NJA1.UK
TB1 52C
RED L1/1 T1/2 RED BLK R
L
C
RED S
GRY
POWER
C COMPRESSOR RUN CAPACITOR FOR
BLU L3/5 T3/6 WHT C CP COMPRESSOR PROTECTOR
SUPPLY N
~/N (1PHASE) 2 C3 FAN MOTOR CAPACITOR
49C MC
220V 60Hz
HC F3 FUSE(5A)
GRN/YLW
BLU BLU HC CRANKCASE HEATER
1 4 MC COMPRESSOR
RED RED
RED
GRY
BLU
WHT
ORN
GRY
GRY
YLW
VLT
310
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PU-2NJA1.UK,PU-2.5NJA1.UK
TB1 52C
MC C RUN CAPACITOR FOR MC
RED L1/1 T1/2 RED BLK R
L CP COMPRESSOR PROTECTOR
C
RED S C3 FAN MOTOR CAPACITOR
POWER
BLU L3/5 T3/6 WHT C
F3 FUSE(5A)
SUPPLY
N MC COMPRESSOR
~/N (1PHASE)
49C MF3 FAN MOTOR
220V 60Hz
GRN/YLW MF3 TB1 TERMINAL BLOCK (POWER SUPPLY)
BLU BLU
4 TB3 TERMINAL BLOCK (CONNECTING WIRES INDOOR/OUTDOOR)
RED RED
RED
C3
2
ORN ORN
1 49F3 INTERNAL THERMOSTAT FOR MF3
WHT WHT
3 52C COMPRESSOR CONTACTOR
A1 63H 63L 49F3 63H HIGH PRESSURE SWITCH
F3 52 63L LOW PRESSURE SWITCH
(5A) C 13 52C14
A2 NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.
WHT
WHT
ORN
GRY
GRY
YLW
VLT
VLT
X14 X6
CP
TB3 RED
1 X17
1 X6
2 X14 X17
2
WHT
PU-3YJA2.UK PU-4VLJSA2.UK
POWER SUPPLY
3N~ (3PHASE 4WIRES) TB1 52C
MC
380/220-415/240V 50Hz RED RED BLK
52C 51C L1/1 T1/2 R
L C
RED L1/1 RED U MC POWER RED S
L1 SUPPLY GRY
~/N (1PHASE)
T1/2 220-240V 50Hz BLU WHT C
WHT L2/3 WHT V L3/5 T3/6
L2 N
T2/4 49C
BLU
BLK L3/5 BLK W 2
GRN/YLW
L3 MF3
WHT
GRY
RED
T3/6
BLU
WHT
HC BLU BLU
4
N MF3 RED RED
2
GRY
WHT BLU 1 C3
R S T 47 4 32
ORN
1 ORN
RED RED
GRN/YLW 2 WHT WHT
RED
C3 52C 3
BLU
ORN ORN
1 31
49F3
HC BLU WHT
1 3 A1
GRY
MF4
RED
63L
BLU
13 52C 14
WHT
ORN
GRY
GRY
YLW
A1 A 3
VLT
VLT
49F4
52 13 52C 14 63L
C A B P1 52C 52C P3 P3 P2
WHT
WHT
ORN
YLW
GRY
BLU
VLT
VLT
A2
X14 X6
A B P1 52C 52C P3 P3 P2
CP
TB3 RED
X17
X14 X6 1
1 X6
TB3 RED
2 X14 X17
1 X17
1 X6 CP
2
2 X14 X17 WHT
2
WHT
311
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PU-4TJSA1.UK
WHT
BLU
GRN/ T3/6
MF3
WHT
GRY
RED
BLU
1
RED
WHT
ORN
GRY
BRN
YLW
3
VLT
VLT
A2
49F4
A B P1 52C 52C P3 P3 P2
PU-4YJSA2.UK
ESQUEMAS ELCTRICOS Y FRIGORFICOS
POWER SUPPLY
3N~ (3PHASE 4WIRES)
380/220-415/240V 50Hz
52C 51C
RED L1/1 RED U MC
L1
L2/3 T1/2
WHT WHT V
L2
T2/4
BLK L3/5 BLK W
L3
WHT
WHT
GRY
RED
BLU
T3/6
N MF3
BLU BLU BLU
47 4
R S T RED RED
C3
2
GRN/YLW ORN ORN
1
HC WHT WHT
RED
3
BLU
WHT
WHT
GRY
BRN
YLW
3
VLT
VLT
A2
49F4
A B P1 52C 52C P3 P3 P2
X14 X6
CP COMPRESSOR PROTECTOR
C3,4 FAN MOTOR CAPACITOR
TB3 RED F3 FUSE(5A)
1 X17
HC CRANKCASE HEATER
1 X6 CP MC COMPRESSOR
2 X14 X17
MF3,4 FAN MOTOR
2 TB1 TERMINAL BLOCK (POWER SUPPLY)
WHT TB3 TERMINAL BLOCK (CONNECTING WIRES INDOOR/OUTDOOR)
26C THERMAL SWITCH
47 ANTI-PHASE PROTECTOR
49F3,4 INTERNAL THERMOSTAT
51C THERMAL RELAY
52C COMPRESSOR CONTACTOR
63H HIGH PRESSURE SWITCH
63L LOW PRESSURE SWITCH
NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.
2. TO INDOOR UNIT TERMINAL BLOCK.
3.POWER SUPPRY 3N~ (3PHASE 4WIRES) 380/220-415/240V 50Hz
312
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PU-5TJSA.UK, PU-6TJSA.UK
POWER SUPPLY
3~ (3PHASE) 52C
220V 60Hz
RED L1/1 RED T1 MC
L1
T1/2 49C
CIRCUID WHT L2/3 WHT T2
BREAKER L2
T2/4 49C
BLK L3/5 BLK T3
L3
WHT
T3/6
RED
BLK
49C
WHT
BLU
GRN/YLW
MF3
BLU BLU
4
R S T 47 RED RED
C3
2
ORN ORN
1
WHT WHT
3
WHT
RED
26C
47 49F3
GRY C A MF4
F3 BLU BLU
(5A) BLK 4
BRN RED
A1 63H C4
2
YLW ORN
52 13 52C 14 1
C WHT WHT WHT
RED
YLW
GRY
GRY
RED
3
BLK
A2
49F4
A B P1 52C 52C P3 P3 P2
PU-5YJSA.UK, PU-6YJSA.UK
POWER SUPPLY
3N~ (3PHASE 4WIRES)
380/220-415/240V 50Hz
52C
RED L1/1 RED T1 MC
49C
RED
BLK
WHT
BLU
N MF3
BLU BLU
4
R S T 47 RED RED
GRN/YLW C3
2
ORN ORN
1
WHT WHT
3
RED
BLU
26C
49F3
47 MF4
GRY C A BLU BLU
F3
(5A) BLK 4
BRN RED
A1 63H C4
2
52C 14 YLW ORN
52 13
WHT
1
C WHT WHT
3
YLW
GRY
GRY
RED
RED
BLK
A2
49F4
A B P1 52C 52C P3 P3 P2
CP COMPRESSOR PROTECTOR
X14 X6
C3,4 FAN MOTOR CAPACITOR
TB3 RED F3 FUSE(5A)
1 X17 MC COMPRESSOR
* 1 X6 CP MF3,4 FAN MOTOR
X14 X17 TB1 POWER SUPPLY TERMINAL BLOCK
2
TB3 INDOOR/OUTDOOR CONNECTING LINE TERMINAL BLOCK
* 2 26C THERMAL SWITCH
WHT 47 PHASE PROTECTOR
49F3,4 FAN MOTOR INTERNAL THERMOSTAT
49C INTERNAL THERMOSTAT FOR MC
52C COMPRESSOR CONTACTOR
63H HIGH PRESSURE SWITCH
313
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
WIRING DIAGRAM
PUH-1.6VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
HC CRANKCASE HEATER MC COMPRESSOR (INNER THERMOSTAT) X12<O.B> COMPRESSOR RELAY
C1 OUTDOOR FAN CAPACITOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13<O.B> 21S4 RELAY
C2 COMPRESSOR CAPACITOR O.B OUTDOOR CONTROLLER BOARD X14<O.B> 21R RELAY
FC<O.B> FAN CONTROLLER SW123<O.B> CHECK,SERVICE SELECTOR ZNR<O.B> VARISTER
F<O.B> FUSE(6A) T TRANSFORMER 52C CONTACTOR
21S4 R.V.COIL TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
OUTDOOR COIL THERMISTOR
21R B.V.COIL RT (0C/15k,25C/5.4k)
LED
1 YLW
FROOM INDOOR UNIT RT
2 ORN
CONNECTING WIRES
12V DC (polar) 3 BRN
O.B
TB3
SW1 4 3 2 1
CN2 14 13 12 11 FC
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW2 CN4
S
SW2
OFF 26C
63H1
2 1 ON 14 13 12 11 MF2
3
2 CN3 63H2
MF1
1
CN4T F 51CM
4 3 2 1 4
SV TRF 21S4 52C CH ZNR R/1 S/2 T/3
WHT
WHT
WHT
WHT
WHT
RED
RED
RED
RED
GRY
GRY
BLU
BRN
BRN
YLW
YLW
YLW
YLW
BLU
S BLU BLU
GRY
A 63H1
GRY
RED
BLK
TB1 52C
L RED R U BLU R
POWER SUPPLY
N BLK WHT C
~/N(1phase) MC
T W BLU RED
220-240V 50Hz S
GRY/YLW C2
Main functions of LED (when both Nos. 1 and 2 of SW3 are OFF)
314
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-2VKA2/PUH-2.5VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3(O.B) CONNECTING WIRES MC COMPRESSOR (INNER THERMOSTAT) X12(O.B) MC RELAY
INDOOR/OUTDOOR CONNECTOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13(O.B) 21S4 RELAY
CN4T(O.B) TRANSFORMER CONNECTOR O.B OUTDOOR CONTROLLER BOARD X14(O.B) 21R RELAY
HC CRANKCASE HEATER 21R BYPASS VALVE SOLENOID COIL ZNR(O.B) SURGE ABSORBER
C1 OUTDOOR FAN CAPACITOR SW123(O.B) CHECK,SERVICE SELECT SWITCH 21S4 4-WAY VALVE SOLENOID COIL
C2 COMPRESSOR CAPACITOR T TRANSFORMER 52C CONTACTOR
FC(O.B) FAN CONTROLLER TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
F(O.B) FUSE(6,3A) RT OUTDOOR COIL THERMISTOR
LD1-LD8 CHECK,SERVICE LED X11(O.B) HC RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT
BLU
BLU
WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
L RED L1/1 T1/2 BLU R
N BLU WHT C
MC
L3/5
Since LD8 lights when normal power is turned ON, check the power supply with the ON or OFF LD8. RED 220V WHITE
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the ORANGE 230V
wiring connection in the following procedure
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Main functions of LED
(when both Nos.1 and 2 of SW3 are OFF)
LED No. Output display (light) Check display (flash)
LD1 Compressor indoor command
LD2 Heating indoor command
LD3 63H1 ON Outdoor coil thermistor short/open
LD4 Compressor ON
LD5 Outdoor fan ON
LD6 4-way valve ON 26C functions
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE :
If the operation stops to function of the protection device, the check
display flashes.
315
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-3VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3(O.B) CONNECTING WIRES MC COMPRESSOR (INNER THERMOSTAT) X12(O.B) MC RELAY
INDOOR/OUTDOOR CONNECTOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13(O.B) 21S4 RELAY
CN4T(O.B) TRANSFORMER CONNECTOR O.B OUTDOOR CONTROLLER BOARD X14(O.B) 21R RELAY
HC CRANKCASE HEATER 21R BYPASS VALVE SOLENOID COIL ZNR(O.B) SURGE ABSORBER
C1 OUTDOOR FAN CAPACITOR SW123(O.B) CHECK,SERVICE SELECT SWITCH 21S4 4-WAY VALVE SOLENOID COIL
C2 COMPRESSOR CAPACITOR T TRANSFORMER 52C CONTACTOR
FC(O.B) FAN CONTROLLER TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
F(O.B) FUSE(6,3A) RT OUTDOOR COIL THERMISTOR
LD1-LD8 CHECK,SERVICE LED X11(O.B) HC RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT
BLU
BLU
WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
ESQUEMAS ELCTRICOS Y FRIGORFICOS
Main functions of LED (when both Nos.1 and 2 of SW3 are OFF) How to use SW1 and 2
Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command The output display (light) remains lit during operation but
LD2 Heating indoor command pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Outdoor coil thermistor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON (light).
LD5 Outdoor fan ON
LD6 4-way valve ON
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE : If the operation stops to function of the protection device, the check display flashes.
SinceLD8 lights when normal power is furned ON, check the power supply with the ON or OFF LD8. RED 220V WHITE
Sincethe transformer (T) is connected with 240V power, if 220V or 230V power is used, ORANGE 230V
change the wiring connection in the following procedure.
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor
316
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-3YKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14<O.B> SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR<O.B> SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW123<O.B> CHECK,SERVICE SELECT SWITCH 21R BYPASS VALVE SOLENOID COIL
C FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6.3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11<O.B> CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12<O.B> COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13<O.B> SOLENOID COIL RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
ORN
ORN
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
WHT
WHT
RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V
POWER SUPPLY T
RED
3N~ WHT
380/220-415/240V 50Hz BLK
BLU
TB1
L1 RED L1/1 L1/1 T1/2 BLU U
L2 WHT L2/3 T2/4 WHT V
Main functions of LED (when both Nos.1 and 2 of SW3 are OFF) How to use SW1 and 2
Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
Making wiring connection in anti-phase or missing phase L2 or L3 causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
When power supply is 220V
ation. If phase L1 or N is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned ON. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) con- RED 220V WHITE
tained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection in ORANGE 230V
the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
317
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
5 - WIRING DIAGRAM
PUH-4VKSAUK
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTOR(CONNECTING MC COMPRESSOR X12<O.B> COMPRESSOR RELAY
WIRES INDOOR/OUTDOOR) MF FAN MOTOR X13<O.B> SOLENOID COIL RELAY
CN4T<O.B> CONNECTOR(TRANSFORMER) O.B OUTDOOR CONTROLLER BOARD X14<O.B> SOLENOID COIL RELAY
HC CRANKCASE HEATER 21R SOLENOID COIL(BYPASS VALVE) X16 HIGH PRESSURE RELAY
C1 FAN MOTOR CAPACITOR SW1 2 3<O.B> SELECT SWITCH(CHECK,SERVICE) ZNR<O.B> SURGE ABSORBER
C2 COMPRESSOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 52C COMPRESSOR CONTACTOR
F<O.B> FUSE(6A) TH OUTDOOR COIL THERMISTOR 63H1 CONTROL HIGH PRESSURE SWITCH
LD1-LD8<O.B> LED(CHECK,SERVICE) X11<O.B> CRANKCASE HEATER RELAY 63H2 PROTECT HIGH PRESSURE SWITCH
26C DISCHARGE PIPE THERMOSTAT EARTH
1 YLW
TO INDOOR UNIT LED TH
2 ORN
CONNECTING WIRES O.B
DC 12V 3 BRN
SW1
TB3 4 3 2 1
SW2
CN4
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW3
OFF CN2 X14 X13 X12 X11
ON
21
3
2 CN3
1 26C F.C
X14 X13 X12 X11
63H2 MF2
63H1
CN4T MF1
F 51CM
4 3 2 1
4 ZNR R S T 5
SV TRF 21S4 52C CH
RED
WHT
WHT
RED
RED
BLU
BRN
BRN
GRY
GRY
BLK
BLK
YLW
YLW
BLU
BLU
VLT
VLT
RED
BRN BLU BLU
BRN A1 1 WHT 3 WHT
YLW 21 HC 63H1 X16 26C BLU 4 BLU
AC 21R 52C
12.3V ORN 240V
230V
S4
A2
5
C1
RED
ORN
2 RED
ORN
MF
1
RED GRY GRY
220V WHT 7 6 X16 2
AC12.3V WHT 63H2
X16
T 8 GRY
WHT WHT
3
RED BLU BLU
ESQUEMAS ELCTRICOS Y FRIGORFICOS
4
BLU C1
BRN
YLW
2
BRN
YLW
MF
1
TB1 T1/2
RED L1/1 RED BLK R
POWER SUPPLY L
BLU S
~ (1PHASE) N L3/5 T3/6
C2
RED MC
220-240V 50Hz
GRN/YLW 52C WHT C
Main functions of LED (when both No.1 and No.2 of SW3 are "OFF") How to use SW1 and SW2
LED No. Output Display (light) Check Display (flashing) Pressing SW1 erases the past check contents
LD1 Compressor indoor command stored on the microcomputer.
LD2 Heating indoor command The output display (light) remains during operation
LD3 63H1 ON Pipe sensor short/open but pressing SW2 displays the past check contents
LD4 Compressor ON 63H2 functions in flashing mode. Pressing the switch again returns
LD5 Outdoor fan ON to output display(light).
LD6 4-way valve ON 26C Overheat protection
LD7 Bypass valve ON TH overheat protection
LD8 Crankcase heater ON Defective input
NOTE: If the operation of the protection device stops to function, then check the display flashes.
change the wiring connections according to the following procedure. RED 220V WHITE
318
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-4YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14(O.B) SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR(O.B) SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW123(O.B) CHECK,SERVICE SWITCH 21R BYPASS VALVE SOLENOID COIL
C1,2 FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6,3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11(O.B) CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12(O.B) COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13(O.B) SOLENOID COIL RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
ORN
ORN
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
WHT
WHT
RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF1
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ WHT 4
ORN ORN MF2
380/220-415/240V 50Hz 1
BLK C2 RED
BLU RED 2
TB1
L1 RED L1/1 T1/2 RED U
L2 WHT L2/3 T2/4 WHT V
MC
Main functions of LED (when both Nos.1 and 2 of SW3 are OFF) How to use SW1 and 2
Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect The output display (light) remains during operation but press-
LD2 Heating indoor command Missing-phase detect ing SW2 displays the past check contents in flashing mode.
LD3 63H1 ON Pipe sensor short/open Pressing the switch again returns to output display (light).
LD4 Compressor ON
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
Making wiring connection in anti-phase or missing phase L2 or L3 causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor opera-
When power supply is 220V
tion. If phase L1 or N is missing it causes all displays to go out. Under normal condition LD8 light when power is turned
ON. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) contained in RED 220V WHITE
the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection in ORANGE 230V
the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
319
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-5YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR T TRANSFORMER X12(O.B) COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) TB1,3 TERMINAL BLOCK X13(O.B) SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 63H1 HIGH PRESSURE SWITCH X14(O.B) SOLENOID COIL RELEY
RT OUTDOOR COIL THERMISTOR 26C DIS.CHARGE THERMAL SWITCH CN3(O.B) CONNECTOR(CONNECTING
HC CRANKCASE HEATER O.B OUTDOOR CONTROLLER BOARD WIRES INDOOR/OUTDOOR)
49C INTERNAL THERMOSTAT FOR MC ZNR(O.B) SURGE ABSORBER CN4T(O.B) TRANSFORMER CONNECTOR
52C CONTACTOR F(O.B) FUSE(6.3A) SW1,2,3(O.B) CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL FC(O.B) FAN CONTROLLER LD1-LD8(O.B) CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL X11(O.B) CRANKCASE HEATER RELAY 51CM(O.B) JUMPER CONNECTOR
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED
BRN
BRN
BLU
BLU
BLK
BLK
BLK
BLK
RED
BRN
BRN 13 A1 WHT WHT
63H1 26C 3
AC 52C 21R 21 52C HC BLU BLU
RED 14 S4 4
12.3V 220V RED RED MF1
2
RED
ORN A2
230V WHT C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 T3
ESQUEMAS ELCTRICOS Y FRIGORFICOS
BLU
N
52C
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are OFF) How to use SW1 and 2
Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
320
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PUH-6YKSA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR TB1,3 TERMINAL BLOCK X12<O.B> COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) 63H1 HIGH PRESSURE SWITCH X13<O.B> SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 26C DIS.CHARGE THERMAL SWITCH X14<O.B> SOLENOID COIL RELEY
RT OUTDOOR COIL THERMISTOR X15 BYPASS VALVE RELAY CN3<O.B> CONNECTING WIRES
HC CRANKCASE HEATER O.B OUTDOOR CONTROLLER BOARD INDOOR/OUTDOOR CONNECTOR
49C INTERNAL THERMOSTAT FOR MC ZNR<O.B> SURGE ABSORBER CN4T<O.B> TRANSFORMER CONNECTOR
52C CONTACTOR F<O.B> FUSE(6.3A) SW1,2,3<O.B> CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL FC<O.B> FAN CONTROLLER LD1-LD6<O.B> CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL X11<O.B> CRANKCASE HEATER RELAY 51CM<O.B> JUMPER CONNECTOR
T TRANSFORMER
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 14 13 12 11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 14 13 12 11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED
BRN
BRN
BLK
BLK
BLK
BLK
BLK
BLK
RED
BRN BLK
BRN 13 A1 WHT WHT
7
21 63H1 26C 3
AC 52C 21R 15 S4 52C BLU BLU
RED 14 HC 4
12.3V 220V 8 RED RED MF1
2
RED
RED
ORN A2
230V 3 15 5 BLK C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
Main functions of LED (when both Nos.1 and 2 of SW3 are OFF) How to use SW1 and 2
Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
321
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
ORN
RED
14.5VAC
YLW
GRN/YLW LS
T W.B
SW1
MV 7 7
MF
CNB
LD1
W.R
1 3 5
REMORT
C CONTROLLER
Ru
WHT
WHT
RED
RED
RED
BRN
BRN
RED
YLW
BLU
I.B
BLK
BLK
BLK
MULTIPLE
F2 F1
CN51
OUTDOOR
X4 TB4
3 2 1
ORN
CN30
2 TO OUTDOOR UNIT
YLW 1 CONNECTING WIRES
DC12V
2 1
ZNR CN21 RT2
X4 PIPE
2 1
SW3 CN20 RT1
7 1 INTAKE
ON
OFF CN23 WHT
VANE
123
SW1 SW2
CN70 2 1 RED
JR WIRELESS
CN2B CN2A ON
TIMER
L.TEST
TWIN.2 TWIN.1
CN2
CN28
CN2B<I.B> TRANSMISSION WIERS No.2 CONNECTOR ROOM TEMPERATURE THERMISTOR TB2 POWER SUPPLY TERMINAL BLOCK
RT1
CN27<I.B> DRAIN LIFT-UP MECHANIM (0%/15k",25C/5.4k" DETECT) INDOOR/OUTDOOR CONNECTING WIRE
TB4
CN28<I.B> TIME SHORTENING CONNECTOR INDOOR COIL THERMISTOR TERMINAL BLOCK
RT2
CN51<I.B> MULTIPLE CONNECTOR (0%/15k". 25C/5.4k" DETECTI X4<I.B> FAN MOTOR RELAY
F1,2<I.B> FUSE(6.3A 250V) Ru<W.B> RECEIVING UNIT ZNR VARISTOR
I.B INDOOR CONTROLLER BOARD SW1<I.B> FUNCTION SWITCH W.B WIRELESS REMOTE CONTROLLER BOARD
JR FUNCTION SELECTOR JUMPER RESISTORS SW2<I.B> UNIT SEITCH W.R WIRELESS REMOTE CONTROLLER
NOTES:
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the
indoor controller board as shown is fig:w1.
SW1 SW1
fig w1 ON ON
Indoor fan motor (MF) for 230,240V.
OFF OFF
12345678 12345678
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Since the indoor transtormer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2.
220V YELLOW
fig w2
When power supply is 230V ORANGE
230V
240V RED
220V
322
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PK-2.5FLA2
PK-3FLA2
L POWER SUPPLY
PK-4FLSA2 N ~(1 PHASE)
AC220-240V 50Hz
GRN/YLW AC220V 60Hz
220V 10.6VAC
MF TB2
230V 7
ORN
RED
240V
YLW
14.5VAC
C
T CNB W.B
Ru
LD1
I.B
WHT
WHT
RED
RED
BRN
RED
RED
BRN
YLW
BLK
BLU
SW1
7
FAN1 1 3 5 CND 1 3 1 3 CNT 4 3 2 1 CN4T
POWER TRANS TRANS
F2 F1 6 W.R
MV REMOTE
X4 6 1
CONTROLLER
MULTIPLE
CN51
CN6V
VANE
OUTDOOR 2 1
TB4
3 2 1
CN30
ZNR ORN 2 TO OUTDOOR UNIT
X4
1 2 3 4 5 YLW 1 CONNECTING WIRES
DC12V
SW3 CN50 CN21
ON 7 1 DRAIN PIPE
RT2
OFF
D.U.M
CN27
CN20
2 1
123 CN70 RT1
JR SW1 SW2 WIRELESS INTAKE
CN2B CN2A ON
TWIN-2 TWIN-1
L.TEST
TIMER
CN28
OFF
CN2
1 2 3 4 5 6 12345678 12345
MODELS PK-2.5FLA2
PK-4FLSA2
PK-3FLA2
ON ON
SW1 OFF OFF
12345678 12345678
NOTES:
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the
indoor controller board as shown is fig:w1.
SW1 SW1
fig w1 ON ON
Indoor fan motor (MF) for 230,240V.
OFF OFF
12345678 12345678
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Since the indoor transtormer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2.
220V YELLOW
fig w2
When power supply is 230V ORANGE
230V
240V RED
220V
323
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Outdoor heat
Indoor heat Flared exchanger
exchanger connection
Flared
Strainer
connection
Distributor
Accumulator Compressor
Capillary tube
Capillary tube
for injection
(Only PU-2VJA2)
Ball valve PU-1.6 (O.D.3.2 I.D.1.8 R900) PU-2NJA1
(with service port)
PU-2 (O.D.4.0 I.D.2.0 R430)
Refrigerant pipe [9.52(3/8)
(with insulator) option flow of refrigerant
PK-2.5FLA2/PU-2.5VJA2,PU-2.5NJA1
PK-3FLA2/PU-3VJA2,PU-3NJA1
PK-4FLSA2/PU-4VLJSA2,PU-4YJSA2,PU-4TJSA2
ESQUEMAS ELCTRICOS Y FRIGORFICOS
Ball Charge
Check
valve pIug
pIug
Flared
Indoor heat connection Strainer
exchanger Flared
connection Outdoor heat
exchanger
Distributor Accumulator
Compressor Capillary
tube
Capillary tube for
injection Only
PU-2.5NJA1 PU-3YJA2
PU-2.5VJA2 PU-4TJSA2
PU-3NJA1 PU-4YJSA2
PU-3VJA2
Ball valve
(with service port)
Refrigerant pipe [ 9.52(3/8)
(with insulator) option flow of refrigerant
Capillary tube size
PU-2.5 (O.D.3.2 I.D.1.6 R760) 2pcs
PU-3 (O.D.3.2 I.D.1.8 R800) 2pcs
PU-4 (O.D.3.2 I.D.2.0 R840) 2pcs
324
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PKH-1.6FKHA3 /PKH-2FKHA3
GRN/YLW L POWER SUPPLY
N ~(1 PHASE)
AC220-240V 50Hz
MF LS
RED
GRN/YLW
WHT
11.1VAC
AC220V 60Hz
240V
230V
TB2
MV
ORN
RED
220V
YLW
14.2VAC
C MODELS 1.6FKHA 2FKHA
T ON ON
SW7
I.B
WHT
OFF OFF
WHT
RED
RED
BRN
RED
RED
BRN
YLW
BLK
BLU
123 123
REMOCON
TO
BLU
CN6V F1
CN22
2 1
VANE POWER BLU 1
X4
4 3 2 1
POWER
REMOCON
3 TB4
CN40
LED1 12V BRN
OUTDOOR
TO OUTDOOR UNIT
3 2 1
CN30
POWER ORN 2
CONNECTING WIRES
YLW 1 DC12V
X4 ZNR
CN21 R.B
2 1
SW7 SW3 RT2
PIPE SW18 TB6
CONTROL
FAN2 1 3 5 ON CENTRALLY
OFF CN51 OFF A01 B02
CN20
2 1
ON
123 12 INTAKE
RT1 4321 CN1
SW2 SW5 SW6 SW1 SW17 5 4 3 2 1
LOSSNAY
HEATER
OFF
CN2L
CN23
CN24
CN2
VANE
ON
2 1
ON
OFF 87654321 3 2 1
123456 1234 1234 1 2 3 4 5 6 7 8 9 10
3 6
BRN
~(1 PHASE) L RED
CN24
BLU 1 2 YLW 26H
AC220-240V 50Hz N HEATER
GRN/YLW GRY
AC220V 60Hz
325
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
ORN
RED
220V
YLW
14.3VAC
C 6 MODELS 2.5,3FKHA 4FKHSA
T MV ON ON
I.B SW7
WHT
WHT
BRN
OFF
RED
RED
BRN
RED
RED
BLK
OFF
YLW
BLU
1234 1234
FAN1 1 3 5 CND 1 3 1 3 CNT 6 1 4 3 2 1 CN4T TRANSMISSION WIRES
POWER TRANS TRANS
TB5 2 DC12V
REMOCON
TO
X4 CN6V BLU
F2 F1
CN22
2 1
VANE BLU 1
4 3 2 1
LED2 5V
POWER
REMOCON
TB4
CN40
BRN 3
POWER
OUTDOOR
TO OUTDOOR UNIT
3 2 1
CN30
ORN 2
CONNECTING WIRES
YLW 1 DC12V
CONTROL
CENTRALLY
X4 ZNR LED1 12V R.B
CN51
CN21
2 1
SW7 SW3 POWER RT2
PIPE SW18 TB6
D.U.M
CN27
ON
OFF A01 B02
OFF CN20
2 1
ON
1234 12 5 4 3 2 1 INTAKE
RT1 4321 CN1
SW2 J5 J9 SW6 J1 SW17 5 4 3 2 1
CN50
DRAIN
LOSSNAY
HEATER
OFF
CN2L
CN24
ON ON
CN2
OFF 87654321 3 2 1
123456 2 4 2 1234 4 5 6 7 8 9 10
5 6
BRN
~(1 PHASE) L RED
CN24
1 2
BLU HEATER YLW 26H
AC220-240V 50Hz N GRY
GRN/YLW
AC220V 60Hz
NOTES:
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will reqire a setting change of the dip switch (SW7<I.B>) on the indoor
controller board as shown in fig : w 1.
fig w 1 Indoor fan motor (MF) for 220V. ON ON
SW7 OFF OFF
SW 7 1234 1234
2. Since the indoor transformer (T) is connected with 240V power, if 220,230V power is used. Change the wiring connection showing fig : w 2.
fig w 2 When power supply is
240V YELLOW
230V ORANGE
230V
220V RED
220V
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector, / : Terminal block.
6. Emergency operation
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor con-
troller board.
[Check items]
(1) Make sure that no other trouble exist the outdoor unit. Troble with the outdoor unit prevents emegency operation.
(If any trouble exists the outdoor unit error code P8 will be displayed on the remote controller and the trouble position will be shown on the outdoor con-
troller board LED. See electrick wiring diagram of the outdoor unit for details.)
(2)Make sure that there is mo trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF(ON/OFF wsth the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4)Themostat will not function. Cold air belows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
326
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Flexible tube
Indoor
heat Service Outdoor coil
exchanger port thermistor
Flared (TH)
Strainer Bypass
connection
valve
Accumulator
Rastrictor Capillary
Indoor coil valve tube
thermistor Restrictor
valve Compressor
(RT1)
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with Service port)
Capillary 9.52mm( 3/8")
(with heat insulator) PUH-1.6 (O.D.3.2 I.D.1.8-R400)
tube PUH-2 (O.D.4.0 I.D.2.0-R430)
PKH-1.6 (O.D.3.2 I.D.1.6-R700) PKH-2.5 (O.D.3.2 I.D.1.8-R430) PUH-2.5 (O.D.4.0 I.D.2.4-R1550)
PKH-2 (O.D.3.2 I.D.1.6-R300) PKH-3 (O.D.4.0 I.D.2.0-R500) PUH-3 (O.D.4.0 I.D.2.4-R1070)
PKH-4FKHSA2 /PUH-4YKSA3
High pressure
control switch
Oil separator Outdoor unit
Refrigerant pipe Outdoor heat exchanger
(option) Service
Indoor unit 19.15mm( 3/4")
4-way valve port
Ball valve
(with heat insulator)
Flexible tube
Indoor Outdoor coil
Service
heat thermistor
port
exchanger (TH3)
(check)
Rastrictor
Strainer Flared valve
connection Bypass
valve Capillary
tube
Indoor coil
thermistor Restrictor
valve Accumulator Compressor
(RT1)
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with Service port)
Capillary 9.52mm( 3/8")
tube (with heat insulator) PUH-4 (O.D.3.2 I.D.2.0-R820) 2pcs
R.V. coil
Heating:ON
Cooling:OFF
327
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PC-2GJA1 / PC-2.5GJA1 / PC-3GJA1 / PC-4GJSA1 / PC-5GJSA1 / PC-6GJSA1
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
C FAN MOTOR CAPACITOR LD1<R.B> RUN INDICATOR LED SWC<I.B> OPTION SWITCH TB4 INDOOR / OUTDOOR CONNECT-
CN120<I.B> REMOTE CONTROLLER TRANS- LD3<R.B> COOLING INDICATOR LED SW1<I.B> FUNCTION SWITCH ING WIRE TERMINAL BLOCK
MISSION WIRE CONNECTOR LD4<R.B> FAN MODE INDICATOR LED SW2<I.B> UNIT SWITCH RT1 ROOM TEMPERATURE THERMISTOR
CN2<I.B> TIMER ADAPTOR CONNECTOR LD5<R.B> FAN HIGH INDICATOR LED SW3<I.B> EMERGENCY OPERATION SWITCH (0 /15k ,25 /5.4k DETECT)
CN2A<I.B> TRANSMISSION WIRE No.1 LD6<R.B> LOUVER RUN INDICATOR LED SW1<R.B> ON / OFF SWITCH RT2 INDOOR COIL THERMISTOR
CONNECTOR LD7<R.B> INDICATOR MODE TEMPERATURE LED SW2<R.B> OPERATION MODE SWITCH (0 /15k ,25 /5.4k DETECT)
CN2B<I.B> TRANSMISSION WIRE No.2 LD8<R.B> INDICATOR MODE TIMER LED SW3<R.B> FAN HIGH/LOW SWITCH X1<I.B> DRAIN-UP MACHINE RELAY
CONNECTOR LD9<R.B> DRY INDICATOR LED SW4<R.B> LOUVER ON / OFF SWITCH X4<I.B> FAN MOTOR RELAY
CNP<I.B> DRAIN-UP MACHINE CONNECTOR LD10<R.B> FAN LOW INDICATOR LED SW5<R.B> INDICATOR SWITCH ZNR VARISTOR
CN28<I.B> TIME SHORTENING CONNECTOR LD11<R.B> OFF TIMER INDICATOR LED SW6<R.B> TEMPERATURE / TIMER DP OPTION DRAIN-UP MACHINE
CN50<I.B> DRAIN SENSOR CONNECTOR LD12<R.B> ON TIMER INDICATOR LED SETTING UP SWITCH DS OPTION DRAIN SENSOR
CN51<I.B> MULTIPLE CONNECTOR LD13-24<R.B> TEMPERATURE / TIMER RE- SW7<R.B> TEMPERATURE / TIMER W/B OPTION WIRELESS REMOTE
CN120<R.B> REMOTE CONTROLLER TRANS- MAINING TIME INDICATOR LED SETTING DOWN SWITCH CONTROLLER BOARD
MISSION WIRE CONNECTOR MF FAN MOTOR SW8<R.B> TIMER CONTINUOUS ON / OFF SWITCH CNB(W.B) INDOOR BOARD CONNECTOR
F1,2<I.B> FUSE (6.3A 250V) MV VANE MOTOR R.B REMOTE CONTROLLER BOARD LED1(W.B) RUN INDICATOR LED
CN70<I.B> WIRELESS REMOTE CONT- SWA<I.B> HIGH CELING TYPE SWITCH T TRANSFOMER SW2(W.B) COOL OPERATION SWITCH
ROLLER CONNECTOR JR<I.B> FUNCTION SELECTOR TB2 POWER SUPPLY TERMINAL BLOCK RU(W.B) BEAM RECIEVE UNIT
I.B INDOOR CONTROLLER BOARD JUMPER RESISTORS
L
POWER SUPPLY Service Ref. 2GJA1 2.5GJA1 3GJA1
N (1 PHASE)
AC220-240V 50Hz ON ON ON
220V 11.8VAC GRN/YLW AC220V 60Hz SW1 OFF OFF OFF
MF 230V TB2 1 2 34 5 6 7 8 1 2 34 5 6 7 8 1 2 34 5 6 7 8
240V 14.7VAC Service Ref. 4GJSA1 5GJSA1 6GJSA1
ORN
RED
YLW
C 6 6
T ON ON ON
MV SW1 OFF OFF OFF
fig:*3
WHT
WHT
BRN
BRN
RED
RED
RED
RED
1 2 34 5 6 7 8 1 2 34 5 6 7 8 1 2 34 5 6 7 8
BLU
YLW
BLK
I.B
FAN1 1 3 5 CNP 1 3 CND 1 3 1 3 CNT 4 3 2 1 CN4T
INDOOR UNIT
D.U.M POWER TRANS TRANS
F2 F1 REMOTE CONTROLLER
12
CN120
TO.RC
VANE
LD24
LD23
LD22
LD21
LD20
LD19
LD18
LD17
LD16
LD15
LD14
LD13
OUTDOOR
2
ZNR LD8
MULTIPLE
CONNECTING WIRES
ESQUEMAS ELCTRICOS Y FRIGORFICOS
X4 X1 YLW 1
CN51
5 4 3 2 1 DC12V
LD7
SW3
SW7
SW6
SW5
CN50 BLK
CN21
2 1
2 1
LD10
OFF
WIRELESS
LD6
LD5
LD4
LD9
LD3
LD1
CN20
CN120
2 1
123 RT1
SW1 SW2 INTAKE
JR
CN2B CN2A 3
L.TEST
TIMER
ON
CN28
SWA
CN2
SW8
SW4
SW3
SW2
SW1
OFF
1 2 34 5 6 12345678 12345 1 OP
NOTES :
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board
as shown in fig : w1.
fig : w1 SW1 ON ON
Indoor fan motor (MF) for 230, 240V.
OFF OFF
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
2. Since the indoor transformer (T) is connected with 220V power, if 230, 240V power used. Change the wiring connection showing fig : W2.
fig : w2
When power supply is 240 YELLOW
240V
230 ORANGE
230V
220 RED
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Symbols used in wiring diagram above are. : Connector , : Terminal block
5. Emergency operation
If remote controller or microcomputer fails but there is no other trouble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1)Compressor and fan.
(2)Check the abnomality using self diagnostic function. When the result of self diagnosis indicates protective device such as freeze protection, emergency operation is not possible
unless the cause is removed.
(3)Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch(SW3<I.B>) on the indoor controller board to1 2 onand 3 off for cooling.
328
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Accumulator
Flared
Distributor connection Compressor
with strainer
Capillary tube
for injection
Strainer
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Indoor coil
Flared Accumulator
thermistor
RT2
connection Compressor w
Capillary
Capillary tube for tube
Distributor
injection
with strainer
Only PU-2.5
PU-3
PU-4YJSA,
4TJSA
Ball valve
(with service port)
Refrigerant pipe 9.52 (3/8) flow of refrigerant
(With insulator) option w Capillary tube size
PU-2.5 (O.D.3.2 I.D.1.6 R760) 2pcs
PU-3 (O.D.3.2 I.D.1.8 R800) 2pcs
PU-4YJSA, 4VLJSA, 4TJSA (O.D.3.2 I.D.2.0 R840) 2pcs
329
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Ball High
valve pressure
switch
Flared
Indoor heat connection
exchanger
Flared Accumulator
Distributor connection Compressor
with strainer
Capillary tube
PU-5YTJSA
(O.D. 4.0 oI.D. 2.4 R840)o2pcs
PU-6YJSA
(O.D. 4.0 oI.D. 2.4 R1200)o2pcs
PU-6TJSA Strainer
(O.D. 4.0 oI.D. 2.4 R740)o2pcs
330
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PCH-2GKHA1/PCH-2.5GKHA1/PCH-3GKHA1
PCH-4GKHSA1/PCH-5GKHSA1/PCH-6GKHSA1
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C FAN MOTOR CAPACITOR J9<I.B> MODEL SELECTOR JUMPER RESISTORS SW17<R.B> ADDRESS SELECTOR
CN1<R.B> PROGRAM TIMER CONNECTOR LED1<I.B> DC 12V POWER LED SW18<R.B> FUNCTION SELECTOR
CN2<R.B> REMOTE SWITCH CONNECTOR LED2<I.B> DC 5V POWER LED T TRANSFORMER
CN2L<I.B> LOSSNAY CONNECTOR MF FAN MOTOR TB2 POWER SUPPLY TERMINAL BLOCK
CNP<I.B> DRAIN-UP MACHINE CONNECTOR MV VANE MOTOR TB4 INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK
CN50<I.B> DRAIN SENSOR CONNECTOR R.B REMOTE CONTROLLER BOARD TB5,6 REMOTE CONTROLLER TERMINAL BLOCK
CN51<I.B> CENTRALLY CONTROL CONNECTOR RT1 ROOM TEMPERATURE THERMISTOR LINE TRANSMISSION
F1,2<I.B> FUSE(6.3A 250V) (0:/15k", 25:/5.4k" DETECT) X4<I.B> FAN MOTOR RELAY
FS1,2 THERMAL FUSE(98:10A:2GKHA / 117:16A: RT2 INDOOR COIL THERMISTOR ZNR VARISTOR
4GKHA110:16A:2.5,3GKHA.5.6GKHSA) (0:/15k", 25:/5.4k" DETECT) 26H HEATER THERMAL SWITCH
H HEATER SW2<I.B> ADDRESS SELECTOR 88H HEATER CONTACTOR
I.B INDOOR CONTROLLER BOARD SW3<I.B> EMERGENCY OPERATION SWITCH DP OPTION DRAIN-UP MACHINE
J1<I.B> FUNCTION SELECTOR JUMPER RESISTORS SW6<I.B> TWIN/TRIPLE SELECTOR DS OPTION DRAIN-UP SENSOR
J5<I.B> MODEL SELECTOR JUMPER RESISTORS SW7<I.B> MODEL SELECTOR
L 88H FS1 FS2 H
POWER SUPPLY RED RED
1 2
N ~(1 PHASE) 3 5 BLU
AC220-240V 50Hz RED
220V 10VAC GRN/YLW AC220V 60Hz L
BLU
MF DP 230V TB2 N
(OPTION) 240V 14.3VAC TB2
ORN
RED
YLW
C 6 6
T MV I.B
YLW
HEATER
RED
CN24
2 1
INDOOR UNIT
WHT
WHT
6 5
BRN
BRN
RED
RED
RED
RED
YLW
BLU
BLK
REMOCON
TO
VANE
X4 F2 F1 BLU 2 DC12V
CN22
D.U.M
2 1
BLU 1
1
OUTDOOR
3 2 1
CN30
ORN 2
POWER CONNECTING WIRES SW18 TB6
ZNR YLW 1 DC12V
X4 LED1 12V OFF A.1 B.2
CONTROL
CENTRALLY
POWER BLK ON
CN21 CN1
2 1
2 1
CN51
SW2 J5 J9 SW6 J1 3 2 1
DRAIN
87654321
CN50
CN2L
CN24
ON BLK
ON ON ON
2
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities. make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are.
: Connector, / : Terminal block.
6. Emergency operation
If remote controller or microcomputer fails but there is no other truble. emergency operation is possible by setting dip switch
(SW3<I.B>) on the indoor controller board.
[Check items]
(1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code P8will be displayed on the remote controller and the trouble position will be
shown on the outdoor controller LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possi-
ble).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
331
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
valve Capillary
tube
Indoor coil
thermistor Restrictor
RT2 valve Accumulator Compressor (O.D.3.2 I.D.2.0-R820) 2
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port)
Capillary 9.52mm( 3/8")
tube (with heat insulator)
(O.D.4.0 I.D.2.0-R350)
PCH-5GKHSA1/PUH-5YKSA3
PCH-6GKHSA1/PUH-6YKSA2 Oil High pressure Outdoor unit
separator control switch
Refrigerant pipe Outdoor heat exchanger
(option) 4-way valve
Indoor unit 19.05mm( 3/4") Ball valve Service
(with heat insulator) Strainer port
Outdoor
Indoor Flexible tube coil
Service thermistor
heat port (RT)
exchanger
Restrictor
Strainer Flared valve
connection Bypass
valve Capillary
tube
Indoor coil
thermistor
RT2 Restrictor valve Accumulator Compressor Capillary tube
Distributor
with Ball valve Strainer
Refrigerant pipe
strainer (option) (with service port)
PUH-5 (O.D.4.0 I.D.2.4-R840) 2
Capillary 9.52mm( 3/8") Thermal switch PUH-6 (O.D.4.0 I.D.2.4-R1200) 2
tube (with heat insulator)
PCH-5 O.D.4.0 I.D.2.4-R270
PCH-6 O.D.4.0 I.D.3.0-R300
332
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PL-1.6KJB.UK / PL-2KJB.UK / PL-2.5KJB.UK
SYMBOL NAME SYMBOL NAME SYMBOL NAME
I.B INDOOR CONTROLLER BOARD CN50<I.B> DRAIN SENSOR CONNECTOR SW1<R.B> ON/OFF SWITCH
MF INDOOR FAN MOTOR CN51<I.B> MULTIPLE CONNECTOR SW2<R.B> MODE SWITCH
MV VANE MOTOR CN2A<I.B> TRANSMISSION WIRES No.1 CONNECTOR SW3<R.B> FAN SPEED HIGH/LOW SWITCH
LS LIMIT SWITCH CN2B<I.B> TRANSMISSION WIRES No.2 CONNECTOR SW4<R.B> VANE ON/OFF SWITCH
RT1 ROOM TEMPERATURE THERMISTOR (0C/15k, 25C/5.4k) CN28<I.B> TIME SHORTENING CONNECTOR SW5<R.B> DISPLAY SWITCH
RT2 INDOOR COIL THERMISTOR (0C/15k, 25C/5.4k) CN2<I.B> TIMER ADAPTOR CONNECTOR SW6<R.B> SET TEMPERATURE/TIMER UP SWITCH
DS DRAIN SENSOR SW1<I.B> FUNCTION SWITCH SW7<R.B> SET TEMPERATURE/TIMER DOWN SWITCH
DP DRAIN PUMP SW2<I.B> UNIT SWITCH SW8<R.B> TIMER MODE SWITCH
T TRANSFORMER SW3<I.B> EMERGENCY OPERATION SWITCH LD1<R.B> RUN INDICATOR LED
C1 INDOOR FAN CAPACITOR SWA<I.B> HIGH CEILING, NOISE SAVING SWITCH LD3<R.B> COOLING INDICATORLED
TB2 POWER SUPPLY TERMINAL BLOCK SWB<I.B> NUMBER OF AIR OUTLETS SWITCH LD4<R.B> FAN MODE INDICATOR LED
TB4 INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK SWC<I.B> OPTION SWITCH LD5<R.B> FAN HIGH INDICATOR LED
CND<I.B> POWER SUPPLY CONNECTOR X1<I.B> DRAIN PUMP/D.HEATER RELAY LD6<R.B> VANE ON INDICATOR LED
FAN1<I.B> FAN MOTOR CONNECTOR X3<I.B> VANE MOTOR RELAY LD7<R.B> INDICATOR MODE TEMPERATURE LED
CNV<I.B> VANE MOTOR CONNECTOR X4<I.B> FAN MOTOR RALAY LD8<R.B> INDICATOR MODE TIMER LED
CNP<I.B> DRAIN PUMP CONNECTOR F1<I.B> FUSE (6.3A) LD9<R.B> DRY INDICATOR LED
CN30<I.B> INDOOR/OUTDOOR CONNECTING WIRE CONNECTOR F2<I.B> FUSE (6.3A) LD10<R.B> FAN LOW INDICATOR LED
CN120<I.B> REMOTE CONTROLLER TRANSMISSION WIRE CONNECTOR ZNR<I.B> VARISTOR LD11<R.B> OFF TIMER INDICATOR LED
CN23<I.B> VANE POSITION CONNECTOR H DEW PREVENTION HEATER LD12<R.B> ON TIMER INDICATOR LED
CN20<I.B> INTAKE CONNECTOR R.B REMOTE CONTROLLER BOARD LD13~24<R.B> TEMPERATURE TIMER REMAINING TIME INDICATOR LED
CN21<I.B> PIPE CONNECTOR CNR120<R.B> CONNECTOR (REMOTE CONTROLLER TRANSMISSION WIRE)
LY
UPP
ER S
POWPHASE)50Hz
L ~(1 -240V
0 z
N 22 0V 60H
22
120
CNR
/YLW
GRN
TB2
SW1
LD1
LD7
LD8 SW5 SW2
LD3
GRILL 3
LD1 4
LD9
LD4
LD1 5 SW3
LD1 6 LD5 0
LS LD1 7 LD1
LD1 8 SW4
2 MV 12 LD1 9 SW6
LD6
7 LD1 0 SW8
ORN
YLW
RED
LD2 1 SW7
1
LD1 2
LD2 2
WHT
BLU
YLW
BRN
BRN
YLW
RED
BLU
6 LD2 4
BRN
RED BRN
BRN
2
RT2
1
333
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
PL-1.6KJB.UK, PL-2KJB.UK/PU-1.6VLJA2.UK,PU-2VJA2.UK,PU-2NJA1.UK
Ball Charge
valve plug
Strainer
Flared
Indoor heat connection
Outdoor heat
exchanger exchanger
Flared Accumulator
Distributor connection Compressor
Capillary tube
Ball valve
(with service port) : flow of refrigerant
Refrigerant pipe {9.52(3/8)
(With insulator) option wCapillary tube size
PU-1.6(O.D.3.2oI.D.1.8-R900)
PU-2 (O.D.3.2oI.D.2.0-R430)
ESQUEMAS ELCTRICOS Y FRIGORFICOS
PL-2.5KJB.UK/PU-2.5VJA2.UK,PU-2.5NJA1.UK
Strainer
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Indoor coil
Flared Accumulator
thermistor
connection Compressor
RT2 Capillary
Capillary tube for tube
Distributor
injection
with strainer
Ball valve
(with service port)
Refrigerant pipe 9.52 (3/8) flow of refrigerant
(With insulator) option
wCapillary tube size
PU-2.5 (O.D.3.2oI.D.1.6-R760)o2pcs
334
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PL-3GJB1, PL-4GJSB1, PL-5GJB1, PL-6GJSB1
LS H POWER SUPPLY
L ~(1 PHASE) LD8 LD7 CNR120
MF MV GRN/YLW N AC220-240V 50Hz LD13 SW5
220V 10.6VAC AC220V 60Hz LD14 LD1
1 2 3 DP 230V TB2 LD15 LD3 SW1
240V Remote Controller LD16 LD9
ORN
RED
SW6 SW2
YLW
2 7 5 10 1 6 14.5VAC
C1 BLU ~ LD17 LD4
T
BRN
BRN
WHT
BRN
BRN
BRN
BRN
RED
RED
RED
RED
RED
YLW
YLW
BLK
BLU
I.B LD21 LD6
LD11 SW8
CND CNT LD22
1 CN4T
1
FAN1 1 3 5 1 3 1 3 1 3 1 3 4 3 2 LD23 LD12
TRANS
CN120
POWER TRANS 12
TO.RC
FAN CNV CNP LD24
VANE DRAIN PUMP F2 F1
R.B
12
X4 TB4
1
MULTIPLE
X3 X1 ZNR TO OUTDOOR UNIT
OUTDOOR
CN51
3
2 CONNECTING WIRES
CN30
BLK ORN
2
DC12V(non-polar)
1
YLW
X4 X3 X1
1
2
4
DRAIN
CN50
BLK BLK
1
SW3 GRY BLK BLK DS
CN21
4
2
RT2
2
ON GRY BLK GRY
OFF PIPE
5
3
1
123
GRY
4
CN20
RT1
2
SW1 SW2 INTAKE
CN2B CN2A 3 2
1 CN28
ON
SWA
SWB
2 3
L.TEST
TIMER
CN23
OFF
VANE
JR01
JR02
JR03
JR04
JR05
JR06
CN2
2
12345678 12345 1 4 OP BRN
1
BG79N599H01
[Check items]
(1) Compressor and fan.
w PL-4GJSB1
Service Ref. SW1 (2) Check the trouble position using self diagnostic function.
TYPE MF1 MF2 If the result of self diagnosis indicates protective device such as freeze protec-
ON tion is functioning emergency operation is not possible unless the cause is
PL-3GJB1
WHT
RED
BLK
OFF removed.
PL-4GJSB1 12345678 (3) Do not attempt emergency operation when drain pump fails[drain overflows].
WHT
WHT
RED
BLK
(4) Emergency operation will be continuous operation mode due to power ON/OFF
1 3 4 2 [ON/OFF with remote controller is not possible].
BLK
FAN1 (2) Turn on outdoor unit side circuit breaker. then indoor unit side circuit breaker in
FAN 1 3 5 this order.
(3) During emergency operation indoor fan runs at high speed but vane remains
stop.
(4) Thermostat will not function.
(5) Emergency cooling should be limited to 10 hours maximum
[the indoor unit heat exchanger may freeze].
335
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Strainer
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Flared Accumulator
Distributor connection w
Compressor Capillary
with strainer
Capillary tube for injection tube
PU-3VJA O.D.3.2 o I.D.2.0 r520
PU-3YJA O.D.3.2 o I.D.1.4 r800
PU-3NJA O.D.3.2 o I.D.1.6 r500
PU-4YJSA/4TJSA
O.D.3.2 o I.D.1.2 r500
Ball valve
(with service port)
PL-3GJB1.UK,PL-4GJSB1.UK Refrigerant pipe [9.52 (3/8) Flow of refrigerant
(With insulator) option
Capillary tube size
PU-3 (O.D.3.2 o I.D.1.8 r 800) o 2pcs
PU-4 (O.D.3.2 o I.D.2.0 r 840) o 2pcs
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Flared Accumulator
Distributor connection Compressor
with strainer
Capillary tube
PU-5YJSA/5TJSA
(O.D. 4.0 oI.D. 2.4 R840)o2pcs
PU-6YJSA
(O.D. 4.0 oI.D. 2.4 R1200)o2pcs
PU-6TJSA Strainer
(O.D. 4.0 oI.D. 2.4 R740)o2pcs
336
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PLH-1.6KKHBUK/PLH-2KKHBUK/PLH-2.5KKHBUK
SYMBOL NAME SYMBOL NAME SYMBOL NAME
R.B REMOTE CONTROLLER BOARD CN2L<I.B> LOSSNAY CONNECTOR X3<I.B> VANE MOTOR RELAY
SW17<R.B> ADDRESS SELECTOR CN51<I.B> CENTRALLY CONTROL CONNECTOR X4<I.B> FAN MOTOR RELAY
SW18<R.B> FUNCTION SELECTOR FAN2<I.B> EMERGENCY OPERATION CONNECTOR F1<I.B> FUSE (6.3A)
CN1<R.B> PROGRAM TIMER CONNECTOR F.C<I.B> FAN PHASE CONTROL LED1<I.B> DC 12V POWER LED
CN2<R.B> REMOTE SWITCH CONNECTOR SW1<I.B> MODE SELECTOR LED2<I.B> DC 5V POWER LED
MV VANE MOTOR SW2<I.B> ADDORESS SELECTOR CNP<I.B> DRAIN PUMP CONNECTOR
LS LIMIT SWITCH SW3<I.B> EMERGENCY OPERATION SWITCH CN50<I.B> DRAIN SENSOR CONNECTOR
H2 DEW PREVENTION HEATER SW5, SW7<I.B> MODEL SELECTOR DP DRAIN PUMP
RT1 ROOM TEMP. THERMISTOR(0C/15K,25C5.4K) SW6<I.B> TWIN, TRIPLE SWITCH DS DRAIN SENSOR
RT2 INDOOR COIL THERMISTOR(0C/15K,25C5.4K) SWA<I.B> HIGH SEILING, NOISE SAVING SELECTOR H1 HEATER
T TRANSFORMER SWB<I.B> NUMBER OF AIR OUTLETS SELECTOR FS1,2 THERMAL FUSE
MF INDOOR FAN MOTOR SWC<I.B> OPTION SELECTOR 26H HEATER THERMAL SWITCH
C1 FAN MOTOR CAPACITOR ZNR<I.B> VARISTOR 88H HEATER CONNECTOR
TB2~6 TERMINAL BLOCK X1<I.B> DRAIN PUMP/D.HEATER RELAY CNV<I.B> VANE MOTOR CONNECTOR
I.B INDOOR CONTROLLER BOARD
LY
UPP
ER S
POW HASE) 0Hz
L ~(1P-240V 5
0 z
N 22 0V 60H
22
/YLW
GRN
TB2
8
1 SW1 OFF
. 2 ON
R.B
CN2 TB6
GRILL
V
7
SW1 OF
F
C12
3
1 2 ON
ES D
LS
CN1
WIR
MV 5
2 3 4
SION
7 1 2
ORN
YLW
YLW RED
R
DOO
SMIS
BLU 1 OUTIT
T H2 5 10
TRN
UN
YLW
YLW
BRN
BRN
RED
RED
BLU
BLU 6
BRN
BRN
RED BRN V 1
C12
1 3 1 3 1 3 1 3 14.2V AC 11.1V AC 1 ES D 2
5 BRN WIR
C1 BLK 4 3 2 1 DP BLU ION 3
MF 3 2 S MISS
WHT FAN1 CNV CNP CND CNT LED2 BLU TRN
CN4T BRN
RED 1 FAN VANE D.U.M.
F1
POWER TRANS
TRANS
5V POWER 1 TB3
BRN 01
1 CN22 1 ORN
2
3 9Y4 08H
F.C X4 X3 X1
2
1
TO REMOCON 2 YLW BG7
3 CN40 2 1 TB4
ZNR
X4 SW7 SW3 SWC X3 X1 CN50 4 REMOCON
POWER 3 CN30 2
1 3 5 DRAIN 5 OUTDOOR
OP 4 3
Showing STD CN41
FAN2 CN51 1
NOTES :
1. Since the indoor transformer (T)is connected with 240Vpower. If 220, 230v power is used. change the wiring connection showing fig: w2
fig:w2 240V YELLOW
230V ORANGE
230V
When power supply is 220V RED
220V
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Indoor and outdoor connecting wires are made with polarities. make wiring matching terminal numbers.
4. Symbols used in wiring diagram above are. / : Terminal block, : Connector.
5. Emergency operation
If remote controller or microcomputer fails but there is no other truble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor con-
troller board.
[Check items]
(1)Make sure that no other trouble exists the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code P8will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous run with the power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Switch the fan connector on the indoor controller board from FAN 1 to FAN 2.
(2)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(3)Turn on the outdoor unit side circuit breaker, then the indoor unit side circuit breaker.
(4)During emergency operation indoor fan runs at High speed but auto-vane does not work.
(5)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for a long time.
(6)Emergency cooling should be limited to 10 hours maximum. (the indoor unit heat exchanger may freeze).
(7)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
NOTE: If the drain water lift up mechanism is identified to be defective with the microcomputer doctor during cooling, do not use emergency operation
(it causes drain overflow)
337
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Flexible tube
Indoor Service Outdoor coil
heat port thermistor
exchanger (TH)
Flared Bypass
Strainer connection
valve w
Accumulator Restrictor Capillary
valve tube
Indoor coil Restrictor
thermistor valve Compressor
(RT2)
Distributor Strainer High pressure
with Refrigerant pipe Ball valve
(option) protect switch
strainer (with service port)
9.52mm( 3.8")
Capillary (with heat insulator) wPLH-1.6 (O.D.3.2 I.D.1.8 R400)
tube PLH-2 (O.D.4.0 I.D.2.0 R430)
PLH-1.6 (O.D.3.2 I.D.1.6 R630) PLH-2.5 (O.D.3.2 I.D.1.8 R430) PLH-2.5 (O.D.4.2 I.D.2.4 R1550)
PLH-2 (O.D.3.2 I.D.1.8 R630)
R.V.coil
Refrigerant flow in cooling
Heating ON
Refrigerant flow in heating Cooling OFF
ESQUEMAS ELCTRICOS Y FRIGORFICOS
338
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PLH-3GK(H)B1.UK/PLH-5GK(H)SB1.UK
PLH-4GK(H)SB1.UK/PLH-6GK(H)SB1.UK
I.B
Remote Controller Indoor unit fig: w 3
TO OUT FAN2
DOOR MODELS SW7
REMOCON REMOCON (WHT) ON
TRANSMISSION WIRES DC12V CN30 POWER 3GK(H)B
CN22 5 3 1 4GK(H)SB OFF
1 2 3
(WHT) CN40
R.B (WHT) ON
TB5 3 2 1 (WHT) 5GK(H)SB OFF
A01 1 2 B02 2 X1 X3 1 2 3
ORN
BRN
YLW
SW18 4 3 2 1 ON
BLU
OFF CENTRALLY 6GK(H)SB OFF
TB6 1 1 2 3
ON HA CONTROLL
CN1 X1
4321 CN41 CN51 X3 ZNR
SW17 5 4 3 2 1
OFF CN2 SW7 SW1 SW3
ON
87654321 ON FAN CON X4
3 2 1 OFF
1 2 3 1 2 3 4 5 6 7 8 9 10 1 2 SWA SWB VANE
SW2 SW6 SW5 SWC POSITION X4
ON PIPE DRAIN LOSSNAY HEATER TRANS F
OFF DRAIN-UP VANE D HEATER
CN21 CN50 CN2L CN23 CN24 CN4T CNT CNP CNV FAN1 CND
1 2 3 4 5 6 1 2 3 4 1 2 3 4
INTAKE (RED) (WHT) (WHT) (GRN) (YLW) (RED) (WHT) (BLU) (WHT) (WHT) (WHT)
CN20 4 3 2 1 3 1 3 1 6 4 2 1 5 3 1 3 1 FAN1
TB4 (WHT)
WHT
GRY
BRN
BRN
BRN
RED
RED
RED
RED
RED
YLW
YLW
BLK
BLU
BLK
3 AC AC 5 3 1
TO OUTDOOR UNIT Showing fig:w3
15.4 11.3
WHT
Showing fig: w 1
RED
BLK
CONNECTING WIRES 2 7 3 V V C1
RED
BLK
6 2 5 1
BRN
DC12V(polar) 1
T 3 2 1
YLW
YLW
DP
BLU
BLU
4 3 2 1
ORN
RED
YLW
For C2 C1
WHT
RED
BLK
PLH-4,5,6 2 4 3 1
H2 3 2 1
WHT
WHT
RED
BLK
LS
MF1
RT1 RT2 MV
POWER SUPPLY DS 321 3 2 1
L RED GRILLE
w
(1 phase) N MF2 MF1
BLU
220-240V 50Hz GRN/YLW
220V 60Hz
TB2 BG79J990H03
NOTES : [Check items]
1. Since the indoor fan motor (MF 1.2) is connected with 230~240V power. If (1)Make sure that no other trouble exist the outdoor unit. Trouble with the out-
220V power is used. change the dip switch (SW5<1.B>)on the indoor con- door unit prevents emergency operation.
troller board showing fig: w1. (If any trouble exists the outdoor unit error code P8will be displayed on the
fig w1 SW5 SW5 remote controller and the trouble position will be shown on the outdoor con-
ON ON troller LED. See electric wiring diagram of the outdoor unit for details.)
Indoor fan motor (MF1.2)for 220V. (2)Make sure that there is no trouble with the indoor fan.
OFF 1 2 3 4 OFF 1 2 3 4
Emergency operation will be continuous run with power ON/OFF (ON/OFF
2. Since the indoor transformer (T)is connected with 240V power.if 220.230V with the remote controller is not possible).
power is used. Change the wiring connection showing fig: w2.
3. Since the outdoor side electric wiring may change be sure to check the out- [Emergency operation procedure]
door unit electric wiring for servicing. (1)Switch the fan connector on the indoor controller board from FAN 1 to FAN
2.
fig w2 240 YELLOW (2)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2
230 ORANGE off for cooling and 1 - 2 on for heating.
When power supply is 230V
220 RED (3)Turn on the outdoor unit side circuit breaker, then the indoor unit side circuit
339
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Flexible tube
Indoor Service
heat port Thermistor
exchanger TH
Flared
Strainer connection Bypass
valve
Accumulator Restrictor Capillary
valve tube
Thermistor Restrictor
valve Compressor
RT2
Thermistor Restrictor
RT2 valve Accumulator Compressor
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port)
Capillary 9.52mm([ 3.8") (O.D.3.2 o I.D. 2.0 -r820)X2
tube (with heat insulator) PUH-4
PLH-5GK(H)SB1.UK/PUH-5YKSA2.UK
Control
PLH-6GK(H)SB1.UK/PUH-6YKSA2.UK Oil high pressure Outdoor unit
separator switch
Refrigerant pipe Outdoor heat exchanger
(option) 4-way valve Protect
Indoor unit 19.05mm([ 3/4") Ball valve Service high Pr.
(with heat insulator) Strainer port SW
Distributor
with Ball valve Thermal Switch Strainer
Refrigerant pipe
strainer (option)r (with service port)
9.52mm([ 3/8")
Capillary (with heat insulator) PUH-5 (O.D.4.0 o I.D. 2.4 -r 840) o2
tube PUH-6 (O.D.4.0 o I.D. 2.4 -r1200) o2
6 - WIRING DIAGRAM
PS-3GJA1, PS-4GJSA1, PS-5GJA1, PS-6GJSA1
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C INDOOR FAN MOTOR CAPACITOR LD9<R.B> DRY INDICATOR LED SW2<R.B> OPERATION MODE SWITCH
CN2<I.B> TIMER ADAPTOR CONNECTOR LD10<R.B> FAN LOW INDICATOR LED SW3<R.B> FAN SPEED SWITCH
CN2A<I.B> TRANSMISSION WIRES No.1 CONNECTOR LD11<R.B> OFF TIMER INDICATOR LED SW4<R.B> LOUVER ON/OFF SWITCH
CN2B<I.B> TRANSMISSION WIRES No.2 CONNECTOR LD12<R.B> ON TIMER INDICATOR LED SW5<R.B> DISPLAY SWITCH
CN28<I.B> TIME SHORTENING CONNECTOR LD13~24 TEMPERATURE/TIMER SW6<R.B> RAISES SET TEMPERATURE/TIMER SWITCH
CN51<I.B> MULTIPLE CONNECTOR <R.B> REMAINING TIME INDICATOR LED SW7<R.B> LOWERS SET TEMPERATURE/TIMER SWITCH
FUSE1,2<I.B> FUSE<6.3A> MF INDOOR FUN MOTOR SW8<R.B> TIMER MODE SWITCH
I.B INDOOR CONTROLLER BOARD ML LOUVER MOTOR T TRANSFORMER
LD1<R.B> RUN INDICATOR LED R.B CONTROLLER BOARD TB1 POWER SUPPLY TERMINAL BLOCK
LD3<R.B> COOLING INDICATOR LED RT1 ROOM TEMPERATURE THERMISTOR TB2 INDOOR/OUTDOOR
LD4<R.B> HEATING INDICATOR LED (0C/15k, 25C/5.4k DETECT) CONNECTING WIRE TERMINAL BLOCK
LD5<R.B> FAN HIGH INDICATOR LED RT2 INDOOR COIL THERMISTOR X2<I.B> LOUVER MOTOR RELAY
LD6<R.B> LOUVER ON INDICATOR LED (0C/15k, 25C/5.4k DETECT) X4,X5,X6<I.B> INDOOR FAN RELAY
LD7<R.B> TEMPERATURE MODE TEMPERATURE LED SW1<I.B> FUNCTION SWITCH ZNR VARISTOR
LD8<R.B> TIMER MODE INDICATOR LED SW2<I.B> UNIT SWITCH
SW3<I.B> EMERGENCY OPERATION SWITCH
SW1<R.B> ON/OFF SWITCH
POWER SUPPLY
L ~ (1 PHASE)
N AC220 ~ 240V 50Hz
C GRN/YLW AC220V 60Hz
220V 10.6VAC
TB1
ORN
RED
230V
ORN
YLW
RED
MF ML 240V 14.5VAC
YLW/GRN T
WHT
WHT
I.B
YLW
YLW
YLW
BRN
BRN
YLW
BRN
RED
BLU
RED
BLK
BLU
FAN1 1 3 5 7 CNL
1 3 LOUVER CND 1 3 1 3 CNT 4 3 2 1 CN4T
POWER TRANS TRANS
12
FUSE2 FUSE1
CN120
12
TO.RC
X6 X5 X4
MULTIPLE
CN51
1 3 2 1
X2
HEATER
CN31
5 4 3 2 1
X6 X5 X4 X2 ZNR
CN50
DRAIN
OUTDOOR
3 2 1
CN30
SW3 ORN
LD8 LD7 CNR120 R.B
YLW
ON
OFF LD1 SW1
TIMER
LD13 SW5
LD14
SW1 SW2 LD15 LD3
CN20 CN21 SW2
2 1
CN2B CN2A
2 1
LD16 LD9
ON INTAKE PIPE
L.TEST
NOTES :
1. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig : W1.
fig : W1
220V RED
230V ORANGE
When power supply is 230V
240V YELLOW
240V
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Symbols used in wiring diagram above are. :connector / :Terminal block
4. Emergency operation
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor
controller board.
[Check items]
(1) Compressor and fan.
(2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is function-
ing, emergency operation is not possible unless the cause is removed.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
[Emergency operation procedure]
(1) Set the dip switch (SW3<I.B>) on the indoor controller board to 1 2 on and 3 off for cooling.
(2) Turn on outdoor unit side circuit breaker, and then indoor unit side circuit breaker in this order.
(3) During emergency operation, the indoor fan runs on high speed but swing louver remains stop.
(4) Thermostat will not function.
(5) Emergency cooling should be limited to 10 hours maximum (the indoor unit heat exchanger may freeze.)
341
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Strainer
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Flared Accumulator
Distributor connection w
Compressor
with strainer Capillary
Capillary tube for tube
injection
Only PU-3NJA,3VJA wSize of capillary tube for injection
3YJA,4TJSA,4YJSA PU-3 (O.D.3.2 o I.D.1.8 -R800) o 2pcs
PU-4 (O.D.3.2 o I.D.2.0 -R840) o 2pcs
Ball valve
(with service port)
Refrigerant pipe 9.52 (3/8F) flow of refrigerant
(With insulator) option PU-3VJA O.D.3.2 o I.D. 2.0 - R 520
PU-3YJA O.D.3.2 o I.D. 1.4 - R 800
PU-3NJA O.D.3.2 o I.D. 1.6 - R 500
PU-4YJSA/4TJSA O.D.3.2 o I.D. 1.2 - R 500
ESQUEMAS ELCTRICOS Y FRIGORFICOS
Ball High
valve pressure
switch
Thermal
switch
Flared
Indoor heat connection
exchanger Outdoor heat
exchanger
Flared Accumulator
Distributor connection Compressor
with strainer
Capillary tube
PU-5YTJSA
(O.D. 4.0oI.D. 2.4 R840)o2pcs
PU-6YJSA
(O.D. 4.0oI.D. 2.4 R1200)o2pcs
PU-6TJSA Strainer
(O.D. 4.0oI.D. 2.4 R740)o2pcs
342
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
6 - WIRING DIAGRAM
PSH-3GJHA1 / PSH-4GJHSA1 / PSH-5GJHSA1 / PSH-6GJHSA1
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C FAN MOTOR CAPACITOR LD9<R.B> DRY INDICATOR LED SW2<R.B> OPERATION MODE SELECTOR
CN2<I.B> TIMER ADAPTOR CONNECTOR LD10<R.B> FAN LOW INDICATOR LED SW3<R.B> FAN SPEED HIGH/LOW SELECTOR
CN2A<I.B> TRANSMISSION WIRES No.1 CONNECTOR LD11<R.B> OFF TIMER INDICATOR LED SW4<R.B> LOUVER ON/OFF SWITCH
CN2B<I.B> TRANSMISSION WIRES No.2 CONNECTOR LD12<R.B> ON TIMER INDICATOR LED SW5<R.B> DISPLAY SELECTOR
CN28<I.B> TIME SHORTENING CONNECTOR LD13~24 TEMPERATURE/TIMER SW6<R.B> RAISES SET TEMPERATURE/TIMER UP SWITCH
CN51<I.B> MULTIPLE CONNECTOR <R.B> REMAINING TIME INDICATORLED SW7<R.B> LOWERS SET TEMPERATURE/TIMER DOWN SWITCH
FUSE1,2<I.B> FUSE<6.3A> MF INDOOR FUN MOTOR SW8<R.B> TIMER MODE SELECTOR
FS1,2 THERMAL FUSE (110C 6A) ML LOUVER MOTOR T TRANSFORMER
H HEATER R.B CONTROLLER BOARD TB1 POWER SUPPLY TERMINAL BLOCK
I.B INDOOR CONTROLLER BOARD ROOM TEMPERATURE THERMISTOR INDOOR/OUTDOOR
RT1 TB2
LD1<R.B> RUN INDICATOR LED (0C/15k", 25C/5.4k" DETECT) CONNECTING WIRE TERMINAL BLOCK
LD3<R.B> COOLING INDICATOR LED INDOOR COIL THERMISTOR X2<I.B> LOUVER MOTOR RELAY
RT2
LD4<R.B> HEATING INDICATOR LED (0C/15k", 25C/5.4k" DETECT) X4,X5,X6<I.B> INDOOR FAN RELAY
LD5<R.B> FAN HIGH INDICATOR LED SW1<I.B> FUNCTION SELECTOR ZNR VARISTOR
LD6<R.B> LOUVER ON INDICATOR LED SW2<I.B> UNIT SELECTOR 26H HEATER THERMAL SWITCH
LD7<R.B> TEMPERATURE MODE TEMPERATURE LED SW3<I.B> EMERGENCY OPERATION SWITCH 88H HEATER CONTACTOR
LD8<R.B> TIMER MODE INDICATOR LED SW1<R.B> ON/OFF SWITCH
POWER SUPPLY
L ~(1 PHASE)
N AC220|240V 50Hz
C GRN/YLW AC220V 60Hz
220V 10.6VAC
H TB1
ORN
88H
RED
6 5 4 3 2 1
ORN
RED
YLW
I.B
WHT
YLW
YLW
BRN
YLW
BRN
RED
RED
BRN
YLW
BLU
BLK
BLU
RED
FAN1 1 3 5 7 CNL
1 3 LOUVER CND 1 3 1 3 CNT 4 3 2 1 CN4T
POWER TRANS TRANS RED YLW
88H
12
FUSE2 FUSE1 6 1
CN120
26H 12
TO.RC
X6 X5 X4
MULTIPLE
CN51
1 3 2 1
X2
YLW
HEATER
CN31
5 4 3 2 1
YLW
X6 X5 X4 X2 ZNR
CN50
DRAIN
BRN
OUTDOOR
3 2 1
CN30
SW3 ORN
LD8 LD7 CNR120 R.B
YLW
ON
OFF SW1
TIMER
123 LD14
SW1 SW2 CN21 LD15 LD3
CN20 SW2
2 1
CN2B CN2A
2 1
LD16 LD9
ON INTAKE PIPE
L.TEST
NOTES :
1. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig : w1.
fig : w1
220V YELLOW
230V ORANGE
When power supply is 230V
240V RED
240V
2.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring during servicing.
3.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal.
4.Symbols used in circuit diagram above are. :connector :Terminal block
5.Emergency operation
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor
controller board.
[Check items]
(1) Compressor and fan.
(2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning,
emergency operation is not possible unless the cause is removed.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
[Emergency operation procedure]
(1) Set the dip switch (SW3<I.B>) on the indoor controller board to 1 2 on and 3 off for cooling, and 1 2 3 on for heating.
(2) Turn on outdoor unit side circuit breaker, and then indoor unit side circuit breaker in this order.
(3) During emergency operation, the indoor fan runs on high speed but swing louver remains stop.
(4) Thermostat will not function. Cold air blows out for defrosting during heating, thus do not operate defrosting for a long time.
(5) Emergency cooling should be limited to 10 hours maximum (the indoor unit heat exchanger may freeze.)
343
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
Flexible tube
Indoor Service Thermistor
heat port TH
exchanger
Flared Bypass
Strainer connection valve
Accumulator Restrictor Capillary
valve tube
Thermistor Restrictor Compressor
RT2 valve
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port) High pressure
9.52mm ([3/8") protect switch
Capillary (with heat insulator) PUH-3VK2, YK3O.D.4.0 I.D.2.4- R1,070
tube PUH-3VKA, YKA
PSH-3GJHA1O.D.4.0 I.D.2.0-R500
valve Capillary
tube
344
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
345
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
346
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
347
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
348
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
349
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
350
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA COMERCIAL
351
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
Y FRIGORFICOS
353
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
354
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
355
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
356
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
357
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
358
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
359
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
360
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
361
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
362
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
363
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
364
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
365
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
ESQUEMAS ELCTRICOS Y FRIGORFICOS
366
ESQUEMAS ELCTRICOS Y FRIGORFICOS GAMA INDUSTRIAL
367
PEDIDO RECAMBIOS
Y GARANTA
369
MITSUBISHI ELECTRIC EUROPE, B.V. ALICANTE - Fax: 961 270 897 MADRID - Fax: 916 743 336
BARCELONA - Fax: 936 970 459 PALMA DE MALLORCA - Fax: 971 432 913
BILBAO - Fax: 944 761 485 SEVILLA - Fax: 954 253 279
GRANADA - Fax: 958 263 350 VALENCIA - Fax: 961 270 897
LEON - Fax: 987 802 808 ZARAGOZA - Fax: 976 754 131
SU PEDIDO
PEDIDO DE RECAMBIO NUMERO
FECHA
CLIENTE CODIGO
(EMPRESA CLIENTE
INSTALADORA)
TELEFONO FAX
NOMBRE DE
CONTACTO Sr./Sra.
DIRECCION
DE ENTREGA
NUMERO DE SERIE
...............................................................................................................................................................
...............................................................................................................................................................
...............................................................................................................................................................
...............................................................................................................................................................
...............................................................................................................................................................
...............................................................................................................................................................
...............................................................................................................................................................
SI LO SOLICITA EN SI ........................................................................................................................................................................
GARANTIA (MARQUE
CON UNA X) ........................................................................................................................................................................
........................................................................................................................................................................
Deben adjuntar impreso de GARANTIA o en su
defecto Factura o Albarn de compra. ........................................................................................................................................................................
NOTA: Si la solicitan en GARANTIA, recuerden que deben retornar la pieza averiada al Dto. Tcnico en un plazo mximo de 20 das. En caso
contrario les ser facturada.
371
GARANTIA MITSUBISHI ELECTRIC EUROPE, B.V.
AIRE ACONDICIONADO
Nombre ...........................................................................................................................................................................................
(Rellenar en
en caso multi) Unidad interior. Modelo N de Serie
Fecha de instalacin
CONDICIONES DE GARANTIA
Esta garanta es otorgada por MITSUBISHI ELECTRIC EUROPE, B.V. especficamente al comprador mencionado al dorso, durante
el plazo de 3 aos para el compresor y 1 ao para el resto de piezas y componentes de la unidad, contra todo defecto de fabricacin.
La garanta se limita exclusivamente a la sustitucin del componente averiado por defecto de fabricacin, no incluyendo en
ningn caso la mano de obra, gastos de locomocin y dietas del personal. Se excluyen de esta garanta las averas no imputables
a defectos de fabricacin o de los materiales, as como las originadas por mala instalacin o manipulacin indebida o durante el
envo, que debern reclamarse al personal de la compaa de transporte (inspeccionar los paquetes antes de conformar el envo),
los provocados por tensiones de alimentacin indebidas, y las originadas por la obstruccin de filtros de aire y bateras.
PEDIDO RECAMBIOS Y GARANTA
NOTA: Para que la garanta sea vlida es imprescindible que la empresa instaladora la cumplimente debidamente y la enve a MITSUBISHI ELECTRIC
EUROPE, B.V.
Los aparatos que hayan sido manipulados por personal no autorizado expresamente por MITSUBISHI ELECTRIC EUROPE, B.V. quedarn
excluidos automticamente de la garanta.
372
CERTIFICADOS
DOMSTICO
Mr. SLIM
INDUSTRIAL
CITY MULTI
CERTIFICADOS AO 2000
373
POLGONO INDUSTRIAL CAN PI DE VILAROCH
C/ CESAR MARTINELL Y BRUNET 43
08191 RUB (BARCELONA)
Estimados seores,
Estos equipos no utilizan las fechas en sus algoritmos de funcionamiento, por lo que los
das del ao 2000 y siguientes sern considerados como cualquier da anterior al citado ao.
Ramn Bacardit
CERTIFICADOS AO 2000
374
RE: CERTIFICACIN DEL AO 2000.
Estimados Sres.:
Con respecto al tema mencionado en la cabecera, nosotros confirmamos que los productos de la gama
City Multi de Mitsubishi Electric (fabricados en AC & R) en las que estn incluidas versiones actuales y
anteriores de controles opcionales, no se vern afectadas en su funcionamiento y prestaciones por las
fechas antes, durante y despus del ao 2000.
Especialmente en nuestro sistema de control City Multi, y que confirmamos los siguientes puntos de
funcionamiento.
1.- Ningn valor de la fecha actual causar interrupcin alguna en su funcionamiento.
2.- Las funciones basadas en la fecha sern vlidas antes, durante, y despus del ao 2000.
3.- Todas la pantallas y sistemas de almacenamiento de fecha (horas, segundos...) estn especificadas
explcitamente por reglas algortmicas no ambiguas. Los equipos frigorficos City Multi de Mitsubishi
Electric, sistemas de control no incorporan ningn calendario anual.
4.- El ao 2000 es reconocido como un ao cualquiera, y los equipos no se vern afectados en ningn
momento.
En cuanto a los controles opcionales hacemos constar:
a. Los controles PAR-F25 MA, PAC-SE 51 CRA, MJ100, MJ103, y MJ180, no se vern afectados por
las fechas antes, y durante el ao 2000, y cuyas programaciones diarias informticas, funcionarn
correctamente hasta el ao 2090.
b. El programa de control MJ300, se ha de instalar en un ordenador personal, personal ser usuario.
Siempre que el ordenador personal no se vea afectado en su funcionamiento por el ao 2000 (debido
a otro software o hardware), nuestro programa MJ300 funcionar correctamente, antes, durante y
despus del ao 2000.
c. El programa Request-M, se ha de instalar en un ordenador personal, personal ser usuario. Siempre
que el ordenador personal no se vea afectado en su funcionamiento por el ao 2000 (debido a otro
software o hardware), nuestro programa Request-M funcionar correctamente, antes, durante y
despus del ao 2000.
d. El programa de control M-Net de mantenimiento de herramientas, se ha de instalar en un
ordenador personal, personal ser usuario. Siempre que el ordenador personal no se vea afectado en
su funcionamiento por el ao 2000 (debido a otro software o hardware), nuestro programa M-Net
mantenimiento de herramientas funcionar correctamente, antes, durante y despus del ao 2000.
Ramn Bacardit
CERTIFICADOS AO 2000
Responsable Dpto.
De Aire Acondicionado.
375
MITSUBISHI ELECTRIC CORPORATION
6 de Julio de 1999
Ramn Bacardit
CERTIFICADOS AO 2000
376
GARANTIA
RECUERDEN QUE PARA QUE LA GARANTIA TENGA VALIDEZ DEBEN RESPETARSE LAS CONDICIONES
INDICADAS Y HABERSE RELLENADO Y ENVIADO EL IMPRESO DE GARANTIA CORRESPONDIENTE A:
MITSUBISHI ELECTRIC EUROPE, B.V.
TODAS LAS UNIDADES INCLUYEN LOS IMPRESOS DE GARANTIA. EN CASO DE EXTRAVIO O FALTA NO
DUDE EN SOLICITARLO A SU DELEGACION COMERCIAL. GRACIAS.
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
PEDIDO RECAMBIOS Y GARANTA
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
377
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
378
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
379
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
380
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
NOTAS
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
..................................................................................................................................................................................................................................................................................................................
381