_ [DECR-S MICROCOMPUTER EXCITATION DEVICES)

Dynamic Test Report of DECR-S


Excitation Devices

Experimenter: *f-W ~

Audit

Sanction

Beijing TuoDe electrical equipment Co., Ltd

Date: 2012.8.24
_--===[:::D=E=C=R=-=S=M=I=C=R=O=C=O=M==PU=T=E=R==E=X=C=I=TA==T=IO=N==D=E=V=IC=E=S=,]===--

DECR-S Excitation Devices

Parameter Settings

Part l, Insulation and wiring check

1 insulation test
Project Insulating resistance Test gear test result
Terminal connection cabinet enclosures 200MQ 500V Passed
DC positive and negative between 200MQ 1000V Passed

2 power supply check

Power supply mode input cv : output/DYl A)/24V output(DY2A)/24V

DC power supply 223V 23V 23V

3 Standard Requirements: DC input: 16~300V; output: 24V1 V 0

4 Testing device:
1, Oscilloscopes

2, Digital Multimeter

5 GIO G20 analog input check


Parameter Actual Value of Set G 10 Actual Value of Set G20
Excitation current 8.6A 8.6A
Machine voltage 11.0KV 11.0KV
Machine current 998A 998A
_--===[:::D=E=C=R=-=S=M=I=C=R=O=C=O=M==PU==TE=R==E=X=C=I=T=A=T=IO=N==D=E=V=IC=E=S:::::]===--

Part2. Testing Project


1, Generator characteristic test

1.1, We can set stator current (It Base Value) and excitation current (If Base Value)

base value in the generator Short-circuit Test.

1.2, We can set stator voltage (Ut Base Value) base value in the generator No-load

Characteristics test.

2. Test of No-load Closed Loop increasing voltage. (Both controllers in service)

1) Auto steady-state.

2) Switch test of auto and manual.

3) Manual steady-state.

4) Test ofUr5% step.

5) Test of de-excite.

6) Test of auto 90% start up.

7) Test ofVIF. (Optional) 0 (nought)

3. The De-excitation text ofFMK trip.

4. Test after combining to the bus.

1) Auto steady-state.

2) Switch test by Auto - Manual

3) Manual steady-state.

4) Load shedding test. (nought)

6. IEEE TESTS (nought)

ONLINE

- Under-excitation limits.

- Over-excitation limits.
_
[DECR-S MICROCOMPUTER EXCITATION DEVICES]
~~~~~~~~~~~

Part3. No-load Test


BOTH CONTROLLERS IN SERVICE: Auto steady-state
Standard Requirements: the terminal voltage is within the range of 1.0%0
Test record: the terminal voltage is within the range of 1%0
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: Switch test of auto and manual


Standard requirements: Generator voltage should not fluctuate when switch
Test records: Generator voltage is basic steadily and not fluctuate
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: manual steady-state


Standard Requirements: the terminal voltage is within the range of 1.0%0
Test record: the terminal voltage is within the range of 0.5% 0

Test result: PASSED

BOTH CONTROLLERS IN SERVICE: Ur-5% step


Standard requirements: do Ur-5% Step test in Computer , the overshoot of
system response of step signal is no more than 30%, number of
oscillation is no more than 3 times, rise time is no more than 0.6s
and adjustment time is no more than 5s.
Test records: the overshoot of system response of step signal is no more than
26 %, number of oscillation is no more than 3 times, rise time is
no more than 0.5s and time is no more than 5s.
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: Ur+5% step


Standard requirements: do Ur+5% Step test in Computer , the overshoot of
system response of step signal is no more than 30%, number of
oscillation is no more than 3 times, rise time is no more than 0.6s
and adjustment time is no more than 5s.
Test records: the overshoot of system response of step signal is no more than
22 %, number of oscillation is no more than 3 times, rise time is
no more than 0.5s and time is no more than 5s.
_
[DECR-S MICROCOMPUTER EXCITATION DEVICES]
~~~~~~~~~~~

Test result: PASSED

BOTH CONTROLLERS IN SERVICE: The De-excitation test


Standard requirements: Can correct and rapid de-excitation.
Test records: Can correct and rapid de-excitation.
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: auto 90% start up


Standard requirements : when increase the generator voltage from zero start up,
AVR should ensure that not more than generator rated voltage rating
of 110%.
Test record: when increase the generator voltage from zero start up, AVR should
ensure that not more than generator rated voltage rating of 110%.
Test result: PASSED

Part4. Test after combining to the bus.


BOTH CONTROLLERS IN SERVICE: Auto steady-state
Standard Requirements: the terminal voltage is within the range of 1.0%0
Test record: the terminal voltage is within the range of 0.5%0
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: Switch test by Auto - Manual - Auto.


Standard requirements: Generator voltage should not fluctuate when switch.
Test records: Generator voltage is basic steadily and not fluctuate.
Test result: PASSED

BOTH CONTROLLERS IN SERVICE: manual steady-state


Standard Requirements: the terminal voltage is within the range of 1.0%0
Test record: the terminal voltage is within the range of 0.5%0
Test result: PASSED
; ABB Switzerland Ltd

; CMT 1000 v5.001

; UNITROL 1000-7 Parameter File

; Saved: 24.08.2012, 11:24

; AVR Serial Number: 00000828/0023

; Control SW Version: 5.010

; Panel SW Version: 0.000

[SYSTEM DATA]

Ie Nominal=7.5A

Potential Transformer=Three_Phase

UM Nominal=11.00kV

UM Primary=11.00kV

UM Secondary=100.00V

UNet Nominal=11.00kV

UNet Primary=11.00kV

UNet Secondary=100.00V

1M2 Nominal=984.00A

1M2 Primary=1200.00A

IM2Secondary=5.00A

Ie No Load=30.00%

Kceiling=30.00V IV
Xq=0.80

f Nominal=50.00Hz

[FIELD FLASHING]
Off Level=O.OO%

[SOFTSTART]

Starting Level=O.OO%

Hold Time=O.OOs

Ramp Time=10.00s

lV/Hz LIMITER]

fKnee=48.00Hz

Slope=100.00%

[leMin LIMITER]

Minimum=O.OO%

Active=FALSE

[leMax LIMITER]

Maximum=150.00%

Maximum Hold Time=10.00s

Delayed=110.00%

Delayed Hold Time=60.00s

Continuous=105.00%

Active=TRUE

[PQ LIMITER]

Minimum Q (P @ 0%)=-40.00%

Minimum Q (P @ 25%)=-35.00%

Minimum Q (P @ 50%)=-30.00%

Minimum Q (P @ 75%)=-25.00%

Minimum Q (P @ 100%)=-20.00%
Voltage Dependency=TRUE

Active=TRUE

rUM LIMITER]

Minimum=90.00%

Maximum=110.00%

Minimum Active=TRUE

Maximum Active=TRUE

[BOOST]

Treshold=40.00%

Hold Time=3.00s

Hysteresis=lS.00%

[AUTO SETPOINT]

Initial=100.00%

Minimum=90.00%

Maximum=110.00%

Ramp Rate=O.30%js

Disable CB Check=FALSE

[PF SETPOINT]

Minimum=-O.8S00

Maximum=O.8S00

Ramp Rate=O.OOSOjs

[Var SETPOINT]

Minimum=O.OO%

Maximum=100.00%
Ramp Rate=l.OO%js

[MANUAL SETPOINT]

Initial=O.OO%

Minimum=O.OO%

Maximum=150.00%

Ramp Rate=1.67%js

[OPEN LOOP SETPOINT]

Initial=O.OO%

Minimum=O.OO%

Maximum=100.00%

Ramp Rate=1.00%js

[DIGITAL I/O 1]

Input=None

PolaritLIN=Normal

Output=SW _Alarm

PolaritvOtrl=tnverted

Direction=Out

[DIGITAL I/O 2]

Input=None

PolaritLIN=Normal

Output=Diode_Alarm

PolaritLOUT=Normal

Direction=Out

[DIGITAL I/O 3]
Input=None

PolaritLIN=Normal

Output=Limit Active

PolaritLOUT=Normal

Direction=Out

[DIGITAL I/O 4]

Input=Remote_Setpoint

PolaritLIN=Normal

Output=None

PolaritLOUT=Normal

Direction=ln

[DIGITAL INPUT 5]

Input=Open_Loop_Enable

PolaritLIN=Normal

[DIGITAL INPUT 6]

Input=Gen_CB_Closed

PolaritLIN=Normal

[DIGITAL INPUT 7]

Input=ParalieLWith_Grid

PolaritLIN=Normal

[DIGITAL INPUT 8]

Input=Excitation_ON

PolaritLIN=Normal
[DIGITAL INPUT 9 from +AI]

Input=None

PolaritLIN=Normal

[DIGITAL INPUT 10 from -AI]

Input=None

PolaritLIN=Normal

[DIGITAL INPUT 11 from +AI]

lnput=ManualEnable

PolaritLIN=Normal

[DIGITAL INPUT 12 from -AI]

Input=Var_Enable

PolaritLIN=Normal

[DIGITAL INPUT 13 from +AI]

Input=lncrease

PolaritLIN=Normal

[DIGITAL INPUT 14 from -AI]

Input=Decrease

PolaritLIN=Normal

[ANALOG INPUT 1]

Input=Open_Loop_Setpoint

Uin O%=O.OOV

Uin 100%=1O.00V
[ANALOG INPUT 2]

Input=Dinll&12

Uin 0%=2.00V

Uin 100%=5.00V

[ANALOG INPUT 3]

Input=Din13&14

Uin 0%=2.00V

Uin 100%=5.00V

[ANALOG OUTPUT]

Outputl=PWM

Output2=None

Uoutl O%=O.OOV

Uoutl100%=10.00V

Uout2 O%=O.OOV

Uout2 100%=10.00V

Ie 0%=0.00%

Ie 100%=300.00%

Active Power=200.0%

[TUNE AUTO]

Proportional Gain (Vp)=8.00

Derivation Time (Tb)=0.06s

Integration Time (Ta)=2.00s

Droop (Kq)=-4.00%

[TUNE PF/Var/PQ LIMITER]

Proportional Gain (Vp)=10.00


Integration Time (Ta)=3.00s

[TUNE MANUAL/Ie LIMITER]

Proportional Gain (Vp)=3.00

Integration Time (Ta)=O.3Ss

[COMMUNICATION]

AVR ID=2

Channel Identification=Main

[DIODE MONITORING]

f Exc Nominal=SO.OOHz

Tconst Exc=3S0.00ms

Active=TRUE

Alarm Level=S.OO%

Alarm Delay=10.00s

Trip Level=20.00%

Trip Delay=O.30s

[1M Limiter]

IMlim_Active=FALSE

IMlim_K=l.OO

IMlim_lm_th=100.00%

[TEMP INFLUENCE]

IMlim_T1=SO.OOC

IMlim_lm_th2=7S.00%

IMlim_ T2=60.00C

IMlim_lm_th3=SO.OO%
IMlim_T3=70.000(

IMlim_T4=80.000(

IElim_T1=SO.OOO(

IElim_le_th2=7S.00%

IElim_ T2=60.000(

IElim_le_th3=SO.00%

1Elim_ T3=70.000(

IElim_T4=80.000(

[MODBUS]

MB Slave ID=247

M B_ Protoco 1=0

MB_Bitrate=7

MB_(hrFrame=O

MB_KeepAliveTime=Os

MB_KeepAliveAction=O

MB_Enable=TRUE

MB_Delay=10.00ms