You are on page 1of 4

FLUID JET ENERGY CRITERION FOR AS SEEN IN THE SPRING 2006 ISSUE OF...

CONTROL
VALVES

BY HERBERT L. MILLER, P.E.,


LAURENCE R. STRATTON,
THE AUTHORS PRESENT THE RESULTS OF
AND MARK A. HOLLERBACH TESTING DONE ON 500 PROBLEM CONTROL
VALVES WITH RETROFITTED TRIM.THEY
I and standards associated with valve
n addition to all the other guidelines
CONCLUDE THAT MAINTAINING
designand control valves in particu-
larwe should also review jet energy
MANAGEABLE ENERGY LEVELS IN THE
levels. By making sure the fluid jet FLUID JETS HELPS ENSURE GOOD
exiting from the valve trim is con-
trolled, we ensure a good control valve
CONTROL VALVE PERFORMANCE.
application. Maintaining manageable
energy levels in the fluid jets elimi-
nates what happens because of vibra- The Trim Exit Energy Criterion control valve operates without prob-
tion, erosion, cavitation, noise, and An energy approach combines the influ- lems, valve trim should be designed to
other factors that ultimately lead to a ence of fluid density with the velocity of meet an average kinetic energy criterion
poor process control valve. the jet exiting a valve trim. This is of 70 psi (4.85 bar) or lower. (Refer-
The following discussion presents defined as follows: ences 2, 3 and 4 provide more detail on
data on about 500 problem valves for how a user can make the calculation
which only the valve trim was retrofit- r V2 meaningful.)
KE =
ted. The original valve designs did not 2M The pressure drop across a valve
adequately reduce the fluid jets Where: M = 100,000 for Metric or drives the fluid though the trim. The
energy as it passed through the throt- 4,636.8 for Imperial units valves closure member will control the
tling area of the trim. New trim was KE is in bar or psi rate of flow, but not the fluids velocity
designed to control the jet energy and V is in m/s or ft/s through the trim. The only way to lower
limit energy of the fluid within cer- r is in kg/m3 or lb/ft3 the fluid velocity through the trim for
tain limits as it exited the trim. These any given driving pressure drop is to
limits were first published in 1997, The equation expresses, in the form add resistance to the trims flow path. In
Reference 1, and later included in of kinetic energy density, the energy of one valve type, shown in Figure 1, right
ISAs Practical Guides for Measure- the jets exiting the trim. This has the angle turns to the flow path provide
ment and Control, Reference 2. Oper- same units as pressure and is sometimes extra resistance until the energy dictated
ating the same valve body with the called the dynamic pressure. Since most by the outlet velocity and density is at
retrofitted trim but under the same flow through the valve trim is highly the desired level. Many valve suppliers
operating conditions eliminated the turbulent, the measurement is based on now provide similar types of trims. An
problems associated with the original the average velocity and density of the example would be concentric drilled-hole
valve trims. fluid jets exiting the trim. To ensure the cages in which the number of cages are

40 | Valve M A G A Z I N E 2006 Valve Manufacturers Association. Reprinted with permission.


F L U I D J E T E N E R G Y C R I T E R I O N

defined by fluid resistance needed to


slow the exiting jet to a desired level.

Results of Retrofits
Implementing the energy criteria on
about 140 unique valve applications
revealed some interesting data. Each
application was handled by one or more
identical control valves and because of
numerous problems, about 500 valves
were retrofitted. Data on one or more
specified operating conditions was
reviewed for each of the unique applica-
tions. Problematic symptoms expressed
by the users were broken down into cat-
egories, with each application averaging
Figure 1. Energy control trim about two major problems.
Figure 2 shows the major problems
the original valves put into service expe-
rienced with inadequate control of the
Other fluid energy exiting the valve trim. The
15.1% Controllability
21.5%
most significant issues driving cus-
Capacity
4.9%
tomers to make the retrofit changes
Stem break or were controllability, erosion, and vibra-
separation 5.3%
Erosion
tion. Some problems listed as Other
Cavitation 12.9% included frequent maintenance, galling,
5.6% plugging, and lack of vendor support.
Noise Industry design standards address the
Vibration
9.7% issues of capacity and noise, and recom-
Leakage 12.6%
12.4% mendations address cavitation. How-
ever, this retrofit study showed that
more work needs to be done to address
Figure 2.Trim energy-related valve problems Figure 3. Retrofit inlet pressure applications all the symptoms and that the key is to
control the fluid trim exit energy.
A diverse range of valve designs were
All Fluid Cases retrofit from more than 25 different
3000 200 manufacturers. Those designs included
most sizes and the common operating
pressures encountered, from 1 inch to 36
2500
inches (25 mm to 900 mm). Figure 3
Original Trim 150 illustrates the distribution of inlet pres-
Kinetic Energy, psi

2000 sures encountered in the retrofit data-


base. The minimum and maximum inlet
KE, bar

1500 100 pressures in the database range from 60


Energy Control Trim psi to 5840 psi (4 bar to 402 bar).
1000
Figure 4 shows energy of the fluid
exiting the original valve trim and the
90% 50
rank from highest to lowest level of
500 energy control trim. It also shows the
dramatic energy reduction from the
70 4.85
0 0 failed original trim to a level that
1 101 201 301 401 ensures a good control valve applica-
Cases tion. The average reduction in kinetic
energy was from 480 psi to 44 psi (33
Figure 4. Energy before and after retrofit bar to 3 bar). The maximum kinetic

2006 Valve Manufacturers Association. Reprinted with permission.


42 | Valve M A G A Z I N E
F L U I D J E T E N E R G Y C R I T E R I O N

energy was 3280 psi (226 bar), which Figures 6 and 7 present the flow
Retrofit Database
is almost 50 times the recommended cases for liquid and gas conditions,
DESIGNS % criterion. With these high energy lev- respectively. In these figures the energy
Liquid designs 64 els, it is not surprising that much dam- control trim values are shown superim-
Gas designs 36 age was occurring in the control valve posed on the energy level for the original
and associated piping. Figure 4 trim, which illustrates the magnitude of
VALVES %
includes both liquid and gas applica- reduction in the retrofitted trim energy
Liquid Valves 70 tions (see Reference 5 for additional levels for each flow case.
Gas Valves 30 detail), while Figure 5 shows the A few cases where original trim met
breakdown of liquid and gas applica- the energy criterion but the valves were
Figure 5. Breakdown of designs and valves by tions, and valves. still retrofit existed for both liquid and
fluid type
gas categories. In almost all cases, there
were other flow conditions in which
All Liquid Cases energy exceeded the criterion of 70 psi
3000 (4.85 bar).
200 There were also a few cases in which
the energy level exceeded the 70 psi
2500
(4.85 bar) criterion even after retrofit
Original Trim 150 instances in which the criterion could
2000 not be met because of valve body space
Kinetic Energy, psi

limitations. However, the judgment to

KE, bar
1500 100 proceed was made after review of the
application and significant reduction in
Energy Control Trim trim exit energy for each retrofit.
1000
The fact that a few cases existed in
50
90% which the kinetic energy exceeded the
500 criterion would suggest that 70 psi
(4.85 bar) is not a hard rule. The data
70 4.85
0 0 demonstrates some validity to this pos-
1 101 201 sibility; however, during the original
valve procurement, incremental costs
Cases to achieve the criterion were small
Figure 6. Energy before and after for the liquid cases when compared to risk. History and
experience dictate some applications
in which the rule should not be
All Gas Cases exceeded will exist under any circum-
2000 stances. These exceptions would
include applications handling mixed-
120 phase fluids and/or entrained particles.
Another significant finding was that
1500 Original Trim 100 many of the problems occurred when
Kinetic Energy, psi

valves were partially opened. When a


80 valve is partially open, fluid energies
KE, bar

1000 through the trim are high while fluid


60 energies through the rest of the valve
Energy Control Trim
body are low. This demonstrates that
40 designing larger valve bodies is not the
500
94% answer to solving the problems.
20 Figures 4, 6, and 7 show the bene-
70 4.85 fits of controlling the fluid jet energy
0 0
exiting the valve trim. Failing valves
1 11 21 31 41 51 61 71 81 91 101 111 121 131
were transformed into designs that
met the applications control needs
Cases
just by minimizing this energy to 70
Figure 7. Energy before and after for the gas cases psi (4.85 bar).
2006 Valve Manufacturers Association. Reprinted with permission.

44 | Valve M A G A Z I N E
F L U I D J E T E N E R G Y C R I T E R I O N

Conclusion become a reality until users insist that


REFERENCES:
This study showed that the very high valve suppliers look at the fluid energy 1. Miller, H. L., Stratton, L. R., Fluid Kinet-
kinetic energy levels of the original leaving the valve trim. What occurred ic Energy as a Selection Criteria for Con-
designs caused repeated failures before from retrofitting so many valves in this trol Valves, ASME Fluids Engineering
Division, Summer Meeting, Paper
the valves were finally retrofitted. How- case is strong evidence that when the FEDSM97-3464, Vancouver, British
ever, these failures were transformed energy of the trim jets is ignored, we risk Columbia, Canada, June 22-26, 1997.
into successful installations for a wide having a poor control valve application; Published in Valve World, Volume 2, Issue
3, pg. 51-57, August 1997, KCI Publish-
range of designs, applications and condi- the cost of not paying attention to the jet ing B.V., Zutphen, Netherlands.
tions, a range that would represent a sta- energy can be very high. 2. Control Valves Practical Guides for Measure-
tistically significant portion of the Valve users and specification writers ment and Control, Guy Borden, Jr. Editor,
International Society for Measurement
control valve industry. The success was have a responsibility to make the best and Control, Research Triangle Park, NC,
achieved by making only one change to decisions for procuring a control valve Chapter 12 Control Valve Applications,
the original design. That change was to that will do the job at the lowest cost. pg. 411-447, 1998.
3. Liu, Gerald, Miller, Herbert L., Stratton,
insert a trim that reduced the fluid jet Looking at the energy criterion not only Laurence R., Establishing Control Valve
energy exiting the valve trim, a trim minimizes the risk of a problem valve Trim Flow Velocity, ISA EXPO 2004,
designed with a criterion of 70 psi (4.85 that would lead to a system problem and Paper ISA04-P211, The Instrument,
Systems and Automation Society,
bar) kinetic energy density for the fluid higher total costs, it also provides a Research Triangle Park, NC, Houston,
exiting the trim. By applying this addi- means of comparing different design and Oct. 5-7, 2004.
tional design criterion to the valve trim supplier options.VM 4. Steinke, Joseph, Multi-Stage Control
Valve Analysis, ISA Calgary 2005, The
design, valves are less likely to provide Instrument, Systems and Automation
poor control, require extensive mainte- HERBERT L. MILLER, P.E. is a consultant based in
Society, Research Triangle Park, NC, Cal-
nance, and experience damage. gary, April 13-14, 2005
Rancho Santa Margarita, CA; 949.858.1877; 5. Miller, H. L., Stratton, L. R., Hollerbach,
The fact that an industry standard for hlm@ccivalve.com. LAURENCE R. STRATTON is man- M. A., The Case for a Kinetic Energy
this energy criterion does not yet exist ager,Technical Standards and Automation, and Criterion in Control Valves Part 1,
MARK A. HOLLERBACH is engineering manager for ISA EXPO 2005, Paper ISA 2005-
does not mean there shouldnt be one
Control Components Inc. (www.ccivalve.com), P133, The Instrument, Systems and
created in light of the many control valve Rancho Santa Margarita, CA. Reach Stratton at Automation Society, Research Triangle
problems encountered in the field. How- 949.888.4136; lrs@ccivalve.com. Reach Holler- Park, NC, Chicago, Oct. 25-27, 2005.
ever, an industry standard will not bach at 949.888.4137; mah@ccivalve.com.

!LL RIGHTS RESERVED 3OLUTIONS $2!' AND


##) $2!' ARE TRADEMARKS OF ##) ##) VALVES
ARE MANUFACTURED UNDER VARIOUS 5NITED 3TATES
AND INTERNATIONAL PATENTS

 ##)
 

2006 Valve Manufacturers Association. Reprinted with permission.


46 | Valve M A G A Z I N E

You might also like