Calculation Sheet

Outside condition.

Dry bulb temperature (D.B.T.) 110 F


Wet bulb temperature (W.B.T.) 85 F

Inside condition.

Dry bulb temperature (D.B.T.) {75f (+/-) 2.


Relative humidity (R.H) = 50% (+/-) 5% for general building

1- Sensible Load (QLS):

A- QS wall (Exposed) = Net area of wall (ft) U T


U= Overall heat transfer coefficient= 0.35 B.T.U/Hr.Ft2.F- according
to type of wall.
1/U = (1/ho+1/k1+ 2/k2+ 3/k3+000000 1/hi), where ho, hi
Thermal conductivity by convection.
=Thickness
k=Thermal conductivity by conduction.
H= Heat Transfer Coefficient by convection.
T= Equivalent temperature Difference (Ashrae table 3-10).

B- QS roof (Exposed) = Net area of roof (ft) U T


T= Equivalent temperature Difference (Ashrae table 3-3).
U= Overall heat transfer coefficient= 0.16 B.T.U/Hr.Ft2.F- according
to type of roof.

C- QS Glass
- QS radiation = Area of glass (ft) S.C M.S.H.G.F C.L.F
S.C: Shading coefficient.
According to ASHRAE tables.

Without With
Single
Shading Shading
U 1.04 0.81
S.C 1 0.64

1
Without With
Double
Shading Shading
U 0.65 0.58
S.C 0.49 0.42

M.S.H.G.F: Maximum Solar Heat Gain Factor


(From table 3-25).
C.L.F: Cooling Load Factor.
Interior Shading (from table 14).
Without interior Shading (from table 13).

- QS conduction = Area of glass (ft) U T


T= Equivalent temperature Difference (From table 3-23).

D- QS partition = Area of partition U T


T= Different in temperature between room temperature and shaded
partition.

E- QS light = Total watt 3.41 = ( ) B.T.U/HR

Area Watt/m
Office 20 - 25

F- QS equipment: Depend on the kind of place

G- QS infiltration = C.F.M 1.08 T


T = To TR
C.F.M = 1/4 one air change/hr.
1.08= 0.075 0.24 60.

H- QS people = No of person Qs/one person.


Qs/one person = According to type of building from ASHRE table 18.

I- QS Ventilation= Total C.F.M 1.08 T


Total C.F.M (fresh air) = No of person Fresh air / one person
Fresh air /one person = According to type of building from ASHRAE
table.

2
T = To TR

QS Room Total (QSR) = QS wall + QS roof+ QS glass+ QS partition+


QS people+ QS equip+ QS infiltration+ QS light

2) Latent Load(QLR):
A- QL People= No of person QL/one person.
QL/one person =According to type of building from ASHRE table 18.

B- QL infiltration= C.F.M W 4840


C.F.M = 1/4 one air change/hr
W = (W W R).
4840 Factor from ASHRAE.

C- QL equip = Depend on the kind of place.

QL Room Total = QL People+ QL equip+ QL infiltration


3) Ventilation Load(QL Ventilation):

A- QL ventilation = Total C.F.M 4840 W


Total C.F.M (fresh air) = No of person Fresh air / one person.
Fresh air /one person =According to type of building from
ASHRAE table.
W = (W W R)

B- QS ventilation= C.F.M 1.08 T


T = To TR
Total C.F.M (fresh air) = No of person Fresh air / one person.
Fresh air /one person =According to type of building from
ASHRAE table.
1.08= 0.075 0.24 60.

3
QSR
Room sensibl heat factor (R.S.H.F) =
According to the type of building QSR + QLR

QST
A.S.H.F =
QST + QLT

QS Room
T.C.F.M Room =
1.08 (T Room TS)

Total Load
QSG = (QSR + safety factor (10%)) + QS ventilation.
QLG = (QLR + safety factor (5%)) + QL ventilation.

Grand Total load (G.T.L) = QSG + QLG (B.T.U/HR)

(G.T.L) B.T.U/HR
Tonage =
12000