Siemens AG 2007

Distributed I/O
SIMATIC ET 200

5/2 ET 200S
5/2 IM 151-3PN interface module
5/6 Digital electronic modules
5/15 SIPLUS digital electronic modules
(extended temperature range)
5/16 Analog electronic modules
5/29 ET 200S Software
5/29 Motor Starter ES
5/31 ET 200pro
5/31 IM 154-8 PN/DP CPU interface module
5/35 RFID Systems
5/35 SIMATIC RF180C
5/38 Motor Starters
and Frequency Converters
5/38 ET 200pro motor starters
Standard and High-Feature
5/43 ET 200pro isolator modules
5/45 Safety modules
5/48 Accessories for ET 200pro motor starters
5/51 ET 200pro FC Frequency Converter
5/55 ET 200M
5/55 IM 153-4 PN

Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
IM 151-3PN interface module

Overview
Interface module for linking the ET 200S to PROFINET
Handles all data exchange with the PROFIBUS I/O Controller
3 versions:
- IM 151-3 PN STANDARD
- IM 151-3 PN HIGH FEATURE and IM 151-3 PN FO :
supports, in contrast to the STANDARD version, the opera-
tion of PROFIsafe F modules
with integrated 2-port switch for line topology
Note:
Micro Memory Card required for operation.

Technical specifications
5 6ES7 151-3AA22-0AB0 6ES7 151-3BA22-0AB0 6ES7 151-3BB22-0AB0
Supply voltages
Supply voltage of electronics 1L+
Rated value (DC) 24 V 24 V 24 V
reverse polarity protection Yes Yes Yes
Voltages and currents
Mains/voltage failure jumpering, 20 ms 20 ms 20 ms
min.
Current consumption
from supply voltage 1L+, max. 250 mA 250 mA 200 mA
Power loss, typ. 2.5 W 2.5 W 3W
Address area
Adressing volume
Outputs 256 Byte 256 Byte 256 Byte
Inputs 256 Byte 256 Byte 256 Byte
Connection point
RJ45 Yes Yes No
Protocols
PROFINET IO Yes Yes Yes
PROFINET IO
Transmission speed, max. 100 Mbit/s 100 Mbit/s 100 Mbit/s
automatic detection of transmission Yes Yes Yes
speed
Isochronous mode
Isochronouos mode No No No

5/2 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
IM 151-3PN interface module

Technical specifications (continued)


6ES7 151-3AA22-0AB0 6ES7 151-3BA22-0AB0 6ES7 151-3BB22-0AB0
Status information/alarms/
diagnostics
Alarms
Alarms Yes Yes Yes
Diagnoses
Diagnostic functions Yes Yes Yes
Diagnostics indication LED
Bus error BF (red) Yes Yes Yes
Collective error SF (red) Yes Yes Yes
Monitoring 24 V voltage supply ON Yes Yes Yes
(green)
Connection to network LINK Yes Yes Yes
(green)
Transmit/receive RX/TX (yellow) Yes Yes Yes
Isolation
between backplane bus and elec-
tronics
No No No
5
between Ethernet and electronics Yes Yes Yes
between supply voltage and elec- No No No
tronics
General information
Vendor identification (VendorID) 002AH 002AH 002AH
Device identifier (DeviceID) 0301 0301H 0301H
Dimensions
Width 60 mm 60 mm 60 mm
Height 119.5 mm 119.5 mm 119.5 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 120 g 135 g 150 g

Siemens IK PI News July 2007 5/3


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
IM 151-3PN interface module

Ordering data Order No. Order No.


IM 151-3 PN interface module 6ES7 151-3AA22-0AB0 Termination Kit 6GK1 900-0NL00-0AA0
For ET 200S; transfer rates up to SC RJ POF Plug
100 Mbit/s; data volume depends Assembly case for on-site assem-
on the number of modules bly of SC RJ plugs consisting of
inserted, up to 63 modules can stripping tool, buffer stripping
be connected, bus connection tool, kevlar cutter, fiber breaking
through RJ45 tool, microscope

IM 151-3 PN PROFINET High 6ES7 151-3BA22-0AB0 Industrial Ethernet 6GK1 900-0NB00-0AC0


Feature interface module SC RJ PCF Plug
Screw-in plug for on-site assem-
for ET 200S; transfer rate up to bly to PCF fiber optic cable
100 Mbit/s; max. 63 modules up (1 pack = 10 units)
to 2 m wide can be connected;
bus connection via RJ45, Industrial Ethernet 6GK1 901-1GA00
incl. terminating module Fast Connect stripping tool
MMC 64 KB 1)
IM 151-3 FO interface module
for ET 200S; with 2 PROFINET
6ES7 151-3BB22-0AB0 For storing the device name
6ES7 953-8LF20-0AA0

FO-interfaces and integrated 2-


MMC 128 KB 1) 6ES7 953-8LG11-0AA0
port switch, max. 63 modules up
to 2 m wide can be connected, For storing the device name
incl. terminating module MMC 512 KB 1) 6ES7 953-8LJ20-0AA0
Accessories For storing the device name
5 Industrial Ethernet FC RJ45
Plug 90
MMC 2 MB 1) 6ES7 953-8LL20-0AA0
For storing the device name
RJ45 plug connector for Industrial and/or firmware update
Ethernet with a rugged metal
housing and integrated insulation MMC 4 MB 1) 6ES7 953-8LM20-0AA0
displacement contacts for con- For storing the device name
necting Industrial Ethernet FC and/or firmware update
installation cables; with 90 cable
outlet MMC 8 MB 1) 6ES7 953-8LP20-0AA0
For storing the device name
1 unit 6GK1 901-1BB20-2AA0 and/or firmware update
10 units 6GK1 901-1BB20-2AB0 ET 200S distributed I/O are available on the Internet
50 units 6GK1 901-1BB20-2AE0 system manuals as PDF files:
http://www.siemens.de/
Industrial Ethernet FastConnect simatic-doku
installation cables
SIMATIC Manual Collection 6ES7 998-8XC01-8YE0
Fast Connect standard cable 6XV1 840-2AH10
Electronic manuals on DVD,
Fast Connect trailing cable 6XV1 840-3AH10 multi-language:
Fast Connect marine cable 6XV1 840-4AH10 S7-200, TD 200, S7-300, M7-300,
C7, S7-400, M7-400, STEP 7,
Termination Kits Engineering Tools, Runtime Soft-
ware, SIMATIC DP (Distributed
SC RJ POF Plug 6GK1 900-0ML00-0AA0 I/O), SIMATIC HMI (Human
Assembly case for on-site assem- Machine Interface), SIMATIC NET
bly of SC RJ plugs consisting of (Industrial Communication)
stripping tool, kevlar cutter, micro-
scope, abrasive paper, grinding SIMATIC Manual Collection 6ES7 998-8XC01-8YE2
support Update service for 1 year
IE SC RJ POF Plug 6GK1 900-0MB00-0AC0 Scope of delivery: Current DVD
Screw-in plug for on-site assem- "S7 Manual Collection" and the
bly to POF fiber optic cable three subsequent updates
(1 pack = 20 units)
IE SC RJ Refill Set POF 6GK1 900-0MN00-0AA0
Refill set for Termination Kit SC RJ
POF Plug, consisting of abrasive
paper and grinding plate
(set of 5)
1) For operating the IM 151-3, an MMC is essential

5/4 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
IM 151-3PN interface module

Ordering data Order No. Order No.


Label sheets DIN A4 (10 units) Industrial Ethernet Switches
SCALANCE X-200IRT
Each sheet contains 60 label
strips for peripheral modules and Managed Industrial Ethernet
20 label strips for interface mod- Switches; Isochronous Real-Time,
ules LED diagnostics, error signaling
contact with SET button, redun-
petrol 6ES7 193-4BH00-0AA0 dant voltage supply SCALANCE
red 6ES7 193-4BD00-0AA0 X202-2P IRT; 2 x 10/100 Mbit/s
RJ45 ports, 2 x 100 Mbit/s
yellow 6ES7 193-4BB00-0AA0 POF/PCF SC RJ
light beige 6ES7 193-4BA00-0AA0 SCALANCE X202-2P IRT; 6GK5 202-2BH00-2BA3
Terminating module 6ES7 193-4JA00-0AA0 2 x 10/100 Mbit/s RJ45 ports,
2 x 100 Mbit/s POF/PCF SC RJ
as spare part for ET 200S
SCALANCE X201-3P IRT; 6GK5 201-3BH00-2BA3
DIN rail 35 mm 1 x 10/100 Mbit/s RJ45 ports, 3 x
100 Mbit/s POF/PCF SC RJ
Length: 483 mm 6ES5 710-8MA11
for 19'' cabinets SCALANCE X200-4P IRT; 6GK5 200-4AH00-2BA3
4 x 100 Mbit/s POF/PCF SC RJ
Length: 530 mm 6ES5 710-8MA21
for 600 mm cabinets
Length: 830 mm 6ES5 710-8MA31
for 900 mm cabinets
Length: 2 m 6ES5 710-8MA41
5

Siemens IK PI News July 2007 5/5


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Overview
2, 4 and 8-channel
ET 200S
digital inputs and outputs for the

Can be plugged onto TM-E terminal modules with automatic


coding.
High-feature versions for enhanced plant availability, addi-
tional functions and comprehensive diagnostics
Hot swapping of modules possible

Design
5 Possible combinations of the TM-E terminal modules and digital modules
Electronic modules TM-E terminal modules for electronic modules
Screw-type terminal 15S26-A1 15S24-A1 15S24-01 15S23-01 15S24-AT 30S44-01 30S46-A1
Order No. 6ES7 193 4CA40-0AA0 4CA20-0AA0 4CB20-0AA0 4CB00-0AA0 4CL20-0AA0 4CG20-0AA0 4CF40-0AA0
Spring-loaded terminal 15C26-A1 15C24-A1 15C24-01 15C23-01 15C24-AT 30C44-01 30C46-A1
Order No. 6ES7 193 4CA50-0AA0 4CA30-0AA0 4CB30-0AA0 4CB10-0AA0 4CL30-0AA0 4CG30-0AA0 4CF50-0AA0
FastConnect 15N26-A1 15N24-A1 15N24-01 15N23-01
Order No. 6ES7 193 4CA80-0AA0 4CA70-0AA0 4CB70-0AA0 4CB60-0AA0
2DI 24 V DC ST
2DI 24 V DC HF
4DI 24 V DC ST
4DI 24 V DC HF
4DI 24 V DC /SRC ST
4DI 24 to 48 V UC HF
4 DI NAMUR
8 DI 24 V DC, ST
2 DI 120 V AC ST
2 DI 230 V AC ST
2 DO 24 V DC/0.5 A ST
2 DO 24 V DC/0.5 A HF
4 DO 24 V DC/0.5 A ST
8 DO 24 V DC/0.5 A ST
2 DO 24 V DC/2 A ST
2 DO 24 V DC/2 A HF
4 DO 24 V DC/2 A ST
2 DO 24 230 V AC/2 A
2RO NO
24 to 120 V DC/5 A
24 to 230 V AC/5 A
2RO NO/NC
24 to 48 V DC/5 A
24 to 230 V AC/5 A

5/6 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications
6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131-
4BB01-0AA0 4BB01-0AB0 4BD01-0AA0 4BD01-0AB0 4BD51-0AA0 4BF00-0AA0
Supply voltages
Rated value
DC 24 V Yes; from power Yes; from power Yes; from power Yes; from power Yes; from power Yes
module module module module module
Reverse polarity protection Yes Yes Yes Yes Yes Yes
Current consumption
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA 10 mA
from supply voltage L+, max. dependent on
encoder
Power loss, typ. 0.4 W 0.4 W 0.7 W 0.7 W 0.7 W 1.2 W
Address area
Address space per module
with packing 2 Bit 2 Bit 4 Bit 4 Bit 4 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes;
TWE = 3000 s 5
Digital inputs
Number of digital inputs 2 2 4 4 4 8
Number of simultanneously 8
controllable inputs
Cable length
cable length, shielded, max. 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m
Cable length unshielded, max. 600 m 600 m 600 m 600 m 600 m 600 m
Input characteristic curve Yes Yes Yes Yes Yes Yes; 2-wire sen-
to IEC 1131, Typ 1 sors connectable
Input voltage
Rated value, DC 24 V 24 V 24 V 24 V 24 V 24 V
for signal "0" -30 to 5 V -30 to 5 V -30 to 5 V -30 to 5 V 30 to -5 V -30 to 5 V
for signal "1" 15 to 30 V 11 to 30 V 15 to 30 V 11 to 30 V -15 to -30 V 15 to 30 V
Input current
for signal "1", typ. 7 mA; at 24 V 8 mA 7 mA; at 24 V 8 mA 7 mA; at 24 V 5 mA
Input delay
(for rated value of input voltage)
for standard inputs
- programmable No Yes; 0.1 / 0.5 / 3 / No Yes; 0.1 / 0.5 / 3 / No No
15 ms 15 ms
- at " to "1", min. 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 2 ms
typically 3 ms 14.85 typically 3 ms 14.85 typically 3 ms
- at "0" to "1", max. 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 4.5 ms
15.15 15.15
- at "1" to "0", min. 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 2 ms
typically 3 ms 14.85 typically 3 ms 14.85 typically 3 ms
- at "1" to "0", max. 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 4.5 ms
15.15 15.15
Encoder supply
Number of outputs 0; no encoder
supply
Output voltage min. L+ (-0.5 V), min. L+ (-0.5 V), min. L+ (-0.5 V), min. L+ (-0.5 V), max. M + 0.5 V,
under load under load under load under load under load
Output current, rated value 500 mA 500 mA 500 mA 500 mA 500 mA
Output current, permissible range 0 to 500 mA 0 to 500 mA 0 to 500 mA 0 to 500 mA 0 to 500 mA
Short-circuit protection Yes; electronic Yes; electronic
Encoder
Connectable encoders
2-wire BEROS Yes Yes Yes Yes Yes Yes
permissible quiescent current 1.5 mA 1.5 mA 1.5 mA 1.5 mA 1.5 mA 1.5 mA
(2-wire BEROS), max.

Siemens IK PI News July 2007 5/7


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131-
4BB01-0AA0 4BB01-0AB0 4BD01-0AA0 4BD01-0AB0 4BD51-0AA0 4BF00-0AA0
Parameter
Remark 1 byte 3 bytes 1 byte 3 bytes 1 byte 3-byte parameter
(not accessible
for the user)
Diagnosis: short circuit Disable/enable Disable/enable
Status information/alarms/
diagnostics
Diagnoses
Diagnostic functions No Yes No Yes No No
Short circuit Yes; Short-cir- Yes; Short-cir-
cuit to M, mod- cuit to M, mod-
ule by module ule by module
Diagnostics indication LED
Collective error SF (red) No Yes No Yes No
Status indicator digital input Yes; per channel Yes; per channel Yes; per channel Yes; per channel Yes; per channel Yes
(green)
Isolation
5 Isolation checked with 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC
Isolation
Galvanic isolation, digital inputs
between the channels No No No No No No
between the channels and the Yes Yes Yes Yes Yes Yes
backplane bus
Permissible potential difference
between different circuits 75 V DC/ 75 V DC/ 75 V DC/ 75 V DC/ 75 V DC/ 75 V DC/
60 V AC 60 V AC 60 V AC 60 V AC 60 V AC 60 V AC
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 35 g 35 g 35 g 35 g 35 g 35 g

6ES7 131-4CD00-0AB0 6ES7 131-4EB00-0AB0 6ES7 131-4FB00-0AB0 6ES7 131-4RD00-0AB0


Supply voltages
Rated value
DC 24 V Yes; from power module Yes
permissible range, 24 V
lower limit (DC)
permissible range, 48 V
upper limit (DC)
AC 24 V Yes
AC 120 V Yes; from power module
AC 230 V Yes
permissible range, 24 V
lower limit (AC)
permissible range, 48 V
upper limit (AC)
Reverse polarity protection Yes; AC or DC automatic
Current consumption
from backplane bus 3.3 V DC, max. 10 mA 6 mA 6 mA
Power loss, typ. 0.7 W 0.5 W 0.7 W 1.6 W
Address area
Address space per module
with packing 4 Bit 2 Bit 2 Bit 4 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes No No

5/8 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 131-4CD00-0AB0 6ES7 131-4EB00-0AB0 6ES7 131-4FB00-0AB0 6ES7 131-4RD00-0AB0
Digital inputs
Number of digital inputs 4 2 2
Number of NAMUR inputs 4
Number of simultanneously 4
controllable inputs
Cable length
cable length, shielded, max. 1,000 m 1,000 m 1,000 m 200 m
Cable length unshielded, max. 600 m 600 m 600 m
Parallel switching of inputs No
Input characteristic curve Yes Yes Yes
to IEC 1131, Typ 1
Input voltage
Rated value, AC 120 V 230 V
Rated value, UC 24 V; 24 to 48 V UC
for signal "0" -6 to 6 V DC, 0 to 5 V AC 0 to 20 V AC 0 to 40 V AC
for signal "1" -15 to -57.6 V DC,
15 to 57.6 V DC,
79 to 132 V AC 164 to 264 V AC 5
15 to 48 V AC
Frequency range 47 to 63 Hz 47 to 63 Hz 47 to 63 Hz
Input current
for signal "1", typ. 10 mA; 4 to 10 mA 3 mA; 3 to 9 mA 5 mA; 5 to 15 mA
for 10 k switched contact
- for signal "0" 0.35 mA to 1.2 mA
- for signal "1" 2.1 mA to 7 mA
for unswitched contact
- for signal "0", max. 0.5 mA
(permissible quiescent current)
- for signal "1" typ. 8 mA
for NAMUR encoders
- for signal "0" 0.35 mA to 1.2 mA
- for signal "1" 2.1 mA to 7 mA
Input delay
(for rated value of input voltage)
for standard inputs
- at " to "1", min. 15 ms 15 ms
- at "0" to "1", max. 15 ms 4.6 s
- at "1" to "0", min. 25 ms 45 ms
- at "1" to "0", max. 15 ms 4.6 s
Encoder connection
Fixed current limitation for wire 18 k; Rated voltage 24 V
break monitoring, min. (15 V to 35 V);
rated voltage 48 V
(30 V to 60 V): 39 kohms
Encoder supply
Number of outputs 1
Output voltage min. L+ (-0.5 V), min. 8.2 V, loaded
under load
Output current, rated value 500 mA 45 mA
Output current, permissible range 0 to 500 mA
Short-circuit protection Yes; per module Yes; electronic
Encoder
Connectable encoders
2-wire BEROS Yes No No
permissible quiescent current (2- 2 mA; (0.5 to 2 mA), a 1 mA 2 mA
wire BEROS), max. minimum load current is
necessary in the event of
a wire break.
Parameter
Remark 3 bytes 3 bytes 12 bytes

Siemens IK PI News July 2007 5/9


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 131-4CD00-0AB0 6ES7 131-4EB00-0AB0 6ES7 131-4FB00-0AB0 6ES7 131-4RD00-0AB0
Status information/alarms/
diagnostics
Alarms
Diagnostic alarm Yes; can be set
Process alarm No
Diagnoses
Diagnostic functions Yes; parameterizable No No Yes; Diagnostic alarm
Diagnostic information readable Yes
Short circuit No No
Diagnostics indication LED
Collective error SF (red) Yes Yes
Status indicator digital input Yes; per channel Yes; per channel Yes; per channel Yes; per channel
(green)
Isolation
Isolation checked with 2500 V DC 2500 V DC 4000 V DC 500 V DC
Isolation
5 Galvanic isolation, digital inputs
between the channels No No No No
between the channels and the Yes Yes Yes Yes
backplane bus
between the channels and the Yes
load voltage L+
Permissible potential difference
between different circuits 75 V DC/ 60 V AC 75 V DC/ 60 V AC
between M internally and the inputs 1500 V AC 1500 V AC
Dimensions
Width 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 35 g 31 g 31 g 35 g

6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BB01-0AB0 4BB01-0AA0 4BB31-0AB0 4BB31-0AA0 4BD01-0AA0 4BF00-0AA0
Voltages and currents
Reverse voltage protection Yes; when using Yes; when using Yes; when using Yes; when using Yes; when using Yes
the same load the same load the same load the same load the same load
voltage as on the voltage as on the voltage as on the voltage as on the voltage as on the
power module power module power module power module power module
Load voltage L+
Rated value (DC) 24 V; From 24 V; From 24 V; From 24 V; From 24 V; From 24 V
power module power module power module power module power module
reverse polarity protection Yes; polarity Yes; polarity Yes; polarity Yes; polarity Yes; polarity Yes
reversal can lead reversal can lead reversal can lead reversal can lead reversal can lead
to the digital out- to the digital out- to the digital out- to the digital out- to the digital out-
puts being con- puts being con- puts being con- puts being con- puts being con-
nected through nected through nected through nected through nected through
Current consumption
from load voltage L+ (without load), 5 mA; 5 mA; 5 mA; 5 mA; 5 mA; 5 mA;
max. Per channel per module per channel Per channel Per channel Per channel
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA 10 mA 10 mA;
max. 15 mA at
Power loss, typ. 0.4 W 0.4 W 1.4 W 1.4 W 0.8 W 1.5 W
Address area
Address space per module
with packing 2 Bit 2 Bit 2 Bit 2 Bit 4 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes No Yes No Yes Yes; jitter incum-
bered < 100 s

5/10 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BB01-0AB0 4BB01-0AA0 4BB31-0AB0 4BB31-0AA0 4BD01-0AA0 4BF00-0AA0
Digital inputs
Cable length
cable length, shielded, max. 1,000 m 1,000 m
Cable length unshielded, max. 600 m 600 m
Digital outputs
Number of digital outputs 2 2 2 2 4 8
cable length, shielded, max. 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m
Cable length unshielded, max. 600 m 600 m 600 m 600 m 600 m
Short-circuit protection Yes; Yes; Yes; Yes; Yes; Yes;
of the output per channel per channel per channel per channel per channel per channel
Response threshold, typ. 1.5 A 0.7 to 1.8 A 4A 2.8 to 7.2 A 0.7 to 1.5 A o.k.
Limitation of inductive shutdown -55 to -60 V, -55 to -60 V, -55 to -60 V, -55 to -60 V, -55 to -60 V, o.k.
voltage to typically L+( ) typically L+( ) typically L+( ) typically L+( ) L+( )
Lamp load, max. 2.5 W 5W 5W 10 W 5W 5W
Controlling a digital input
Output voltage
Yes Yes Yes Yes Yes Yes
5
for signal "1", min. L+ (-1.0 V) L+ (-1.0 V) L+ (-1.0 V) L+ (-1.0 V) L+ (-1.0 V) o.k.
Output current
for signal "1" rated value 0.5 A 0.5 A 2A 2A 0.5 A 0.5 A
for signal "1" permissible range 7 mA 7 mA 7 mA 7 mA 7 mA 7 mA
for 0 to 60 C, min.
for signal "1" permissible range 600 mA 600 mA 2.4 A 2.4 A 600 mA 600 mA
for 0 to 60 C, max.
for signal "0" residual current, max. 0.3 mA 0.3 mA 0.5 mA 0.5 mA 0.3 mA 0.3 mA
Output delay with resistive load
"0" to "1", max. 100 s 200 s 100 s 200 s 100 s 300 s
"1" to "0", max. 400 s 1.3 ms 400 s 1.3 ms 300 s 600 s
Parallel switching of 2 outputs
for increased power No No No No No No
for redundant control of a load Yes; Per module Yes; Per module Yes; Per module Yes; Per module Yes; Per module Yes
Switching frequency
with resistive load, max. 100 Hz 100 Hz 100 Hz 100 Hz 100 Hz 100 Hz
with inductive load, max. 2 Hz 2 Hz 2 Hz; 0.5 H 2 Hz; 0.5 H 2 Hz 2 Hz
on lamp load, max. 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz
Aggregate current of the outputs
(per group)
horizontal installation
up to 60 C, max. 1A 1A 4A 4A 2A 4A
Load impedance range
lower limit 48 48 12 12 48 48
upper limit 3,400 3,400 3,400 3,400 3,400 3,400
Parameter
Remark 3 bytes 1 byte 3 bytes 1 byte 1 byte 3-byte parame-
ter (not accessi-
ble for the user)
Diagnosis: wire break disable/enable disable/enable
Diagnosis: short circuit Disable/enable Disable/enable
Behavior on CPU/Master STOP, Substitute a Substitute a
channel-wise value / keep last value / keep last
value value

Siemens IK PI News July 2007 5/11


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BB01-0AB0 4BB01-0AA0 4BB31-0AB0 4BB31-0AA0 4BD01-0AA0 4BF00-0AA0
Status information/alarms/
diagnostics
Substitute values connectable Yes; 0/1 Yes; 0/1
Diagnoses
Diagnostic functions Yes; No Yes; No No No
can be read out can be read out
Wire break Yes; channel by Yes; channel by
channel channel
Short circuit Yes; channel by Yes; channel by
channel channel
Diagnostics indication LED
Collective error SF (red) Yes Yes
Status indicator digital output Yes Yes Yes Yes Yes Yes
(green)
Isolation
Isolation checked with 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC

5 Isolation
Isolation, digital outputs
between the channels No No No No No No
between the channels and the Yes Yes Yes Yes Yes Yes
backplane bus
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 40 g 40 g 40 g 40 g 40 g

6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-


4BD32-0AA0 4FB00-0AB0 4HB01-0AB0 4HB10-0AB0
Voltages and currents
Reverse voltage protection Yes; When using the same Yes; when using the same
voltage source as voltage source as on the
power module
Load voltage L+
Rated value (DC) 24 V; From power module 24 V; From power module 24 V; From power module
reverse polarity protection Yes Yes Yes Yes
Load voltage L1
Rated value (AC) 24.23 V;
from power module
permissible range, 24 V
lower limit (AC)
permissible range, 230 V
upper limit (AC)
permissible frequency range, 47 Hz
lower limit
permissible frequency range, 63 Hz
upper limit
Current consumption
from load voltage L+ (without load), 10 mA; Per channel 30 mA 30 mA 30 mA
max.
from load voltage L1 (without load), 15 mA;
max. per channel
from backplane bus 3.3 V DC, max. 10 mA 18 mA 10 mA 10 mA
Power loss, typ. 1.6 W 4W 0.6 W 0.6 W
Address area
Address space per module
with packing 4 Bit 2 Bit 2 Bit 2 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes No No No

5/12 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BD32-0AA0 4FB00-0AB0 4HB01-0AB0 4HB10-0AB0
Digital outputs
Number of digital outputs 4 2 2 2
cable length, shielded, max. 1,000 m 1,000 m 1,000 m 1,000 m
Cable length unshielded, max. 600 m 600 m 600 m 600 m
Size of motor starter, max. up to 40 C size
acc. to NEMA: 5;
up to 60 C size
acc. to NEMA: 4
Short-circuit protection Yes; per channel Yes; No; external fusing, max. No; external fusing, max.
of the output via fuse in power module 6 A quick-acting 6 A quick-acting
Response threshold, typ. 2.8 to 7.2 A
Limitation of inductive shutdown Typically L+ (-55 to -60 V) -55 to -60 V no no
voltage to
Lamp load, max. 10 W 100 W
Zero-crossing switch Yes; max. 25 V
Controlling a digital input
Output voltage
Yes Yes; possible Yes Yes
5
for signal "1", min. L+ (-1.0 V) L - 1.5 V
Output current
for signal "1" rated value 2A 2A
for signal "1" permissible range 7 mA 0.1 mA
for 0 to 60 C, min.
for signal "1" permissible range 2.4 A 2.2 A
for 0 to 60 C, max.
for signal "1" minimum load current 8 mA 8 mA
for signal "0" residual current, max. 0.5 mA 3 mA
Output delay with resistive load
"0" to "1", max. 50 s; Typically 45s 15 ms
"1" to "0", max. 120 s; Typically 90s 15 ms
Parallel switching of 2 outputs
for increased power No No No No
for redundant control of a load Yes; Per module Yes; Per module No No
Switching frequency
with resistive load, max. 1,000 Hz 10 Hz 2 Hz 2 Hz
with inductive load, max. 2 Hz; At 0.5H 0.5 Hz 0.5 Hz 0.5 Hz
on lamp load, max. 10 Hz 1 Hz 2 Hz 2 Hz
Aggregate current of the outputs
(per group)
vertical installation
- up to 40 C, max. 4 A;
At 55C and 24VDC
horizontal installation
up to 40 C, max. 2A
up to 50 C, max. 1.5 A
up to 60 C, max. 4A 1A
Load impedance range
lower limit 12
upper limit 3,400
Relay outputs
Switching capacity of the contacts
Thermal continuous current, max. 5A 5A
Parameter
Remark 1 byte 3 bytes 3 bytes 3 bytes
Behavior on CPU/Master STOP, Substitute a value / keep Substitute a value / keep
channel-wise last value last value

Siemens IK PI News July 2007 5/13


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Digital electronic modules

Technical specifications (continued)


6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BD32-0AA0 4FB00-0AB0 4HB01-0AB0 4HB10-0AB0
Status information/alarms/
diagnostics
Substitute values connectable Yes; 0/1 Yes; 0/1 Yes; 0/1
Diagnoses
Diagnostic functions No No No No
Diagnostics indication LED
Status indicator digital output Yes Yes Yes Yes
(green)
Isolation
Isolation checked with 500V DC 2500 V DC
tested with
Channels against backplane bus 1500 V AC 2500 V DC
and load voltage L+
Load voltage L+ against back- 500 V DC 500 V DC
plane bus
Isolation
5 Isolation, digital outputs
between the channels No No Yes Yes
between the channels and the Yes Yes Yes Yes
backplane bus
between the channels and the Yes Yes
load voltage L+
Dimensions
Width 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 37 g 50 g 50 g

Ordering data Order No. Order No.


Digital input modules Digital output modules
Ordering unit 5 items Ordering unit 5 items
2 DI 24 V DC Standard 6ES7 131-4BB01-0AA0 2 DO 24 V DC/0.5 A Standard 6ES7 132-4BB01-0AA0
2 DI 24 V DC High Feature 6ES7 131-4BB01-0AB0 2 DO 24 V DC/0.5 A 6ES7 132-4BB01-0AB0
High Feature
4 DI 24 V DC Standard 6ES7 131-4BD01-0AA0
2 DO 24 V DC/2 A Standard 6ES7 132-4BB31-0AA0
4 DI 24 V DC High Feature 6ES7 131-4BD01-0AB0
2 DO 24 V DC/2 A High Feature 6ES7 132-4BB31-0AB0
2 DI 120 V AC 6ES7 131-4EB00-0AB0
4 DO 24 V DC/0.5 A Standard 6ES7 132-4BD01-0AA0
2 DI 230 V AC 6ES7 131-4FB00-0AB0
4 DI 24 to 48 V UC 6ES7 131-4CD00-0AB0
4 DO 24 V DC/2 A Standard 6ES7 132-4BD32-0AA0
2 DO 24 to 230 V AC/1 A 6ES7 132-4FB01-0AB0
4 DI 24 V DC SOURCE INPUT 6ES7 131-4BD51-0AA0
2 DO 24 V DC to 230 V AC/5 A 6ES7 132-4HB01-0AB0
Ordering unit 1 item relay, NO contact
4 DI 24 V DC NAMUR 6ES7 131-4RD00-0AB0 2 DO 24 to 48 V DC to 230 V AC/ 6ES7 132-4HB10-0AB0
8 DI 24 V DC Standard 6ES7 131-4BF00-0AA0 5 A relay, changeover contact
Ordering unit 1 item
8 DO 24 V DC/0.5 A Standard 6ES7 132-4BF00-0AA0
Accessories
Label sheets DIN A4 (10 pieces)
Each sheet contains 60 label strips
for peripheral modules and 20
label strips for interface modules
petrol 6ES7 193-4BH00-0AA0
red 6ES7 193-4BD00-0AA0
yellow 6ES7 193-4BB00-0AA0
light beige 6ES7 193-4BA00-0AA0

5/14 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
SIPLUS digital electronic modules
(extended temperature range)

Overview
2, 4 and 8-channel digital inputs and outputs for the
ET 200S
Can be plugged onto TM-E terminal modules with automatic
coding.
High-feature versions for enhanced plant availability, additio-
nal functions and comprehensive diagnostics
Hot swapping of modules possible

SIPLUS digital electronic module


4 DI 24 V DC standard
SIPLUS digital electronic module
4 DO 24 V DC/0.5 A High Feature
SIPLUS digital electronic module
4 DO 24 V DC/0.5 A Standard 5
Order No. 6AG1 131-4BD01-2AA0 6AG1 132-4BB01-2AB0 6AG1 132-4BD01-2AA0
Order No. based on 6ES7 131-4BD01-0AA0 6ES7 132-4BB01-0AB0 6ES7 132-4BD01-0AA0
Ambient temperature range -25 +60 C; -25 +60 C; -25 +60 C;
condensation permissible condensation permissible condensation permissible
Ambient conditions Suitable for extraordinary medial Suitable for extraordinary medial Suitable for extraordinary medial
load (for example by chloric and load (for example by chloric and load (for example by chloric and
sulphuric atmospheres). sulphuric atmospheres). sulphuric atmospheres).
Technical specifications The technical data are identical The technical data are identical The technical data are identical
with the technical data of the based with the technical data of the based with the technical data of the based
on modules. on modules. on modules.

Ordering data Order No.


SIPLUS digital input module
(extended temperature range
and medial load)
Ordering unit 5 items
4 DI 24 V DC Standard 6AG1 131-4BD01-2AA0
SIPLUS digital output modules
(extended temperature range
and medial load)
Ordering unit 5 items
2 DO 24 V DC/0.5 A 6AG1 132-4BB01-2AB0
High Feature
4 DO 24 V DC/0.5 A Standard 6AG1 132-4BD01-2AA0
Accessories
Label sheets DIN A4
(10 pieces)
Label sheets DIN A4 (10 pieces)
Each sheet contains 60 label
strips for peripheral modules
and 20 label strips for interface
modules
petrol 6ES7 193-4BH00-0AA0
red 6ES7 193-4BD00-0AA0
yellow 6ES7 193-4BB00-0AA0
light beige 6ES7 193-4BA00-0AA0

Siemens IK PI News July 2007 5/15


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Overview
Analog inputs and outputs for the ET 200S
Can be plugged onto TM-E terminal modules with automatic
coding
High-feature versions with enhanced performance, precision
and resolution
Hot swapping of modules possible
Note:
Consult the configuring guide for selection of the appropriate
TM-E terminal modules.

Design
5 Possible combinations of the TM-E terminal modules and analog modules
Electronic modules Terminal modules TM-E for electronic modules
Screw-type terminal 15S26-A1 15S24-A1 15S24-01 15S23-01 15S24-AT 30S44-01 30S46-A1
Order No. 6ES7 193- 4CA40-0AA0 4CA20-0AA0 4CB20-0AA0 4CB00-0AA0 4CL20-0AA0 4CG20-0AA0 4CF40-0AA0
Spring-loaded terminal 15C26-A1 15C24-A1 15C24-01 15C23-01 15C24-AT 30C44-01 30C46-A1
Order No. 6ES7 193- 4CA50-0AA0 4CA30-0AA0 4CB30-0AA0 4CB10-0AA0 4CL30-0AA0 4CG30-0AA0 4CF50-0AA0
FastConnect 15N26-A1 15N24-A1 15N24-01 15N23-01 - - -
Order No. 6ES7 193- 4CA80-0AA0 4CA70-0AA0 4CB70-0AA0 4CB60-0AA0
2AI U ST
2AI U HF
2AI I 2WIRE ST
2AI I 2WIRE HS
4 AI I 2WIRE ST
2AI I 2/4WIRE HF
2 AI I 4WIRE ST
2AI RTD ST
2AI RTD HF
2 AI TC ST
2 AI TC HF
2AO U ST
2AO U HF
2AO U HS
2 AO I ST
2AO I HF
4 IQ-SENSE

5/16 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications
6ES7 134- 6ES7 134- 6ES7 134- 6ES7 134-
4FB01-0AB0 4LB02-0AB0 4GB01-0AB0 4GB52-0AB0
Voltages and currents
Load voltage L+
Rated value (DC) 24 V; 24 V 24 V; 24 V
From the power module From the power module
Short-circuit protection Yes
reverse polarity protection Yes Yes Yes; Yes
Destruction limit 35 mA
per channel
Voltage supply to the transducers
present No Yes
short-circuit proof Yes
Current consumption
from load voltage L+ (without load), 30 mA 55 mA 80 mA 225 mA
max.
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA
Power loss, typ. 0.6 W 0.85 W 0.6 W 2.5 W 5
Address area
Address space per module
Address space per module, max. 4 Byte 4 Byte 4 Byte 4 Byte
Isochronous mode
Isochronouos mode No Yes No Yes
Analog inputs
Number of analog inputs 2 2 2 2
cable length, shielded, max. 200 m 200 m 200 m 200 m
permissible input frequency for volt- 35 V; 35 V permanent, 75 35 V; 35 V continuous, 75
age input (destruction limit), max. V for max. 1 ms (pulse V for max. 1 ms
duty factor 1:20)
permissible input current for current 40 mA
input (destruction limit), max.
Cycle time (all channels), max. Number of active chan- 0.5 ms; Number of active chan- 0.25 ms
nels per module x conver- 0.5ms for 2 channels nels per module x conver-
sion time without interference sion time
suppression 18/21 ms
per channel with interf.
Input ranges (rated values),
voltages
Voltage Yes Yes
1 to 5 V Yes Yes
Input resistance (1 to 5 V) 800 k
-10 V to +10 V Yes Yes
Input resistance (-10 V to +10 V) 800 k
-5 V to +5 V Yes Yes
Input resistance (-5 V to +5 V) 800 k
Input ranges (rated values), currents
Current Yes
0 to 20 mA Yes
Input resistance (0 to 20 mA) 106
4 to 20 mA Yes; on 50 ohms Yes

Siemens IK PI News July 2007 5/17


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134- 6ES7 134- 6ES7 134- 6ES7 134-
4FB01-0AB0 4LB02-0AB0 4GB01-0AB0 4GB52-0AB0
Analog value creation
Measurement principle integrating integrating
Integration and conversion
time/resolution per channel
Resolution with overload area 14 Bit; 16 Bit; 13 Bit; 16 Bit
(bit including sign), max. +/-10 V: 13 bits + sign, ...5 V: 15 bit, 4 to 20 mA: 13 bits
+/-5 V: 13 bits + sign, +/-10 V: 16 bit,
1 to 5 V: 13 bits +/-5 V: 16 bit
Integration time, parameterizable Yes
Integration time, ms 16.7 / 20 ms 16.7 / 20 ms
Interference voltage suppression 60 / 50 Hz 60 / 50 Hz / no 60 / 50 Hz
for interference frequency f1 in Hz
Conversion time (per channel) 65 ms; 55 / 65 ms 0.04 ms; 65 ms; 55 / 65 ms
without interference sup-
pression 17ms / 20ms per
channel with interference

5 Smoothing of measured values


parameterizable Yes; In four stages by Yes; in 4 stages: 1 x , 4 x , Yes; In four stages by Yes
means of digital filtering 16 x , 32 x cycle time means of digital filtering
Level: none Yes; 1 x cycle time Yes; 1 x Yes; 1 x cycle time Yes
Level: weak Yes; 4x cycle time Yes; 4 x Yes; 4x cycle time Yes
Level: middle Yes; 32x cycle time Yes; 16 x Yes; 32x cycle time Yes
Level: strong Yes; 64x cycle time Yes; 32 x Yes; 64x cycle time Yes
Encoder
Connection of signal encoders
for voltage measurement Yes
for current measurement Yes
as 2-wire transducer
Burden of 2-wire transmitter, max. 750
Errors/accuracies
Linearity error (relative to input area) +/- 0,01 % +/- 0,01 % +/- 0,01 % +/- 0,03 %
Temperature error +/- 0,01 %/K +/- 0,003 %/K +/- 0,005 %/K +/- 0,01 %/K
(relative to input areas)
Crosstalk between the inputs, min. -50 dB -100 dB -50 dB 50 dB
Repeat accuracy in settled status +/- 0,05 % +/- 0,01 % +/- 0,05 % +/- 0,1 %
at 25 C (relative to input area)
Operational limit in overall tempera-
ture range
Voltage, relative to input area +/- 0,6 % +/- 0,1 %;
0.2% without interefence
freqency suppression
Current, relative to input area +/- 0,6 % +/- 0,3 %
Basic error limit
(operational limit at 25 C)
Voltage, relative to input area +/- 0,4 % +/- 0,05 %;
0.1% without inteference
frequency suppression
Current, relative to input area +/- 0,4 % +/- 0,2 %
Interference voltage suppression
for f = n x (fl +/- 1 %),
fl = interference frequency
Series mode interference (peak 70 dB 90 dB 70 dB
value of interference < rated value
of input range), min.
common mode voltage 90 dB 100 dB
(USS < 2.5 V) , min.

5/18 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134- 6ES7 134- 6ES7 134- 6ES7 134-
4FB01-0AB0 4LB02-0AB0 4GB01-0AB0 4GB52-0AB0
Parameter
Remark 4 bytes 12 bytes, 4 bytes in com- 4 bytes
patibility mode
Diagnosis: wire break Inhibit/enable (measuring
range 1 to 5 V only)
Measurement type/range deactivated / +/-5 V / deactivated / +/-5 V / deactivated / 4 to 20 mA
1 to 5 V / +/-10 V 1 to 5 V / +/-10 V
Collective diagnostics disable/enable disable/enable disable/enable
Overflow/underflow disable/enable disable/enable disable/enable
Status information/alarms/
diagnostics
Alarms
Process alarm Yes Yes
Diagnoses
Diagnostic functions Yes Yes
Wire break Yes; only measuring
range 1to 5 V
Yes; only measuring
range 1to 5V
Yes Yes
5
Group error Yes Yes Yes Yes
Overflow/underflow Yes Yes Yes Yes
Diagnostics indication LED
Collective error SF (red) Yes Yes Yes Yes
Isolation
Isolation checked with 500 V DC 500 V DC 500 V DC
Isolation
Isolation, analog inputs
between the channels No No; Functional, yes No No
between the channels and the Yes Yes Yes Yes
backplane bus
between the channels Yes Yes No Yes
and the load voltage L+
Permissible potential difference
between the inputs (UCM) 140 V DC/100 V AC
between inputs and MANA (UCM) 2 V AC PP
between MANA and M internally 75 V DC / 60 V AC
(UISO)
Dimensions
Width 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm
Module width, max. 15 mm 15 mm
Weights
Weight, approx. 40 g 45 g 40 g

6ES7 134-4GB11-0AB0 6ES7 134-4MB02-0AB0 6ES7 134-4GD00-0AB0


Voltages and currents
Load voltage L+
Rated value (DC) 24 V; From the power module 24 V 24 V; From the power module
reverse polarity protection Yes Yes
Voltage supply to the transducers
present Yes Yes
short-circuit proof Yes Yes; approx. 200 mA for module
Current consumption
from load voltage L+ (without load), 30 mA 48 mA 125 mA
max.
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA
Power loss, typ. 0.6 W 1.2 W 0.6 W

Siemens IK PI News July 2007 5/19


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4GB11-0AB0 6ES7 134-4MB02-0AB0 6ES7 134-4GD00-0AB0
Address area
Address space per module
Address space per module, max. 4 Byte 4 Byte 8 Byte
Isochronous mode
Isochronouos mode No No
Analog inputs
Number of analog inputs 2 2 4
cable length, shielded, max. 200 m 200 m 200 m
permissible input current for current 40 mA 50 mA 30 mA; limited electronically
input (destruction limit), max.
Cycle time (all channels), max. Number of active channels per 0.5 ms; 0.5ms for 2 channels with- 40 ms; 33 to 40 ms
module x conversion time out interf. suppression, 18/21ms
per channel with interf.
Input ranges (rated values), currents
Current Yes Yes Yes
-20 to +20 mA Yes; 50 ohms Yes
5 4 to 20 mA Yes; 50 ohms Yes Yes; on 25 ohms
Analog value creation
Measurement principle integrating Sigma-Delta
Integration and conversion
time/resolution per channel
Resolution with overload area 14 Bit; +/-20 mA: 14 bits; 4 to 20 16 Bit; as required 13 Bit; 4 to 20 mA: 13 bits
(bit including sign), max. mA: 13 bits
Integration time, parameterizable Yes Yes
Integration time, ms 16.7 / 20 ms 16.7 or 20
Interference voltage suppression 60 / 50 Hz 60Hz / 50Hz / no 60 / 50 Hz
for interference frequency f1 in Hz
Conversion time (per channel) 65 ms; 55 / 65 ms 0.04 ms; without interference sup-
pression 17ms / 20ms per channel
with interference
Smoothing of measured values
parameterizable Yes; In four stages by means of Yes; in 4 stages: 1 x , 4 x , 16 x , 32 Yes; in 4 stages
digital filtering x cycle time
Level: none Yes; 1 x cycle time Yes; 1 x Yes; 1 x cycle time
Level: weak Yes; 4x cycle time Yes; 4 x Yes; 4x cycle time
Level: middle Yes; 32x cycle time Yes; 16 x Yes; 16x cycle time
Level: strong Yes; 64x cycle time Yes; 32 x Yes; 32x cycle time
Encoder
Connection of signal encoders
Burden of 2-wire transmitter, max. 750 750 750
Errors/accuracies
Linearity error (relative to input area) +/- 0,01 % +/- 0,03 % +/- 0,01 %
Temperature error +/- 0,005 %/K +/- 0,03 %/K +/- 0,003 %/K
(relative to input areas)
Crosstalk between the inputs, min. -50 dB -100 dB -50 dB
Repeat accuracy in settled status +/- 0,05 % +/- 0,01 % +/- 0,05 %
at 25 C (relative to input area)

Operational limit
in overall temperature range
Current, relative to input area +/- 0,6 % +/- 0,1 %; 0.2% without interefence +/- 0,4 %
freqency suppression
Basic error limit
(operational limit at 25 C)
Current, relative to input area +/- 0,4 % +/- 0,05 %; 0.1% without intefer- +/- 0,3 %
ence frequency suppression

5/20 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4GB11-0AB0 6ES7 134-4MB02-0AB0 6ES7 134-4GD00-0AB0
Interference voltage suppression
for f = n x (fl +/- 1 %),
fl = interference frequency
Series mode interference (peak 70 dB 90 dB 70 dB
value of interference < rated value
of input range), min.
common mode voltage 100 dB
(USS < 2.5 V) , min.
Parameter
Remark 4 bytes 12 bytes, 7 bytes
4 bytes in compatibility mode
Diagnosis: wire break disable / enable, (only in measuring disable / enable Yes
range 4 to 20 mA)
Measurement type/range deactivated / 4 to 20 mA / deactivated / +/- 20 mA 4 to 20 mA Yes
+/- 20 mA
Collective diagnostics disable/enable disable / enable Yes
Overflow/underflow disable/enable disable / enable Yes
Status information/alarms/
diagnostics
Alarms
5
Process alarm Yes
Diagnoses
Diagnostic functions Yes Yes; can be read out
Wire break Yes; only in measuring range Yes; only in measuring range Yes; only in measuring range
4 to 20 mA 4 to 20 mA 1 to 5 V
Group error Yes Yes Yes
Overflow/underflow Yes Yes Yes
Diagnostics indication LED
Collective error SF (red) Yes Yes Yes
Isolation
Isolation checked with 500 V DC 500 V DC
Isolation
Isolation, analog inputs
between the channels No No; Functional, yes No
between the channels and the Yes Yes Yes
backplane bus
between the channels and the No Yes No
load voltage L+
Dimensions
Width 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm
Module width, max. 15 mm
Weights
Weight, approx. 40 g 45 g 40 g

6ES7 134-4JB50-0AB0 6ES7 134-4NB51-0AB0 6ES7 134-4JB00-0AB0 6ES7 134-4NB01-0AB0


Voltages and currents
Load voltage L+
Rated value (DC) 24 V; From power module 24 V; From power module 24 V; From power module 24 V; From power module
reverse polarity protection Yes Yes Yes Yes
Voltage supply to the transducers
present Yes
short-circuit proof Yes
Current consumption
from load voltage L+ (without load), 30 mA 30 mA 30 mA 30 mA
max.
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA
Power loss, typ. 0.6 W 0.6 W 0.6 W 0.6 W
Address area
Address space per module
Address space per module, max. 4 Byte 4 Byte 4 Byte 4 Byte

Siemens IK PI News July 2007 5/21


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4JB50-0AB0 6ES7 134-4NB51-0AB0 6ES7 134-4JB00-0AB0 6ES7 134-4NB01-0AB0
Isochronous mode
Isochronouos mode No No No
Analog inputs
Number of analog inputs 2 2 2 2
cable length, shielded, max. 200 m 200 m 50 m 50 m
permissible input frequency for volt- 9 V 9V 10 V; permanent 20 V; +/-20 V, continuous
age input (destruction limit), max.
Constant measurement current for 1.5 mA 1.25 mA
resistance-type transmitter, typ.
Cycle time (all channels), max. Number of active Number of active Number of active Number of active
channels per module x channels per module x channels per module x channels per module x
basic conversion time basic conversion time basic conversion time basic conversion time
technical unit for temperature Yes Yes
measurement, adjustable
Input ranges (rated values),
voltages
Voltage Yes Yes
5 -80 mV to +80 mV Yes Yes
Input resistance 1 M 1 M
(-80 mV to +80 mV)
Input ranges (rated values),
thermoelements
thermocouple Yes Yes
Type B Yes Yes
Input resistance (Type B) 1 M 1 M
Type C Yes
Input resistance (Type C) 1 M
Type E Yes Yes
Input resistance (Type E) 1 M 1 M
Type J Yes Yes
Input resistance (type J) 1 M 1 M
Type K Yes Yes
Input resistance (Type K) 1 M 1 M
Type L Yes Yes
Input resistance (Type L) 1 M 1 M
Type N Yes Yes
Input resistance (Type N) 1 M 1 M
Type R Yes Yes
Input resistance (Type R) 1 M 1 M
Type S Yes Yes
Input resistance (Type S) 1 M 1 M
Type T Yes Yes
Input resistance (Type T) 1 M 1 M
Input ranges (rated values),
resistors
Impedance Yes Yes
0 to 150 Ohm Yes Yes
Input resistance (0 to 150 Ohm) 2,000 k 10 M
0 to 300 Ohm Yes Yes
Input resistance (0 to 300 Ohm) 2,000 k 10 M
0 to 600 Ohm Yes Yes
Input resistance (0 to 600 Ohm) 2,000 k 10 M
0 to 3000 Ohm Yes
Input resistance (0 to 3000 Ohm) 10 M

5/22 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4JB50-0AB0 6ES7 134-4NB51-0AB0 6ES7 134-4JB00-0AB0 6ES7 134-4NB01-0AB0
Input ranges (rated values),
resistance thermometers
Resistance thermometer Yes Yes
Cu 10 Yes
Input resistance (Cu 10) 10 M
Ni 100 Yes; Standard/climate Yes
Input resistance (Ni 100) 2,000 k 10 M
Ni 1000 Yes
Input resistance (Ni 1000) 10 M
Ni 120 Yes
Input resistance (Ni 120) 10 M
Ni 200 Yes
Input resistance (Ni 200) 10 M
Ni 500 Yes
Input resistance (Ni 500) 10 M
Pt 100 Yes; Standard/AirCon Yes
Input resistance (Pt 100) 2,000 k 10 M 5
Pt 1000 Yes
Input resistance (Pt 1000) 10 M
Pt 200 Yes
Input resistance (Pt 200) 10 M
Pt 500 Yes
Input resistance (Pt 500) 10 M
Characteristic curve linearization
programmable Yes; for Pt100, Ni100 Yes; for Ptxxx, Nixxx Yes; Type B, E, J, K, L, N, Yes
R, S, T to IEC 584
for thermoelements Type B, C, E, J, K, L, N, R,
S, T to IEC 584
for thermoresistor Pt100, Ni100 Ptxxx, Nixxx
Temperature compensation
external temperature Yes; possible, Yes;
compensation with one external compensat- one external compensat-
compensations socket ing box per channel ing box per channel
internal temperature Yes Yes; possible with
compensation TM-E15S24-AT,
TM-E15C24-AT
Analog value creation
Measurement principle integrating integrating (Sigma-Delta) integrating integrating
Integration and conversion
time/resolution per channel
Resolution with overload area 16 Bit; 150 Ohm: 14 bit; 16 Bit; for Pt100, Ni100, 16 Bit; 15 bit + sign 16 Bit
(bit including sign), max. 300, 600 Ohm: 15 bit; Ni120, Pt200, Ni200,
Pt100, Ni100: 16 bit Pt 500, Ni 500, Pt1000,
Ni1000, Cu10: 15 bits +
sign; for 150, 300, 600,
3000 ohms: 15 bits;
for PTC: 1 bit
Integration time, parameterizable Yes Yes
Integration time, ms 16.7 / 20 ms 16.7 / 20 ms 16.7 / 20 ms 16.7 / 20 ms
Interference voltage suppression 60 / 50 Hz 60 / 50 Hz 60 / 50 Hz 60 / 50 Hz
for interference frequency f1 in Hz
Conversion time (per channel) 110 ms; 110 / 130 ms 65 ms; 55 / 65 ms 66 ms; 66 / 80 ms; addi-
(additional 20 ms on acti- tional conversion time for
vated wire-break test) diagnostic wire break test
Smoothing of measured values
parameterizable Yes; In four stages by Yes; In four stages by Yes; In four stages by Yes; In four stages by
means of digital filtering means of digital filtering means of digital filtering means of digital filtering
Level: none Yes; 1x cycle time Yes; 1x cycle time Yes; 1x cycle time Yes; 1x cycle time
Level: weak Yes; 4x cycle time Yes; 4x cycle time Yes; 4x cycle time Yes; 4x cycle time
Level: middle Yes; 64x cycle time Yes; 32x cycle time Yes; 32x cycle time Yes; 32x cycle time
Level: strong Yes; 128x cycle time Yes; 64x cycle time Yes; 64x cycle time Yes; 64x cycle time

Siemens IK PI News July 2007 5/23


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4JB50-0AB0 6ES7 134-4NB51-0AB0 6ES7 134-4JB00-0AB0 6ES7 134-4NB01-0AB0
Encoder
Connection of signal encoders
for voltage measurement Yes
for resistance measurement with Yes; Yes
2-conductor connection Line resistances are also
measured, jumpers to TR
for resistance measurement with Yes; Yes;
3-conductor connection Line resistances are also internal compensation of
measured, jumpers to TR the line resistances
for resistance measurement with Yes Yes
4-conductor connection
Burden of 2-wire transmitter, max. 750
Errors/accuracies
Linearity error +/- 0,01 % +/- 0.01 % +/- 0,01 % +/- 0.01 %
(relative to input area)
Temperature error +/- 0,005 %/K +/- 0,0009 %/K +/- 0,005 %/K +/- 0.005 %/K
(relative to input areas)
5 Crosstalk between the inputs, min. -50 dB -50 dB -50 dB -50 dB
Repeat accuracy in settled status +/- 0,05 % +/- 0.05 % +/- 0,05 % +/- 0.05 %
at 25 C (relative to input area)
Operational limit in overall
temperature range
Voltage, relative to input area +/- 0,6 % +/- 0.1 %; +/-1.5 K for
thermocouples,
+/-7 K for thermocouples
type C, +/-2.5 K with static
thermal state (ambient
temperature change
< 0.3 K/min)
Resistance-type thermometer, +/- 0,6 % Resistance-type trans-
relative to input area mitter: +/-0.1%; Pt100,
Pt200, Pt500, Pt1000
standard: +/-1.0 K; Pt100,
Pt200, Pt500, Pt1000
climate: +/-0.25 K; Ni100,
Ni120, Ni200, Ni500,
Ni1000 standard and
climate: +/-0.4 K; Cu10
+/-1.5 K
Basic error limit
(operational limit at 25 C)
Voltage, relative to input area +/- 0,4 % +/- 0.05 %; +/-1 K with
thermocouples, +/-5 K
with thermocouples type
C, +/-1.5 K with static
thermal state (ambient
temperature change
< 0.3 K/min)
Resistance-type thermometer, +/- 0,4 % Resistance-type transmit-
relative to input area ter: +/-0.05%; Pt100,
Pt200, Pt500, Pt1000
standard: +/-0.6 K; Pt100,
Pt200, Pt500, Pt1000
climate: +/-0.13 K; Ni100,
Ni120, Ni200, Ni500,
Ni1000 standard and
climate: +/-0.2 K;
Cu10 +/-1 K
Interference voltage suppression
for f = n x (fl +/- 1 %),
fl = interference frequency
Series mode interference (peak 70 dB 70 dB 70 dB 70 dB
value of interference < rated value
of input range), min.
common mode voltage 90 dB 90 dB 90 dB 90 dB
(USS < 2.5 V) , min.

5/24 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 134-4JB50-0AB0 6ES7 134-4NB51-0AB0 6ES7 134-4JB00-0AB0 6ES7 134-4NB01-0AB0
Parameter
Remark 4 bytes 7 bytes 4 bytes 4 bytes
Diagnosis: wire break disable/enable (wire Disable/enable disable/enable (wire disable/enable (wire
break is detected only on break is detected only in break is detected only in
constant current lines) thermocouples) thermocouples)
Measurement type/range deactivated/150 ohms/; deactivated/ 150 ohms/ Deactivated/ Deactivated/
300 ohms/600 ohms/; 300 ohms/ 600 ohms/ +/- 80 mV/;+/- 250 mV / +/- 80 mV/;TC-EL type T
Pt100 climatic/ Pt100 Pt100/ Pt200/ Pt500/ +/- 500 mV /;+/- 1 V /; (Cu-CuNi)/ TC-EL type K
standard; Ni100 standard Pt1000 each standard TC-EL type T (Cu-CuNi)/ (NiCr-Ni)/ TC-EL type
/ Ni100 climatic or climate range/ Ni100/ TC-EL type K (NiCr-Ni)/ B;(PtRh-PtRh)/;TC-EL type
Ni120/ Ni200/ Ni500/ TC-EL type B; (PtRh- c (Wer-Wer); TC-EL type
Ni1000 each standard PtRh)/; TC-EL type N; N; (NiCrSi-NiSi)/ ,TC-EL
or climate range/ Cu10 (NiCrSi-NiSi)/; TC-EL type E; (NiCr-CuNi)/;
each standard or climate type E; (NiCr-CuNi)/; TC-EL type R (PtRh-Pt)/
range / PTC TC-EL type R (PtRh-Pt)/ TC-EL type S (PtRh-Pt)/
TC-EL type S (PtRh-Pt)/ TC-EL type J (Fe-Cu-Ni)/
TC-EL Type J TC
Collective diagnostics Disable/enable Disable/enable Disable/enable Disable/enable
Slot comparison point 1 to 8 disable/enable
Overflow/underflow disable/enable disable/enable disable/enable disable/enable 5
Comparison point none / RTD none / yes, internal
Comparison point number none / 1 / 2 / 3 / 4 / 5 /
6/7/8
Unit Celsius Celsius / Fahrenheit
Status information/alarms/
diagnostics
Diagnoses
Diagnostic functions Yes; can be read out Yes; can be read out
Wire break Yes; A wire break is only Yes Yes; A break in the wire is Yes; only thermocouples
detected on constand only detected on thermo-
current lines couples
Group error Yes Yes Yes Yes
Overflow/underflow Yes Yes Yes Yes
Diagnostics indication LED
Collective error SF (red) Yes Yes Yes Yes
Isolation
Isolation checked with 500 V DC 500 V DC 500 V DC 500 V DC
Isolation
Isolation, analog inputs
between the channels No No No No
between the channels and the Yes Yes Yes Yes
backplane bus
between the channels and the Yes Yes Yes Yes
load voltage L+
Permissible potential difference
between inputs and MANA (UCM) 2 V AC PP 140 V DC/100 V AC
between MANA and M internally 75 V DC / 60 V AC 75 V DC / 60 V AC 75 V DC / 60 V AC 75 V DC / 60 V AC
(UISO)
Dimensions
Width 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 40 g 40 g 40 g

Siemens IK PI News July 2007 5/25


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135-
4FB01-0AB0 4FB52-0AB0 4LB02-0AB0 4GB01-0AB0 4MB02-0AB0
Voltages and currents
Load voltage L+
Rated value (DC) 24 V; From the 24 V 24 V 24 V; From the 24 V
power module power module
reverse polarity protection Yes Yes Yes Yes Yes
Current consumption
from load voltage L+ (without load), 130 mA 100 mA 80 mA 150 mA 80 mA
max.
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA 10 mA
Power loss, max. 2W 2W 1.2 W 2W 1.2 W
Address area
Address space per module
Address space per module, max. 4 Byte 4 Byte 4 Byte 4 Byte 4 Byte
Isochronous mode
Isochronouos mode Yes Yes Yes

5 Analog outputs
Number of analg outputs 2 2 2 2 2
cable length, shielded, max. 200 m 200 m 200 m; 200 m 200 m;
100m if Twa < 2ms 100m if Twa < 2ms
Voltage output, Yes Yes Yes
Short-circuit protection
Voltage output, 25 mA 25 mA 25 mA
short-circuit current, max..
Current output, 18 V 18 V
no-load voltage, max.
Cycle time (all channels) max. 1.5 ms 0.25 ms 0.5 ms; 1.5 ms 0.5 ms
at max. 0.5F
Output ranges, voltage
1 to 5 V Yes Yes Yes; -5 to +5V also
implemented
-10 to +10 V Yes Yes Yes
Output ranges, current
-20 to +20 mA Yes Yes
4 to 20 mA Yes Yes
Connection of actuators
for voltage output 2-conductor Yes; Yes Yes
connection without compen-
sation of the line
resistances
for voltage output Yes Yes Yes
4-conductor connection
for current output Yes Yes
2-conductor connection
for current output No No
4-conductor connection
Load impedance
(in rated range of output)
with voltage outputs, min. 1 k 1 k 1 k
with voltage outputs, capacitive 1 F 1 F 0.5 F
load, max.
with current outputs, max. 500 500
with current outputs, inductive 1 mH 1 mH
load, max.
Destruction limits against externally
applied voltages and currents
Voltages at the outputs towards 15 V; max. 15 V 15 V 15 V; 15 V; max. 15 V
MANA continuous, as required continuous,
75 V for max. 1 s 75 V for max. 1 s
(pulse duty ratio (pulse duty ratio
1:20) 1:20)
Current, max. 50 mA; DC 30 mA 50 mA; DC 50 mA

5/26 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135-
4FB01-0AB0 4FB52-0AB0 4LB02-0AB0 4GB01-0AB0 4MB02-0AB0
Analog value creation
Integration and conversion
time/resolution per channel
Resolution with overload area 14 Bit; 16 Bit 16 Bit; 14 Bit; 16 Bit
(bit including sign), max. 1...5 V: 12 bits, 15 bit + sign 4 to 20 mA: 13 bits,
+/-10 V: +/-20 mA : 14 bits
13 bits + sign
Settling time
for resistive load 0.1 ms 0.05 ms 0.2 ms 0.1 ms 0.3 ms
for capacitive load 0.5 ms 0.05 ms 0.5 ms; at max. 0.5 ms 1 ms
0.5F
for inductive load 0.5 ms 0.05 ms 0.5 ms 0.5 ms 0.5 ms
Ex(i) characteristics
Max. values of output circuits
(per channel)
Uo (output no-load voltage), max. 18 V
Errors/accuracies 5
Output ripple (based on output +/- 0,02 % +/- 0,02 % +/- 0,02 % +/- 0,02 % +/- 0,02 %
range, bandwidth 0 to 50 kHz)
Linearity error +/- 0,02 % +/- 0,03 % +/- 0,01 % +/- 0,02 % +/- 0,01 %
(relative to output area)
Temperature error +/- 0,01 %/K +/- 0,01 %/K +/- 0,01 %/K +/- 0,003 %/K
(relative to output area)
Crosstalk between the outputs, min. 60 dB 60 dB 60 dB
Repeat accuracy in settled status +/- 0,05 % +/- 0,03 % +/- 0,01 % +/- 0,05 % +/- 0,01 %
at 25 C (relative to output area)
Operational limit in overall
temperature range
Voltage, relative to output area +/- 0,4 % +/- 0,2 % +/- 0,1 %
Current, relative to output area +/- 0,5 % +/- 0,1 %
Basic error limit
(operational limit at 25 C)
Voltage, relative to output area +/- 0,2 % +/- 0,01 % +/- 0,05 %
Current, relative to output area +/- 0,3 % +/- 0,05 %
Parameter
Remark 7 bytes 7 bytes 7 bytes 7 bytes
Output type/range Deactivated / deactivated / Deactivated / deactivated /
1 to 5 V / +/-10 V to 5V / +/ - 10V / 4 to 20 mA / 4 to 20mA /
+/- 5V +/-20 mA +/- 20mA
Diagnosis: wire break disable/enable disable / enable
Diagnosis: short circuit disable/enable disable / enable
Interference frequency suppression no disable / enable
Collective diagnostics disable/enable disable / enable disable/enable disable / enable
Behavior on CPU/Master STOP Output current and Output current and Output current and Output current and
de-energized/ voltage-free / de-energized/ de-energized/
substitute a value/ replacement value / substitute a value/ substitute a value/
keep last value keep last value keep last value keep last value

Siemens IK PI News July 2007 5/27


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S
Analog electronic modules

Technical specifications (continued)


6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135- 6ES7 135-
4FB01-0AB0 4FB52-0AB0 4LB02-0AB0 4GB01-0AB0 4MB02-0AB0
Status information/alarms/
diagnostics
Substitute values connectable Yes; 0 to 65535 Yes Yes Yes; 0 to 65535 Yes
(range of values (range of values
must be within the must be within the
rated range) rated range)
Diagnoses
Diagnostic functions Yes
Diagnostic information readable Yes Yes Yes
Wire break No Yes Yes
Short circuit Yes Yes Yes
Group error Yes Yes Yes Yes Yes
Diagnostics indication LED
Collective error SF (red) Yes Yes Yes Yes Yes
Isolation
Isolation checked with 500 V DC 500 V DC

5 Isolation
Isolation, analog outputs
Galvanic isolation, analog outputs Yes
between the channels No No No No No
between the channels and Yes Yes Yes Yes Yes
the backplane bus
between the channels and Yes Yes Yes Yes Yes
the load voltage L+
Permissible potential difference
between MANA and M internally 75 V DC / 60 V AC 75V DC / 60V AC 75 V DC / 60 V AC 75 V DC / 60 V AC
(UISO)
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 40 g 40 g 40 g 40 g

Ordering data Order No. Order No.


Analog input modules Accessories for labeling
Ordering unit 1 item Label sheets DIN A4 (10 pieces)
2 AI U Standard 6ES7 134-4FB01-0AB0 Each sheet contains 60 label strips
for peripheral modules and 20
2 AI U High Feature 6ES7 134-4LB02-0AB0 label strips for interface modules
2 AI I Standard 2-wire 6ES7 134-4GB01-0AB0 petrol 6ES7 193-4BH00-0AA0
2 AI I High Speed 2-wire 6ES7 134-4GB52-0AB0 red 6ES7 193-4BD00-0AA0
2 AI I Standard 4-wire 6ES7 134-4GB11-0AB0 yellow 6ES7 193-4BB00-0AA0
2 AI I High Feature 2-wire/4-wire 6ES7 134-4MB02-0AB0 light beige 6ES7 193-4BA00-0AA0
(15 bits + sign)
Accessories for system-integrated shield connection
2 AI RTD standard 6ES7 134-4JB50-0AB0
Shield connection element 6ES7 193-4GA00-0AA0
2 AI TC standard 6ES7 134-4JB00-0AB0
Ordering unit 5 items
2 AI RTD High Feature 6ES7 134-4NB51-0AB0
For plugging into TM-E and TM-P
2 AI TC High Feature 6ES7 134-4NB01-0AB0
Shield clamps 6ES7 193-4GB00-0AA0
4 AI Standard 2-wire 6ES7 134-4GD00-0AB0 Ordering unit 5 items
Analog output modules For 3 10 mm busbars
Ordering unit 1 item Grounding terminal 8WA2 868
2 AO U Standard 6ES7 135-4FB01-0AB0 Ordering unit 1 item
2 AO U High Speed 6ES7 135-4FB52-0AB0 For cable cross-sections
up to 25 mm2
2 AO U High Feature 6ES7 135-4LB02-0AB0
3 10 mm busbars 8WA2 842
2 AO I Standard 6ES7 135-4GB01-0AB0
Ordering unit 1 item
2 AO I High Feature 6ES7 135-4MB02-0AB0

5/28 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S Software
Motor Starter ES

Overview
Using Motor Starter ES, the communication-capable motor starters
are easily parameterized during start-up, monitored during nor-
mal operation and successfully diagnosed for service purposes.
Preventative maintenance is supported by a function for reading
out diverse statistical data (e.g. operating hours, operating cycles,
cut-off currents, etc.). The user is supported during these proce-
dures with comprehensive Help functions and plain text displays.
Motor Starter ES can either be used as a stand-alone program or
it can be integrated into STEP 7 V5.1 SP3 upwards using an
object manager.
The following components are required for a serial connection:
ET 200S motor starters, High-Feature:
Control module 2DI DC 24 V COM
3RK1 903-0CH10
LOGO! PC cable
6ED1 057-1AA00-0BA0
ET 200pro motor starters:
Motor Starter ES for parameterization, monitoring, diagnostics and RS 232 interface cable
testing of motor starters 3RK1 922-2BP00 5
ECOFAST High-Feature motor starters (interface cable):
Motor Starter ES is used for start-up, parameterization,
diagnostics, documentation and the preventative maintenance PC cable
of the High-Feature motor starters of the SIMATIC ET 200S, 3RK1 911-0BN20.
ET 200pro and ECOFAST product families.
Interfacing is performed
Either through the serial device interface
(applies for ET 200S/ET 200pro/ECOFAST) or
With PROFIBUS DP-V1 capable motor starters
from any point in PROFIBUS
(applies for ET 200pro/ECOFAST)

Siemens IK PI News July 2007 5/29


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200S Software
Motor Starter ES

Selection and ordering data


Version Order No.
Motor Starter ES 2006 Smart 3ZS1 310-1CC10-0YA0
single license
Comprising:
Motor Starter ES for parameterization, monitoring, diagnostics and testing of the
ECOFAST motor starters,
SIMATIC ET 200S High-Feature starters and
SIMATIC ET 200pro motor starters
using a serial connection
- With Online Help
German/English selectable
- Operating system: Windows 2000/XP
System requirements:
- Cable for serial communication through a serial interface
- CD-ROM drive
Motor Starter ES 2006 Professional 3ZS1 310-2CC10-0YA0
single license
Comprising:
Motor Starter ES for parameterization, monitoring, diagnostics and testing of the
ECOFAST motor starters,
SIMATIC ET 200S High-Feature starters and
5 SIMATIC ET 200pro motor starters
using PROFIBUS DP or a serial interface
- With Online Help
German/English selectable
- Operating system: Windows 2000/XP
STEP7 Object Manager (OM)
For integrating the ECOFAST starters as S7 slaves in SIMATIC S7
For calling Motor Starter ES from STEP7
Motor Starter ES 2006 Professional Upgrade 3ZS1 310-2CC10-0YE0
single license
Comprising:
Upgrade from Switch ES Motor Starter 2004 or Motor Starter ES Smart 2005
to Motor Starter ES 2006 Professional
General accessories
USB adapters
For converting from USB to RS 232 interface at the PC end
2SX5 100-3PC07

(for computers without an integrated RS 232 interface)


Accessories for ET 200S motor starters, High-Feature
Control modules 2DI DC 24 V COM 3RK1 903-0CH10
Digital input module with 2 inputs for local motor starter functions for mounting onto
the front of motor starters
Operational voltage 24 V DC (supplied from U1), short-circuit resistant, floating
contact with serial interface for connecting to Motor Starter ES
Connection through LOGO! PC cable, max. cable length (out and back) 50 m
LOGO! PC cables 6ED1 057-1AA00-0BA0
For connecting the High-Feature motor starter
with Motor Starter ES interface to a PC
Accessories for ET 200pro motor starters
RS 232 interface cables 3RK1 922-2BP00
For serial data connection
between an ET 200pro motor starter and a laptop/PC/PG
Accessories for ECOFAST motor starters, High-Feature (interface cable)
PC cables 3RK1 911-0BN20

5/30 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro
IM 154-8 PN/DP CPU interface module

Overview
PROFINET IO Controller to operate distributed I/Os on
PROFINET
Component Based Automation (CBA) on PROFINET
PROFINET proxy for intelligent devices on PROFIBUS DP in
Component Based Automation (CBA)
CPU with PLC functionality equivalent to S7-315-2 PN/DP,
provides distributed intelligence for preprocessing
Interface module to exchange preprocessed I/O data from
ET 200pro with a higher-level master through PROFIBUS DP
Fast, simple and end-to-end programming of a system with
modular programs via STEP 7
Micro Memory Card required for operation of CPU.

Technical specifications
6ES7 154-8AB00-0AB0 6ES7 154-8AB00-0AB0
5
Revision level Nesting depth
Associated programming package STEP 7 V5.4 SP1 Per priority class 8
with hardware update Additionally within an error OB 4
Supply voltages CPU/ Processing times
Rated value For bit operations, min. 0.1 s
24 V DC Yes
For word operations, min. 0.2 s
Permissible range, lower limit (DC) 20.4 V
For fixed point arithmetic, min. 2 s
Permissible range, upper limit (DC) 28.8 V
For floating point arithmetic, min. 3 s
Voltages and currents
External protection for supply lines 24 V DC circuit breaker / 16 A Timers/counters and
(recommended) with tripping characteristic type B their retentivity
and C (see ET 200pro Manual) S7 counters
Current consumption Number 256
Starting current, type 2 A; typical Of which retentive without battery
It 0.04 As; typical - Adjustable Yes
Current consumption 350 mA; typical - Lower limit 0
(nominal value) - Upper limit 255
Power loss, typ. 8.5 As; typical Retentivity
Memory - Adjustable Yes
Memory type - Lower limit 0
- Upper limit 255
Work memory
- Integrated 256 KB Counting range
- Expandable No - Adjustable Yes
- Lower limit 0
Load memory
- Upper limit 999
- Plug-in (MMC) Yes
- Plug-in (MMC), max. 8 MB IEC counter
Available Yes
Buffer
Type SFB
Available Yes
Without battery Yes S7 times
Number 256
CPU/ Chips
DB Retentivity
Number, max. 1,023; Number range: 1 to 1023 - Adjustable Yes
Size, max. 16 KB - Lower limit 0
- Upper limit 128
FB
- Pre-selected No retentivity
Number, max. 1,024; number range: 0 to 2047
Size, max. 16 KB Time range
- Lower limit 10 ms
FC
- Upper limit 9,990 s
Number, max. 1,024; number range: 0 to 2047
Size, max. 16 KB IEC timers
Available Yes
OB
Type SFB
Size, max. 16 KB

Siemens IK PI News July 2007 5/31


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro
IM 154-8 PN/DP CPU interface module

Technical specifications (continued)


6ES7 154-8AB00-0AB0 6ES7 154-8AB00-0AB0
Data areas and their retentivity On MPI, slave Yes
Bit memories In AS, master No
Number, max. 2,048 bytes In AS, slave No
Retentivity available Yes; MB 0 to MB 2047 on Ethernet via NTP Yes; as client
Number of clock memories 8 S7 alarm functions
Data blocks Number of connectable stations 16
Number, max. 1,023; from DB 1 to DB 1023 for message functions, max.
Size, max. 16 KB Process error diagnostic messages Yes
Retentivity adjustable Yes; from DB 1 to DB 1023 Simultaneously active alarm S 40
Retentivity pre-selected Yes modules, max.
Local data Test and commissioning
functions
Per priority class, max. 1,024 bytes; per module max. 510
Status Force
Addressing range Status/Modify variable Yes
I/O addressing range Variables Inputs, outputs, bit memories, DB,
Inputs 2,048 bytes timers, counters
Outputs 2,048 bytes Number of variables, max. 30

5 Of which distributed
- Inputs 2,048 bytes
Of which are Status Variable, max. 30
Of which are Modify Variable, max. 14
- Outputs 2,048 bytes Forcing
Process image Forcing Yes
Inputs, adjustable 2,048 bytes Forcing, variables I/O
Outputs, adjustable 2,048 bytes Number of variables, max. 10
Inputs, pre-selected 128 bytes Status Block Yes
Outputs, pre-selected 128 bytes Single step Yes
Process image partition Number of breakpoints 2
Number of partial process image, 1 Diagnostic buffer
max.
Available Yes
Digital channels Number of entries, max. 500
Inputs 16.384 Adjustable No
Outputs 16.384
Communication functions
Inputs, of which central 128
PG/OP communication Yes
Outputs, of which central 64
Routing Yes
Analog channels
Inputs 1.024 Shared data communication
Outputs 1.024 Supported Yes
Inputs, of which central 64 GD package size, max. 22 bytes
Outputs, of which central 64 S7 basic communication
Hardware configuration Supported Yes
Module rack, max. 1 S7 communication
Modules per rack, max. 16; Expansion width, max. 1m Supported Yes

No. of DP masters Open IE communication


Integrated 1 TCP/IP Yes
- Number of connections, max. 8
Time
- Data lengths, max. 8 KB
Clock
ISO-on-TCP (RFC1006) Yes
Real-time clock Yes
- Number of connections, max. 8
Buffered and synchronized Yes; to MPI: master/slave;
to DP: In operation as DP master: - Data lengths, max. 8 KB
master/slave; on PROFINET: UDP Yes
Via NTP (client only) - Number of connections, max. 8
Fluctuation per day, max. 10 s - Data lengths, max. 1,472 KB
Runtime meter Number of connections
Number 1 Total 16
Value range 2 to the power of 31 hours Applicable for PG communication 15
(when using the SFC 101)
Applicable for OP communication 15
Granularity 1h
Applicable for S7 basic 14
Retentive Yes; must be restarted at each communication
restart.
PROFINET CBA (for set reference
Time synchronization communication load)
Supported Yes Target setting for CPU 50%
On MPI, master Yes communication load

5/32 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro
IM 154-8 PN/DP CPU interface module

Technical specifications (continued)


6ES7 154-8AB00-0AB0 6ES7 154-8AB00-0AB0
Number of remote 32 MPI
interconnection partners Number of connections 16
Number of master/slave functions 30 Services
Total of all master/slave 1.000 - PG/OP communication Yes
connections
- Routing Yes
Data lengths of all incoming 4,000 bytes - Shared data communication Yes
master/slave connections, max.
- S7 basic communication Yes
Data lengths of all outgoing 4,000 bytes
master/slave connections, max. - S7 communication Yes
- S7 communication, as client No
Number of internal and 500
PROFIBUS interconnections - S7 communication, as server Yes
Data lengths of internal and 4,000 bytes Transmission rates, max. 12 Mbit/s
PROFIBUS interconnections, max. DP master
Data lengths per connection, max. 1,400 bytes Services
Remote connections - PG/OP communication Yes
with acyclic transmission - Routing Yes
- Scanning frequency: 500 ms - Shared data communication No
Scanning interval, min.
- S7 basic communication Yes
- Number of incoming
interconnections
100
- S7 communication Yes 5
- Number of outgoing 100 - S7 communication, as client No
interconnections - S7 communication, as server Yes
- Data lengths of all incoming 2,000 bytes - Equidistance support Yes
interconnections, max. - SYNC/FREEZE Yes
- Data lengths of all outgoing 2,000 bytes - Enabling/disabling DP slaves Yes
interconnections, max.
- DPV1 Yes
- Data lengths per connection, 1,400 bytes
max. Transmission rates, max. 12 Mbit/s
Remote connections with cyclic Number of DP slaves, max. 124
transmission
DP slave
- Transfer frequency: 1 ms
Transmission interval, min. Services
- Number of incoming 200 - Routing Yes
interconnections - Shared data communication No
- Number of outgoing 200 - S7 basic communication No
interconnections - S7 communication Yes
- Data lengths of all incoming 2,000 bytes - S7 communication, as client No
interconnections, max.
- S7 communication, as server Yes
- Data lengths of all outgoing 2,000 bytes
- Direct data exchange Yes
interconnections, max.
- DPV1 No
- Data lengths per connection, 250 bytes
max. Transmission rates, max. 12 Mbit/s
HMI variables via PROFINET Transfer memory
(acyclic) - Inputs 244 bytes
- Number of connectable stations 3; 2 * PN OPC / 1 * iMap - Outputs 244 bytes
for HMI variables (PN OPC/iMap)
Address range, max. 32
- HMI variable update 500 ms
- Number of HMI variables 200 2nd interface
- Data lengths of all HMI variables, 2,000 bytes Interface type PROFINET
max. Physical Ethernet
PROFIBUS proxy functionality Electrically isolated Yes
- Supported Yes Automatic calculation of the trans- Yes
- Number of connected PROFI- 16 mission rate
BUS devices
Functionality
- Data lengths per connection, 240 bytes
max. MPI No
DP master No
1st interface
DP slave No
Interface type Integrated RS 485 interface PROFINET IO Controller Yes
Physical RS 485 PROFINET CBA Yes
Electrically isolated Yes Point-to-point link No
Functionality PROFINET CBA
MPI Yes Acyclic transmission Yes
DP master Yes Cyclical transmission Yes
DP slave Yes
Point-to-point link No

Siemens IK PI News July 2007 5/33


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro
IM 154-8 PN/DP CPU interface module

Technical specifications (continued)


6ES7 154-8AB00-0AB0 6ES7 154-8AB00-0AB0
PROFINET IO Controller Software libraries
Services Operation set See operations list
- PG/OP communication Yes
Nesting levels 8
- Routing Yes
User program protection/password Yes
- S7 communication Yes protection
- Open IE communication Yes
System functions (SFC) See operations list
Transmission rate, max. 100 MB/s
System function modules (SFB) See operations list
Number of connectable I/O 128
devices, max. Isolation
Addressing range Between rear panel bus and all Yes
- Inputs, max. 2,048 bytes other switching components
- Outputs, max. 2,048 bytes Between rear panel bus and No
electronics
User data consistency, max. 256 bytes
Between power supply and all Yes
CPU/ Programming other circuits
Programming language
Degree of protection
STEP 7 Yes; as of V 5.3 SP1 + HW support
package IP20 rear panel Yes
5 LAD
FBD
Yes
Yes
Dimensions
Width 135 mm
STL Yes Height 130 mm
SCL Yes Depth 65 mm
CFC Yes
Weights
GRAPH Yes
Weight, approx. 555 g
HiGraph Yes

Ordering data Order No. Order No.


IM 154-8 PN/DP CPU interface 6ES7 154-8AB00-0AB0 Industrial Ethernet FastConnect 6GK1 901-1GA00
module Stripping Tool
PROFINET IO Controller to oper- IE Connecting Cable
ate distributed I/Os on PROFINET, M12-180/M12-180
with integrated PLC functionality
Preassembled IE FC TP Trailing
Accessories Cable GP 2 x 2 (PROFINET Type
C) with two 4-pin M12 plugs
Connection module 6ES7 194-4AN00-0AA0 (4-pin, D-coded), degree of
For CPU IM154-8 PN/DP, with protection IP65/IP67, length:
4 x M12 and 2 x 7/8", to connect
PROFINET and PROFIBUS DP 0.3 m 6XV1 870-8AE30
0.5 m 6XV1 870-8AE50
SCALANCE X-200
Industrial Ethernet Switches 1.0 m 6XV1 870-8AH10
With integral SNMP access, 1.5 m 6XV1 870-8AH15
Web diagnosis, copper cable 2.0 m 6XV1 870-8AH20
diagnosis and PROFINET
diagnosis, for setting up linear, 3.0 m 6XV1 870-8AH30
star and ring structures 5.0 m 6XV1 870-8AH50
SCALANCE X208PRO, 6GK5 208-0HA00-2AA6
10 m 6XV1 870-8AN10
in degree of protection IP65,
with eight 10/100 Mbit/s M12 15 m 6XV1 870-8AN15
ports, incl. eleven M12 dust caps
IE M12 Plug PRO
Industrial Ethernet FC RJ45 M12 plug-in connector suitable
Plug 180 for on-site assembly (D-coded),
RJ45 plug connector for Industrial metal enclosure, fast connection,
Ethernet with a rugged metal for SCALANCE X208PRO and
housing and integrated insulation IM 154-4 PN
displacement contacts for con- 1 units 6GK1 901-0DB10-6AA0
necting Industrial Ethernet FC
installation cables; 8 units 6GK1 901-0DB10-6AA8
with 180 cable outlet IE panel feedthrough
1 unit 6GK1 901-1BB10-2AA0 Cabinet feedthrough for convert-
10 units 6GK1 901-1BB10-2AB0 ing from the M12 connection sys-
tem (D-coded, IP65/IP67) to the
50 units 6GK1 901-1BB20-2AE0 RJ45 connection system (IP20)
Industrial Ethernet FastConnect 1 pack = 5 units 6GK1 901-0DM20-2AA5
installation cables
Fast Connect standard cable 6XV1 840-2AH10
Fast Connect trailing cable 6XV1 840-3AH10
Fast Connect marine cable 6XV1 840-4AH10

5/34 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro RFID Systems
SIMATIC RF180C

Overview Application
The PROFINET communication module SIMATIC RF180C has
been specially designed for a wide range of applications in
industrial automation and logistics. Due to the high degree of
protection IP67, SIMATIC RF180C can be installed in the pro-
cess outside the control cabinet.
Main applications for SIMATIC RF180C:
Machine manufacturing, automation systems, conveyor
systems
Ancilliary assembly lines in the automotive industry / suppliers
Small assembly lines

Design
PROFINET IO
master module
e.g. S7-400 with CP 443-1

The SIMATIC RF180C is a communication module for direct


connection of Siemens RFID systems to PROFINET IO. The
readers (SLGs) of the RFID systems MOBY D, U and RF300 can
5
be operated on SIMATIC RF180C.
Due to the high degree of protection and its ruggedness,
SIMATIC RF180C is ideally suited to use at machine level.
The uniform plug-in connection system ensures rapid commis-
sioning.

Benefits
Two parallel MOBY channels ensure real-time operation of the
dynamic read points
Reader connection with an 8-pole M12 connector for rapid
assembly of all components PROFINET
Easy changeover from PROFIBUS applications to PROFINET
with SIMATIC RF180C thanks to software compatibility
24 V for
The integrated switch allows several PROFINET modules to be RF180C and Reader
installed in star or bus topology. Each application can then be
built up quickly and inexpensively
to other
Powerful hardware ensures rapid data communication with PROFINET IO
the reader (SLG). So that the data are available to the applica- participants
tion more quickly
Simple firmware downloading in the case of function expan-
2. Reader 1. Reader
sions and error rectification ensures high availability of the
G_FS10_XX_00228

RFID system
Adjustable and parameterizable RFID-specific diagnostics
facilitate commissioning and troubleshooting
A broad selection of pre-assembled connecting cables can Tag / MDS
be ordered for connecting PROFINET and readers to SIMATIC
RF180C. This saves time and money during installation and
increases the quality
The hardware configuration with a base unit and connection
block ensures that SIMATIC RF180C is prepared for other con-
nection techniques, such as fiber-optic cables

Siemens IK PI News July 2007 5/35


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro RFID Systems
SIMATIC RF180C

Function Technical specifications


The SIMATIC RF180C comprises a basic module and a connec- Type SIMATIC RF180C
tion block that must be ordered separately. Supply voltage
The connection block is available in the version M12, 7/8''. Rated value 24 V DC
PROFINET is connected through an M12 plug, whereas the sup-
ply voltage is connected through a 7/8'' plug. There are 2 con- Permissible range 20 to 30 V DC
nections for PROFINET as well as for the power supply. This en- Current consumption
sures that SIMATIC RF180C can be connected to additional bus Without reader, typ. 100 mA
stations without the need for external distribution devices. The
removable connection block allows a base module to be re- With two readers, max. 1000 mA
placed without interrupting the supply voltage to other bus sta- Serial reader interface
tions. (gross transmission rate)
SIMATIC RF180C is integrated in SIMATIC STEP 7 via the GS- MOBY I/E 19200 bit/s
DML file. SIMATIC RF180C can then be configured via the SW MOBY U/D, RF300 19200, 57600, 115200 bit/s
tool HW_Config of SIMATIC Manager or another PROFINET tool.
Cable connector 2 x connector plug M12, 7-pin
A pre-assembled reader cable is used to connect one or two
readers to the communication module. The standard cable Cable lengths to the reader
length is 2 m. If other reader cable lengths are required, an ex- Standard lengths 2m
tension cable from 2 to 50 m in length can be used. The cable Optional pre-assembled cable 5 m, 10 m, 20 m, 50 m
can also be assembled by the customer as required.
Self-assembled cable Reader/SLG-dependent.
5 The data in the transponder can be accessed in the following
manner: Direct addressing via absolute addresses
Up to 1000 m
Supply voltage to the reader 24 V
Error messages and operating states (tag in field, transfer, etc.) Max. current per reader
are also displayed on LEDs and support commissioning and
service. 2 readers connected 0.5 A

SIMATIC RF180C has two reader interfaces from which the read- 1 reader connected 1.0 A
ers are also supplied with voltage. There is a solid-state fuse in Ambient temperature
SIMATIC RF180C for the reader power supply. The maximum
During operation -0 ... 60 C
current permitted for the readers per SIMATIC RF180C is 1 A. It
is not important here whether the current is drawn by 1 or 2 read- During storage -40 ... +70 C, 20 K/h
ers. Shock load during operation 30 g
The application accesses the tag via FB45. FB45 accesses the acc. to IEC 61131-2
tag via absolute addresses. For large volumes of data and com- Vibratory load during operation 0.75 mm (10 Hz to 58 Hz)
plex tag operations, the FB45 can process chained commands. acc. to IEC 61131-2 10 g (58 Hz to 150 Hz)
Data is exchanged between SIMATIC RF180C and the applica- Housing
tion by means of acyclic data records. This ensures that a large
Material Thermoplastic
quantity of data can be transferred from/to SIMATIC RF180C (fiberglass reinforced)
without loading the bus cycle. This is advantageous when large
volumes of data are being transferred. SIMATIC RF180C can Color IP Basic 714
also process chained tag commands in this mode extremely Degree of protection IP67
quickly.
Dimensions (W x H x D) in mm
SIMATIC RF180C 60 x 210 x 30
without connection block
SIMATIC RF180C 60 x 210 x 54
with connection block
Weight
Base module only 210 g
Connection block only 230 g

5/36 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro RFID Systems
SIMATIC RF180C

Ordering data Order No. Order No.


SIMATIC RF180C 6GT2 002-0JD00 Accessories for connection to the network
communication module
PROFINET cable 6XV1 870-8Axxx1)
For PROFINET, for connecting 2 with M12 plugs, pre-assembled
readers; without a connection for trailing
block
Cable for supply voltage pre- 6XV1 822-5Bxxx1)
Accessories for MOBY assembled with 7/8'' plugs
Connection block 6GT2 002-1JD00 PROFINET standard cable 2x2 6XV1840-2AH10
for SIMATIC RF180C
Type A, not pre-assembled;
for connecting 2 readers over an minimum order quantity 20 m
M12 cable connector
PROFINET M12 plug connector 6GK1901-0DB10-6AA0
SLG cable for MOBY I/E/U 6GT2 091-0FH20
2m rugged metal housing;
fast connect system; D-coded
SLG cable for MOBY I/E/U 6GT2 091-0FH50 (pack of 1)
5m
7/8'' cable connector
SLG cable for MOBY D 6GT2 691-0FH20 for voltage (pack of 5)
2m
With male insert 6GK1 905-0FA00
SLG cable for RF300 6GT2 891-0FH20
With female insert 6GK1 905-0FB00
Extension cable for MOBY
I/E/U/D/RF300; 2 m IE M12 cabinet bushing 6GK1901-0DM20-2AA5
SLG cable for RF300
Extension cable for MOBY
6GT2 891-0FH50
for conversion from M12
(D-coded) to RJ45; (pack of 5) 5
I/E/U/D/RF300; 5 m IE FC RJ45 PLUG 180 6GK1901-1BB10-2AA0
RJ45 plug connector
SLG cable for RF300 6GT2 891-0FN10
with rugged metal housing and
Extension cable for MOBY
FC connection system; straight
I/E/U/D/RF300; 10 m cable outlet (pack of 1)
SLG cable for RF300 6GT2 891-0FN20
Extension cable for MOBY
I/E/U/D/RF300; 20 m
SLG cable for RF300 6GT2 891-0FN50
Extension cable for MOBY
I/E/U/D/RF300; 50 m
M12 sealing caps for unused 3RX9 802-0AA00
reader connections
(10 units)
Industrial Ethernet Switches
SCALANCE X-200
Industrial Ethernet switches with
integral SNMP access, online
diagnostics, copper cable diag-
nostics and PROFINET diag-
nostics for configuring line, star
and ring topologies;
with eight 10/100 Mbit/s M12 6GK5 208-0HA00-2AA6
ports, incl. eleven M12 dust
protection caps, IP65 degree of
protection
1) This cable is available in different lengths
(see Catalog IK PI 2007 or in the Internet under:
http://www.siemens.com/automation/mall)

Siemens IK PI News July 2007 5/37


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro motor starters
Standard and High-Feature
Isolator modules
Overview
The isolator module with switch disconnector function is used for
safe disconnection of the 400 V operational voltage during repair
work in the plant and provides an integrated group fusing
function (i.e. additional group short-circuit protection for all sub-
sequently supplied motor starters).
Depending on the power distribution concept, all stations can be
equipped with an isolator module as an option.
Safety applications
Safety local isolator module
With the Safety local modules
Safety local isolator module and
400 V disconnecting module
it is possible to achieve safety category 4/SIL 3 with an appropriate
connection.
Safety Solution PROFIsafe
With the Safety PROFIsafe modules
Motor starters F-Switch and
5 Only two variants up to 5.5 kW
All settings can be parameterized by bus
400 V disconnecting module
it is likewise possible to achieve safety category 4/SIL 3 with an
Comprehensive diagnostics signals appropriate connection.
Overload can be acknowledged by remote reset
Current unbalance monitoring Benefits
Stall protection ET 200pro motor starters provide the following advantages:
Emergency start function in the event of overload High flexibility thanks to a modular and compact design
Current value transmission by bus Little variance among all motor starter versions
Current limit monitoring (2 units up to 5.5 kW)
Direct-on-line or reversing starters Extensive parameterization using STEP 7 HW-Config
Power bus can be plugged in using the new Increase of plant availability through fast replacement of units
HAN Q4/2 plug-in connectors (easy mounting and plug-in technology)
Conductor cross-sections up to 6 x 4 mm Extensive diagnostics and information for preventive
25 A per segment maintenance
(power looped through using jumper plug)
Parameterizable inputs for local control functions
In the Standard and High-Feature versions (High-Feature)
(with 4 DI onBoard)
Cabinet-free construction thanks to high degree of
Electromechanical switching and electronic switching protection IP65.
Electronic starter for direct activation or with integrated
smooth starter function
Supplied with 400 V AC brake contact as an option

5/38 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro motor starters
Standard and High-Feature

Application
With the ET 200pro motor starters, any three-phase loads can be As the result of the protection concept with solid-state overload
protected and switched. They are an integral part of ET 200pro evaluation and the use of SIRIUS controls size S00, additional
and have the high degree of protection IP65. This makes them advantages are realized on the standard and High-Feature motor
ideal for operation in modular, distributed peripherals without starters advantages which soon make themselves positively
control cabinets or control enclosures. felt particularly in manufacturing processes with high plant
The ET 200pro motor starters are available both with mechanical stoppage costs:
as well as electronic contacts. Configuration is made easier by the fine modular structure.
When using the ET 200pro motor starters, the list of parts per
The ET 200pro electromechanical starters are offered as direct load feeder is reduced to two main units: the bus module and
(DSe/DSe) and reversing starters (RSe/RSe) in the High-Feature the motor starter. This makes the ET 200pro ideal for modular
version with the following features: machine concepts or solutions for conveying systems and in
4 digital inputs machine-tool building.
Device versions with or without control for externally fed Expansions are easily possible through the subsequent adding
brakes with 400 V AC of modules. The innovative plug-in technology also does away
With expanded parameterization capabilities. with the wiring needed up to now. Through the hot swapping
function (disconnection and connection during operation) a
The ET 200pro electronic starters are offered as direct motor starter can be replaced within seconds if necessary,
(DSe/DSe) and reversing starters (RSe/RSe) in the High-Feature without having to shut down the ET 200pro station and with it
version with the following features: the process in the plant. The motor starters are therefore
4 digital inputs recommendable in particular for applications with special
With soft-starting and soft ramp-down function
With deactivated smooth start function as an electronic starter
demands on availability. Storage costs are optimized in
addition by the low level of variance (2 units up to 5.5 kW). 5
for applications with a high level of switching frequency The ordering option for motor starters with a 400 V AC brake
output provides the possibility of controlling motors with
Device versions with or without control for externally fed 400 V AC brakes. With four locally acting inputs available on the
brakes with 400 V AC High-Feature motor starter it is possible to realize autonomous
With expanded parameterization capabilities special functions which work independently of the bus and the
higher-level control system, e.g. as a quick stop on gate valve
controls or limit position disconnectors. In parallel with this, the
states of these inputs are signaled to the control system.
When using the optional isolator module with switch disconnec-
tor and group fusing function for the ET 200pro, the 400 V supply
of the motor starters can be switched on and off directly in the
field, i.e. locally.

Siemens IK PI News July 2007 5/39


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro motor starters
Standard and High-Feature

Technical specifications
Motor starters, Motor starters, High-Feature
Standard
DSe, RSe DSe, RSe sDSSte, sDSte,
sRSSte, sRSte
General data
Motor starters that can be connected to ET 200pro or modules Max. 8
with a width of 110 mm
Mounting dimensions (W x H x D) in mm
Direct-on-line starter and reversing starter 110 x 230 x 150 110 x 230 x 160
Permissible ambient temperature
During operation -25 ... +55 C, from +40 C with derating
During storage -40 ... +70 C
Permissible mounting positions Vertical, horizontal
Vibration resistance according to IEC 60068, Part 2-6 2g
Shock resistance according to IEC 60068, Part 2-27 Half-sine 15 g/11 ms
Power consumption 24 V DC
From auxiliary circuit L+/M (U1) Approx. 40 mA

5 From auxiliary circuit A1/A2 (U2)


Rated operational current for power bus Ie
Approx. 200 mA
25
Rated operational voltage Ue 400 V AC
Approval according to EN 60947-1, Appendix N Up to 200 V AC Up to 400 V AC
Approval according to CSA and UL Up to 600 V AC Up to 480 V AC
Approval according to DIN VDE 0106, Part 101 Up to 500 V AC Up to 480 V AC
CSA and UL approval Up to 600 V AC Up to 480 V AC
Conductor cross-sections
Incoming energy supply max. 6 x 4 mm2
Degree of protection IP65
Touch protection Touch protection
Degree of pollution 3, IEC 60664 (IEC 61131)
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 400 V
Rated operational current for starters Ie
AC-1/2/3 at 40 C
- At 400 V 0.15 ... 2.0 A/1.5 ... 12.0 A 0.15 ... 2.0 A/1.5 ... 12.0 A1)
- At 500 V 0.15 ... 2.0 A/1.5 ... 9.0 A
AC-4 at 40 C
- At 400 V 0.15 ... 2.0 A/1.5 ... 4.0 A
Rated short-circuit breaking capacity 100 kA at 400 V
Type of coordination according to IEC 60947-4-1 1
Power of induction motors at 400 V Max. 5.5 kW Max. 5.5/4 kW 2)
Utilization categories AC-1, AC-2, AC-3, AC-4 AC-53a3) (max. 9 A with
deactivated soft starter
function up to CLASS 10)
Safe isolation between main and auxiliary circuits 400 V, according to EN 60947-1, Appendix N
Service life of contactor
Mechanical 30 million operating cycles --
Electrical Up to 10 million operating cycles; dependent --
on the current loading (see Manual)
Reliable switching frequency Dependent on the current loading, motor starting time and relative ON
period (see Manual)
Operating times at 0.85 ... 1.1 x Ue
Closing delay 11 ... 50 ms --
Opening delay 5 ... 45 ms --
1) Caution!
With deactivated soft starter control function the the permissible rated
operational current is reduced to 9 A up to CLASS 10.
2) With parameterization as electronic starter max. 4 kW.
3) 8-hour operation.

5/40 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro motor starters
Standard and High-Feature

Technical specifications (continued)


Motor starters, Standard Motor starters, High-Feature
DSe, RSe DSe, RSe sDSSte, sDSte,
sRSSte, sRSte
Device functions
Parameterizable rated operational current Yes
Parameterizable current limit values No Yes, 2 limit values
Parameterizable response in case of current limit violation No Yes
Zero current monitoring Yes
Parameterizable response in case of zero current violation Yes
Parameterizable current unbalance limit No, fixed limit value Yes, 30 % ... 60 % x Ie
(30 % x Ie)
Parameterizable response in case of unbalance limit violation Yes
Motor blocking monitoring No Yes
Parameterizable blocking current limit value No Yes, 150 % ... 1000 % x Ie
Parameterizable blocking time limit value No Yes, 1 ... 5 s
Current value transmission Yes
Group warning diagnostics No Yes, parameterizable 5
Group diagnostics Yes, parameterizable
Emergency start Yes
Digital inputs No Yes, 4 inputs
Parameterizable input signal No Yes, latching/ non-latching
Parameterizable input level No Yes, NC contacts/NO contacts
Parameterizable input signal delay No Yes, 10 ... 80 ms
Parameterizable input signal extension No Yes, 0 ... 200 ms
Parameterizable input control actions No Yes, 12 different actions
400 V brake output Yes, ordering option
Parameterizable brake enabling delay Yes, -2.5 ... 2.5 s
Parameterizable holding time of the brake during stopping Yes, 0 ... 25 s
Parameterizable start-up type No Yes
Parameterizable ramp-down time No Yes
Parameterizable starting voltage No Yes
Parameterizable stop voltage No Yes
Local device interface Yes
Firmware update Yes, by trained personnel
Thermal motor model Yes
Parameterizable trip class No, CLASS 10 fixed Yes, CLASS 5, 10, 15, 20
Parameterizable response in case of overload of thermal motor model No Yes, 3 possible states
Advance warning limit for motor heating No Yes, parameterizable 0 ... 95 %
Advance warning limit time-related trip reserve No Yes, parameterizable 0 ... 500 s
Parameterizable recovery time No Yes, 1 ... 30 min
Parameterizable zero voltage safety No, permanently inte- Yes
grated
Reversing start function Yes, ordering option
Parameterizable interlock time for reversing starters No, 150 ms fixed Yes, 0 ... 60 s
Integrated logbook functions Yes, 3 device logbooks
Integrated statistics data memory Yes
Parameterizable response in case of CPU / master stop Yes
Device indications
Group fault SF LED (red)
Switching state STATE LED ( red, yellow, green)
Device status DEVICE LED ( red, yellow, green)
Digital inputs No IN 1 ... IN 4, LED

Siemens IK PI News July 2007 5/41


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro motor starters
Standard and High-Feature

Selection and ordering data


Version Order No.
1)
Standard motor starters, mechanical
Motor protection: thermal model
DSe direct-on-line starters
Without brake output 3RK1 304-5 7 S40-4AA0
With brake output 400 V AC 3RK1 304-5 7 S40-4AA3
RSe reversing starters
Without brake output 3RK1 304-5 7 S40-5AA0
With brake output 400 V AC 3RK1 304-5 7 S40-5AA3

DSe standard
High-Feature motor starters, mechanical 1)
Motor protection: thermal model
DSe direct-on-line starters
Without brake output and with 4 inputs 3RK1 304-5 7 S40-2AA0

5 With brake output 400 V AC and 4 inputs


RSe reversing starters
3RK1 304-5 7 S40-2AA3

Without brake output and with 4 inputs 3RK1 304-5 7 S40-3AA0


With brake output 400 V AC and 4 inputs 3RK1 304-5 7 S40-3AA3
Setting range
of rated operational current
RSe High Feature
0.15 ... 2.0 A K
1.5 ... 12.0 A L
1) 2)
High-Feature motor starters, electronic N
Full motor protection, comprising thermal motor protection and thermistor motor protection
sDSSte/sDSte direct-on-line starters
Without brake output and with 4 inputs 3RK1 304-5 7 S70-2AA0
With brake output 400 V AC and 4 inputs 3RK1 304-5 7 S70-2AA3
sRSSte/sRSte reversing starters
Without brake output and with 4 inputs 3RK1 304-5 7 S70-3AA0
With brake output 400 V AC and 4 inputs 3RK1 304-5 7 S70-3AA3
Setting range
of rated operational current
sRSSte High-Feature
0.15 ... 2.0 A K
1.5 ... 12.0 A L
1) Only functions when used together with the backplane bus module and the wide module rack.
The backplane bus module and the wide module rack must be ordered separately (see Accessories for ET 200pro motor starters).
2) The solid-state motor starters can be used not only as solid-state motors starters with a high level of switching frequency but also as fully fledged
soft starters for soft starting and smooth ramp-down.
The changeover from motor starter to soft starter takes place through reparameterization in HW Config.
Depending on the settings, this results in the following current ranges:
- Parameterization as solid-state starter: 0.15 ... 2 A and 1.5 ... 9 A (4 kW)
- Parameterization as soft starter: 0.15 ... 2 A and 1.5 ... 12 A (5.5 kW).

5/42 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro isolator modules

Overview Technical specifications


The isolator module with integrated group fusing function Isolator module
(i.e. additional group short-circuit protection for all subsequently General data
supplied motor starters) and switch disconnector function is
used for safe disconnection of the 400 V operational voltage in Mounting dimensions (W x H x D)
the plant. in mm
Direct-on-line starter and 110 x 230 x 170
Depending on the power distribution concept, all stations can be reversing starter
equipped with an isolator module as an option.
Permissible ambient temperature
The isolator module is available in addition in a safety version
(see Safety local Isolator Modules). During operation -25 ... +55 C
During storage -40 ... +70 C
Benefits Permissible mounting positions Any
The following properties apply to the isolator module: Vibration resistance according to 2g
IEC 60068, Part 2-6
Increase of plant availability through fast replacement of units
(easy mounting and plug-in technology) Shock resistance according to Half-sine 15 g/11 ms
IEC 60068, Part 2-27
Cabinet-free construction thanks to high degree of
protection IP65. Power consumption
From auxiliary circuit L+/M (U1) Approx. 20 mA
From auxiliary circuit A1/A2 (U2) --
Rated operational current 25 A 5
for power bus Ie
Rated operational voltage Ue 400 V
Approvals according to
DIN VDE 0106, Part 101 Up to 500 V
CSA and UL Up to 600 V
Conductor cross-sections
Incoming energy supply Max. 6 x 4 mm2
Degree of protection IP65
Touch protection Touch protection
Degree of pollution 3, IEC 60664 (IEC 61131)
Rated impulse withstand voltage 6 kV
Uimp
Rated insulation voltage Ui 400 V
Rated operational current
for starters Ie
AC-1/2/3 at 40 C
- At 400 V 25 A
- At 500 V 25 A
Rated short-circuit breaking 50 kA at 400 V
capacity
Type of coordination according to 2
IEC 60947-4-1
Safe isolation between main and 400 V,
auxiliary circuits according to DIN VDE 0106,
Part 101
Device functions
Group diagnostics Yes, parameterizable
Device indications
Group fault SF LED (red)

Siemens IK PI News July 2007 5/43


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro isolator modules

Selection and ordering data


Version Order No.
ET 200pro isolator modules, mechanical
Isolator modules1)
Rated operational current 25 A 3RK1 304-0HS00-6AA0

3RK1 304-0HS00-6AA0
Safety local isolator modules 2) 3)
Rated operational current 16 A 3RK1 304-0HS00-7AA0

5
3RK1 304-0HS00-7AA0

1) Only functions when used together with the corresponding backplane bus module 110 mm and the wide module rack.
The backplane bus module and the wide module rack must be ordered separately
(see Accessories for ET 200pro motor starters).
2) The Safety local isolator module only functions when used together with the 400 V disconnecting module.
3) Only in combination with the special backplane bus module for the Safety local isolator module
(see Accessories for ET 200pro motor starter).

5/44 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Safety modules

Overview Application
Safety local isolator modules
The Safety local isolator module features the same functions as
a standard isolator module with an additional local safety function.
The Safety local isolator module contains a 3TK28 41 module
and is equipped with M12 terminals for the connection of external
safety components.
Terminals 1 and 2 can be used to connect either 1-channel or
2-channel EMERGENCY-STOP circuits or protective door
circuits (IN 1, IN 2).
For monitored starts, an external START switch can be connected
to terminal 3.
The required safety functions can be set using 2 slide switches
located under the left M12 opening.
In the event of an EMERGENCY-STOP, the Safety local isolator
module trips the downstream 400 V disconnecting module. This
safely isolates the 400 V circuit up to Cat. 4/SIL 3.

Safety local isolator modules In combination with the 400 V disconnecting module, the

The Safety local isolator module is a maintenance switch with in-


Safety local isolator module can be used for safety applications
up to Cat. 4/SIL 3.
5
tegrated safety evaluation functions that can be parameterized
using DIP switches. 400 V disconnecting modules
It is used for: The 400 V disconnecting module can be used together with the
Connection of a 1 or 2-channel EMERGENCY-STOP circuit up Safety local isolator module for local safety applications and
to category 3-4/Sil 3 (protective door or EMERGENCY-STOP together with the F-Switch for PROFIsafe safety applications.
pushbuttons) and parameterizable start behavior It contains two contactors connected in series for safety-oriented
Control of the 400 V disconnecting module by means of a disconnection of the main circuit.
safety rail signal. The auxiliary circuit supply of the device is over a safety power
400 V disconnecting modules rail in the backplane bus module.
The 400 V disconnecting module enables the safe disconnection The 400 V disconnecting module can be used together with the
of the operational voltage of 400 V up to category 3-4/Sil 3.For Safety local isolator module or with the F-Switch for safety
operation in a Safety Solution local application it functions only applications up to Cat. 4/SIL 3.
in combination with the safety local isolator module. F-Switch N
For operation in a Safety PROFIsafe application it functions only The F-Switch is a failsafe solid-state module for PROFIsafe
in combination with the F-Switch. safety applications. It has two failsafe inputs and outputs for safe
switching of the 24 V supply over backplane bus bars. In com-
F-Switch N bination with the 400 V disconnecting module it can be used in
Failsafe digital inputs/outputs in degree of protection IP65/66/67 PROFIsafe applications for the failsafe disconnection of
for near-machine, cabinet-free use. ET 200pro motor starters up to Cat. 4/SIL 3.
Failsafe digital inputs
For the failsafe reading in of sensor information
(1-/2-channel)
Including integrated evaluation
for 2v2 signals
Internal sensor supplies (incl. testing) available
Failsafe digital outputs
3 failsafe PP-switching outputs for safe switching of the back-
plane bus bars
The F-Switch is certified up to Cat. 4 (EN 954-1) and up to SIL 3
(IEC 61508) and has detailed diagnostics.
It supports PROFIsafe in PROFIBUS configurations as well as in
PROFINET configurations.

Siemens IK PI News July 2007 5/45


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Safety modules

Technical specifications
Safety local 400 V disconnecting modules
isolator modules
General data
Mounting dimensions (W x H x D) in mm
Direct-on-line starter and reversing 110 x 230 x 170 mm 110 x 230 x 150 mm
starter
Permissible ambient temperature
During operation -25 ... +55 C
During storage -40 ... +70 C
Permissible mounting positions Any
Vibration resistance according to 2g
IEC 60068, Part 2-6
Shock resistance according to Half-sine 15 g/11 ms
IEC 60068,
Part 2-27
Power consumption
From auxiliary circuit L+/M (U1) Approx. 20 mA
5 From auxiliary circuit A1/A2 (U2) --
Rated operational current for 25 A
power bus Ie
Rated operational voltage Ue 400 V
Approval according to DIN VDE 0106, Up to 500 V
Part 101
CSA and UL approval Up to 600 V
Conductor cross-sections
Incoming energy supply max. 6 x 4 mm2
Degree of protection IP65
Touch protection Touch protection
Degree of pollution 3, IEC 60664 (IEC 61131)
Rated impulse withstand 6 kV
voltage Uimp
Rated insulation voltage Ui 400 V
Rated operational current
for starters Ie
AC-1/2/3 at 40 C
- At 400 V 16 A 25 A
- At 500 V 16 A 25 A
Rated short-circuit breaking capacity 50 at 400 V
Type of coordination according to 2
IEC 60947-4-1
Safe isolation between main and 400 V, according to DIN VDE 0106, Part 101
auxiliary circuits
Operating times at 0.85 ... 1.1 x Ue
Closing delay -- 25 ... 100 ms
Opening delay -- 7 ... 10 ms
Device functions
Group diagnostics Yes, parameterizable
Device indications
Group fault SF LED (red)

5/46 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Safety modules

Selection and ordering data


Version Order No.
ET 200pro safety modules
Safety local isolator modules
Rated operational current 16 A 3RK1 304-0HS00-7AA0
The Safety local isolator module only functions when used together with the 400 V
disconnecting module.
Only in combination with the special backplane bus module for the Safety local
isolator module (see Accessories for ET 200pro motor starters).

3RK1 304-0HS00-7AA0
400 V disconnecting modules
Rated operational current 25 A 3RK1 304-0HS00-8AA0
The 400 V disconnecting module only functions when used together with the
Safety local isolator module.
Only functions when used together with the backplane bus module and the wide
module rack. The backplane bus module and the wide module rack must be
ordered separately (see Accessories for ET 200pro motor starter).
5
3RK1 304-0HS00-8AA0
F-Switch PROFIsafe N
24 V DC, 6ES7 148-4FS00-0AB0
incl. bus module
Connection module to be ordered separately

6ES7 148-1FS00-0AB0
Connection modules for F-Switch N
24 V DC 6ES7 194-4DA00-0AA0

Siemens IK PI News July 2007 5/47


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Accessories for ET 200pro motor starters

Overview

Infeed on
isolator module
1

RSM

MS MS MS MS

NSA0_00467
NSA0_00465

3 4 7

5 2 9

5 / 6

Infeed on the RSM isolator module


M M

Basic design of an ET 200pro motor starter

Legend:
Infeed on $ Power feeder plug, see Seite 49
Motorstarter ET 200pro
% Power connection plug, see Seite 49
& Power jumper plug, see Seite 49
( Motor connection plug, see Seite 49
MS MS ) Motor plug, see page 49
* Motor plug with EMC suppressor circuit, see page 49
+ Power loop-through plug, see page 49
, Power connection cable, see page 49
NSA0_00466

- Power connection cable for isolator modules, see page 49


. Motor cable, see page 49

10
8

Infeed on the ET 200pro motor starter

5/48 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Accessories for ET 200pro motor starters

Selection and ordering data


Version Order No.
ET 200pro accessories
$ Power feeder plugs N
Connector set for energy supply, e.g. for connecting to T terminal connectors,
comprising a coupling enclosure, straight outgoing unit (with bracket),
pin insert for HAN Q4/2, incl. gland
5 male contacts 2.5 mm2 3RK1 911-2BS60
5 male contacts 4 mm2 3RK1 911-2BS20
5 male contacts 6 mm2 3RK1 911-2BS40
% Power connection plugs
Connector set for energy supply for connection to ET 200pro motor starters/
ET 200pro isolator modules,
comprising a cable-end connector hood, angled outgoing unit,
female insert for HAN Q4/2, incl. gland
5 female contacts 2.5 mm2 3RK1 911-2BE50
5 female contacts 4 mm2 3RK1 911-2BE10
2
5 female contacts 6 mm 3RK1 911-2BE30
& Power jumper plugs
( Motor connection plugs
3RK1 922-2BQ00
5
Connector set for motor cable for connection to ET 200pro motor starters,
comprising a cable-end connector hood, angled outgoing unit,
pin insert for HAN Q8/0, incl. gland
8 male contacts 1.5 mm2 3RK1 902-0CE00
2
6 male contacts 2.5 mm 3RK1 902-0CC00
) Motor plugs N
Connector set for motor cable for connection to motors,
comprising a cable-end connector hood, straight outgoing unit,
female insert for HAN 10e, incl. star jumper, incl. gland
7 female contacts 1.5 mm2 3RK1 911-2BM21
7 female contacts 2.5 mm2 3RK1 911-2BM22
* Motor plugs with EMC suppressor circuit N
Connector set for motor cable for connection to motors,
comprising a cable-end connector hood, straight outgoing unit,
female insert for HAN 10e with EMC suppressor circuit,
incl. star jumper, incl. gland
7 female contacts 1.5 mm2 3RK1 911-2BL21
7 female contacts 2.5 mm2 3RK1 911-2BL22
+ Power loop-through plugs N
Connector set for power supply for connection to ET 200pro motor starters/
ET 200pro isolator modules,
comprising a cable-end connector hood, angled outgoing unit,
pin insert for HAN Q4/2, incl. gland
4 male contacts 2.5 mm2 3RK1 911-2BF50
4 male contacts 4 mm2 3RK1 911-2BF10
, Power connection cables, assembled at one end
Power connection cable for ET 200pro motor starters,
N
ECOFAST, open at one end, for HAN Q4/2,
angled, insert turned at isolator module end, 4 x 4 mm2
Length 1.5 m 3RK1 911-0DB13
Length 5.0 m 3RK1 911-0DB33
- Power connection cables for isolator modules, assembled at one end
Power connection cable for ET 200pro isolator modules, open at one end,
N
for HAN Q4/2, angled, insert turned at isolator module end, 4 x 4 mm2
Length 1.5 m 3RK1 911-0DF13
Length 5.0 m 3RK1 911-0DF33
. Motor cables, assembled at one end
Open at one end, HAN Q8, angled,
N
length 5 m
Motor cable for motor without brake, for ET 200pro, ET 200X, AS-i Compact, 4 x 1.5 mm2 3RK1 911-0EB31
Motor cable for motor with brake, for ET 200pro, 6 x 1.5mm2 3RK1 911-0ED31

Siemens IK PI News July 2007 5/49


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
Accessories for ET 200pro motor starters

Selection and ordering data (continued)


Version Order No.
Wide module racks1)
Length 500 mm 6ES7 194-4GB00-0AA0
Length 1000 mm 6ES7 194-4GB10-0AA0
Length 2000 mm 6ES7 194-4GB20-0AA0
Module racks, wide, compact1)
Length 500 mm 6ES7 194-4GD00-0AA0
Length 1000 mm 6ES7 194-4GD10-0AA0
Length 2000 mm 6ES7 194-4GD20-0AA0
Backplane bus modules 110 mm2) 3RK1 922-2BA00
Backplane bus module for Safety local isolator module 3RK1 922-2BA01
RS 232 interface cables 3RK1 922-2BP00
Hand-held devices 3RK1 922-3BA00
For ET 200pro motor starters, (also for ET 200S High-Feature and ECOFAST),
for local operation.
A serial interface cable must be ordered separately.
5 Sealing caps (for power supply)
(1 pack contains 10 units)
3RK1 902-0CJ00

Dismantling tools for HAN Q4/2 N 3RK1 902-0AB00


Crimping tools for pins/sockets 4 mm2 and 6 mm2 N 3RK1 902-0CW00

3RK1 922-3BA00
Crimping tools for male contacts and sockets up to 4.0 mm2 (HAN Q8/0) 3RK1 902-0CT00
Dismantling tools for male contacts and sockets (HAN Q8/0) 3RK1 902-0AJ00
M12 sealing caps N
For sealing unused input and output sockets
3RX9 802-0AA00

(one set contains ten sealing caps)


1) The module rack can accommodate all ET 200pro motor starters and
any optional modules (isolator module, Safety local isolator module
and 400 V disconnecting module).
2) The backplane bus module is a prerequisite for operation of the
ET 200pro motor starter and the optional module.

5/50 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro FC Frequency Converter

Overview Benefits
The frequency converter is completely integrated into the
ET 200pro system and offers all the system advantages such
as cabinet-free installation, easy mounting on the module car-
rier, reduction of the wiring overhead due to self-assembling
communication and supply rails in the backplane bus, com-
prehensive diagnostic mechanisms and high availability
thanks to replaceability without affecting other modules in the
ET 200pro station.
The load voltage is routed to downstream frequency convert-
ers or motor starters with minimal installation costs through
pre-assembled jumper plugs. The maximum current carrying
capacity of the jumper plugs is 25 A.
Easy combination and expansion of converter functionality
using I/O modules or RSM isolator modules within the distrib-
uted station.
Input for PTC/KTY encoder for comprehensive motor protec-
tion
The integral 180 V DC brake control makes the rectifier in the
motor terminal box superfluous
Slot for optional memory card (MMC) to save the parameter
settings for fast replacement of modules with automatic repa-
rameterization
5
Available control modes: Frequency control, sensorless
vector control or torque control
STARTER, the graphical parameterization tool for Siemens
drives, is used to set the parameters either over the connected
fieldbus or over a point-to-point connection
Note: Access to the frequency converter over the bus is not
possible using STARTER when a CPU is located between the
PC and a frequency converter. This also applies to the
IM154-8 CPU.
Active and dynamic braking of the motor is possible without
incurring any additional costs. The generated braking energy
is fed back into the power supply, so there is no need for
braking choppers and pulse resistors.
The fail-safe version of the frequency converter offers auto-
nomous, certified safety functions that ensure that persons
and machines are protected from the dangerous movement of
machines. Integration of the safety system into the drive also
simplifies the machine architecture and supports system-wide
diagnostics.
Minimum reaction time of the fail-safe frequency converter to
signals of safe sensors thanks to local activation through the
Safety Local Isolator Module F-RSM or via field bus with the
PROFIsafe F-Switch module.

ET 200pro FC Standard frequency converter and converter with


integral safety functions

Two versions with and without integral safety functions


1.1 kW output (1.5 kW at max. 45 C ambient temperature)
Sensor-free vector control, frequency control or torque control
Integral brake control 180 V DC
Regenerative feedback
Power is looped through using jumpers with 25 A per segment
Easy parameterization over the bus
Extensive diagnostics

Siemens IK PI News July 2007 5/51


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro FC Frequency Converter

Application Design
The frequency converter controls the speed of asynchronous
motors steplessly
The modular, service-friendly concept of the frequency con-
verter is ideally suited to manufacturing processes with high
plant standstill costs
Optimal solutions can be created using several frequency
converters combined in one distributed station when drives
are operated in the same area or for the same purposes.
The frequency converter handles frequency control for simple
applications as well as vector control for more complex drive
tasks. It also handles the optimal control of a motor brake,
if used.
The converter also supports torque control, for example, for Installation of an ET 200pro station with 2 ET 200pro FC frequency
applications with mechanically coupled drives converters with integral safety functions
The advantages of line-commutated power regeneration are
primarily evident in continuous regenerative operation. The ET 200pro FC consists of the following components:
Examples include unwinding units, lowering of loads, or ET 200pro FC Standard frequency converter or converter with
dynamic braking of large centrifugal masses. integral safety functions
The integral safety functions significantly reduce the overhead Special backplane bus module to hold the frequency
5 for drive solutions in plant sections where there is a hazard
potential. Additional savings can be made thanks to sensor-
converter

less speed monitoring of standard asynchronous motors. Accessories


The following accessories are available:
Description Order No.
Connector set
for power supply, HanQ4/2
2.5 mm 3RK1911-2BE50
4.0 mm 3RK1911-2BE10
6.0 mm 3RK1911-2BE30
Pre-assembled motor cable
with connector on one end,
shielded, HanQ8
Length 1.5 m 6ES7194-1LA01-0AA0
Length 3 m 6ES7194-1LB01-0AA0
Length 5 m 6ES7194-1LC01-0AA0
Length 10 m 6ES7194-1LD01-0AA0
Frequency converter connector 6ES7194-1AB01-0XA0
for motor cable, shielded, HanQ8
Power jumper plug 3RK1922-2BQ00
for 400 V power transmission
to following 400 V modules
RS232 interface cable 3RK1922-2BP00
for parameterizing the converter
with the STARTER tool via a direct
point-to-point connection
Memory card (MMC) 6SL3254-0AM00-0AA0
for parameter settings of the
ET 200S FC and ET 200pro FC

If required, the complete parameter settings of the frequency


converter can be saved on a memory card (MMC).
When servicing, the plant is immediately ready for use again
after replacing the frequency converter and inserting the
memory card.

5/52 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro FC Frequency Converter

Technical specifications
ET 200pro frequency converter ET 200pro frequency converter
with integral safety functions with integral safety functions
Selection features Functions
Integral safety functions according Safe Torque Off (STO) Open-loop/closed-loop V/f control linear (M~n)
to Category 3 of EN 954-1 and Safely Limited Speed (SLS)1) control procedure with/without flux current control
according to SIL 2 of IEC 61508 Safe Stop 1 (SS1) 1) (FCC), quadratic (M~n 2) or pa-
Activation of the integral safety rameterizable
functions through Safety Local Vector closed-loop control with-
Isolator Module F-RSM or out encoder
through PROFIsafe F-Switch Closed-loop torque control
Electrical data Operating functions Jogging mode, free function
blocks (FFB), positioning deceler-
Line voltage 3 AC 380 V to 480 V +10% / -10% ation ramp, automatic restart fol-
Output 1.1 kW lowing interruption due to power
(at 0 C to 55 C ambient tempera- failure, bumpless connection of
ture) converter to rotating motor
Rated input current 2.0 A Braking functions Regenerative braking operation
(at 0 C to 55 C ambient tempera- without brake chopper and pulse
ture) resistor
Contol of an electromagnetic
Rated output current 3.5 A holding brake
(at 0 C to 55 C ambient tempera-
ture)
Protective functions Undervoltage, overvoltage,
ground faults, short circuits, stall
5
Output 1.5 kW prevention, thermal motor
(at 0 C to 45 C ambient tempera- protection I2t, or sensor), con-
ture) verter overtemperature, motor
blocking protection
Rated input current 2.5 A
(at 0 C to 45 C ambient tempera- Connectable motors Low-voltage asynchronous mo-
ture) tors
Motor cable lengths: max. 15 m
Rated output current 3.9 A (shielded)
(at 0 C to 45 C ambient tempera-
ture) Mechanical data
Line frequency 47 Hz to 63 Hz Degree of protection IP65
Overload capability Overload current 1.5 x rated out- Operating temperature 0 C to +55 C
put current (i.e. 150% overload) Increased output
for 60 s, cycle time 300 s at 0 C to +45 C
Overload current 2 x rated out-
put current (i.e. 200% overload) Mounting position Vertical wall mounting (vertical
for 3 s, cycle time 300 s alignment of the cooling fins)

Output frequency 0 Hz to 650 Hz Mounting dimensions 155 x 230 x 213


(W x H x D) in mm
Pulse frequency 4 kHz (standard), (including terminal module)
2 kHz to 16 kHz (in 2 kHz steps)
Weight 2.5 kg
SCCR 10 kA
(Short Circuit Current Rating)2) Standards

Skipped frequency range 1, programmable Compliance with standards UL, cUL ,CE, c-tick, Low Voltage
Directive 73/23/EEC, EMC Direc-
Converter efficiency 96% tive 89/336/EEC
Interfaces Connection to PROFIBUS
(PROFINET available soon) over
the ET 200pro backplane bus
Optical interface with USS proto-
col for optical RS232 connecting
cable
Slot for an optional memory card
(MMC) for uploading or down-
loading parameter settings
PTC/KTY84 interface for motor
temperature monitoring
1) The safety functions "Safely limited speed" and "Safe stop 1" are
certified for asynchronous motors without encoders - these safety
functions are not permitted for pull-through loads as in the case of
lifting gear and winders.
2) Valid for industrial control cabinet installation according to NEC Article
409 / UL 508A. Additional information is available in the Internet under:
http://support.automation.siemens.com/ww/view/en/23995621

Siemens IK PI News July 2007 5/53


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200pro Motor Starters and Frequency Converters
ET 200pro FC Frequency Converter

Technical specifications (continued)


Derating data Pulse frequency
Ambient temperature Rated output current in A
C at a pulse frequency of
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
0 55 (1.1 kW) 3.5 3.5 2.8 2.2 1.6 1.1 0.5 -
0 45 (1.5 kW) 3.9 3.9 3.9 3.9 3.4 3.0 2.6 2.2

Ordering data
Order No.
ET 200pro FC frequency converter with integral safety functions 6SL3235-0TE21-1SB0
380 V 480 V 3 AC +10/-10%
47 Hz 63 Hz
Overload:
150% 60 s
200% 3 s
Output:
5 1.1 kW (0 55 C)
1.5 kW (0 45 C)

ET 200pro FC Standard frequency converter 6SL3235-0TE21-1RB0


380 V 480 V 3 AC +10/-10%
47 Hz 63 Hz
150%, 60s
200% 3s
Output:
1.1 kW (0 55 C)
1.5 kW (0 45 C)

Backplane bus module to hold the frequency converter 6SL3260-2TA00-0AA0

Dimensional drawings

Grounding point
Clearance required
50

Mounting rail
24
36

due to heat build-up


Bus module
G_D011_EN_00088

279.5
230

Frequency
Converter

Grounding point

62 155
248

ET 200pro FC frequency converter with backplane bus module and mounting rail

5/54 Siemens IK PI News July 2007


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200M
IM 153-4 PN

Overview Technical specifications


6ES7 153-4AA00-0XB0
Supply voltages
Rated value
DC 24 V Yes
Power supply and voltage jumper-
ing
Mains/voltage failure jumpering 5 ms
Current consumption
Current consumption, max. 600 mA
Power loss, typ. 6W
Address area
Adressing volume
Outputs 192 Byte
Inputs 192 Byte
Hardware config.
To connect ET 200M to PROFINET IO (via copper line, RJ45)
Number of modules per DP slave 12
as an IO device
Integrated 2-port switch
interface, max. 5
Status information/alarms/diag-
12 modules per station nostics
Usable I/O capacity: 192 byte each Diagnostics indication LED
Active bus backplane to hot-swap modules available as an Connection to network LINK Yes
option (green)
Baud rate 10 Mbit/s / 100 Mbit/s (autonegotiation / full duplex) Transmit/receive RX/TX (yellow) Yes
I&M functions according to PNO Guideline Order No. 3.502, Environmental requirements
Version V1.1
Operating termperature
min. 0 C
max. 60 C
Degree and class of protection
IP 20 Yes
Dimensions
Width 40 mm
Height 125 mm
Depth 118 mm
Weights
Weight, approx. 215 g

Siemens IK PI News July 2007 5/55


Siemens AG 2007

Distributed I/O SIMATIC ET 200


ET 200M
IM 153-4 PN

Ordering data Order No. Order No.


IM 153-4 PN interface module 6ES7 153-4AA00-0XB0 S7 Manual Collection 6ES7 998-8XC01-8YE0
I/O device to connect an ET 200M Electronic manuals on DVD,
to PROFINET multi-language:
S7-200, TD 200, S7-300, M7-300,
Accessories C7, S7-400, M7-400, STEP 7,
Bus modules for ET 200M Engineering Tools, Runtime Soft-
ware, SIMATIC DP (Distributed
To accommodate a power 6ES7 195-7HA00-0XA0
I/O), SIMATIC HMI (Human
supply and an IM 153 for the hot-
Machine Interface), SIMATIC NET
swapping function during RUN,
(Industrial Communication)
incl. bus module cover
To accommodate two 40 mm 6ES7 195-7HB00-0XA0 S7 Manual Collection update 6ES7 998-8XC01-8YE2
wide I/O modules for the service for 1 year
swapping function Scope of delivery:
To accommodate one 80 mm 6ES7 195-7HC00-0XA0 Current DVD "S7 Manual Collec-
wide I/O module for the tion" and the three subsequent
swapping function updates
SIMATIC Micro Memory Card 6ES7 953-8LF20-0AA0 Industrial Ethernet
FC RJ45 Plug 90
64 KB1)
RJ45 plug connector for Industrial
SIMATIC DP DIN rail Ethernet with a rugged metal
for ET 200M housing and integrated insulation

5 To accommodate up to 5 bus
modules for
displacement contacts for con-
necting Industrial Ethernet FC
installation cables;
Length 483 mm 6ES7 195-1GA00-0XA0 with 90 cable outlet
Length 530 mm 6ES7 195-1GF30-0XA0 1 unit 6GK1 901-1BB20-2AA0
SIMATIC S7-300 DIN rail 10 units 6GK1 901-1BB20-2AB0
Length 160 mm 6ES7 390-1AB60-0AA0 50 units 6GK1 901-1BB20-2AE0
Length 480 mm 6ES7 390-1AE80-0AA0 Industrial Ethernet
FastConnect
Length 530 mm 6ES7 390-1AF30-0AA0 installation cables
Length 830 mm 6ES7 390-1AJ30-0AA0 FastConnect standard cable 6XV1 840-2AH10
Length 2,000 mm 6ES7 390-1BC00-0AA0 FastConnect trailing cable 6XV1 840-3AH10
FastConnect marine cable 6XV1 840-4AH10
Industrial Ethernet 6GK1 901-1GA00
Fast Connect Stripping Tool
1) To operate the IM153-4, an MMC is required with at least 64 KB
memory. Cards with higher memory capacity may also be used.

7