You are on page 1of 135

s

Medium Voltage Technology


Switchgear Application Guide
s

Medium Voltage Technology


Switchgear Application Guide

A Selection of Switching Devices

B Switching Duties in MV networks Overview on page 20

C Characteristic Values of Switching Devices

D Selection of HRC Fuses

E Selection of Surge Arresters

F Switchgear Configuration

G Influences and Stress Variables

H Selecting and Rating Switchgear Overview on page 90

I Annexes

J Standards

Dipl. Ing. Ansgar Mller


Siemens AG
Energy Sector
E D MV ST
P.O. Box 3220
91050 Erlangen
Germany
E-Mail: ansgar.mueller@siemens.com
Edition 12E3 2011-07

Siemens AG 12E3 3
Contents

CONTENTS
A Selection of the Appropriate Device .......................................................... 11
A1 Selection criteria ................................................................................................................11
A2 Suitability under normal operating conditions...................................................................12
A3 Suitability under fault conditions.......................................................................................12
A4 Switching frequency and endurance classes ......................................................................13
A 4.1 Circuit-breaker ...................................................................................................................13
A 4.2 Switches and switch-disconnectors....................................................................................15
A 4.3 Contactos............................................................................................................................16
A 4.4 Disconnectors and earthing-switches.................................................................................17
A 4.5 Three-position switching devices.......................................................................................17
A 4.6 Guidance for use ................................................................................................................18
A5 Aspects of selection for disconnectors...............................................................................19

B Switching Duties in Medium Voltage Networks....................................... 20


B1 Overview............................................................................................................................20
B2 Distribution transformers ...................................................................................................22
B3 Unit transformer.................................................................................................................22
B4 Petersen (arc suppression) coil...........................................................................................23
B 4.1 Overvoltage protection.......................................................................................................23
B 4.2 Selection of surge arresters ................................................................................................23
B5 Cable or overhead line .......................................................................................................24
B6 Cable or line with short-circuit limiting reactor.................................................................24
B7 Compensation coils (shunt reactors) ..................................................................................26
B8 Motors ................................................................................................................................26
B 8.1 Overvoltage protection for motors.....................................................................................27
B 8.2 Direct connected motor (direct on line) .............................................................................27
B 8.3 Motor with transformer (unit) ............................................................................................28
B 8.4 Motor with starting transformer.........................................................................................29
B 8.5 Motors with starting converter...........................................................................................30
B 8.6 Motors with their own p.f. improvement ...........................................................................31
B9 Generators ..........................................................................................................................32
B 9.1 Selection of the circuit-breaker ..........................................................................................32
B 9.2 Overvoltage protection.......................................................................................................33
B 9.3 Generators with Ik" 600 A feeding into a cable system ..................................................33
B 9.4 Generator-transformer unit ................................................................................................33
B 9.5 Generators connected to the HV grid.................................................................................35
B 10 Furnace transformer ...........................................................................................................35
B 10.1 Insulation co-ordination for operating voltages above 36 kV............................................36
B 10.2 Protective measures against overvoltage ...........................................................................36

Siemens AG 12E3 5
Contents

B 11 Converter transformer ........................................................................................................37


B 11.1 Protective measures............................................................................................................37
B 11.2 Systems up to 15 kV operating voltage .............................................................................38
B 11.3 Systems above 15 kV operating voltage ............................................................................38
B 12 Capacitor banks and filter circuits .....................................................................................39
B 12.1 Capacitor banks (without reactor)......................................................................................39
B 12.2 Reactor-capacitor combinations.........................................................................................39
B 12.3 Permissible inrush current..................................................................................................40
B 12.4 Measures to limit the inrush making current .....................................................................41
B 12.5 Permissible voltage at the circuit-breaker..........................................................................43
B 12.6 Determination of the voltage on the load side of the breaker ............................................44
B 12.7 Check for permissible stress on the circuit-breaker ...........................................................45
B 13 Audio frequency ripple control systems ............................................................................46

C Rated Values of Switching Devices ............................................................ 47


C1 Overview............................................................................................................................47
C2 Rated voltage Ur .................................................................................................................48
C3 Rated insulation level Ud and Up........................................................................................48
C4 Rated normal (operating) current Ir....................................................................................48
C5 Rated short time withstand current Ik.................................................................................49
C6 Rated duration of short circuit tk ........................................................................................49
C7 Rated peak withstand current Ip .........................................................................................49
C8 Rated short-circuit making current Ima ...............................................................................49
C9 Rated short-circuit breaking current Isc ..............................................................................50
C 10 Rated mainly active load-breaking current I1 ....................................................................50
C 11 Rated closed-loop breaking current I2a, I2b ........................................................................50
C 12 Rated no-load transformer breaking current I3 ..................................................................50
C 13 Rated cable-charging breaking current I4a .........................................................................50
C 14 Rated line-charging breaking current I4b............................................................................50
C 15 Rated earth fault breaking current I6a .................................................................................50
C 16 Rated cable- and line-charging breaking current under earth fault conditionsI6b .............51
C 17 Cable switching current under earth fault conditions with superimposed load current.....51
C 18 Rated transfer current Itransfer ..............................................................................................51
C 19 Rated voltage UL (surge arrester with spark gaps).............................................................51
C 20 Rated voltage Ur (metal oxide surge arrester)....................................................................51
C 21 Continuous operating voltage Uc (metal oxide surge arrester) ..........................................51
C 22 Sparkover voltage ..............................................................................................................52
C 23 Residual voltage ures ...........................................................................................................52
C 24 Rated discharge current isn .................................................................................................52

6 Siemens AG 12E3
Contents

D Short-Circuit Protection with HRC Fuses ................................................ 53


D1 Selection criteria ................................................................................................................53
D2 HRC fuses for distribution transformers............................................................................53
D 2.1 Fuse rated current IrHH ........................................................................................................53
D 2.2 Rated voltage UrHH .............................................................................................................55
D3 HRC fuses for capacitors ...................................................................................................56
D 3.1 Fuse rated current IrHH ........................................................................................................56
D 3.2 Rated voltage UrHH .............................................................................................................56
D4 HRC fuses for motors ........................................................................................................56
D 4.1 Fuse rated current IrHH ........................................................................................................56
D 4.2 Rated voltage UrHH .............................................................................................................58
D5 Co-ordination with a switch or contactor...........................................................................59
D6 Let-through (cut off) current ..............................................................................................62
D7 Heat losses..........................................................................................................................63

E Selection of Overvoltage Protection Devices............................................. 64


E1 Selection criteria ................................................................................................................64
E2 Continuous operating voltage and rated voltage................................................................64
E3 Rated discharge current......................................................................................................65
E4 Residual and sparkover voltage (protection level).............................................................66
E 4.1 Switching overvoltages ......................................................................................................66
E 4.2 3 arresters in line-earth connection ....................................................................................67
E 4.3 6 arrester format .................................................................................................................67
E 4.4 Lightning overvoltages ......................................................................................................68
E5 Energy absorbtion capability .............................................................................................68
E6 Short-circuit withstand and housing ..................................................................................69
E7 Switchgear with overhead line connections.......................................................................69

F Switchgear Configuration........................................................................... 71
F1 Principles of configuration.................................................................................................71
F 1.1 General ...............................................................................................................................71
F 1.2 Requirements and complementary characteristics.............................................................71
F 1.3 Procedure ...........................................................................................................................72
F2 Switchgear requirements....................................................................................................73
F3 Properties to be selected.....................................................................................................74

Siemens AG 12E3 7
Contents

G Influences and Stress Variables ................................................................. 75


G1 Network characteristic values ............................................................................................75
G 1.1 Line voltage........................................................................................................................75
G 1.2 Short-circuit current ...........................................................................................................75
G 1.3 Normal current and load flow ............................................................................................76
G 1.4 Neutral point earthing ........................................................................................................76
G 1.5 Underground / overhead lines ............................................................................................77
G 1.6 Overvoltage protection.......................................................................................................77
G 1.7 Power quality (unstable loads)...........................................................................................78
G2 Line Protection, measurement and metering......................................................................78
G 2.1 Short-circuit protection ......................................................................................................78
G 2.2 Protection functions ...........................................................................................................79
G 2.3 Tripping times ....................................................................................................................79
G 2.4 Measurement and metering................................................................................................79
G 2.5 Redundancy........................................................................................................................80
G3 Infeed types ........................................................................................................................80
G4 Operating sites....................................................................................................................81
G 4.1 Installation location............................................................................................................81
G 4.2 Accessibility.......................................................................................................................81
G 4.3 Switchgear room ................................................................................................................82
G 4.4 Buildings ............................................................................................................................82
G 4.5 Transportation and assembly .............................................................................................83
G5 Environmental conditions ..................................................................................................83
G 5.1 Ambient room conditions...................................................................................................83
G 5.2 Altitudes above 1000 m .....................................................................................................84
G 5.3 Ambient temperature and humidity ...................................................................................84
G6 Industry-specific application..............................................................................................85
G 6.1 Switching duty and capacity ..............................................................................................85
G 6.2 Switching frequency of the loads.......................................................................................85
G 6.3 Frequency of switchover between busbars ........................................................................86
G 6.4 Availability (faults, redundancy, switchover time)............................................................86
G 6.5 Modifications or extensions ...............................................................................................87
G7 Operating procedures .........................................................................................................87
G 7.1 Operation............................................................................................................................87
G 7.2 Work activities ...................................................................................................................88
G 7.3 Inspection and maintenance ...............................................................................................89
G8 Regulations.........................................................................................................................89

8 Siemens AG 12E3
Contents

H Selecting and Rating Switchgear................................................................ 90


H1 Overview (Checklist) .........................................................................................................90
H2 Primary rated values...........................................................................................................93
H 2.1 Rated voltage Ur .................................................................................................................93
H 2.2 Rated insulation level.........................................................................................................94
H 2.3 Rated short-circuit currents................................................................................................96
H 2.4 Rated duration of short-circuit tk........................................................................................97
H 2.5 Rated normal current Ir ......................................................................................................98
H3 Busbar arrangement ...........................................................................................................99
H 3.1 Single busbars ....................................................................................................................99
H 3.2 Double busbars...................................................................................................................99
H 3.3 Design of double busbars.................................................................................................100
H 3.4 Operating principle of bus couplings ...............................................................................100
H4 Switching Devices ...........................................................................................................101
H5 Switchgear design and panel type....................................................................................102
H 5.1 Basic selection criteria .....................................................................................................102
H 5.2 Panel and block design.....................................................................................................103
H 5.3 Installation conditions, transportation and assembly .......................................................104
H 5.4 Additional aspects ............................................................................................................104
H6 Electrical and mechanical reserves ..................................................................................105
H7 Insulation medium............................................................................................................106
H8 Design of the isolating distance .......................................................................................107
H 8.1 Accessibility.....................................................................................................................107
H 8.2 Voltage tests on cables.....................................................................................................108
H 8.3 Switching frequency ........................................................................................................108
H9 Enclosure..........................................................................................................................109
H 9.1 Degree of protection.........................................................................................................109
H 9.2 Internal arc classification .................................................................................................110
H 9.3 Pressure absorbers and pressure relief ducts....................................................................110
H 10 Compartments ..................................................................................................................111
H 10.1 General selection criteria .................................................................................................111
H 10.2 Loss of service continuity category .................................................................................111
H 10.3 Access control ..................................................................................................................113
H 11 Feeder circuit components ...............................................................................................113
H 11.1 Cable connections ............................................................................................................114
H 11.2 Instrument transformers ...................................................................................................114
H 11.3 Earthing switches .............................................................................................................114
H 11.4 Surge arresters..................................................................................................................114
H 12 Busbar / metering panel components ...............................................................................115
H 13 Electronic secondary equipment ......................................................................................116
H 13.1 Electromagnetic compatibility (EMC).............................................................................116
H 13.2 EMC requirements on the switchgear..............................................................................116
H 13.3 EMC requirements on electronic equipment ...................................................................117
H 13.4 Legal EMC requirements .................................................................................................118

Siemens AG 12E3 9
Contents

I Appendix..................................................................................................... 119
I1 Damping relaxation oscillations.......................................................................................119
I 1.1 Relaxation oscillations (ferroresonance)..........................................................................119
I 1.2 Standard values for damping resistors .............................................................................120
I 1.3 Calculating the damping resistance..................................................................................120
I 1.4 Formula, symbols and indices..........................................................................................120
I 1.5 Standard, uninterrupted line operation.............................................................................120
I 1.6 Operation with earth fault ................................................................................................121
I 1.7 Damping resistance ..........................................................................................................122
I 1.8 Sample calculations..........................................................................................................122
I2 RC-circuitry for protection of MV equipment.................................................................123
I3 Installation of overvoltage protection devices .................................................................124
I4 Overvoltage factors (Definition)......................................................................................125
I5 Abbreviations, Symbols and Formula Variables .............................................................126
I6 Diagram Symbols.............................................................................................................127

J Relevant Standards and Regulations....................................................... 128


J1 Statutory regulations for medium-voltage equipment .....................................................128
J2 Generic standards for switching devices and switchgear.................................................129
J3 Product standards for switching devices..........................................................................130
J4 Product standards for switchgear and accessories ...........................................................131

K References and Further Reading .......................................................... 132

10 Siemens AG 12E3
Selection of the appropriate switching device

A SELECTION OF THE APPROPRIATE DEVICE

A1 Selection criteria
The effective selection of devices for a particular switching duty is determined by three main re-
quirements:
a) the operational current switching capability
b) the fault current switching capability
c) the frequency of switching

The section below deals with the criteria for following devices:
Circuit breakers Vacuum contactors HRC fuses
Vacuum switches SF6 switch disconnectors
Hard gas (gas evolving) and airbreak switches and switch disconnectors

The most important of these is the required switching capability. If more than one device fulfils
these requirements a) and b), the frequency of switching might be the critical factor. Individual
equipments differ in the number of mechanical and electrical operations for which they are de-
signed, the length of time between maintenance and the cost and inconvenience of that mainte-
nance.
Additional criteria may be:
the voltage withstand level of the gap;
in switchboards where the switches are not withdrawable, devices which ensure a safe isolation
gap are needed. Switch disconnectors fulfil the safety gap requirements, switches, circuit break-
ers and contactors do not. They need an additional disconnector or similar device in series. In
switchboards with withdrawable or truck-mounted equipment this is unimportant, the gap is es-
tablished by the act of withdrawal.
the drive mechanism;
for duties such as synchronising and (multiple-) auto-reclose, a drive mechanism with defined,
short closing and opening times. Only stored energy systems suffice; springs which have to be
charged first are unsuitable.

Circuit breakers can switch on and off (make or break) all values of current within their rated ca-
pability, from small inductive or capacitive load currents up to full short circuit currents, and under
all the fault conditions like earth fault, phase displacement (out-of-phase switching) etc.
Switches can switch on and off operating currents up to their rated interrupting capability and can
close onto existing short circuits up to their rated fault making current. They have very limited fault
current breaking capability only.
Switch disconnectors combine the functions of switches and disconnectors or, put another way,
they are switches with the specific safety gap required of disconnectors.
Contactors are load switching devices with limited short circuit making and breaking capacity.
They are electrically operated and are used for high switching rates, e.g. for motor control.

Fuses (or, more accurately, the fuse link) provides a single interruption of a short circuit current.
Fuses are installed in combination with load switching devices.

Siemens AG 12E3 11
Selection of the appropriate switching device

A2 Suitability under normal operating conditions


No. Operating duty Circuit- Switch and switch-disconnector Vacuum
breaker Vacuum SF6 Air-, Hard gas contactor
1 Transformer
X X X X X
(Star point transformer)
2 Converter transformer X
3 Furnace transformer X X
4 Petersen coil X X X
5 Compensation coil X
6 Motor X X (X) X
7 Generator X X (X)
8 Cable, Ring mains X X X X
9 Overhead lines X X X X
10 Single capacitor X X X (X) X
11 Paralleling of
X X X
capacitors
12 Filter circuit X X
13 Ripple control circuit X X X
14 Synchronising X
X = suitable and effective use (X) = limitedly suitable

Table A-1: Switching capability under normal conditions

A3 Suitability under fault conditions


Using the following three tables, check the fault currents the device must be able to switch.
No. Fault duty Circuit- Switch and switch-disconnector Vacuum
breaker Vacuum SF6 Air-, Hard gas contactor
1 Closing onto fault X X X X (1)
2 Terminal fault X (2) (2) (2) (2)
3 Auto-reclose X
Fault on load side of
4 - Generator X
5 - Reactor X
6 - Transformer X (2) (2) (2) (2)
7 Locked rotor motor X X (2) X
8 Double earth fault X (2) (2) (2) (2)
9 Phase opposition X
(1) Without HRC fuse, only limited fault switching capability.
(2) Only as switch-fuse combination; current interruption by the fuse.

Table A-2: Switching capability under fault conditions

12 Siemens AG 12E3
Selection of the appropriate switching device

No. Fault duty Circuit- Switch and switch-disconnector Vacuum


breaker Vacuum SF6 Air-, Hard gas contactor
10 Unloaded cable, OHL X X X (1) X
fault on network side
11 Loaded cable, OHL X X X X
fault on network side
12 Unloaded cable, OHL X X X X X
fault on load side
13 Loaded cable, OHL X X X (1) X
fault on load side
(1) for small currents only

Table A-3: Switching under earth fault conditions

No. Fault duty Circuit- Switch and switch-disconnector Vacuum


breaker Vacuum SF6 Air-, Hard gas contactor
14 Safe disconnection X X
(Disconnection under
load)
15 Rapid changeover X
16 Transformer with X X (1) (1) (1)
short-circuited winding
(1) Only as switch-fuse combination; current interruption by the fuse.

Table A-4: Other fault conditions

A4 Switching frequency and endurance classes


When a range of devices fulfils the electrical requirements, the frequency of switching in connec-
tion with the endurance can be an additional selection criterion. The standards distinguish between
mechanical and electrical endurance, which are also applicable to equipment "mixed"; e.g. a switch
can mechanically correspond to the class M1 and electrically to the class E3.
The following tables show the endurance classes of the switching devices and give a recommenda-
tion about useful use with that.

A 4.1 Circuit-breaker

A 4.1 a Mechanical and electrical endurance classes M and E


IEC 62271-100 [7] defines the mechanical endurance by a certain number of operating cycles (class
M), the electrical endurance, however, merely with the verbal description normal and extended
endurance.
To the orientation, what normal and extended electrical endurance means, the grey shaded table
elements indicate the operating cycles which average modern vacuum circuit-breakers can perform.

Siemens AG 12E3 13
Selection of the appropriate switching device

The numbers for short circuit operation (Isc) are derived from the operating sequences of the type
test. As a rule these are minimum numbers; actually, vacuum circuit-breakers of the class E2 with
auto-reclosing capability, which are used in electricity grids with overhead lines, may break the
smaller short-circuit currents, usual there, several hundred times.
Furthermore it is worth mentioning, that almost all modern vacuum circuit-breakers can switch the
rated normal current with the number of the mechanical operating cycles.

Class Description
M1 2.000 Operations normal mechanical endurance
M
M2 10.000 Operations extended mechanical endurance, limited maintenance
*
Ir 2.000 Operations
* normal electrical endurance
E1 Isc 6 x Open
(circuit-breaker, not falling into class E2)
4 x Close
*
Ir 10.000 Operations
* without auto-
E Isc 6 x Open
reclosing duty extended electrical endurance
4 x Close
E2 *
without maintenance of interrupting
Ir 10.000 Operations parts
* with auto-reclosing
Isc 50 x Open
duty
15 x Close
* Derived numerical values to the orientation = > see text.

Table A-5: Classes M and E of circuit-breakers

A 4.1 b Capacitive current switching class C

Class C defines the capacitive current breaking performance comprising the characteristics of three
switching duties, i.e. the closing and switching off of lines, cables and capacitor banks (single and
back-to-back capacitor banks).

Class Peformance on breaking of capacitive currents

C1 24 x O per 1040% Ilc, Icc, Ibc


Low probability of restrikes Restrike-free breaking
24 x CO per 1040% Ilc, Icc, Ibc
C operations at 2 of 3
C2 24 x O per 1040% Ilc, Icc, Ibc Very low test duties
128 x CO per 1040% Ilc, Icc, Ibc probability of restrikes

Table A-6: Classes for capacitive current switching

The selection of the class depends on the operating conditions, the switching frequency and the pos-
sible effects of restrikes.
- Class C1 is suitable for infrequent switching of transmission lines and cables;
- Class C2 is recommended for capacitor banks as well as for frequent switching of transmission
lines and cables.

14 Siemens AG 12E3
Selection of the appropriate switching device

A 4.1 c Cable or line system class S


Class S defines the type of the grid where the circuit-breaker is intended to be employed. The
switching duties differ in magnitude and rate of rise of the the transient recovery voltage (TRV)
while breaking short-ciruit currents. In line systems the TRV and the associated dielectric stress on
the contact gap can be much higher due to the smaller phase-to-earth capacitances.

Circuit-breakers of indoor switchgear are always to be assigned to class S1, i.e. cable system. The
same applies to feeders where an overhead line is connected to the switchgear via a cable. Class S2
is virtually not relevant to metal-enclosed medium voltage switchgear. In terms of the standard a
circuit-breaker in an overhead line system is, for example, a (outdoor) breaker directly connected to
the line without cable.

Class Description

S1 Circuit-breaker intended to be used in a cable system


S
S2 Circuit-breaker used in a line-system, or
in a cable-system with direct connection (without cable) to overhead lines

Table A-7: Classes for cable or line system system

A 4.2 Switches and switch-disconnectors


IEC 62271-103 [8] specifies classes for so-called general purpose switches. In addition there are
limited purpose and special purpose switches1. General purpose switches as the name sug-
gests have to switch different kinds of operating currents: load currents, closed-loop currents,
transformer magnetising currents, cable and line charging currents as well as making short-circuit
currents. General purpose switches intended for use in isolated neutral point systems or in systems
earthed by a high impedance shall be capable of switching under earth fault conditions. This versa-
tility is reflected in the relatively comprehensive definition of the classes, which are applicable for
Vacuum switches
SF6 switches and switch-disconnectors
Air and hard-gas switches and switch-disconnectors

For switch-disconnectors the table details apply to the function switch.

See also section A 4.5 Three-position switching devices.

1
Limited purpose switches need only cope with a certain range of the performance of a general purpose switch. Special
purpose switches are used for selected duties such as switching of single capacitor banks, paralleling of capacitor
banks, closed-loop circuits built up by transformers in parallel, or motors (under steady-state and stalled conditions).

Siemens AG 12E3 15
Selection of the appropriate switching device

Class Switching cycles Description


M1 1000 Mechanical endurance
M
M2 5000 Increased mechanical endurance
E1 10 x Iload
10 x Iloop 20 x 0.05 Iload
2 x Ima Test currents: (old)
10 x Icc
Iload active load-breaking current I1
E2 30 x Iload 10 x 0.2 to 0.4 Icc Iloop closed-loop breaking current I2a
E 20 x Iloop
10 x Ilc Icc cable-charging breaking current I4a
3 x Ima
Ilc line-charging breaking current I4b
10 x Ief1
E3 100 x Iload Isb capacitor bank breaking current I4c
20 x Iloop 10 x Ief2 Ibb back-to-back capacitor bank I4d
5 x Ima breaking current
Ief1 earth fault breaking current I6a
C1 10 x Icc Restrikes permitted
Ief2 cable- and line-charging breaking I6b
10 x Ilc (number not defined)
current under earth fault conditions
10 x Isc
C C2
10 x Ibb Ima Short-circuit making current Ima
additionally each 10x No restrikes
0,1 0,4 x Icc, Isb, Ibb

Table A-8: Classes for switches

A 4.3 Contactos
The standard for contactors has not yet defined endurance classes. Customary designs feature me-
chanical and electrical endurance in the order of 250,000 and 1,000,000 operation cycles. The can
be encountered where extremely high switching rates occur; e.g. > 1 / hour.
However, classes for the suitability of breaking capacitive currents are defined.

Class Description
1 restrike
C0 24 x O Not defined
per interruption
24 x CO
C each per 1040% Ilc, Icc, Ibc Low probability 5 cummulated restrikes on
C1
of restrikes test duties BC1 and BC2
24 x O per 1040% Ilc, Icc, Ibc Very low probability
C2 No restrikes 2
128 x CO per 1040% Ilc, Icc, Ibc of restrikes

Table A-9: Classes for contactors

- Contactors of C2 class are suitable for capacitor banks.

2
Class C2 is recommended for capacitor banks.

16 Siemens AG 12E3
Selection of the appropriate switching device

A 4.4 Disconnectors and earthing-switches


IEC 62271-102 [21] defines the classes for disconnectors and earthing-switches. Since disconnec-
tors have no switching capacity3, only classes fort he mechanical endurance are specified.

Class Operations Description


M0 1000 for general duties
M M1 2000
extended mechanical endurance
M2 10.000

Table A-10: Classes for disconnectors

The classes for earthing switches specify the short-circuit making capability (earthing in case of
voltage still being present). E0 designates a normal earthing switch, whereas E1 and E2 correspond
to earthing switches with short-circuit making capability; so-called make-proof earthing switches.

Class Operations Description


E0 0 x Ima no short-circuit making capability
for general duties
E E1 2 x Ima
short-circuit making capability
E2 5 x Ima reduced maintenance

Table A-11: Classes for earthing-switches

A 4.5 Three-position switching devices


Three-position switching devices combine two or three functions within one device
Disconnecting
Earthing and short-circuiting
Load switching
Interrupting short-circuits
For three-position switching devices classes are designated for each individual function, i.e. as if
there were two or three separate switching devices.

3
Disconnectors up to 52 kV rated voltage can switch off only negligible currents up to 500 mA (for example voltage
transformers), or higher currents only if no significant change in voltage occurs (for example busbar transfer when bus
coupler is closed).

Siemens AG 12E3 17
Selection of the appropriate switching device

A 4.6 Guidance for use


Table A-12 shows the average lives of switching devices and gives a recommendation for appropri-
ate usage. The table gives only guide values; they can be taken into account when no other criterion
is of greater importance.

Device Mechanical Operations at rated Switching frequency


operations which gives reason-
able lifetime
Nos. Class normal breaking Class
current current
Circuit-breaker 10 000 M2 10 000 5 - 400 E2 no criterion
Vacuum switch 5 000 M2 5 000 10 E3 1 / week
30 E2
SF6 switch 1 000 M1 5 1 / month
100 E3
10 E1
Hard-gas switch 1 000 M1 2 1 / year
30 E2
Vacuum contactor 106 not
defined 106 1 000 not
defined > 1 / hour

Table A-12: Endurance of switching devices

The column breaking current gives only average numbers of operations. The actual lifetime can
be much higher since the full rated value rarely occurs in practice. For circuit-breakers the lower
value refers to high short-circuit currents ( 50 kA), the upper value to small currents (12.5 kA). For
switches the column mentions the transfer current (Itransfer) of switch-fuse combinations [30]. With
vacuum contactors the value refers to the limit breaking capacity. The class designation refers to the
corresponding product standard.

Regarding switching frequency circuit-breakers are an exception: The switching rate is not a decid-
ing factor for the choice because circuit-breakers are used, if short-circuit breaking capacity is re-
quired.

18 Siemens AG 12E3
Selection of the appropriate switching device

A5 Aspects of selection for disconnectors


For work on switchboard components, it must always be possible to establish a safe disconnection
gap. For this, a switching device or an arrangement of equal value is essential, also an interlock be-
tween this disconnector and the load, power or earthing switch. With combined devices like switch-
disconnectors or three-position devices, an additional disconnector is unnecessary and even separate
interlocking may become superfluous.
The average mechanical endurance of disconnectors (truck or withdrawable part) amounts 1000 or
2000 operations, corresponding to the classes M0 or M1. This is completely sufficient for most of
the applications.
The life of the disconnector in double busbar switchboards plays an important role: In some net-
works, for operational reasons, it is necessary to switch frequently from one busbar to the other.
Because of the limited life of conventional disconnectors in comparison to the main switching de-
vices, not all switchboards are suitable for this application.

See chapter H 3.3.

Siemens AG 12E3 19
Switching duties in medium voltage systems

B SWITCHING DUTIES IN MEDIUM VOLTAGE NETWORKS

B1 Overview
The table gives an overview whether special measures have to be taken on selection of switching
devices. Details are described in the chapters listed in the right column.

Switching duty Advice Section

Distribution transformers 4 If the transformer is fed by a switch-fuse combina- B 2,


tion, the fuses must be selected according to the D 2 and
Power transformers rules for transformer circuits and, in order to pro- D5-D7
tect the switch, according to the IEC standard for
switch-fuse combinations.

For circuit-breakers no special requirements apply


in this respect.

Unit transformer See Motor B8


Generator B9
Furnace transformer B 10
Converter transformer B 11

Petersen coil Surge arrester or limiter B4

Overhead line or cable Switches and switch-disconnectors are very limited B 5


in suitability for earth fault location (by selective
switching of circuits): only up to their switching
capability under earth fault conditions - with or
without load (see manufacturer data)!

Cable or overhead line with Surge arresters are required at the short end of B6
short-circuit limiting reactor the cable / line

Compensation coil Overvoltage protection is required generally B7


(shunt reactor) - RC-circuits
- if current < 600 A, additionally surge arresters
- protection at the busbar, depending on the net-
work configuration

Motor Overvoltage protection is required if motor starting B 8


current is < 600 A

(see next page)

4
Distribution transformers (rated power uo to 2.5 MVA) transform energy from a primary to secondary distribution or
industrial network. Equipment connected downstream a distribution transformer have its own switchgear for switch-
ing under normal service conditions.

20 Siemens AG 12E3
Switching duties in medium voltage systems

Switching duty Advice Section

Motor Peak and short-circuit making current: due to re-


(continued) verse power feed with large motors or some motors
connected, the peak current rating of the switch-
gear may exceed the standardized value of 2.5 Ik
(or 2.6 Ik at 60 Hz).

Motor with HRC fuse: select the fuse according to D4+


starting current and time of the motor! D 5 to D 7

Generator Overvoltage protection is necessary, if short-circuit B 9


current of generator is < 600 A

Peak and short-circuit making current: with large


machines the peak current may exceed the stan-
dardized value of 2.5 Ik (or 2.6 Ik at 60 Hz) the
critical share is the peak current from the network
side.
Rated voltage: Consider temporary overvoltage
due to the effect of load shedding.
Rated short-circuit breaking current: Consider the
DC component of the generator current.

Furnace transformer Protection by RC-circuits and surge arresters is B 10


required, individually matched to the system (in
most cases also at the busbar)

Converter transformer Surge arresters B 11

Capacitor bank Inrush current: consider the maximum permissible B 12


closing current of the circuit-breaker; where appli-
Back-to-back switching cable, use damping measures.
of capacitor banks
Rated normal current: consider additional heating
due to harmonic currents.
Rated voltage: consider the increased voltage if
capacitor bank is fitted with limiting reactors
HRC fuses: select rated voltage and rated current
1-2 steps higher D3

Filter circuit Rated voltage: Consider operating voltage limits at B 12


filter capacitor (see capacitor banks)

Audio frequency B 13
ripple control system

Table B-1: Planning criteria for switching duties in MV networks

Siemens AG 12E3 21
Switching duties in medium voltage systems

B2 Distribution transformers
This covers all transformers in industrial and power utility networks, with exception of the special
transformers in section B 2.

Duty: Unloaded transformer Loaded transformer

Current: - Magnetising current 1 to 3 % of rated up to 120 % of rated trans-


transformer current (IrT) former current
- Inrush current up to 15 IrT

cos : < 0.3 induktive 0.7 to 1.0 ind.


< 0.15 during inrush

Remarks: - Protection relays shall have inrush restraint


- Switching device shall have low chopping
current

Table B-2: Switching of distribution transformers

Transformer during inrush: when switching off during the inrush phase, currents up to 15 times the
rated current at cos = 0.15 may occur, heavily superimposed by harmonic currents. Air or hard-
gas switches are not capable of interrupting those currents. The transformer protection relay must
feature an inrush restraint in order to avoid switching off of the transformer during the inrush.

Where HRC fuses are used for short-circuit potection, the selection may be done in accordance with
the procedure defined in IEC 60787 [27]; the corresponding German standard VDE 0670-402 [28]
presents a table of fuse ratings allocated to transformer ratings see table 2 therein. Additionally
where applicable the requirements of switch-fuse combinations to IEC 62271-105 [30] must be
taken into account. See section D 5 for the procedure to configure these combinations.

B3 Unit transformer
Transformers in this arrangement normally feed only one, special load. The switching duty is then
determined by the characteristics of that load. For further clarification see:
Motor (with transformer, starting transformer) Section B 8
Generator Section B 9
Furnace transformer Section B 10
Converter transformer Section B 11

22 Siemens AG 12E3
Switching duties in medium voltage systems

B4 Petersen (arc suppression) coil


Petersen coils in earth fault compensated, normally unearthed, networks earth the network at the
starpoint of either a transformer or an earthing transformer. When an earth fault occurs, the coil is
switched in to produce a purely inductive current which should compensate (equal) the capacitive
earth fault current which is flowing into the fault. If the Petersen coil is switched off during the
fault, multiple re-ignitions can cause overvoltages. Surge arresters will protect against these.

Switching: without earth fault in network with earth fault in network


Current: approx. 1% of transformer rated up to 300 A
current
cos : less than 0.15 ind. less than 0.15 ind.
Remarks: as unloaded transformer overvoltages due to multiple
re-ignition possible

Table B-3: Switching of arc suppression coil

B 4.1 Overvoltage protection


Arresters at the transformer or neutral point earthing transformer terminals in phase-earth connec-
tion, or parallel to Petersen coil; if the coil can be switched directly (left figure), the arrester has to
be installed there.

Figure B-1: Protection methods for arc suppression coils

B 4.2 Selection of surge arresters


It is essential that the transformer insulation corresponds to the upper standard value of the rated
insulation level in accordance with table 2, IEC 60076-3 [6]; these insulation ratings equal the val-
ues in column (4), Table H-3. Otherwise the arrester can be selected as described in section E.

Siemens AG 12E3 23
Switching duties in medium voltage systems

Surge arrester Rated voltage Ur Continuous operating voltage Uc


At the primary terminals of the Ur 1.25 Uc Uc Um
(neutral earthing) transformer
Parallel to Petersen coil Ur 0.8 Um Uc Um / 3
Umax Maximum operating voltage of the power system

Table B-4: Selection of surge arresters for an arc-suppression coil

B5 Cable or overhead line


This refers to unloaded cables and lines. In this case, only the capacitive charging current flows.
See section B 6 for cable and lines with short-circuit limiting reactor.

Switching: Cable Overhead line


Current: up to 100 A up to 10 A
cos : capacitive capacitive
Remarks: Vacuum switches are restrike-free
Switches and switch-disconnectors are very limited in suitability for earth fault
location (by selective switching of circuits): only up to their switching capabil-
ity under earth fault conditions - with or without load (see manufacturer data)!

Table B-5: Switching of cables or overhead lines

Additional measures: None

B6 Cable or line with short-circuit limiting reactor


If two switchgear installations with different peak and short-time current ratings are connected, a
reactor must limit the short-circuit current to the level of the installation with the lower rating.

On energising the connection between installation A and B under no-load condition impermissible
overvoltages may occur if the circuit-breaker in installation A closes the long cable (some hun-
dred metres) while the breaker in installation B is open. The very small line-earth capacitance of the
short connection (only a few metres of cable or bar) together with the inductance of the reactor
leads to a high-frequency inrush voltage which can reach unduly high amplitudes. Hence in order to
avoid disruptive discharges at the reactor terminals or at the open end of the short cable or bar
connection surge arresters or limiters have to reduce the overvoltage to permissible values.
In contrast to this, when the breaker in installation B closes first, no significant overvoltages occur
at the long end in installation A, as the closing overvoltage at the open circuit-breaker remains
small due to the much higher earth capacitance of the long cable.

24 Siemens AG 12E3
Switching duties in medium voltage systems

Current: 0 A; only on closing under no-load condition


cos :
Remarks: The energising of the cable at the long end can cause overvoltages
at the short, open end.
It is recommended to install surge arresters.

Table B-6: Switching of a line or cable connection with reactor

Surge arresters should be installed in the station with the short cable or bar connection between
reactor and circuit-breaker (installation B). The arresters can be mounted either at the terminals of
the breaker or at the reactor.

Figure B-2: Surge arresters in line-earth connection at the


circuit-breaker (preferably) or at the reactor

Operating voltage 5 Surge arresters for installation at


of system up to: circuit-breaker short-circuit limiting reactor
3.6 kV 3EF1 036-0A
4.8 kV 3EF1 048-0A Indoor: type 3EF1,
same type as at the circuit-breaker.
7.2 kV 3EF1 072-0A
Outdoor: arresters with equal protection
12 kV 3EF1 120-0A level; selection see chapter E.
15 kV 3EF1 150-0A
> 15 kV Selection see chapter E

Table B-7: Recommended surge arresters for the reactor

5
For other voltages and those above 24 kV any surge arrester can be selected;
selection criteria are described in section E.

Siemens AG 12E3 25
Switching duties in medium voltage systems

B7 Compensation coils (shunt reactors)


These compensate the capacitive charging current on unloaded networks. Compensation coils are
switched daily and thus the circuit-breakers reach large numbers of operations. The high rate of rise
of the recovery voltage makes this a very difficult duty for conventional units, whereas vacuum
breakers master these conditions excellently.
Current: up to 2000 A
cos : 0.15 ind.

- RC-circuits individually matched to the network are generally required


Remarks:
- surge arresters are required if the coil current is 600 A

Table B-8: Switching of compensation coils

Compensation coils are always equipped with an RC-circuit which prevents resonant harmonics in
the coil during switch-off. When the coil current is 600 A, surge arresters are also fitted to prevent
overvoltages.
In case of certain network conditions, where the line-earth capacitance on the feeding side is very
small, additional protection at the busbar (x) by RC-circuitry and surge arresters is required.

Coil current I Protection


I 600 A RC-circuits
+ arresters

I > 600 A RC- circuits

Figure B-3: Surge protection for compensating coils

The protection devices must always be individually matched to the network characteristics and data
of the equipment.

B8 Motors
This area of application covers many types of machines:
- Asynchronous motor: cage rotor, slipring rotor
- Synchronous motor (with asynchronous start)
- Motor with unit transformer
- Motor with starting transformer
- Motor with starting converter (soft starter)
- Motor with individual power factor compensation
- Variable speed drives (converter motors) see B 11 Converter transformers

26 Siemens AG 12E3
Switching duties in medium voltage systems

Duty: Motor during starting Normal operation,


Machine with locked rotor no-load up to full load
Current: Cage rotor 5 7 IrM 0.1 1.2 IrM
Slip ring rotor 1 2 IrM
cos : 0.2 to 0.3 inductive 0.9 to 0.3 inductive
Remarks: Switching of starting currents Ist 600 A 6 Switching of normal operating
can cause overvoltages as result of multi- currents causes no impermissible
ple re-ignition and virtual current chopping overvoltages.
Motors with starting current 600 A6 must be equipped with surge arresters;
except motors with individual power factor correction.

Table B-9: Switching of motors

B 8.1 Overvoltage protection for motors


For economical reasons the insulation level of machine windings, particularly the impulse withstand
capability, is considerably lower than the insulation level of switchgear; see table 1 in [2]. This does
not play any role when switching under normal service conditions. However, when a motor is
switched off with blocked rotor or during start-up, inadmissibly high overvoltages can occur which
must be limited by surge arresters. Exceptions are motors with power-factor correction, which do
not need overvoltage protection, if the compensation power amounts at least 1/5 of the motor appar-
ent power, see chapter B 8.6.
A simple decision criterion, whether overvoltage protection is required or not, is the starting cur-
rent. Is the latter in the area up to 600 A, the motor must be equipped with overvoltage protection.
For motor-transformer combinations, the current flowing through the circuit-breaker (or contactor)
is the decisive criterion. Further considerations of other installation parameters, such as e.g. the ca-
ble to the motor, thus are no longer required; [3], [4].
The following clauses show various arrangements with different connections points of surge limit-
ers or surge arresters.

B 8.2 Direct connected motor (direct on line)

M Ist 600 A

Surge limiters in
phase-earth connection at the
circuit-breaker / contactor

Figure B-4: Surge arresters at the breaker terminals

6
For motor-transformer combinations, the transformer primary current is the criterion.

Siemens AG 12E3 27
Switching duties in medium voltage systems

At first sight, surge arresters at the breaker or contactor contradict the known rule to connect arrest-
ers at the object to be protected. However, there are good reasons for it: arresters are susceptible
against vibration and high ambient temperatures prevailing in a motor terminal box. Moreover a
large terminal box would be required for which most often there is no space. Surge arresters at the
breaker / contactor must have a particularly low residual voltage so that they protect the motor de-
spite the travelling wave effects at the cable end on the motor side. The Siemens surge limiters type
3 EF or other arresters with the same protection level are recommended (Chapter E). 3 EF type is an
especially developed arrester for the protection of motors or other equipment with sensitive wind-
ings [5]. It satisfies the prerequisite of a particularly low residual voltage and therefore can be at-
tached also at the breaker side of the motor cable.

Motor 3.6 kV 4.8 kV 7.2 kV 12 kV 7 15 kV


voltage up to:
Surge limiter
3EF1 036-0A 3EF1 048-0A 3EF1 072-0A 3EF3 120-1 3EF1 150-0A
types

Table B-10: Recommended surge limiters for motors

B 8.3 Motor with transformer (unit)


Two variants of overvoltage protection are possible for motors with block transformer at the same
protective effect.

Arrangement 1

Surge limiters in phase-


earth connection at the cir-
cuit-breaker or contactor

Arrangement 2
(prefered)

Surge limiters or arrester in


phase-earth connection at
the transformer

Figure B-5: Surge protetion for a motor-transformer combination

Recommended surge arresters are the Siemens 3EF surge limiters or other arresters with equal
protection level; see chapter E.

7
For direct connected motors with 12 kV surge limiters at the breaker the type underlined must be used to ensure the
protection level required.

28 Siemens AG 12E3
Switching duties in medium voltage systems

Rated voltage of the motor Surge arresters for installation at the


or transformer up to: circuit-breaker transformer
3.6 kV 3EF1 036-0A 3EF1 036-0

4.8 kV 3EF1 048-0A 3EF1 048-0

7.2 kV 3EF1 072-0A 3EF1 072-0


12 kV 3EF1 120-0A 3EF1 120-0A
15 kV 3EF1 150-0A 3EF1 150-0A

Table B-11: Recommended surge limiters for motor-transformer combinations

Note to arrangement 2: At the transformer normal arresters can also be used (see chapters E) instead
of the recommended surge limiters if the transformer insulation corresponds to the upper value of
the rated insulation levels to table 2, IEC 60076-3 [6]; the values are the same as in column (4),
Table H-3.

B 8.4 Motor with starting transformer

Starting current Connection of surge limiters RC circuitry

Ist 600 A at main main switch (1) or transformer (2); always at transformer neutral
and at transformer neutral point (3) point, irrespective of the starting
current
Ist > 600 A at transformer neutral point (3)

Figure B-6: Surge protection for motors with starting transformer

Siemens AG 12E3 29
Switching duties in medium voltage systems

The insulation level of starting transformers8 frequently does not meet the values standardised for
power transformers according to table 2, IEC 60076-3 [6]. Therefore, only surge limiters 3EF
should be installed at the transformer (2), because of their very low residual voltage (standard surge
arresters may not be suitable for this duty). Recommended devices are the Siemens 3EF surge limit-
ers or other surge arresters at equal protection level. The arresters at the transformer neutral point
must be selected in accordance with rated voltage of the transformer and the insulation level of its
neutral point. Additionally, RC- circuitry must be installed at the transformer neutral point, as listed
in Table B-12.

Rated voltage of Surge arresters at RC circuitry


transformer up to: circuit-breaker transformer
3.6 kV 3EF1 036-0A 3EF1 036-0A R = 30 Ohms
C = 200 nF
4.8 kV 3EF1 048-0A 3EF1 048-0A
The values for R and C
7.2 kV 3EF1 072-0A 3EF1 072-0A are valid with a cable
length lC < 30 m between
12 kV 3EF3 120-1 3EF1 120-0A
transformer neutral and
15 kV 3EF1 150-0A 3EF1 150-0A circuit-breaker.

Table B-12: Recommended surge limites for motors with starting transformer

B 8.5 Motors with starting converter

3a 3b
Surge limiters in line earth
connection at the three con-
nection points 1a or 1b, 2 and
3a or 3b, if:
Circuit-breakers S1 to S3
2
are not interlocked with
the converter, and
The motor starting current
1a 1b is 600 A.

Figure B-7: Motor with starting converter (example with two transformers)

8
Autotransformers have a gapped iron core to increase the magnetizing current during the reactor starting phase (i.e.
second phase of start-up with open transformer neutral). Transformers with a closed iron core are not suitable for
this starting method.

30 Siemens AG 12E3
Switching duties in medium voltage systems

Starting converters (soft starters) are bridged or switched off after the start-up of the motor. Under
normal service conditions the converter controls the current and the breaking operation. However,
instantaneous tripping of the circuit-breaker during the start-up phase cannot be precluded unless
the control of the converter is interlocked with the circuit-breaker (the circuit-breaker must be fitted
with a leading auxiliary switch for this purpose).
Surge protection is not required if the converter control and the corresponding interlockings en-
sure that the circuit-breakers (1) to (3) never switch off starting currents 600 A.
If the circuit-breakers are not included in the control of the converter and the motor starting cur-
rent is 600 A, surge protection must be installed for the converter transformers and the motor.
The surge limiters for the motor must be mounted at the circuit-breaker S2 (connection point 2).
For the converter transformers they may be mounted at the circuit-breaker (connection points 1a
and 3a) or alternatively at the transformer terminals (connection points 1b and 3b). Surge limiters
according to chapter B 8.2 are applied to the motor; for the converter transformers refer to chap-
ter B 11.2 and B 11.3.

B 8.6 Motors with their own p.f. improvement


No overvoltage protection is necessary.
Motors with individual power factor correction do not need overvoltage protection, if the p.f. cor-
rection capacitors are permanently connected to the motor and the compensation rating (QC) is at
least 1/5 of the motor's rated power (SrM), normally QC = (1/3) SrM is installed. The compensation
capacitance reduces the frequency of the transient recovery voltage for the first pole-to-clear to less
than the limit where multiple reignitions occur. Therfore no overvoltages occur either.
Thus individual compensation can also be used as an alternative method of providing protection.

1
Prerequisite: QC S rM
5
1
normally QC = S rM
3

Figure B-8: Motor with power-factor improvement

Siemens AG 12E3 31
Switching duties in medium voltage systems

B9 Generators

Duty Generator short-circuited Load and no-load operation


Current: short-circuit current9 up to 1.2 IrG
cos : 0.15 lag. lag. lead.
Remarks: When short-circuit currents Ik" 600 A 10 Switching off under load or no-
are switched off, overvoltages due to multiple load conditions causes no im-
re-ignitions may occur. permissible overvoltages
In many cases surge protection is basically installed to ensure safety of operation
since overvoltages may be transferred from elsewhere in the network.

Table B-13: Switching of generators

B 9.1 Selection of the circuit-breaker


Special attention has to be paid to the rated voltage and rated short-circuit breaking current when
selecting a breaker for generators.

Rated voltage: The event of load shedding has to be considered when selecting this rating. The volt-
age on the generator side of the breaker rises after load shedding. A standard value of 20 % rise is
usually assumed. A higher value up to 40 % may be assumed if the simultaneous occurrence of sev-
eral faults need be considered (e.g. load rejection and defective voltage regulator). The requirements
for the circuit-breaker should be co-ordinated with the client.

Rated short-circuit breaking current: The peak value (making current) and the DC component of the
current during short-circuit near-to-generator11 are higher than during short-circuit elsewhere in the
system (far-from-generator). Typically the DC component is very high so that in some cases the
AC component may decrease more rapidly than the DC component. This leads to delayed current
zeros (DC component > 100 %). However the circuit-breaker needs current zeros for clearing.

The real breaking current depends on the time interval between initiation of the short-circuit and the
opening of the breaker because of the current decays during that time (tripping times of protection
relay and opening time of c.b.). The values of the breaking current and the DC component must be
stated by the customer or be calculated in case of doubt.

See also chapter H 2.3 for short-circuit current and DC component.

9
In case of fault at the busbar or breaker terminals
10
The current through the breaker is decisive in generator-transformer arrangements
11
The short-circuit is near-to-generator if the ratio initial to continuous symmetrical short-circuit current is Ik"/Ik > 2

32 Siemens AG 12E3
Switching duties in medium voltage systems

B 9.2 Overvoltage protection


Switching of generators is similar to motor switching with respect to the transients. The decisive
criterion for surge protection on account of the breaker is the short-circuit current of the generator
during fault at the busbar or breaker terminals. If it is 600 A, surge limiters or arresters are used.
However, surge protection is often universally fitted as a basic measure against overvoltages which
may be carried over from the network.

B 9.3 Generators with Ik" 600 A feeding into a cable system

a) Direct connected generator

Surge arresters
line-earth

Figure B-9: Surge protection for generators

Recommended surge arresters are the Siemens types 3EF and 3EE as well as other arresters with
equal protection level.

Generator volt- 3.6 kV 4.8 kV 7.2 kV 12 kV 15 kV


age up to: 12
Type 3EF 3EF1 036-0A 3EF1 048-0A 3EF1 072-0A 3EF1 120-0A 3EF1 150-0A
3EF3 036-0 3EF3 048-0 3EF3 072-0 3EF3 120-0
Type 3EE For the selection of ratings refer to chapter E

Table B-14: Recommended surge arresters or limiters for generators

For operating voltages above 15 kV the type 3EE2 is used; refer to chapter E for the selection of the
ratings.

B 9.4 Generator-transformer unit

For generator-transformer combinations there are two arrangements of the surge arresters with
equal effect of protection.

12
Maximum value, including temporary voltage rise where applicable

Siemens AG 12E3 33
Switching duties in medium voltage systems

Arrangement 1

Surge arrester line-earth


at the circuit-beaker

Arrangement 2
(preferred)

Surge arrester line-earth


at the transformer

Figure B-10: Overvoltage protection of generator-transformer units

With arrangement 2 normal surge arresters can also be used at the transformer instead of the rec-
ommended surge limiters if the transformer insulation complies with the upper value of the rated
insulation levels to table 2, IEC 60076-3 [6]; the values are the same as in column (4), Table H-3.

Transformer voltage13 Surge arresters at


up to: circuit-breaker transformer
3.6 kV 3EF1 036-0A 3EF1 036-0A

4.8 kV 3EF1 048-0A 3EF1 048-0A

7.2 kV 3EF1 072-0A 3EF1 072-0A


12 kV 3EF3 120-1 3EF1 120-0A
15 kV 3EF1 150-0A 3EF1 150-0A
> 15 kV For the selection of ratings refer to chapter E

Table B-15: Recommended surge arresters for generator-transformer units

13
Maximum value including temporary voltage rise where applicable

34 Siemens AG 12E3
Switching duties in medium voltage systems

B 9.5 Generators connected to the HV grid


This almost only concerns generators of large size, which feed into high voltage systems 110 kV.
The protective measures must be planned individually; they are independent of the breaker.

Machine Station services


transformer transformer
G
~
Generator
High voltage circuit-breaker
system 110 kV Protective
Machine
capacitors arrester

Figure B-11: Generator connected to a HV grid

B 10 Furnace transformer
The following duties are included in this field:
- Arc furnaces, reduction furnaces, induction furnaces
- Exception: medium frequency furnaces are not included see converter transformers.

Switching duty: Arc furnace Reduction furnace,


induction furnace
Current: 0.01 up to 2.0 x 0.01 up to 2.0 x
rated transformer current rated transformer current
cos 0.2 0.9 lag. 0.5 0.8 lag.
Remarks: During opening operations, multiple re-ignitions may cause resonant oscil-
lations in the transformer; at currents 600 A high overvoltages due to
virtual current chopping may occur as well.
Consider the insulation co-ordination; see section B 10.1

Table B-16: Switching of furnace transformers

Additional measures: RC-circuitry and surge arresters at the transformer and the busbar.

Circuit-breakers for furnace transformers have to meet very high electrical and mechanical require-
ments partly under unfavourable operating conditions such as high temperature environments or
pollution from electrically conductive dust. The currents to be switched are between almost zero
and two times the rated current of the furnace transformer; they may be unbalanced and distorted.
The switching frequency may be up to 100 cycles per day and in exceptional cases it may be even
higher.

Siemens AG 12E3 35
Switching duties in medium voltage systems

B 10.1 Insulation co-ordination for operating voltages above 36 kV


Under certain conditions 36 kV vacuum circuit-breakers can also be used with higher operating
voltages up to 40.5 kV (mainly in networks with effectively earthed neutral). Frequently a maxi-
mum voltage of 38.5 kV is used which corresponds to installations with 35 kV, plus 10% tolerance.
Insulation co-ordination: the insulation level of 36 kV circuit-breakers can be rated to maximum
values 185 kV lightning impulse withstand voltage (BIL) and 85 kV short-duration power-
frequency withstand voltage (the standard insulation relating to the upper values according to IEC is
170 kV / 70 kV). All other equipment, including protective components such as RC-circuits and
surge arresters, shall be correspondingly dimensioned; the complete switchgear installation must
fulfil these insulation values.

B 10.2 Protective measures against overvoltage


Furnace transformers are generally equipped with RC-circuitry and surge arresters. RC elements
prevent resonant oscillations in the transformer in that they form a high pass filter to earth for tran-
sient high-frequency currents caused by multiple re-ignitions. Arresters limit the overvoltages
caused by virtual current chopping, which can occur on switching off currents up to 600 A. Currents
in this range are possible even if the rated operating current of the transformer is far above 600 A,
as the actual values to be switched during operation lie between the magnetising current (no-load)
of the furnace and twice the rated value (electrode short circuit). Depending on the method of neu-
tral point earthing 3 surge arresters in phase-earth connection are used or additionally between the
phases (6 arrester connection).
It depends on the network configuration whether the busbar needs surge protection as well. Installa-
tions with a low earth capacitance of the inferring system require power capacitors at the busbar
with a damping resistor (as shown in the figure below) or RC-circuitry similar to that on the trans-
former. Under certain conditions surge arresters must be additionally fitted to busbar: they limit
together with the arresters at the transformer the overvoltages across the contact gap.

F urnace transformer

R
C
C-R circuitry Arc furnace
at the busbar

Figure B-12: Overvoltage protection of a furnace transformer

The protection devices have to be matched individually to each system configuration by means of a
system study. This optimises the efficiency of protection and is inevitably necessary to protect the
components themselves. The arc furnace causes harmonics which in turn drive harmonic current
through the capacitors. The latter plus the damping resistors must be dimensioned for the resulting
thermal load. Furthermore the capacitance must be matched to the inductance of the inferring net-
work in order to avoid resonances, which stress the equipment by voltage rise and reactive current.
See also chapter I 2 for information.

36 Siemens AG 12E3
Switching duties in medium voltage systems

B 11 Converter transformer
This heading comprises transformers with:
- controlled rectifiers
- converter-fed drives
- voltage / frequency converters
- static compensators (static VAR or SVC)

Duty: unloaded loaded


Current: magnetising current up to rated current
0.5 - 3 % rating current
cos : < 0.3 ind. lag. lead.
Note: See distribution transformers When switching off under load at currents
600 A, overvoltages may occur; there-
fore overvoltage protection is required.

Table B-17: Switching of converter transformers

B 11.1 Protective measures


In normal service the load current is controlled by the converter so that the transformer is switched
off only under no-load condition, which is uncritical just like distribution transformers. However,
a direct switching off operation, initiated by the circuit-breaker, cannot be precluded unless the con-
trols of converter and circuit-breaker are interlocked (for this purpose the circuit-breaker must be
fitted with a leading auxiliary switch). Switching off a loaded converter transformer may provoke
the same conditions that prevail during the transformer inrush phase and can be associated with
unduly high overvoltages. Therefore overvoltage protection should be generally installed. Experi-
ence has revealed that in converter installations above all the line-to-line insulation must be pro-
tected against overvoltages whereas the line-to-earth insulation is less critical.

In systems up to 15 kV operating voltage surge limiters or arresters in line-to-earth connection can


also reduce the line-to-line switching surges to permissible values. This is, however, only applicable
if the transformer is insulated in accordance with the upper rated insulation level of table 2, IEC
60076-3 [6] these value are the same as of column (4), Table H-3.

All other cases require a 6-arrester arrangement which must be individually rated according to the
operating voltage, method of system neutral point earthing and insulation level of th eequipment;
see chapter E. The same applies to installations at operating voltages above 15 kV.

Siemens AG 12E3 37
Switching duties in medium voltage systems

B 11.2 Systems up to 15 kV operating voltage

Figure B-13: Overvoltage protection of converter transformers up to 15 kV

Surge limiters or arresters at the circuit-breaker (1) are permissible only if the transformer insulation
complies with the upper value of the rated insulation level according table 2, IEC 60076-3 [6]; the
values correspond with column (4) Tabelle H2. If the insulation level is lower, the limiters or arrest-
ers must be installed at the transformer (2).

B 11.3 Systems above 15 kV operating voltage

Figure B-14: Overvoltage protection of converter transformers above 15 kV

Rated voltage of trans- Suge limiters at


former up to: circuit-breaker transformer
3.6 kV 3EF1 036-0A 3EF1 036-0A

4.8 kV 3EF1 048-0A 3EF1 048-0A

7.2 kV 3EF1 072-0A 3EF1 072-0A

12 kV 3EF1 120-0A 3EF1 120-0A

15 kV 3EF1 150-0A 3EF1 150-0A

> 15 kV For the selection of ratings refer to chapter E

Table B-18: Recommended surge limiters for converter transformers

38 Siemens AG 12E3
Switching duties in medium voltage systems

B 12 Capacitor banks and filter circuits


Capacitor banks and filter circuits pose similar demands on the circuit-breaker. Potentially critical
impacts are the inrush current and the stress of the recovery voltage. The following paragraphs deal
with the requirements of
- capacitor banks without reactors
- capacitor banks with inrush limiting reactors (reactor-capacitor units)
- filter circuits

B 12.1 Capacitor banks (without reactor)


Duty: - Single capacitor bank
- Paralleling of capacitors (back-to-back switching)
Current: - up to 1.43 times the capacitor rated current at the fundamental component
(factor 1.43 includes harmonics and tolerances of the capacitance)
- on back-to-back switching, 100 times the rated current of the capacitor may
occur [9]
cos : leading
Remarks: When paralleling, a high inrush current (Ie) with high rate of rise (considerably
above the value of a short-circuit) may occur. The permissible inrush current
(peak value) of a circuit-breaker depends on the geometry and the mechanical
travel characteristics of the breaker contact and should not exceed following
values:
- with flat contact pieces (vacuum circuit-breaker and contactor) Ie =10 kA
- with tulip contact pieces (SF6-, minimum oil, compressed air) Ie = 5 kA
When closing on a single capacitor bank, the inrush current does not exceed
the peak value and the rate of rise of a power-frequency short-circuit, which
the breaker must be capable to cope with in any case.
Measures: Circuit-breaker must feature a very low restrike probability and comply with
class C 2 according to IEC 62271-100 [7].
Single capacitor banks do not require additional measures.
When back-to-back switching of capacitor banks, the inrush current must be
determined and where applicable be limited; B 12.3.

Table B-19: Switching of capacitor banks (without reactor)

B 12.2 Reactor-capacitor combinations

Duty: - Single capacitor bank


- Paralleling of capacitors (back-to-back switching)
Current: up to rated current of the capacitor bank or the filter

Siemens AG 12E3 39
Switching duties in medium voltage systems

cos : leading
Remarks: After the opening operation the voltage on the capacitor side is higher than the
system voltage (Figure B-18), so that the recovery voltage is higher in contrast
to capacitors without reactor. The rated voltage of the breaker must not be
exceeded by this effect.
When paralleling, high inrush currents (Ie) with high rate of rise may occur,
depending on the reactor ratings. However, the inrush current does not exceed
the permissible limits of breaker and capacitor if reactors are used (usually
tuned to between 4th and 5th harmonic).
Measures: If the voltage at the breaker exceeds its rated value, either a breaker of a higher
rated voltage level or 2 series-connected breakers have to be used.
Circuit-breaker must feature a very low restrike probability and comply with
class C 2 according to IEC 62271-100 [7].
When back-to-back switching of capacitor banks, the inrush current must be
determined and where applicable be limited; see B 12.3.

Table B-20: Switching of reactor-capacitor units and filters

B 12.3 Permissible inrush current


The permissible inrush current depends on the ratings of both the circuit-breaker and the capacitor
bank.
Capacitor bank: Independent of the circuit-breaker, the peak value of the inrush current may not
exceed 100 times the rated normal current of the capacitor, in order to limit the effect of the electro-
dynamic forces. The factor 100 is a general rule only, at high switching rates the standard [9] rec-
ommends to limit the inrush current to lower values.
Capacitors are normally equipped with discharge voltage transformers or resistors. If re-closing
cycles may occur in normal service, the discharge time constant must be chosen short enough that
the capacitor is almost completely ( 10 %) discharged before re-energising. Otherwise the inrush
current can increase to undue values if the polarity of the system voltage is in opposition to the re-
sidual charge.

Circuit-breaker: In order to avoid inadmissible stress and wear of the contact pieces, permissible
limits of the inrush current must be observed. For Siemens circuit-breakers the following inrush
currents are permissible without reservations:
- Ie 5 kA for tulip contacts (SF6 or minimum-oil circuit-breakers)
- Ie 10 kA for flat contacts (vacuum circuit-breakers)

Regarding flat contacts the limit value is founded on the tendency to contact welding if the inrush
current does not decay rapidly enough during the pre-arcing time (1 2 ms) of the contact closing
travel. Inrush currents above the limits mentioned above require an agreement with the manufac-
turer. On the other hand, if the inrush current decays rapidly below the limit, considerably higher
initial values of the inrush current are permissible (Figure B-15).

40 Siemens AG 12E3
Switching duties in medium voltage systems

10
LS Ie
8 Tulip contact
Time constant [ ms ]

4 L1 L2

permissible range
2 QC1 QC2
of flat contact

0
0 5 10 15 20 25 30 35 40
Inrush current (peak value) [ kA ]

Figure B-15: Permissible back-to-back inrush making current dependent on the time constant

The limit value 20 kA of the inrush making current marks the rated back-to-back inrush making
current for capacitor banks recommended by the circuit-breaker standard [7].

The decay time constant of the back-to-back inrush making current can hardly be determined with-
out knowledge of the impedance (cable or bar, length, cross section and shape) between the capaci-
tor banks. It is extremly difficult to determine the resistive component since the skin effect reduces
the active conductor cross-section at some kHz frequency of the back-to-back inrush making cur-
rent. An assessment by means of the inductance between the capacitor bank gives a hint whether the
inrush current lies in the critical range and requires detailed calculation.

B 12.4 Measures to limit the inrush making current


There are two possible ways to reduce a high inrush making current and to move it into the permis-
sible region:
- The limitation of the inrush current to 10 kA (or 5 kA) by means of a reactor
- The reduction of the time constant (attenuation constant) by means of a resistor-inductor
unit in parallel with the reactor. However this measure is only convenient for existing
reactor-capacitor units.

For a given reactive power and inductance between the capacitor banks, the inrush making current
on back-to-back switching can be read from the graphs (Figure B-16). If the inrush current is too
high, the diagram shows the inductance which is required to keep the inrush current below the limit.
The difference between the existing and the required inductance should be installed as an additional
reactor; see (a), Figure B-17. The red border lines (Figure B-16) mark the area (grey) for 6 kV to 30
kV operating voltages within which the attenuation constant of the inrush making current is to high.
For these border lines a Q-factor (quality factor) 60 of the parallel oscillating circuit is presumed.

Siemens AG 12E3 41
Switching duties in medium voltage systems

Inrush making current Ie = 40 kA 30 kA 20 kA 15 kA


100,0

10 kA
Back-toback reactive power Qc* [MVA]

30 kV 7 kA
20 kV
5 kA
10,0
10 kV 4 kA

6 kV 3 kA

2 kA

1,0

0,1
10 100 1000
Inductance L* between the capacitor banks [H]

Figure B-16: Back-to-back inrush making current of two capacitor banks,


depending on the inductance between the banks

The back-to-back reactive power results from the series connection of the QC1 QC 2
two capacitor banks (Figure B-15). QC* =
QC1 + QC 2

The inductance between the capacitor banks consists of the inductances


of the connecting conductors and the switchgear assembly. The following L* = L1 + L2 + LS
values can be presumed: for L1 and L2 insert the values of the relevant
cables / bars (in the range of ca. 0.3 0.7 H/m). For each functional
unit (panel) of the switchgear assembly insert 2 H for the busbar, and
5 H for the two feeders (including current transformers); n = number of Ls 5H + n 2H
functional units (panels) between the capacitor bank feeders.

Figure B-17: A reactor which can be freely selected (a) is the easiest method to limit the inrush
making current. In the case a reactor is already installed or planned but the inrush current is still too
high, a resistor in parallel (b) can tune the attenuation constant. The resistance, however, may vary
in a small range only. It must neither be too high (to be efficient) nor to low (to avoid thermal over-
load of the resistor). An L-R impedance in parallel to the reactor (c) facilitates more exact tuning. In
any case the damping damping elements need to be individually planned for the given installation.

42 Siemens AG 12E3
Switching duties in medium voltage systems

Ie Ie Ie

L
L L R L
R

a) Reactor to attenuate the in- b) Resistor-reactor unit to tune c) Reactor with resistor-
rush making current the attenuation constant inductor unit in parallel to
tune the attenuation constant

Figure B-17: Methods to limit the inrush making current

B 12.5 Permissible voltage at the circuit-breaker


When filter circuits or reactor-capacitor units are switched off the recovery voltage across the
breaker is higher than when other loads are switched. The reasons for this are on the one hand the
properties of the combination of reactor + capacitor and on the other hand the fact that these filters
are used in systems where the voltage stress on the equipment is increased by distorted voltage due
to harmonic oscillations.
The voltage on the load side of the breaker can exceed the rated value, even if the system voltage is
below the rated breaker voltage, because the capacitor voltage appears at the breaker after switching
off. The capacitor voltage in turn is higher than the system voltage; see B 12.6 (Figure B-18).

Additional stress stress across the breaker may occur after for example faulty or unintentionally
tripping, if the system is still inductively loaded and the system voltage on the busbar side drops
after switching off the filter (due to the loss of capacitance). If, moreover, the system voltage is
heavily loaded with harmonics, the addition of all unfavourable effects can lead to an extremely
high voltage across the breaker. Consequently it must be checked very accurately whether the stress
on the circuit-breaker is within the permissible range.
If the capacitor voltage (Uc) exceeds the rated breaker voltage (Ur), a breaker of the next higher
voltage rating must be used; e.g. a 36 kV breaker instead of a 24 kV breaker, or two breakers must
be connected in series.

The following section summarises how the voltage stress caused by filters and reactor-capacitor
units are determined, und which parameters need be checked regarding the circuit-breaker.

Siemens AG 12E3 43
Switching duties in medium voltage systems

B 12.6 Determination of the voltage on the load side of the breaker


Immediately after switching off the voltage UF is present on the load side of the breaker, which can
be determined as described below.

UC UL
UN
IF
UC
UF UL
UF

UC IF
IF U
L

UN Voltage of network 1
UF Voltage at filter Filters frequency: f F =
2 L C
UL Voltage across reactor
UC Voltage at capacitor Filter- / system frequency ratio = fF / fN
IF Filter current = Harmonic number (ordinal number)
L Reactance
C Capacitance of capacitor bank

Figure B-18: Voltage at a filter or a reactor-capacitor unit

When circuit is closed the voltage on both sides of the circuit-breaker, filter and busbar, is the same
(UF = UN). Immediately after switching off (marked by subscript o) the capacitor voltage appears
at the breaker since the voltage across the reactor drops to zero.
Thus the voltage on the breaker load side is UFo = UCo

After the opening operation the filter voltage is equal to the ca- 2
pacitor voltage which is calculated with the harmonic number : U Fo = U Co = U N
2 1

52
Example: = 5, i.e. filter frequency 250 Hz: U Fo = U Co = U N = 1,042 U N
52 1

This means that immediately after switching off the voltage on the load side of
the circuit-breaker is 4.2 % higher than the the system voltage on the busbar side.

44 Siemens AG 12E3
Switching duties in medium voltage systems

B 12.7 Check for permissible stress on the circuit-breaker

Back-to-back switching Reactor-capacitor and


of capacitor banks filter combinations
No additional measures required

+ Inrush making current + Determination of the


(peak value) breaker load side voltage
Ie 10 kA (5 kA) (Uc) after switching off

+ Attenuation constant + Breaker load side


(time constant) in the
voltage Uc Ur
permissible range?

Limitation of inrush current by Apply a circuit-breaker


reactor, where applicable with next higher
additional resistor-inductor unit rated voltage Ur
in parallel

Figure B-19: Inrush current check Figure B-20: Voltage check

If the back-to-back inrush making current is below the permissible peak values (see section B 12.3)
or the ateenuation of the current is strong enough, no additional measures are required. Otherwise a
detailed assessment as described in section B 12.4 has to be carried out.

With filters or reactor-capacitor units the voltage on the load side of the circuit-breaker must not
exceed the rated value at the instant of switching off. There is a particular danger if the operating
voltage of the system is very close to the rated voltage and at a low ordinal number of the harmon-
ics.

Siemens AG 12E3 45
Switching duties in medium voltage systems

B 13 Audio frequency ripple control systems


AF ripple control systems feed audio-frequency impulses into distribution systems. The audio-
frequency varies from 160 Hz up to 1.600 Hz. Series injection is usual for the lower frequencies, for
the upper range only parallel injection is used. In both cases the circuit-breaker switches a capaci-
tive current, consisting of a power-frequency proportion on which the audio-frequency proportion is
super-imposed. Vacuum circuit breakers are restrike-free and thus they are well suited for this
switching duty.

Current: up to 20 A
cos : leading
Remarks: An audio-frequency current (160 Hz up to 1.6 kHz) is superimposed on the
power-frequency control (50/60 Hz).
Air and hard gas (gas evolving) switches are not suitable for this switching
duty.

Table B-21: Switching of AF ripple control systems

Additional measures: None

46 Siemens AG 12E3
Rated values of switching devices

C RATED VALUES OF SWITCHING DEVICES

C1 Overview
The following table lists the most important values of the primary circuit, in accordance with which
a device has to be selected. The symbols are those used in the standards IEC 62271 series.

Value Symbol Circuit- Switch (dis- Contactor1) HRC Surge


breaker connector) fuse arrester
Rated -
Voltage Ur x x Ue x UL/Uc/Ur
Insulation level Ures/uai
- lightning impulse withst. volt. Up x x x
- power-frequency withst. volt. Ud x x x
Frequency fr x x x
Current Ir x x 2) Ie 2) x
Short-time withstand current Ik x x x
Duration of short-circuit tk x x x
Peak withstand current Ip x 3) discharge
current Is
Short-circuit making current Ima x x Im
Short-circuit breaking current Isc x Ic
Mainly active load-breaking I1 x
current
Closed-loop breaking current I2a, I2b x
No-load transformer breaking I3 x
current
Cable-charging breaking cur. I4a x
Line-charging breaking current I4b x
Earth fault breaking current I6a x
Cable- and line-charging break- I6b x
ing current under earth fault
conditions
Cable- and line-charging break- *
ing current under earth fault
conditions with superimposed
load current
Transfer current Ir-transfer x 4)

Table C-1: Primary ratings of equipment

x Selection values foreseen by the standards.


* Recommended selection value, not required by the standards.
1) The symbols used for high voltage contactors are sometimes different, since they
were historically designed in accordance with the low voltage standards.

Siemens AG 12E3 47
Rated values of switching devices

2) In switch-fuse combinations the rated current is limited to the rated current of the fuse.
3) Not defined in the standard; see note (1).
4) Applies only to switch-fuse combinations.

C2 Rated voltage Ur
is the upper limit of the highest voltage of systems for which the device is intended and designed. It
must be at least equal to the highest expected operational voltage at the installed location, consider-
ing effects such as:
short duration voltage rises
harmonics
load shedding
increased levels at capacitors and filters

C3 Rated insulation level Ud and Up

is the dielectric strength (lightning impulse and power-frequency withstand) phase to earth, between
phases and across open switch gaps or isolating distances. The insulation level comprises the
Rated lightning impulse withstand voltage Up (1.2/50 s)
Rated power-frequency withstand voltage Ud (50 Hz / 1 min)
Instead of rated lightning impulse withstand voltage Up the term BIL (basic impulse level) is also
often used.
For medium voltage the standards do not specify a switching impulse voltage withstand but this
value is of importance for the selection of overvoltage protection devices for transient switching
surges. This switching impulse level (SIL) is set at
0.8 BIL, because the much longer transient tail time of the switching impulse requires a lower di-
electric strength than the lightning impulse.
The insulation level is related to the rated voltage. If it is not adequate for a particular duty, because
external or internal overvoltage sources have to be considered, the fitting of surge arresters is rec-
ommended.

C4 Rated normal (operating) current Ir


is the (r.m.s.) current which the main current path of the device can carry continuously under de-
fined conditions.
The value normally applies to equipment in free air. The actual permissible value depends, there-
fore, on the temperature at the installed location. The permissible value may be reduced by

installation within a housing or cubicle (restricted heat dispersion)

48 Siemens AG 12E3
Rated values of switching devices

the current carrying capacity of connected equipment (cables, fuses)

harmonics (total current I ges I 502 Hz + I OS


2
)

With HRC fuses, the rated current is just an "ordering size". Because of the particular character of
this device, the actual value to be chosen depends on various other factors; see section D.

C5 Rated short time withstand current Ik


is the effective (r.m.s.) value of the short circuit current which the device, when closed, can carry
for a specified time under defined conditions.

C6 Rated duration of short circuit tk


is the time for which the device, when closed, can carry a current equal to its rated short time with-
stand current. The standard value is 1 second. If a longer time is necessary, the recommended alter-
native is 3 seconds. By agreement between manufacturer and user, a value < 1 s may be chosen.

C7 Rated peak withstand current Ip


is the peak current of the first major loop of the rated short time withstand current which the device
can carry, when closed, under defined conditions. For devices which have full fault closing capabil-
ity ( rated short-circuit making current) this value is inherent.
In switch and fuse combinations, the magnitude of the let through current of the largest fuse for
which the combination is designed, is adequate.

C8 Rated short-circuit making current Ima


is the current which the device can safely handle when making onto a short circuit at its terminals.
The stress is greater than that given by the rated peak withstand current since dynamic forces and
the movement of the switch blades aggravate the condition.
Normally the short circuit making current is taken as 2.5 times the r.m.s. short time short cir-
cuit current. That multiple corresponds to the relationship in distribution networks when a
generator-remote short circuit occurs (peak value of the initial short circuit a.c. current IP =
1.8 2 Isc"; peak factor = 1.8). Close up to motors and generators, the peak value of the
making current may be more than the power frequency short circuit current. In such cases, the
switching device must have a rated value at least equal to this duty!
In switch and fuse combinations, the magnitude of the let through current of the largest fuse
for which the combination is designed, is adequate.

Siemens AG 12E3 49
Rated values of switching devices

C9 Rated short-circuit breaking current Isc


is the current which the device can safely interrupt when the short circuit is at its terminals.
In the selection of this value, the rated making current shall also be considered. Normally
Ima = 2.5 Isc, but if the relationship Im/Isc > 2.5 in the network, then a device with a larger
rated breaking current must be chosen.

C 10 Rated mainly active load-breaking current I1


Is used with switcheas only and designates the same as the rated (normal) current.

C 11 Rated closed-loop breaking current I2a, I2b


is the same as the rated (normal) current.

C 12 Rated no-load transformer breaking current I3


applies to general purpose switches and is defined as the current of an unloaded transformer; the
value amounts 1 % of the rated operating current.

C 13 Rated cable-charging breaking current I4a


is between 6A (at 7.2 kV) and 20 A (at 36 kV) according to the standard. Manufacturers may give
higher values. Here, the charging current of unloaded cables is meant.

C 14 Rated line-charging breaking current I4b


is between 0.5A (at 7.2 kV) and 2 A (at 36 kV) according to the standard. Manufacturers may give
higher values. Here, the charging current of unloaded overhead lines is meant.

C 15 Rated earth fault breaking current I6a


is the largest earth fault current which the switching device, in a network with unearthed neutral
point, must be able to interrupt.
This refers to a fault on the line side of the switch, with unloaded line (see Table A-3, case No. 11).
The switch must be able to interrupt the charging current of all galvanically connected lines (some-
times a larger value), at normal recovery voltage

50 Siemens AG 12E3
Rated values of switching devices

C 16 Rated cable- and line-charging breaking current


under earth fault conditionsI6b
is the largest current in the fault-free conductors, which the switch must be able to interrupt.
This refers to a fault on the line side of the switch, with unloaded cable (see Table A-3, case No. 9).
The switch must be able to interrupt the charging current of the connected cables (or lines). And
that at 3 x recovery voltage, because the earth fault remains, on the line side. Hard gas and air-
break switches have very small capability in this case.

C 17 Cable switching current under earth fault conditions


with superimposed load current
This current is not defined in the standards but is a realistic operational case. The standard requires
only a value for unloaded cable switching under fault conditions. In practice, however, load currents
are almost always present.
For hard gas and airbreak switches, this is a very critical case (see Table A-3, case No. 10). Before
using such a switch, the network conditions must be ascertained and the capability requested from
the manufacturer.

C 18 Rated transfer current Itransfer


is the largest current which a switch, in a fuse switch combination, must be able to interrupt. This
value is critical for the selection of the associated fuse; see section D.

C 19 Rated voltage UL (surge arrester with spark gaps)


is the highest power frequency (network) operating voltage at which the arrester can still extinguish
the follow current after sparkover.

C 20 Rated voltage Ur (metal oxide surge arrester)


is the maximum power frequency voltage which the arrester can withstand, when operating, under
the conditions of a short term voltage rise of at least 10 seconds.

C 21 Continuous operating voltage Uc (metal oxide surge arrester)


is the maximum network operating voltage which may be applied continuously to the arrester.

Siemens AG 12E3 51
Rated values of switching devices

C 22 Sparkover voltage
is the voltage which causes the arrester to operate; that is, to break down its spark gap(s). The form
of the voltage determines the speed of the breakdown and the threshold; one therefore qualifies this
value by distinguishing between switching impulse sparkover voltage uai, front of wave sparkover
voltage uast and 100% lightning impulse sparkover voltage uas100.

C 23 Residual voltage ures


is the maximum voltage across the arrester terminals when the discharge current is flowing. Spark-
over and residual voltage determine the protection quality of the arrester and are thus very impor-
tant values for insulation coordination calculations.

C 24 Rated discharge current isn


is the maximum value of the discharge current which the arrester can carry without exceeding the
highest permissible residual voltage.

52 Siemens AG 12E3
Selection of HRC fuses

D SHORT-CIRCUIT PROTECTION WITH HRC FUSES

D1 Selection criteria
In switch and fuse combinations, protection against short circuit is performed by the fuses. Switches
will interrupt operating currents and only small overcurrents, since their interrupting capability is
limited. Between operating current and full short circuit the switching duty transfers from one com-
ponent to the other. Switch and HRC fuses must, therefore, be matched correctly to each other.
Mostly, one uses current limiting fuses; selection procedures are described later in this chapter.
The electrical characteristics of a fuse are: rated voltage and rated current (UrHH, IrHH). The diagram
clarifies the factors which determine selection. The factors are coupled by a logic "AND", that is,
they must all be considered in determining rated voltage and current.

Highest system voltage


Rated voltage UrHH
Load characteristics

Load characteristics
Breaking capability of switch or contactor
Rated current Coordination with other equipment:
- dynamic and thermal withstand capability
- heat dissipation
- selectivity to up- and downstream protection

Rated breaking current Short-circuit current of system

Fuse base (length, diameter)


Housing and striker
Striker (e.g. 80 N / 100 N / 120 N)

Figure D-1: Criteria influencing the selection of fuses

Mechanical criteria, e.g. diameter, length, striker pin power, all depend upon the type and design of
the switchgear assembly or switch; they are not discussed here.

D2 HRC fuses for distribution transformers


D 2.1 Fuse rated current IrHH
There is a reference list of fuses defined by the manufacturer, which HRC fuses are suitable for
transformers of given voltage and power ratings. This list is based on the requirements of IEC
60787 [27]. The selection is determined by:
- the inrush current on energising the transformer
- the primary current when the secondary is short circuited
- selectivity requirements and coordination with up- and downstream equipment

Siemens AG 12E3 53
Selection of HRC fuses

D 2.1 a Inrush current


It affects the fuse in the same way as a large, time limited overcurrent. The fuse element of the fuse
shall not be pre-conditioned by the heating effect of this current. A fuse with rated current larger
than the transformer rated current is therefore selected. Depending on power, short circuit voltage
and connection group, the smallest usable fuse size results.
- For a simplified selection method the inrush current is set to 12 15 times the rated normal
current of the transformer, with a duration of 0.1 s; point A in the figure below.

D 2.1 b Primary current while terminal short-circuit on the LV side of the transformer
On interruption of such a terminal short circuit, very steep transients result. Because of the limited
interrupting capability of the switch, these currents should be interrupted by the fuses. The primary
side short circuit current can be very much damped but, even so, the HRC fuses must operate and
interrupt positively and safely. This factor determines the largest possible rated fuse current.
- For a simplified selection method the short-circuit duration on the HV side shall correspond to
the maximum permissible short-circuit duration of the transformer; as a rule the value is 2 s;
point B in the figure below.
- Minimum values of the short-circuit impedance uk are listed in IEC 60076-5 [29].

Time Derating due to high HRC fuse link


[s] ambient temperature

100

Protective device
10 characteristic on Load capability
LV side of cable
Imin
2 B
1

Protective device
0,1
A characteristic on
source side

0,01
C

1 2 3
10 IrT IT-overload 10 IT-Rush IrT/uk 10 Current [A]

Figure D-2: HRC fuse characteristic for the protection of distribution transformers

54 Siemens AG 12E3
Selection of HRC fuses

The fuse time-current characteristic must lie between the points A and B.
Point A: I = 10 12 IrT Point B: I = IrT / uk
t = 0.1 s t=2s

D 2.1 c Coordination with other equipment


- The fuse rated current must be selected such that the temperature rise of the fuse link does not
exceed the limit given at the installation location. In particular this applies to the installation in
enclosed switchgear.
- The same condition is applicable for locations at very high ambient temperatures;
see section D 7.
- When using switch-fuse or contactor-fuse combinations, the breaking capability of the switching
device must not be exceeded; see section D 5.
- The time-current characteristic of the HRC fuse should lie to the left of the thermal load capabil-
ity of the cable.
- The cut-off (let through) current assigned to the rated normal current of the fuse must be smaller
than the dynamic load capability of the cable.

D 2.1 d Selectivity to other protection devices


- Between HRC fuses: when two fuses are operated in series which can occur in long radial
feeders (dead-end feeder), the rated current of the upstream fuse must be 1.6times the rated cur-
rent of the downstream one (IrHH-up 1.6 IrHH-down). Factor 1.6 roughly corresponds to two steps
of the rated current.
- Between HV and LV fuses: firstly, the currents must be adjusted for the voltage levels. The rated
current of the high voltage fuse must be compatible with the current of the (largest - if a number
are in parallel) low voltage fuse.
- Between HV fuse and LV circuit breakers: the LV breaker shall clear all faults which are down-
stream of its terminals. For selectivity one needs the pre-arcing time characteristic of the fuse
(calculated for the low voltage side) and the opening time of the LV breaker. The procedure is
similar to that determining selectivity between fuse and motor protection relay.

Additionally, the requirements of chapters D 5 to D 7 must be observed.

D 2.2 Rated voltage UrHH


The rated voltage of the fuse in most cases is determined by the network voltage only.

Siemens AG 12E3 55
Selection of HRC fuses

D3 HRC fuses for capacitors


D 3.1 Fuse rated current IrHH
When energising capacitors particularly when paralleling them extremely high inrush currents
can occur, with amplitudes of the order of short circuit magnitude. Inrush duration, however, is
short - in the range of milliseconds. These short circuit-like currents impose a very high degree of
stress on the fuses.
In addition to the 50/60 Hz basic frequency, higher harmonics always flow through a capacitor,
dependent upon the harmonic content of the network. The effective value of the total current can,
under normal network conditions, reach 1.43 times the capacitor rated current.
For these reasons, the rated fuse current shall be explicitely higher than the capacitor rated current
(IrC), preferably 4 times higher at least twice as high,: IrHH = 2 4 IrC

Additionally, the requirements of chapters D 5 to D 7 must be observed.

D 3.2 Rated voltage UrHH


The rated voltage of the fuses shall be one step higher than the network voltage, so that there is ade-
quate margin to cover the harmonic content.

D4 HRC fuses for motors


Fuses provide short circuit protection, not overload protection for the motor! For the termal motor
protection, a definite minimum time, current proportional protection relay is used. (In English ter-
minology an i.d.m.t. relay, in German, an AMZ relay).

D 4.1 Fuse rated current IrHH


Catalogues from fuse manufacturers give selection recommendations, which consider the following
points:
- the starting current of the motor
- the run-up time and starting frequency
- compatibility with a motor protection relay, if fitted.

D 4.1 a Motor starting current, run up time and frequency of starting


Starting currents, which can be 5 to 7 times the motor full load current, have the same effect on the
fuses as a large, time limited overcurrent. The fuse element of the fuse shall not be pre-conditioned
by the heating effect of this current. The motor starting current and run up time gives the smallest
usable fuse.
If no reference list of the fuse manufacturer is available, the fuse can be selected in the following
way:

56 Siemens AG 12E3
Selection of HRC fuses

Time HRC fuse link


[s]
Inverse time
Motor current

overcurrent relay Imin


100

B
A A*
10
Starting time
Load capability
of cable

Instantaneous fault
Starting current

relay (earth fault) Breaking


0,1
capability
of contactor

1 3
10 Ist Ist / k 10 Current [A]

Figure D-3: HRC fuse characteristic for motor protection

The motor starting current (Ist) is given, otherwisw the starting current is presumed to be
6 times the motor rated current (Ist = 6 IrM) this refers to direct starting asynchronous
machines.
On indirect starting, i.e. slipring motor or run-up via autotransformer or converter (soft starter),
the starting current (Ist) is much smaller; regularly in the range of 1.2 2 IrM

The motor starting current (Ist) is divided by a derating factor (k) of the HRC fuse, which takes
into account the the number of starts per hour; see Table D-2: Derating factor k depending on
the number of starts per hour.

The value Ist / k together with the starting time tst result in point A*, which must lie to the left of
the fuse characteristic (a fuse may be selected whose characteristic is directly next point A*).

For slipring motors or for motors running up at reduced starting current, via autotransformer or
converter, smaller HRC fuses can be selected. However, the fuse rated current must be at least
1.3 times the motor rated current (IrHH IrM).

Siemens AG 12E3 57
Selection of HRC fuses

Starting time / s Motor application


6 Pump
15 Mill
30 60 Fan

Table D-1: Typical starting times (Source: SIBA, catalogue HHM)

Starts per hour Derating factor Derating factor


Nmax / h kSIBA kgeneral14
2 0.59 0.55
4 0.53 0.50
8 0.48 0.45
16 0.43 0.40
32 0.39 0.33

Table D-2: Derating factor k depending on the number of starts per hour

D 4.1 b Coordination with other equipment


If the motor is equipped with a inverse overcurrent protection, the current at intersection point
B must be larger than the minimum operating current Imin of the fuse. If that cannot be
achieved, it must be ensured that overcurrents up to Imin will be broken by the switching device,
for example, by a contactor-fuse combination with tripping by the fuse striker pin.
The fuse rated current must be selected such that the temperature rise of the fuse link does not
exceed the limit given at the installation location. In particular this applies to the installation in
enclosed switchgear. The same condition is applicable for locations at very high ambient tem-
peratures; see section D 7.
When using contactor-fuse combinations, the breaking capability of the switching device must
not be exceeded; see section D 5.
The time-current characteristic of the HRC fuse should lie to the left of the thermal load capa-
bility of the cable.
The cut-off (let through) current assigned to the rated normal current of the fuse must be
smaller than the dynamic load capability of the cable.

Additionally, the requirements of chapters D 5 to D 7 must be observed.

D 4.2 Rated voltage UrHH


The rated voltage of the fuse is determined by the network voltage only in almost all cases.

14
The factor kgeneral should be used if no information from the fuse manufacturer is available.

58 Siemens AG 12E3
Selection of HRC fuses

D5 Co-ordination with a switch or contactor


A switch-fuse or contactor-fuse combination must be able to safely interrupt every possible current,
up to full short circuit. The procedure is laid down in IEC 62271-105 [30] 15. Switch and fuse must
be so co-ordinated that
- the switch safely handles all currents up to the minimum interruption current of the fuse;
- the fuse interrupts all currents which lie beyond the interruption capability of the switch.
The largest (inductive) current which the switch can interrupt is called the rated transfer current of
the switch.
Dependent upon the fuse rated current and the opening time of the switch there is a current above
which the fuses alone must interrupt the circuit. This current is the transfer current for the fuse and
switch combination, with the fitted HRC fuse. The transfer current shall not be larger than the rated
transfer current of the switch.

Determination of the transfer current uses the following data:


- the time current characteristic of the fuse
- the characteristic opening time of the switchT0 (for direct release by striker pin or tripping coil)
- the rated transfer current of the switch Itransfer (manufacturer's data)

c For direct mechanical striker pin release of the switch: Draw a line parallel to the current
axis through the point 0.9 T0 , to the pre-arcing time axis. Then to e.

d For electrical release of the switch, by a tripping coil: Draw a line parallel to the current axis
through the point T0 to the melt axis; if a relay is in circuit with the tripping coil, draw the line
through the point T0 + 0.02s.

e The intersection of this line with the lower time/current characteristic of the fuse gives the as-
sociated transfer current Itransfer (three pole, symmetrical value).

f The transfer current Itransfer thus determined must be smaller than the rated transfer current
Ir-transfer stated by the manufacturer, that means Itransfer > Ir-transfer, and must be larger than the
minimum breaking current (Imin) of the fuse, i.e. Itransfer > Imin.

Additional requirement for the protection of distribution transformers


In case of a short-circuit at the transformer secondary terminals (LV side), the HRC fuses shall
interrupt the short-circuit curent, so that the switch although the current still may be within
the range of the breaking capacity is not stressed with the high transient recovery voltage.
This results in the following condition which must be fulfilled additionally:

g The transfer current Itransfer must be smaller than the short-circuit current IkT-3pol of the trans-
former at secondary terminal short-circuit; (IkT-3pol > Itransfer).

15
Contactor-fuse combinations are not within the scope of this standard. The described method can, however, be used
for the practical use also for contactors.

Siemens AG 12E3 59
Selection of HRC fuses

Time HRC fuse


[s]
Imin
I"kT-3ph
10 Requirements:
Ir-transfer
a) Transfer current
Itransfer < Ir-transfer
Itransfer > Imin
1 b) Transformer short-circuit
IkT-3pol > Ir-transfer

0,1
0,9 T0
TX

0,01

1 2 3
10 10 Itransfer 10 Current I [ A ]

Figure D-4: Coordination of HRC fuse and switch

Example to determine the transfer current from the HRC fuse characteristic (50 A) and the opening
time of a switch:
- HRC fuse, type 3GA: IrHH = 50 A
- characteristic opening time of switch: T0 = 50 ms
transfer current of this combination: Itransfer = 405 A

Largest permissible HRC fuse


Conversely one can determine the largest permissible fuse for a combination, using the opening
time of the switch (T0) and the rated transfer current (Itransfer).

c For direct mechanical striker pin release of the switch: Draw a line parallel to the current
axis through the point 0.9 T0, to the pre-arcing time axis. Then to e.

d For electrical release of the switch, by a tripping coil:


Draw a line parallel to the current axis through the point T0 to the pre-arcing time axis; if a re-
lay is in circuit with the tripping coil, draw the line through the point T0 + 0.02s.

e Draw a line parallel to the time axis, through the point Itransfer on the current axis.

60 Siemens AG 12E3
Selection of HRC fuses

f This gives an area bordered by current axis, time axis, line through 0.9 T0 and line through
Itransfer.

g All fuses whose characteristics run through this area are suitable for use in this switch and fuse
combination.

The illustration shows this procedure in diagram form.


IkT-3pol is the current on the primary side in case of a short-circuit at the secondary terminals of the
transformer (short-circuit at the LV terminals).

Figure D-5: Suitable HRC fuses for a given rated transfer current of the switch

Depending on the tripping method TX is: 0.9 T0 for direct striker-pin release
1.0 T0 for electrical release
T0 + 0.02 s for electrical release using a relay

Siemens AG 12E3 61
Selection of HRC fuses

D6 Let-through (cut off) current


An HRC, current limiting fuse restricts the rising prospective fault current to its let-through value
and protects connected equipment from the extreme dynamic and thermal effects of the unrestricted
current. The connected equipment does not need to be designed for the full prospective short circuit
current of which the network in front of the fuse is capable.
- The let-through current must not exceed the rated withstand current of connected equipment; and
- must not exceed the rated short circuit making current of the associated switch.

Current limiting characteristics give the maximum let-through (cut off) current ICO related to initial
power frequency short circuit current and fuse rating. Conversely, one can determine the maximum
permissible fuse rating from the given dynamic withstand capability of the equipment.
The diagram shows how the let-through current can be found from the characteristic. For example,
at 40 kA (r.m.s. value) short-circuit current, a 50 A HRC fuse limits the peak current to only 9 kA,
whereas the prospective value is 100 kA.

Cut-off
current prospective peak current (cos 0,15)
Ico [ A ]
ID (50 A) 100 A
104 50 A
25 A

103

102
102 103 104 S.-c. current I"k [ A ]

Figure D-6: Cut-off (let-through) current characteristic of an HRC fuse

62 Siemens AG 12E3
Selection of HRC fuses

D7 Heat losses
The actual maximum permissible operating current of a fuse is, in general, less than its nominal
rated current due to the thermal conditions at the point of installation (in a cubicle or enclosure),
where heat dissipation may be restricted in comparison with installation in free air. In that case, the
fuse cannot be operated at its full rating.

Heat loss check


2.5
I
The actual heat loss in operation at any current IB is: PV = PVr B
I rHH
PV heat loss generated by HRC fuse at operating current
PVr rated heat loss from HRC fuse at IrHH
IB actual operating current

For IB insert the maximum value which can occur continuously in operation; e.g. transformer
rated current or 1.2 times the transformer rated current for extensive overcurrent operation.

Check if this heat loss is properly dissipated at the installed location.

If not, choose the next higher fuse rating, as long as the other selection criteria permit it.

The above mentioned equation includes the influence of the temperature on the internal resistance
of the fuse-element. When the fuse-element is loaded with less than its rated current, it heats less so
that in turn the heat loss decays disproportionally high. This temperature influence is represented by
the exponent 2.5 in the formula.

Example: HRC fuse with Ur = 12 kV; IrHH = 100 A; PVr = 110 W


10-kV- transformer 800 kVA, operating current IB = 46.2 A
2,5
46,2 A
Actual heat loss PV = 110W
100 A

Actual heat loss PV = 16,0 W

Siemens AG 12E3 63
Selection of surge arresters

E SELECTION OF OVERVOLTAGE PROTECTION DEVICES

E1 Selection criteria
The selection of surge arresters and their rated values can be done by the following scheme. The
figure is an adapted version taken from several standards and selection guidelines for surge arresters
[14] to [16].

Continuous operating voltage Uc


Maximum network voltage
Type of neutral earthing
Rated voltage Ur Temporary overvoltages

Relative frequency of occurrence


Rated discharge current
of overvoltage

Switching duty
Protection level for lightning and switching
Insulation level
impulse (residual voltage)
Protection level

Relative frequency of occurrence


Energy absorption capacity
of overvoltage

Short-circuit withstand capability Short-circuit level

Connector (plug or bolt)


Housing Site altitude
Degree of pollution

Figure E-1: Selection of medium voltage surge arresters

E2 Continuous operating voltage and rated voltage


Continuous operating voltage Uc is the maximum permissible power-frequency voltage that may be
applied continuously across the arrester terminals; continuously means more than 30 minutes.
Rated voltage Ur is the maximum permissible power-frequency voltage which the arrester can with-
stand for 10 seconds without suffering damage. This duration takes into account temporary over-
voltages. The rated voltage also is a reference value for other characteristics of the arrester and used
as ordering information.
Rated voltage of a spark-gap arrester Ur is the maximum permissible power-frequency voltage
across the arrester terminals at which the arrester can safely interrupt the discharge follow-current.
The rated voltage corresponds to the continuous operating voltage of non-gapped arresters.

64 Siemens AG 12E3
Selection of surge arresters

For metal oxide arresters, one first selects the continuous voltage, then the rated voltage. In net-
works with free or resonant earthed neutral point, the continuous voltage must be equal to the max.
line-line voltage, so that the arrester is also suitable for continuous earth fault conditions (voltage
rise in the healthy phases).

For arresters with spark gap and surge limiters, almost only the rated voltage needs to be selected.
If the values of rated and continuous operating voltage are not equal for the devices selected, the
selection must be done as described for metal oxide arrester.

System neutral Metal-oxide arrester Spark-gap arrester


point Continuous operat- Rated voltage Ur Rated voltage Ur
ing voltage UC

solidly earthed Uc 1.05 Um / 3 Ur 1.25 1.05 Um / 3 Ur 1.4 Um / 3

impedance earthed Uc 1.05 Um / 3 Ur 1.25 1.05 Um / 3 Ur 1.4 Um / 3

isolated or
Uc Um Ur 1.25 Um Ur Um
resonant earthed

Table E-1: Rated and continuous operating voltage for line-earth arresters,
depending on the method of neutral point earthing

For line-line arresters (arresters between the phases) applies: Uc 1.05 Um

Um is the maximum voltage for equipment, i.e. the highest operating voltage of the system at the
point of installation. If the value Um is not exactly known, the rated voltage Ur of the equipment to
be protected can be used instead. Um must include temporary overvoltages, e.g. caused by load
shedding or by earth fault.

E3 Rated discharge current


The rated discharge current is a characteristic value for use in insulation coordination, which de-
fines the discharge current at which a given residual voltage (also called discharge voltage) will not
be exceeded (nominal operating point). However, the arrester can withstand much higher discharge
currents. It will not be destroyed when the rated discharge current is exceeded during a discharge,
only the residual voltage is higher. Three typical rated discharge current values can be selected.

5 kA is adequate in medium voltage distribution systems under normal service conditions if the
galvanically connected line system is less than 5 km.

10 kA is recommended for larger cable systems, connections to capacitor banks or in distribution


systems where high rates of lightning strikes occur.

20 kA is applied in exceptional cases only, where high discharge energies prevail, high rates of op-
eration can be expected, or where very low residual voltages are required (e.g. in arc furnace instal-
lations, large generators).

Siemens AG 12E3 65
Selection of surge arresters

E4 Residual and sparkover voltage (protection level)


The required residual or sparkover voltage of an arrester is derived from the insulation capability of
the object(s) to be protected. The reference variable is the rated lightning impulse withstand volt-
age16 Up. It is also used as reference for the protection against switching overvoltages, since the
rated switching impulse withstand voltage17 Us is not a standardised rating in the medium voltage
range below 52 kV. Instead the switching impulse withstand capability is derived from the lightning
impulse withstand voltage.
Sparkover (for gapped arresters) or residual voltage (MO arresters) must be less than the insulation
strength of the connected equipment whereby the sparkover voltage of gapped arresters may lie a
few kV above their residual voltage. The withstand capability of an insulation material depends on
the duration of the overvoltage; it is greater for a short, steep front than for the slowly decaying
transient. Devices can, therefore, withstand a short lived sparkover voltage which is slightly greater
than the residual voltage.
When selecting an arrester to protect against switching overvoltages while breaking of small induc-
tive currents, the permitted residual voltage should be related to a discharge current of 0.5 kA. If
this value is not present in the selection tables, one must take the value for the smallest given cur-
rent (e.g. at 1 kA, 2.5 kA or 5 kA).

E 4.1 Switching overvoltages


Switching operations can initiate transient oscillations with different instantaneous polarity of the
voltages in the phases (differential mode overvoltage), so that the voltage between them can add up
to greater values than to earth. If the switching operation might cause unduly high overvoltages,
arresters must limit the overvoltages between the phases (L-L) just as phase-to-earth (L-E) to ac-
ceptable values. The objective is to achieve this with 3 arresters in phase-earth connection. If this is
not possible, one needs a 6 arrester format.
Protection against switching overvoltages is always necessary for switching duties where multiple
re-ignition or virtual current chopping can occur, when circuit breakers may interrupt pure inductive
currents of less than 600 A. The necessary residual current of an arrester relates then to a discharge
current in this range. The rated values are somewhat differently arranged. One looks in the data
sheets for the residual voltage at a discharge current of 0.5 kA. If 0.5 kA is not listed as a rated
value, one must take the smallest given value.
Both metal oxide and spark gap arresters are equally suitable for protection against switching over-
voltages. If spark gap arresters are used, select only types for which a switching impulse sparkover
voltage is given in the selection tables.

16
Often referred to in insulation coordination terms as the BIL (Basic Impulse Level)
17
SIL (Switching Impulse Level)

66 Siemens AG 12E3
Selection of surge arresters

E 4.2 3 arresters in line-earth connection

Figure E-2: Overvoltage protection by line-earth surge arresters

Required residual voltage, respectively switching surge 1 U P 0.83


sparkover voltage for protection line-line and line-earth: U ai or U res
2 1.15
Required residual voltage, respectively switching surge U P 0.83
sparkover voltage for protection line-earth: U ai or U res
1,15
ures Residual voltage at 0.5 kA follow current ( rated discharge current)
uai Switching impulse sparkover or residual voltage
Up Rated lightning impulse withstand voltage of protected object (BIL)
0.83 Reduction factor, compared to the BIL, for switching impulse withstand voltage
1.15 Recommended safety factor to IEC [16]
Since the line-line overvoltage can rise to twice the line-earth voltage, the arresters must
limit the overvoltage to half the permissible line-line value.
At system voltages above 15 kV in networks with isolated or resonant earthed neutral point, line-
earth arresters with sufficiently small residual or sparkover voltage to ensure also the protection
line-line are hardly available. In these cases one needs to install three additional arresters between
the lines, i.e. a 6 arrester format.

E 4.3 6 arrester format

Figure E-3: Overvoltage protection by line-earth and line-line surge arresters

Siemens AG 12E3 67
Selection of surge arresters

U P 0.83
Required residual, respectively switching surge sparkover voltage: U ai or U res
1.15
ures Residual voltage at 0.5 kA follow current ( rated discharge current)
uai Switching impulse sparkover (or residual) voltage
Up Rated lightning impulse withstand voltage of protected object (BIL)
0.83 Reduction factor, compared to the BIL, for switching impulse withstand voltage
1.15 Recommended safety factor to IEC [16]

E 4.4 Lightning overvoltages


These occur only between conductor and earth, single phase, in all conductors (common mode
overvoltages). Therefore, to select the correct protection level one needs only to consider the stress
to earth; 3 arresters in line-earth-connection always provide sufficient protection against light-
ning surge.
U
Required residual, respectively switching surge sparkover voltage: Ures; Uax P

uax 100% sparkover lightning impulse voltage uas100 respectively front-of-wave impulse sparkover
voltage uast
Up Lightning impulse withstand voltage (BIL)
1.25 ... 1.4 recommended safety factor for lightning protection

The recommended safety factor is higher than for switching overvoltages. It shall be at least 1.25
but it is recommended that one should aim for = 1.4.

E5 Energy absorbtion capability


The energy absorbtion capability is no criterion for medium voltage surge arresters in pure distribu-
tion networks. The same applies to most of the industrial applications with the aforesaid inductive
switching duties. The interruption of inductive currents can be associated with switching overvolt-
ages which are, however, low-energy overvoltages. Unduly high overvoltages may occur only up to
600 A inductive breaking current. Table E-2 lists some benchmark values.

Operating values 6 kV 10 kV 15 kV 20 kV 30 kV

Residual voltage 18 kV 30 kV 42 kV 55 kV 79 kV

Absorbed energy 5.2 kJ 8.9 kJ 13.2 kJ 17.9 kJ 26.8 kJ

Table E-2: Average values of absorbed energy by surge arresters 18

18
Siemens type 3EK7 operating in one phase when interrupting an inductive current of 600 A. Parameters: load cable
200 m, total feeding side cable lenth 3000 m (cable: XLPE, cross-sections 95 mm to 500 mm)

68 Siemens AG 12E3
Selection of surge arresters

The energy absorbed by the arrester is much smaller than the rated absorbtion capability of most
arrester types. If an arrester type features more than one rating for the energy absorbtion capability,
always the lowest one may be selected. Exempted from this rule are arresters in connection with
very large capacitors, large generators or motors as well as applications with extremely frequent
discharges (for example arc furnaces). In these cases the energy absorbtion capability must be di-
mensioned individually.

E6 Short-circuit withstand and housing


The short-circuit withstand capability19 designates the rated short-circuit current the arrester can
withstand a defined time duration in case of an internal fault (internal flashover) without violent
shattering of the housing. If more than one value is available for a certain type of arrester, the se-
lected value should correspond with the rated short-time current at the place of installation respec-
tively with the rating of the switchgear.

When selecting the housing the outer insulation capability must be considered. For indoor use as
well as for site pollution severity classes a to c according to IEC/TR 60815-1 [17] the smallest
housing available can be selected. Only higher degrees of pollution require larger housings with
extended creepage distance.

E7 Switchgear with overhead line connections


Such switchboards mostly have a (short) cable connection between station and overhead line. At the
end of the OHL c, an arrester is installed as lightning protection. Dependent upon the length of the
cable, a second arrester, in the station, may be worthy of recommendation.
A lightning surge, limited to the residual voltage of the first arrester travels down the cable and,
because of the alteration in wave resistance at the junction between cable and switchboard, will be
reflected at point d. The voltage at this cable end can approach double the value point c. To pro-
tect the switchboard and, particularly the cable terminal, an arrester should always be installed at
that point if travelling waves can build up in the cable. Above specific lengths that is always the
case.

Figure E-4: Switchgear with connection to an overhead line, example of substation

19
The standards also use the terms pressure relief class or rated short-current.

Siemens AG 12E3 69
Selection of surge arresters

Lower limit of cable length


IEC 60071 [16] recommends to install additional arresters in the substation at d for cable lengths
exceeding the following length:

Highest voltage Cable travelling Dielectric strength Maximum permissible


for protected object wave resistance ZK of protected object cable length without arrester

12 kV 10 75 kV 50 m
15 30 m
20 20 m

24 kV 15 125 kV 20 m
20 15 m
30 10 m

Refernece value of overhead line: ZF 400

Table E-3: Recommendation for surge protection depending on the cable length

For lower values of insulation rating, the recommended cable lengths are shorter.

Upper limit of cable length


If the length of plastic insulated cables exceeds approximately 500 m or with oil-paper insulated
cables exceeds approximately 300 m the arrester at d in the substation is not necessary since the
travelling wave is effectively damped and furthermore the earth capacitance of the cable reduces the
surge amplitude additionally.

r
The surge impedance of a cable is: Z K =
m
C '300
s

r relative dielectric factor for the cable insulation


C' operational capacity of the cable per unit length (from data sheets)

Typical values r : 3.4 ... 4 oil paper


2.4 PE, XLPE
5 ... 8 PVC
3 EPR

Arrester c is an outdoor arrester, which must be suitable for lightning protection duty; for arrester
d, an indoor arrester with smaller energy absorption capacity. If the energy absorption capacity of
arrester d is smaller, it must be ensured that the sparkover or residual voltages are properly graded,
so that the outdoor arrester always operates first.

70 Siemens AG 12E3
Switchgear configuration

F SWITCHGEAR CONFIGURATION

F1 Principles of configuration
F 1.1 General
This section covers the basic technical aspects involved in selecting and rating the switchgear as-
sembly and its main components, focussed on the primary (HV) part (the application guide does not
replace the ordering data catalogue).
The process of designing secondary systems with devices for protection, control, measurement, and
counting purposes is not covered here.
It is assumed that the network parameters and the switching duties the switchgear assembly has to
comply with are already known for configuring the installation.

F 1.2 Requirements and complementary characteristics

Requirements Configuration Product charactistics


must be observed Selecting and Rated values
can be influenced rating the Operating
product properties
freely selectable properties
Reserves

Result

Optimum
Medium Voltage
Switchgear

Figure F-1: Requirements and corresponding product features

On the basis of the requirements specified which may be of different nature and vary in a wide
range the right products with the right rated values must be selected and configured. There is not
always a clear choice or a definite configuration rule, so that for some requirements only recom-
mendations can be given.

Requirements that must be observed are those that relate to the electrical aspects of the switch-
gear, whereby the switchgear must offset the corresponding strength properties against the physi-
cal stresses. For these requirements clearly-defined configuration rules are almost always avail-
able. Legal regulations as well as personnel protection, fire protection, and environmental com-
patibility requirements must also be strictly observed.

Siemens AG 12E3 71
Switchgear configuration

Some requirements can be influenced, that is, measures taken on the electrical or spatial environ-
ment may affect the requirements regarding the switchgear which, in turn, optimises the selection
and rating of the whole installation. For example, measures can be taken to reduce the duration of
the short-circuit current; overvoltage protection can help avoid excessive insulation levels, while the
building housing the switchgear may be modified to improve environmental conditions and reduce
climatic stress.
There are recommendations provided for these "soft" requirements, rather than definite selection
and rating rules.

Freely-definable "negotiable" requirements offer the greatest scope with regard to designing the
switchgear. Operators can select specific product characteristics at their discretion to optimize the
switchgear in line with their own requirements. Decisions may be based on, for example, tried-and-
tested operating processes or internal company guidelines.

This document only covers those aspects of freely-selectable requirements that are relevant for con-
figuration activities.

F 1.3 Procedure
Section G of this guide not only covers the influences and stress variables but also the associated
characteristics and properties of the switchgear.

Section H breaks down the process of selecting and rating a switchgear system into individual steps
and describes which influences and stress variables must be taken into account in each individual
step. As far as avaialble, rules and recommendations are provided for selection and configuring;
otherwise the aspects that must be taken into account are defined.

A wide range of non-technical aspects must be taken into account when switchgear is configured:
Requirements of state legislation always take priority over normative regulations (e.g. protecting
the public, work safety, environmental protection).
Tried-and-tested operations and procedures carried out by the operators can determine which
equipment is required. After all, taking into account "standard practices" of operators also con-
tributes to a safe working environment.
Requirements and features that focus on operations and procedures can vary considerably from
region to region.
If applicable, company guidelines may also have to be taken into account.
Recommendations of industrial associations.

These are just some of the requirements that manufacturers, planners, and operators must agree
upon. A configuration guide cannot cover all aspects of these requirements. It can only highlight
those points that are applicable to all switchgear systems at all times.

72 Siemens AG 12E3
Switchgear configuration

F2 Switchgear requirements
The key influences and stress variables for switchgear depend on the task in hand and its position in
the distribution network.

Rated voltage Neutral point grounding


S.-c. current Underground/overhead lines
Line parameters
Normal current Overvoltage protection
Load flow Energy quality

Protection functions Redundancy


Line protection and measurement Selectivity Tripping times
Measurement Metering

Public grid Emergency supply


Infeeds
In-plant generation Redundancy

Installation location Accessibility


Operating sites Service room Building
Transportation Assembly

Ambient conditions Altitude


Environmental conditions
Temperature Humidity

Switching duty Switching frequency


Industry-specific applications
Busbar switchover Availability

Operation Personnel protection


Specific operating procedures Work activities Work instructions
Inspection Maintenance

Standards Laws
Regulations
Association guidelines Company guidelines

Figure F-2: Influences on the configuration of switchgear assemblies

These influencing factors and stresses, which are explained in detail in Section G, determine the
selection and rating variables for the switchgear.

Siemens AG 12E3 73
Switchgear configuration

F3 Properties to be selected
This diagram provides an overview of the main switchgear features to be configured in the se-
quence normally carried out when switchgear is selected and rated.

Switchgear features Selection and rating variables

Voltage Normal current


Primary rating values
Insulation level Short-circuit current

Single / double busbar


Circuit arrangement Bus section / transfer
Bus coupler unit

Circuit-breaker Contactor
Switching devices
Switch HRC fuse

Circuit-breaker/switch-disconnector unit
Design and switchgear panel types Air / gas insulation
Withdrawable unit (truck) / fixed mounted

Degree of protection
Enclosure
Internal arc classification

Accessibility / access control


Compartmentalisation
Loss of service continuity + partition class

Cable terminals Instrument transformers


Components in the feeder
Surge arresters Earthing switch

Instrument transformers Earthing switch


Components at the busbar
Surge arresters Cable terminals

Electromagnetic compatibility (EMC)


Secondary equipment Protection, metering, communication
Interlocks, control, monitoring

Figure F-3: Selection criteria and ratings of a switchgear assembly

Section H contains a detailed explanation of the configuration rules that need to be applied and
other aspects that need to be taken into account.

74 Siemens AG 12E3
Switchgear configuration

G INFLUENCES AND STRESS VARIABLES

G1 Network characteristic values


G 1.1 Line voltage
This determines the rated voltage of the switchgear, switching devices, and other installed compo-
nents. The determining factor here is the maximum line voltage at the upper tolerance limit.

Assigned configuration criteria for switchgear:


Rated voltage Ur
Rated insulation level Ud; Up
Rated primary voltage of voltage transformers Upr
and surge arrester where applicable

G 1.2 Short-circuit current


This is characterized by the variables peak current Ip (peak value of the initial symmetrical short-
circuit current) and sustained short-circuit current Ik. The required short-circuit current level in the
network is specified by the dynamic behaviour of the loads and the quality of the energy, which
must be maintained, and determines the making, breaking, and withstand capacity of the switch-
gear.
Note that the ratio of the peak current to the sustained short-circuit current in the network can be
significantly greater than the standard factor Ip/Ik = 2.5 at 50 Hz (or 2.6 at 60 Hz) according to
which the circuit-breakers and switchgear are designed. This could be due, for example, to motors
that supply energy back to the network if a short-circuit occurs, which significantly increases the
peak current.
For the short-circuit duration, see G 2.3 Tripping times

Assigned configuration criteria for switchgear:


Main and earthing circuit: - Rated peak current Ip
- Rated short-time current Ik
Switchgear: - Rated short-circuit making current Ima
- Rated short-circuit breaking current Isc
Current transformer: - Rated dynamic current Idyn
- Rated short-time thermal current Ith

Siemens AG 12E3 75
Switchgear configuration

G 1.3 Normal current and load flow


The normal current refers to the current paths of the infeeds, busbar(s), and load feeders. The cur-
rent is also subdivided due to the physical arrangement of the switchgear panels with the effect that
different rated current values can be found in sequence along the conducting path (the currents in
busbars and feeders are normally different).
Reserves must be planned for the value of the rated normal current:
- In accordance with the ambient temperature;
- For the planned overload;
- For temporary overloads in the event of faults.
With high normal currents, large cable cross-sections or several parallel cables must be connected
in the switchgear panel; the field terminal must be designed to accommodate this.

Assigned configuration criteria for switchgear:


Rated current of busbar(s) and feeders
Number of cables for each conductor in the switchgear panel (parallel cables)
Rating of the current transformers

G 1.4 Neutral point earthing


The type of neutral point earthing used, insulated / resonant earthed with an arc suppression coil20 /
(temporarily) resistively earthed / solidly (directly) earthed governs the behaviour of the line volt-
age when switching operations are carried out or if a earth fault occurs in the network as well as the
characteristics of the earth fault currents. This means that neutral point earthing has a major influ-
ence on the dielectric stress on the equipment and is important for insulation coordination.

Assigned configuration criteria for switchgear:


Insulation level of the equipment assigned to the rated voltage Ur
Choice of switchgear
Rating and damping of voltage transformers
Design of current transformers and protection relays for earth fault detection
Rating of surge arresters

20
Petersen coil

76 Siemens AG 12E3
Switchgear configuration

G 1.5 Underground / overhead lines


The network type governs insulation coordination and which overvoltage protection measures need
to be taken. In overhead systems, powerful overvoltages can be caused by a lightning strike, while
only weak switching overvoltages generally occur in underground networks. Overvoltages from
overhead systems can reach switchgear indirectly or via a transformer. These connecting points
must be taken into account and checked to determine whether surge arresters are needed.
The network type also affects the choice of switchgear: in overhead systems, for example, transient
faults are more likely to occur. Circuit-breakers must be able to manage reclosing cycles and a high
number of make-break operations. The short-circuit currents in medium-voltage overhead systems,
however, are low (generally between 8 kA and 12 kA).

Assigned configuration criteria for switchgear:


Selection and rating of circuit-breakers
Insulation level
Use and rating of surge arresters

G 1.6 Overvoltage protection


If the expected voltage stresses exceed the insulation level of the equipment, insulation coordination
requires overvoltage protection. This can apply, for example:
- When external overvoltages can be expected as a result of lightning strikes;
- When (multiple) earth faults occur frequently;
- High transient overvoltages may occur as a result of switching operations;
- When, in the interests of economy, certain equipment (e.g. motors, resin-encapsulated / dry-type
transformers) is rated for lower insulation levels than the other network components.
Overvoltage protection is also used as a general precaution to minimize the risk of failure and to
protect equipment against any form of overvoltage. It is generally used for very large motors or
transformers that are not only expensive and difficult to procure but also incur high costs if they
fail.
Frequent overvoltages can also cause some insulation systems to age, even if the stresses are still
within permissible limits. Overvoltage protection measures are also recommended in unstable
networks (=> see G 1.7 Power quality).
Overvoltage protection systems normally comprise surge arresters. In certain cases, surge capacitors
or resistance-damped surge capacitors (RC elements) are also required.
Switchgear must be checked to determine whether overvoltage protection is required, whether pro-
tection measures have already been taken, or whether existing protection devices need to be up-
graded.

Siemens AG 12E3 77
Switchgear configuration

Assigned configuration criteria for switchgear:


Insulation level
Check for "critical" switching duties
Application and rating of the surge arresters,
space for installtion and possibility for the connection of external arresters

G 1.7 Power quality (unstable loads)


The power quality refers to unwanted interference, such as voltage dips, flickers, asymmetry, har-
monics etc.. These can be caused for example by rectifiers, converters, welding machines, direct-
starting motors. Other loads (e.g. IT systems), however, are sensitive. To protect them, the interfer-
ence is compensated as much as possible or the "stable" and "unstable" loads are distributed across
sub-networks with separate infeeds. Depending on the circuit arrangement, switchgear with single
or double busbars is required.

Assigned configuration criteria for switchgear:


Single/double busbar
- Bus section panel
- Bus coupler unit
Rated normal current (busbar)
Rated short-circuit currents

G2 Line Protection, measurement and metering

G 2.1 Short-circuit protection


The line protection concept has a major influence on the switchgear that is selected and its design.
The following devices can be used for short-circuit protection:
- HRC fuse (in a switch- or contactor-fuse combination)
- Instrument transformer + protection relay + circuit-breaker
If the majority of network branches are equipped with switch-fuse combinations, switch-discon-
nector units can be used; otherwise, circuit-breakers are used.

Assigned configuration criteria for switchgear:


Design: circuit-breaker or switch-disconnector unit

78 Siemens AG 12E3
Switchgear configuration

G 2.2 Protection functions


Protection relays obtain their measurement signals from current and voltage transformers, which are
installed in the switchgear. The range of available protection functions (e.g. inverse/definite-time
overcurrent, distance/differential protection) requires current transformers whose cores can be com-
bined in a variety of ways with different rated currents, overcurrent number, output, and class accu-
racy. Voltage transformers are also provided for protection with directional control or for determin-
ing the fault location (distance protection). Sensitive earth fault protection devices require a core-
balance transformer around the three conductors to measure small earth fault currents in compen-
sated networks or networks with an insulated neutral point.
The switchgear must provide a space in which these instrument transformers can be installed as
well as space for the protection relays and their wiring. This may seem obvious, but it is important
to remember that other components (surge arresters, multiple cable terminals etc.) also need space
in the switchgear.

Assigned configuration criteria for switchgear:


Installation of instrument transformers in the switchgear panel and on the busbar
Installation of a core-balance transformer
(normally cable-type current transformer, or "earth fault winding")
Installation of protection relays and wiring in the low-voltage compartment

G 2.3 Tripping times


The set tripping times (specified by means of selectivity requirements in accordance with the num-
ber of subordinate network levels and their equipment) are governed by the rated short-circuit dura-
tion of the switchgear, the current transformer, and the earthing circuit. The standards permit vari-
ous rated values for the components. For short-circuit durations of > 1 s in particular, it is important
to ensure that all components are dimensioned to manage the actual short-circuit duration at the
minimum.
For the actual short-circuit duration, the mechanical delay (opening time) of the switching device
must also be added to the tripping time of the protection system.

Assigned configuration criteria for switchgear:


Rated duration of short-circuit
- Main circuit (switchgear, disconnector, and earthing switch)
- Earthing circuit
- Current transformer
- Number and type of releases in the circuit-breaker

G 2.4 Measurement and metering


Measurement and metering systems generally require separate, additional transformer cores with a
different rating to that of the protection cores.

Siemens AG 12E3 79
Switchgear configuration

Assigned configuration criteria for switchgear:


Room for installing transformers as well as measurement devices and meters (see G 2.2).

G 2.5 Redundancy
Different protection functions can be combined in a single network branch (e.g. differential and
overcurrent-time protection as backup). Depending on the degree of redundancy required, addi-
tional instrument transformers and protection devices may also have to be installed in the switch-
gear. Enough space must be available for these too (see above).
For contractual reasons, the same measurement device or meter may also be installed twice if con-
tractual partners use their own devices at the point of supply ("check measurement"). This increases
the number of built-in components.

Assigned configuration criteria for switchgear:


Room for installing transformers as well as measurement devices and meters (see G 2.2).

G3 Infeed types
The operating principle and number of infeeds are crucial for connecting the switchgear and for its
rated current values. The supply from different networks, such as
- the public network
- in-plant generation
- the emergency power supply

sometimes has to be disconnected during normal operation for safety, business, or contractual
reasons. A decision must, therefore, be made regarding how the supply can be divided into busbar
sections and which ones can be linked. The switchgear design as well as the rated normal and short-
circuit current values depend on the infeed operating principle and the couplings.

Assigned configuration criteria for switchgear:

System connection
- Single/double busbar
- Bus section panel
Rated values of the switchgear
- Normal current of the busbar(s)
- Peak current and short-time current
Control, interlocks, and switchgear interlocking
Installation of instrument transformers in the switchgear panel and on the busbar
Room for installing the protection relays and wiring in the low-voltage compartment

80 Siemens AG 12E3
Switchgear configuration

G4 Operating sites
The type of operating site can also govern the choice and rating of switchgear. Given the broad
range of different influencing factors, only the key points that need to be taken into account can be
described here.

G 4.1 Installation location


Many locations are subject to legal regulations concerning safety and health, fire protection, and
environmental compatibility. This mainly applies to systems in public areas (e.g. pedestrian zones),
industrial premises (offices, workshops), public buildings (high-rises, hospitals, office buildings,
bars, conference centers etc.). Special regulations also apply for nature reserves, mines, railways,
and boats.
Even if the switchgear malfunctions, it must behave in such a way as to minimize negative impact.
Malfunctions include situations in which the switchgear is subject to external damage (e.g. fire) or
is itself the cause of the problem (e.g. internal faults).

Assigned configuration criteria for switchgear:

Design
Internal arc fault classification
Pressure absorber, pressure release duct

G 4.2 Accessibility
The standards also take into account the different levels of accessibility of operating sites:
- Only authorized and trained personnel have access to closed electrical operating area; all other
people must be accompanied.
- Operating sites in public areas can be accessed by everyone (e.g. standard for stations and
switchgear in workshops).
Switchgear in public areas are subject to more stringent requirements.

Assigned configuration criteria for switchgear:


Air or gas insulation
IP degree of protection
IK degree of protection (mechanical shock)
Internal arc fault classification

Siemens AG 12E3 81
Switchgear configuration

G 4.3 Switchgear room


Certain standards, e.g. IEC 61936 [22], and laws define specifications regarding how the system is
set up in service rooms (e.g. the minimum width of operating and assembly aisles) and define the
binding requirements for escape routes (e.g. width and maximum length of escape routes, preferred
direction in which doors close etc.).
The service room might also contain other equipment for which operators can define their own
specifications regarding free areas and setup.
The switchgear must enable all requirements to be fulfilled.

Assigned configuration criteria for switchgear:

Dimensions of the switchgear panels, in particular the panel width


Position of door stops; opening angle of the switchgear panel doors
Position of controls and displays/indicators (front/rear)
Cable connection from the front or rear
Required accessories (switching levers, tools, etc.)
Labelling, information plates, warning signs

G 4.4 Buildings
The building itself can also influence the choice of switchgear. The following aspects must be taken
into account:
- The available space
- The quality of the building fabric (in existing, older buildings)
- Vent outlets in the event of an internal arc fault

Assigned configuration criteria for switchgear:


Switchgear panel width, depth, and height
Air or gas insulation
Internal arc fault classification
Pressure absorber, pressure release duct

Irrespective of the chosen switchgear, a dynamic pressure calculation must be carried out for the
building to determine the stresses on the structure and the required cross-sections for vent outlets.
The building is also a crucial factor regarding the conditions under which the switchgear operates;
see G 5 Environmental conditions.

82 Siemens AG 12E3
Switchgear configuration

G 4.5 Transportation and assembly


In certain albeit rare cases, transportation and assembly conditions are a key selection criterion
for the switchgear. Whether or not switchgear can be installed in a building depends on certain con-
structional factors, such as:
- The size and position of doorways
- Permissible floor loading
- Floor level
- Goods elevator

Assigned configuration criteria for switchgear:


Size of the transportation units
Weight of the transportation units
Packaging (stability, weather protection if the device is in temporary storage over a long period)

G5 Environmental conditions

G 5.1 Ambient room conditions


Switchgear installed in service rooms can be subject to the following ambient conditions:
- Heat and humidity
- Pollution
- Dust and smoke
- Salt (near the coast or in mining)
- Corrosive gases and vapours (natural and artificial)
- Insects / small animals

Due to the infinite variety of ambient conditions at installation locations, the applicable standards
only define basic requirements for "normal service conditions". Each system much be examined
individually to determine whether or not these are observed.
Numerous measures can be taken to provide protection against exceptional climatic conditions. For
example, gas-insulated, hermetically sealed compartments that are completely immune to external
conditions can be used. The degree of protection of the housing can also be increased. In parts of
the world where high insect/small animal populations can cause problems, protection against bridg-
ing may be appropriate by fitting additional insulation to live and exposed components.

Siemens AG 12E3 83
Switchgear configuration

Assigned configuration criteria for switchgear:


Design: air or gas-insulated switchgear
IP degree of protection for housing (can be increased with drip-water protection if necessary)
Type of ventilation
Additional insulation for live and exposed components

Measures to provide protection against extreme ambient conditions can also be taken in the service
room (air conditioning). In some cases, this can be more efficient than designing each individual
component accordingly. It is also important to remember that protection, measurement, and control
systems are more sensitive than switchgear, which is reason enough to ensure that the minimum
requirements for air quality are observed.

G 5.2 Altitudes above 1000 m


The standardized insulation levels apply to normal ambient conditions at sea level. As the altitude
increases, however, the air density decreases as do the insulating properties. The applicable stan-
dards take this into account and allow for a reduction of approx. 9% at altitudes of up to 1000 m. At
higher altitudes, the required insulation level must be ensured by increasing the rated voltage (with
respect to sea level values). Insulation coordination can also be ensured by means of additional
surge arresters. Alternatively, gas-insulated switchgear in which the primary section is hermetically
sealed can be used. In this case, the external air pressure is not an issue.

Assigned configuration criteria for switchgear:


Design: air or gas-insulated switchgear
Selection of a higher rated voltage with a higher insulation level
Use of surge arresters

G 5.3 Ambient temperature and humidity


The ambient temperature directly affects the temperature of the switchgear which, in turn, affects its
current-carrying capacity. As the ambient temperature increases, the current-carrying capacity de-
creases (and vice versa). To compensate for this, either the rated current value must be increased or
sufficient ventilation must be ensured (ventilation openings affect the IP degree of protection).
Humidity has a negative effect on the insulating properties. High levels of humidity together with
sudden temperature changes can cause condensation which, in turn, drastically reduces insulation
levels. To prevent this, controlled or permanent heaters can be used in conjunction with humidistats.

84 Siemens AG 12E3
Switchgear configuration

Assigned configuration criteria for switchgear:


Rated normal current
Type of ventilation
Differentiation of IP degree of protection according to protection against ingress of solid foreign
bodies and shock-hazard protection
Installation of a heater in the switchgear panel or in the low-voltage compartment

G6 Industry-specific application
The following aspects cover the role and significance of the switchgear in the operator's network
(industrial or public utility companies).

G 6.1 Switching duty and capacity


The choice and rating of the switchgear depends on the switching duty and the loads to be switched.
Is the switchgear only required to switch normal currents? Or does it need to interrupt short-circuits
too? Due to the transient switching operations, certain loads require overvoltage protection. In other
cases, additional rating criteria apply to the switch and switchgear.

Assigned configuration criteria for switchgear:


Switchgear: circuit-breaker, switch or contactor with HRC fuses
Rated electrical values
Additional measures (e.g. overvoltage protection)
Classes for mechanical and electrical endurance
Design: circuit-breaker or switch-disconnector unit

G 6.2 Switching frequency of the loads


Alongside the electrical requirements regarding the switching capacity, the switching frequency is
an important selection criterion. The switching frequency depends on the process in which the
switching device is used. Switches are rated for a short electrical lifetime (number of make-break
operations), while contactors are rated for extremely long lifetimes; circuit-breakers fall in between.
Once a basic decision has been reached regarding the type of switchgear, standardized lifetime in-
crements can be selected for the switches (endurance classes).
For higher switching frequencies under normal operating conditions, switchgear must be serviced or
replaced more often. In this case, the components must be easily accessible.

Siemens AG 12E3 85
Switchgear configuration

Assigned configuration criteria for switchgear:


Switching devices: circuit-breaker, switch or contactor
Classes for mechanical and electrical endurance
Design of the switchgear assembly
- Air or gas-insulated system
- Withdrawable or fixed disconnector
Loss of service continuity category

G 6.3 Frequency of switchover between busbars


In switchgear with double busbars, the lifetime of the disconnector plays a crucial role. For opera-
tional reasons, some networks require frequent switchovers between busbars. Due to the short me-
chanical lifetime of a disconnector / withdrawable unit as compared with a circuit-breaker, "stan-
dard" double busbar switchgear systems with just one circuit-breaker are unsuitable for this type of
operation. Standard double busbar systems have a common connection (cross connection between
the two busbars) between the two disconnectors and the circuit-breaker.
To prevent wear and tear to the disconnector / withdrawable unit and, in turn, minimize mainte-
nance cycles, the busbars are switched by means of circuit-breakers. This requires two single busbar
systems each with two circuit-breakers in one feeder circuit.

Assigned configuration criteria for switchgear:

Design of the switchgear


Double busbar with common connection or two single busbars
Interlocks and switchgear interlocking

G 6.4 Availability (faults, redundancy, switchover time)


The term "availability" in this context means providing ways of compensating for line failures, for
example, by means of redundant supply channels or defined switchover times. It also refers to the
reliability of switchgear and features for planned maintenance activities or troubleshooting.
The switchgear provides the current paths for multiple supply channels and the switchover options.
This can be used to determine the system circuit: single or double busbars and separated into differ-
ent sections. The various options for linking busbars (busbar sections) with separate infeeds and the
operating principle (NO / NC) of the couplings govern the rated current values.
The switchgear itself must also be sufficiently reliable, maintenance friendly (and not require exces-
sive maintenance), and accessible. A decision regarding the Design of the switchgear assembly and
the partitions can be made on the basis of there criteria.

86 Siemens AG 12E3
Switchgear configuration

Assigned configuration criteria for switchgear:


Circuit arrangement
- Single/double busbar
- Bus section panel
Interlocks and switchgear interlocking
Rated values of the switchgear
- Normal current of the busbar(s)
- Peak current and short-time current
Design: air or gas-insulated switchgear
Loss of service continuity category
- Design of partitions

G 6.5 Modifications or extensions


Switchgear is sometimes set up in sub-sections or needs to be extended or modified during the
course of its operating life. If such measures are anticipated, these should be taken into account in
the planning stage.

Assigned configuration criteria for switchgear:

Design
Extension to include additional switchgear panels
Rated values for normal and short-circuit current
Replacement of instrument transformers
Option of upgrading the secondary system

G7 Operating procedures
Operating procedure is a catch-all term that, with respect to configuration activities, will only be
used to describe the following activities:
Operation

Work activities

Maintenance

G 7.1 Operation
Operational activities include monitoring, switching, making settings, and reading displays / indica-
tors. Operators can define how these activities are to be carried out, that is, whether they are to be
carried out on site or remotely, (completely or partially) manually or automatically.

Siemens AG 12E3 87
Switchgear configuration

The automated integration of the switchgear in the network system management and production
process makes important demands on the measurement, control, and remote control systems (sec-
ondary technology).

During operation, the switchgear must provide the required level of personnel protection (e.g. pro-
tection against accidental contact with hazardous live or mechanical components (IP degree of pro-
tection). Even in the (unlikely) event of an internal fault, the switchgear must offer means to protect
the operator.

Assigned configuration criteria for switchgear:


Design of the switchgear
- Air or gas-insulated system
- Withdrawable or fixed disconnector
Type of compartments (access control)
Loss of service continuity category
Control and secondary equipment
Interlocks and switchgear interlocking
Manual or automatic drive mechanisms
IP degree of protection
Internal arc fault classification

G 7.2 Work activities


Activities in this context refers, for example, to modification, servicing, and maintenance activities
or replacing fuses. When such activities are carried out, the system must be either fully or partially
taken out of service. How much of the system is taken out of service depends on the loss of service
continuity category, which must be defined by the operator along with the type of access control to
the disconnected compartments. Shock-hazard protection for live components can, to varying de-
grees, be installed permanently in the system or implemented manually. Again, the operator must
decide which method to use. How the work procedures are organized and the level of training of the
personnel play an important role here.

Assigned configuration criteria for switchgear:

Loss of service continuity category


Type of compartments (access control)
Partition class

88 Siemens AG 12E3
Switchgear configuration

G 7.3 Inspection and maintenance


System inspection and maintenance requirements can vary enormously and are subject to numerous
influencing factors completely unrelated to electrical engineering, such as:
- Environmental conditions
- Industry-specific operating procedure
- Legal regulations
- Internal organization and work instructions
- Level of personnel training
Inspection and maintenance must be treated as separate activities. It may be the case that certain
procedures require more frequent inspections, for example, which means that the switchgear must
be more readily accessible. In this case, therefore, a completely hermetically-sealed system may not
be the best solution because it cannot be accessed. Components may need to be readily accessible if,
for instance, they need to be replaced more often due to a high switching frequency. The degree of
required accessibility also depends on various regulations and the level of personnel training. These
aspects also govern the switchgear design.

Assigned configuration criteria for switchgear:


Design of the switchgear
- Air or gas-insulated system
- Withdrawable or fixed disconnector
Loss of service continuity category
Type of compartments (access control)
Selection of switching devices and its endurance classes

G8 Regulations
Switchgear is subject to numerous regulations relating to its design, manufacture, inspection, setup,
and operation:
- Electrical engineering standards
- Recommendations of industry or utility associations
- Legal regulations
- Internal company regulations
While the electrical engineering standards are fulfilled by nearly all products, legal or internal regu-
lations in different industries can pose special challenges.

Assigned configuration criteria for switchgear:

Determine any deviations from the requirements defined in the IEC / EN standards.

Siemens AG 12E3 89
Switchgear configuration

H SELECTING AND RATING SWITCHGEAR

H1 Overview (Checklist)
This table lists all the rating and selection variables along with the requirements and influencing
variables, which are explained in detail in the following sections.

Selection variable Key influencing factors

Ur Rated voltage System voltage


Rated insulation level Insulation coordination


Ud short-duration power-frequency Neutral point earthing
withstand voltage Underground/overhead lines
Up lightning impulse withstand voltage "Critical" loads
Overvoltage protection
Primary rated values

Altitude
Ambient conditions (pollution)

Rated withstand capability Characteristic line values


IP peak current Loads and power quality
IK short-time current Line protection, response times
tK duration of short-circuit
Tripping time
Rated switching capability
Ima short-circuit making current Selectivity
Isc short-circuit breaking current
Ir Rated current Load (feeder circuit),
- busbars power to be distributed
- feeder circuits Ambient temperature
Reserves / availability
Single/double busbar Line structure
Bus sectionaliser panel Line protection, tripping times,
(with switch or circuit-breaker) selectivity
Busbar arrangement

Switchover with switch or circuit-breaker Reserves / availability, switchover time


Bus coupler unit (with double busbar) Operating procedures
In-plant generation, emergency supply
Power quality (unstable loads)
Double busbar with common connection Operating procedures
Two single busbar systems Frequency of busbar switchover
Interlocks and switchgear interlocking
Setup (physical)

90 Siemens AG 12E3
Switchgear configuration

Selection variable Key influencing factors

Circuit-breaker Operating current and switching duty


Switching de-

Switch Switching capacity (fault currents)


vice

Contactor Switching frequency


HRC fuse Line protection,
selectivity requirements
Circuit-breaker unit Primary (HV) ratings
Design and switchgear panel types

Switch-disconnector unit Switching devices


Design Operating current, switching capacity
- extendable panels Line protection
- block type
No. of switch / circuit-breaker panels
Operating procedures and operation
Expandability,
electrical / mechanical reserves
Installation conditions
Transportation and assembly
Air (AIS) Ambient room conditions: temperature
change, humidity, pollution, salt, corro-
Insulating medium

Gas (GIS)
sive gases
Type of operating site
Installation location (space requirements)
Fire protection requirements (fire load)
Altitude
Switching frequency and switch lifetime
Withdrawable unit / truck Switching frequency
Disconnector

Disconnector (built in) Component lifetime


Operational requirements
(e.g. access to cable terminal, for mainte-
nance and cable testing)
Degree of protection (IP) Ambient conditions
Internal arc classification (IAC) Personnel protection
Type of operating site
Enclosure

- A or B type of accessibility
- F / L / R classified sides Building
- IA, tA arc fault current and duration
Pressure release duct

Siemens AG 12E3 91
Switchgear configuration

Selection variable Key influencing factors

Loss of service continuity category Operating procedures


(interal structure of panel) - operation, work activities
- LSC 1 - maintenance requirements
- LSC 2 Servicing / maintenance
- LSC 2A (component lifetime)
Compartments

- LSC 2B
Operators regulations
Access control by means of: Personnel training
- interlocking
- work instruction + locking Shock-hazard protection during work
- tools activities
None-accessible compartment Switchgear space requirements
Partition class
- PM (metal)
- PI (insulating material)
Cable connection Operating and short-circuit current
- Sealing end: plug / standard Switching duty
- Number of cables
Feeder circuit components

Underground / overhead cables


- Cable cross-sections
Altitude
Surge arrester
Voltage transformer Line protection
- earth fault winding (if required) Measurement, metering
Current transformer Control
- core number and data
Core-balance transformer Neutral point earthing
(cable-type current transformer)
Earthing switch Operating procedures
- Class E0, E1 or E2
components

Instrument transformer Line protection and measurement


Busbar

Earthing switch Operating procedures


- Class E0, E1 or E2 Space requirements
Surge arrester
Protection relay Line parameters
Secondary equipment

Equipment for control, interlocks and Type of line and load protection
switchgear interlocking Line system management
Devices for measurement, metering, Integration in (industrial) processes
measuring transducer
Operational procedures
Monitoring, communication devices
Motorized drive mechanisms
Voltage detecting system
Damping resistors for VT
Table H-1: Summary of selection criteria for switchgear assemblies

92 Siemens AG 12E3
Switchgear configuration

H2 Primary rated values

Selection variable Key influencing variables

Rated voltage Ur System voltage (operating voltage)


Insulation coordination
Rated insulation level - Neutral point earthing
- Lightning impulse withstand voltage Up - Underground / overhead cables
- Switching duties
- Short-duration power-frequency
- Overvoltage protection
withstand voltage Ud
- Altitude
- Ambient conditions (pollution)
Rated peak current Ip Characteristic line values
short-time current Ik Loads and power quality
short-circuit duration tk
Protection, tripping times, selectivity
Rated short-circuit making current Ima
short-circuit breaking current Isc
Rated normal current Ir Load (feeder circuit),
- busbar power to be distributed (busbar)
- feeder circuits Ambient temperature
Reserves / availability

Table H-2: Key factors for the rated voltage

H 2.1 Rated voltage Ur


The maximum operating voltage of the network (UNmax) at the upper tolerance limit and the re-
quired insulation level of the equipment determine the rated voltage.

Rating rule: Ur UNmax and Ur corresponds with the required insulations level (see H 2.2)

For switchgear, the next highest standard value above the maximum operating voltage is set as the
rated voltage. The value of the maximum operating voltage must cover effects of temporary over-
voltages, for example caused by
- harmonics
- load shedding (generators for emergency supply, customer generation etc.)
- capacitive equipment, such as capacitor banks, filters
If a particular insolation level is pre-determined, the rated voltage must correspond with it.

Comments:
a) The rated voltage of the switchgear may differ from that of
Voltage transformers
Surge arresters

Siemens AG 12E3 93
Switchgear configuration

HRC fuses
This is because these devices are subject to additional rating criteria (see sections D and E 2).
b) Some switching duties require the switching devices to have an even higher rated voltage, al-
though this is rare (see table in B 1). In certain cases, the entire switchgear system must be de-
signed for higher voltages.
c) Due to the reduced insulating properties tt altitudes of above 1000 m above sea level, a higher
rated value may be selected where applicable (see H 2.2).
d) A higher rated voltage can be set to fulfil the requirements of a higher insulation level in order
to cope with special ambient conditions, for example pollution or humidity.
(see H 2.2).

H 2.2 Rated insulation level


The insulation level comprises the lightning impulse withstand voltage (Up) and the short-duration
power-frequency withstand voltage (Ud).

Rating rule: Ur Ud and Up (see table in IEC 62271-1)


The rated insulation level is assigned to the rated voltage in accordance with table 1a, IEC
62271-1 [1] the applicable standard and is, therefore, set at the same time as the rated voltage.
Different allocations must be specified separately.
In medium-voltage systems, the standard insulation levels do not differ with respect to the neu-
tral point earthing.

Rated voltage Rated short-duration power-frequency Rated lightning impulse withstand volt-
Ur / kV withstand voltage age
(r.m.s. value) Ud / kV (r.m.s. value) Up / kV (peak value)
Line-earth, line-line, Across isolat- Line-earth, line-line, Across isolating
across contact gap ing distance across contact gap distance
(1) (2) (3) (4) (5)
20 23
3.6 10 12
40 46
40 46
7.2 20 23
60 70
60 70
12 28 32
75 85
75 85
17.5 38 45
95 110
95 110
24 50 60
125 145
145 160
36 70 80
170 195
52 95 110 250 290

Table H-3: Rated voltages and insulation levels in the medium voltage range

94 Siemens AG 12E3
Switchgear configuration

Comments:
a) Operators may specify a higher insulation level in accordance with operational requirements.
Reasons for this include foreseeable reduction in insulation due to moisture or pollution or high
dielectric stresses during standard operation due to connected overhead systems, traction supply
systems etc.

b) At altitudes of at least 1000 m above sea level, the insulation level decreases caused by the
lower air density. There are alternatives to compensate this decrease:
- a higher rated voltage is set;
- surge arresters are installed to limit possible overvoltages below the actual insulation capa-
bility. Based on the voltage withstand value at the relevant altitude (see Figure H-1) the re-
quired protection level of the arresters is determined, as described in section E 4;
- gas-/solid-insulated switchgear is used with shielded, earthed connections (cable plug con-
nectors, insulated bars), where the HV conductors are nor surrounded by ambient air.

For low-voltage auxiliary and control equipment no precautionary measures need be taken up
to 2000 m altitude. Regarding installation sites at higher altitude see IEC 60664-1 [18].

200
Lightning impulse withstand voltage [ kV ]

36 kV

150

24 kV

100 17,5 kV

12 kV
7,2 kV
50
3,6 kV

Rated voltage
(U r ) of Altitude
equipment
0 [m]
0 1000 2000 3000 4000 5000 6000

Example for diagram above: a lightning impulse withstand voltage of Up = 120 kV is required at an
altitude of 1800 m. A system with a rated voltage of 36 kV achieves this, while a 24 kV system is not
suitable because it can only maintain a lightning impulse withstand voltage of 125 kV up to 1000 m.

Figure H-1: Lightning impulse withstand capability in air, depending on the site altitude

c) In environments with high levels of pollution, longer creepage paths may be required [16]. This
can be achieved not only with a higher insulation level, but also with alternative methods:
- avoiding unprotected insulation

Siemens AG 12E3 95
Switchgear configuration

- additional insulation for exposed parts (e.g. heat shrink tube to act as bridging protection)
- gas-insulated switchgear with shielded, earthed connections
(cable plug connectors, insulated bars)

Note:
In many cases, surge arresters fitted at central points can be used as an alternative to increasing in-
sulation levels.

H 2.3 Rated short-circuit currents


Rated short-circuit currents include:
- The peak current Ip and short-circuit making current Ima
- The short-time current Ik and short-circuit breaking current Isc
The peak current and short-time current are withstand capability variables (steady state), while the
short-circuit making and breaking current indicate the switching capacity. The applicable standard
defines a fixed ratio between the impulse and short-time current as a basic design requirement for
switching devices and switchgear: Ip/Ik = 2.5 (2.6 at 60 Hz). The same ratio applies to the dynamic
variables Ima/Isc. The values that actually occur in the network, however, have priority.

Rating rule: Standard value System variable


a) Ima and Ip ip
b) Isc and Ik Ik (resp. Ib or Ik)

Both conditions (a) and (b) must be fulfilled. For switchgear, the next highest standard value above
the actual line variable is set.

Rated short-circuit breaking current


The rated short-circuit breaking current Isc is charcterised by the r.m.s. value of the AC component
and the relative DC component, which results from the opening time of the circuit-breaker and the
DC time constant of the short-circuit current.
The circuit-breaker may be equipped with more than one release having different tripping times,
which in turn means different opening times. Thus depending on the release the DC component
can also vary. The selection of the rated value Isc must be based on the shortest opening time.
Unless otherwise specified the DC time constant of the short-circuit current is = 45 ms (standard
value). In some systems or with some applications the time constant may be higher, so is the result-
ing DC component then related to the opening time of the circuit-breaker. Therefore the circuit-
breaker standard IEC 62271-100 [7] allows another time constant of 120 ms (also 60 ms and 75 ms)
for special applications.
Whether or not a circuit-breaker at given rated short-circuit breaking current is suitable for other
(than the rated) DC components based on different opening time or different short-circuit current
time constant, can be verified by the total breaking current. Keeping Itotal constant, higher DC com-
ponents at lower AC component may be calculated. However, the total breaking current resulting
from the rated values of the circuit-breaker Isc, Top and must not be exceeded.

96 Siemens AG 12E3
Switchgear configuration

(
Top +Tr )
DC component () at the instant of contact separation: =e

Permissible total current, resulting from the rated short-


circuit breaking current (AC component) at = 45 ms I total = I sc 1 + 2 2
and shortest opening time Top-min:

For other short-circuit breaking currents ( Isc) and other


I total I AC ( eff ) 1 + 2 2
DC components ( 45 ms; Top Top-min) applies:

Warning: The conversion of breaking currents makes sense only up to 50 % DC component;


higher values require the approval of the circuit-breaker manufacturer.

relative DC component at the instant of contact separation


DC component of the systems short-circuit current
fN prower-frequency, 50 Hz or 60 Hz
IAC(eff) IAC Isc; short-circuit breaking current (AC component, r.m.s. value)
Isc rated short-circuit breaking current (AC component)
Itotal total (short-circuit) breaking current
Top opening time of the circuit-breaker
Tr cycle of the rated frequency; 10 ms (50 Hz) or 8.3 ms (60 Hz)

Rated short-circuit making current and rated peak current


The design specification, given by the standard, establishes a fixed ratio between the rated peak and
short-time withstand currents: Ip / Ik = 2.5 (2.6 at 60 Hz); the same ratio applies to the dynamic rat-
ings Ima / Isc. In pure distribution networks the current almost always keep to this ratio. However,
factor 2.5 (2.6 at 60 Hz) may be exceeded in the network, particularly when regenerative loads are
connected to the system. The following can indicate a higher making or peak current that differs
from the standard:
- higher number of motors
- motors of high rated power
- generators.

To minimize voltage drops (voltage quality) caused by large, direct-starting motors, networks may
be designed for high short-circuit current levels. In those installations, the magnitude of the peak
current must be thoroughly taken into account.

Rated short-time withstand current


Main and earthing circuits of switchgear assemblies can have different ratings. The rated short-time
withstand current may be converted into other current or time values; see H 2.4 d).

H 2.4 Rated duration of short-circuit tk


This refers to the duration for which switchgear can conduct the rated short-time current in a steady
state.

Siemens AG 12E3 97
Switchgear configuration

Rating rule: tk tk line


A key factor here is the total short-circuit duration, which is governed by the settings of the protec-
tion relay, the selectivity requirements, the set tripping times, and the opening times of the switch-
ing devices.21 Values of between 3 s and 1 s are normal for switching devices and switchgear.

a) In accordance with the applicable standard [1], the preferred value is tk = 1 s, although 3 s has
since established itself for most switching devices and switchgear; the protection settings do
not, therefore, need to be taken into consideration. With very high short-circuit current values
40 kA, however, 1 s is still typical for cost reasons.

b) Main and earthing circuits can have different rated values.

c) For cost reasons, current transformers mostly are designed for times of < 3 s.

d) "Thermal" conversion between the short-time current and the short-circuit duration:
The short-time current and the short-circuit duration can be converted by means of the It value:
I12 t1 = I 22 t2 . A conversion for lower short-circuit currents with longer duration is harmless. A
conversion for larger short-time currents with shorter durations may only be carried out within
the rated values, so that the peak withstand current and the making and breaking capacity of the
circuit-breakers and the switchgear assembly are not exceeded.

H 2.5 Rated normal current Ir


A key factor for the rated value is the actual operating current IB, which flows continuously or for a
long period in the network, and the prevailing ambient temperature.

Rating rule: Ir IBmax at a given ambient temperature

For switchgear, the next highest standard value above the maximum operating current is set as the
rated current. Reserves have to be taken into account in the standard value to be selected if the am-
bient temperature or the characteristics of the load may change.

a) Busbars and feeder circuits can have different rated values; the same applies to individual
sections of busbars that have been sub-divided.
b) Reserves for temporary (planned) overload or emergencies must be taken into account.
c) When busbars are rated, the operating principle of couplings with parallel infeeds must also be
taken into account at the planning stage.
d) The operating current may contain harmonics which considerably contribute to the temperature
rise; the total current determines the rating.
e) The influence of the site altitude on the current carrying capacity in almost negliglible in prac-
tice. The dissipation of heat losses just as the insulation capacity depends on the air density
which decays with increasing altitude. Regarding the current carrying capacity, however, the
reduced cooling effect at high altitudes is compensated by lower ambient temperatures [19].

21
A general value of 100 ms is normally assumed as the shortest possible breaking time (opening + arcing time),
using a protection relay and a standard circuit-breaker.

98 Siemens AG 12E3
Switchgear configuration

H3 Busbar arrangement

If the switching principle has not yet been defined during network planning or in accordance with
operator specifications, the following general aspects should be taken into account to help reach a
decision:

Selection variable Key influencing factors

Single / double busbars Line structure


Bus section panel Line protection, tripping times, selectivity
Reserves / availability, switchover time
Bus section panel / transfer panel with
switch or circuit-breaker Operating procedures
In-plant generation, emergency supply
Bus coupler unit (with double busbar)
Power quality (unstable loads)

Table H-4: Key factors for the busbar design

H 3.1 Single busbars


A single busbar is suitable for most supply duties. In systems with a higher number of feeder cir-
cuits, the busbars can be sub-divided into sections each with their own infeed. In this way, each
section can potentially draw a reserve supply from an adjacent section. Single busbar switchgear
has the following benefits:
- it is completely transparent in all switching states;
- as a result, it is easy to use if network failures need to be rectified urgently, which greatly re-
duces the risk of switching faults;
- if switchovers caused by faults need to be carried out, only the circuit-breakers need to be oper-
ated. If the wrong circuit-breaker is operated inadvertently, this will not affect safety of the
switchgera because circuit-breakers can make or break all load and short-circuit currents, even
during earth fault and under any other fault conditions.

H 3.2 Double busbars


For technical or contractual reasons, some requirements can only be properly fulfilled by means of
double busbars, for example if
- two (or more) infeeds must always be operated separately (e.g. infeeds from different public util-
ity companies or the strict separation of in-plant generation and the public network);
- loads can interfere with the power quality when causing voltage fluctuations or flickers, and
other equipment is sensitive to those interferences. Non-sensitive loads depending on the load
status should be switched to either the stable or the unstable busbar;
- loads of different importance need to be distributed across "safe" and "less safe" busbars (i.e.
busbars with different requirments on the availability);

Siemens AG 12E3 99
Switchgear configuration

- a network must be divided into two sub-networks due to the limited short-circuit strength of the
installed equipment. Switchovers permit to balance fluctuating load current consumption.

H 3.3 Design of double busbars


The lifetime of a disconnector plays an important role for double busbar switchgear. If frequent
switchovers are required, disconnectors should not be integrated in the switchover process due to
their relatively short operating cycle lifetime. The average mechanical endurance of a disconnector
(drawout unit or truck) is 1000 or 2000 operating cycles, corresponding with classes M0 and M1
[21]. Because of this low endurance in comparison to circuit-breakers, not every design of double
busbar switchgear is suitable for frequent busbar switchovers. A version with two circuit-breakers
that switch between the busbars is more suitable.

Fixed mounted disconnector Fixed mounted disconnector Two withdrawable


with one circuit-breaker with two circuit-breakers circuit-breakers

Figure H-2: Design alternatives of double busbar arrangements

Only the designs B1 and B2 suit the requirements for frequent busbar switchover. Only the circuit-
breakers are operationally switched, the disconnectors are opened only for maintenance or work
purposes. In contrast to this the classic double busbar design (A) is less suitable since every busbar
switchover implies to operate the disconnectors.

H 3.4 Operating principle of bus couplings


If the system contains more than one busbar section, the planned operating principle of couplings
governs the rated short-circuit current of the switchgear and the rated normal current of the busbars.

Normally open coupling (NO)


In "open" mode, the short-circuit currents remains low, which allows systems, switches, cables etc.
with low rated values to be used. With a bus section panel and an automatic changeover circuit,
instantaneous reserves (dead time < 300 ms) can still be ensured even if the infeed fails. The short-
circuit current is not increased as a result of this because one infeed line has already been discon-
nected.

100 Siemens AG 12E3


Switchgear configuration

Normally closed coupling (NC)


In "closed" mode, the switchgear must be rated for the total fault current of all the interconnected
infeeds, even if selective mains decoupling has been achieved by means of a bus section panel and
quick-disconnect technology. The advantage is that load differences can balance themselves, on the
other hand disturbances can cause interference that affects the entire network.

Comments:
a) Provided that certain safety measures are observed, system sections that are normally operated
separately can be briefly interconnected during switchovers, even if the short-circuit current
exceeds the rated system value; see subclause 7.1.1 of IEC 61936-1 [22].
b) Interlocking and switchgear interlocking: whenever any type of bus section panel or bus cou-
pler unit is used for busbars, the extent to which interlocks and switchgear interlocking are re-
quired must be determined.
- An interlock system must simulate the planned operating procedures and prevent impermissi-
ble switching states.
- If disconnectors are directly involved in busbar switchovers or coupling maneuvers, switch-
gear interlocking must prevent impermissible switching operations with the disconnector.

H4 Switching Devices

Selection variable Key influencing variables Section


Circuit-breaker Operating current and switching duty B1
Switch Switching frequency A4
Contactor Switching capacity A 2 to A 3, H 1
HRC fuse Protection concept, selectivity D 2 pp.

Table H-5: Key factors for the selection of the switching device

The listed influencing variables are equally important when it comes to choosing and rating the
switching devices.

Rating rules: see section A 1 to A 4 Selection of the appropriate device


B Switching duties in medium voltage networks
C Rated values of switching devices

Comments:
In cases where switches or circuit-breakers can be used likewise for a particular switching duty, the
selection can be determined by the protection concept and selectivity conditions. Examples of this
include:
- Short-circuit protection shall be realised with defined characteristics, for which only circuit-
breakers are suitable in combination with instrument transformers and protection relay.

Siemens AG 12E3 101


Switchgear configuration

- Overload protection can be achieved only with restrictions using standard back-up HRC fuses,
since they do not melt after a defined period in the lower overload current range. If overload pro-
tection is to be achieved in this range, current transformers and protection relays are required.
The switch then must be equipped with a stored-energy spring mechanism. Moreover it must be
considered that the breaking capacity of the switch for inductive overcurrents is not exceeded.
- Protection functions (overload, load unbalance, etc.) for sensitive loads (motors, transformers)
that are in accordance with defined characteristics can only be achieved by means of circuit-
breakers in conjunction with instrument transformers and protection relays.
- A switch-fuse combination has the advantage in contrast to a circuit-breaker to limit the
short-circuit current and cut the peak value, which is of onterest for the personnel protection.
- A switch without fuse, on the other hand, may be required in order to avoid breaking operation at
certain points in the network for selectivity reasons and to enforce the tripping of a certain
breaker at a different point.

These requirements are normally already given by the network design.

H5 Switchgear design and panel type

Selection variable Key influencing factors

Circuit-breaker unit Primary rated values


Switch-disconnector unit Switching devices
Design Operating current, switching capacity
- extendable panels
- block type Line protection
No. of switch /circuit-breaker panels
Operating procedures and operation
Installation conditions
Transportation and assembly
Upgradeability,
electrical / mechanical reserves

Table H-6: Key factors for the switchgear design

H 5.1 Basic selection criteria


The primary rated values must always cover the requirements that result from the line parameters.
Switchgear with the required properties must be available with the required design. Unless the de-
sign is specified otherwise and the primary rated values permit switch-disconnector units and cir-
cuit-breaker units, the comparison of the standard characteristics of the two designs may give hints
for the decision.

102 Siemens AG 12E3


Switchgear configuration

Switch-disconnector unit Circuit-breaker unit

Normal current: up to 630 A or 1250 A Normal current: up to 4000 A


Short-circuit current strength: Short-circuit current strength:
up to 25 kArms / 63 kApeak up to 63 kArms / 160 kApeak
Switching devices Switching devices
- mainly switches - mainly circuit-breakers
- some circuit-breakers - some switches
- contactors
No or only low short-circuit breaking Short-circuit breaking capacity required
capacity required
HRC fuses as short-circuit protection Short-circuit protection by instrument
in feeder circuits transformers plus protection relay
Small switching frequency High switching frequency
Simple secondary equipment Complex secondary equipment
Sometimes suitable for harsh climates Generally requires a protected environment
(for control, protection, and measurement
electronics)

Table H-7: Characteristic features of switch and circuit-breaker switchgear

H 5.2 Panel and block design


The list below highlights some of the differences between panel and block design, which could be
key decision-making criteria. Which of the following characteristics must the switchgear fulfil?

Panel design Block design


Flexible applications Given applications
Panel type can be freely selected Standardized versions
- Switch with/without HRC fuse
- Circuit-breaker
- Transfer and measurement panel
Number of switchgear panels can be freely Number of switching functions depends on
selected container size, containers can be arranged
side by side
All equipment variants Customized equipment
Range of functions can be extended Standard range of functions
Can be freely extended Can only be extended after prior planning

Table H-8: Distinguishing features of switchgear designs

Siemens AG 12E3 103


Switchgear configuration

H 5.3 Installation conditions, transportation and assembly


Switchgear dimensions and ambient condition at the installation site are a key decision-making cri-
terion. Many new systems are replacements for "old" switchgear in existing buildings.
In addition to space for the switchgear in the room, adequate space must be available for operating
and assembly activities as well as escape routes. Sufficient distance from other installations must
also be ensured. Alongside the installation conditions specified by the manufacturer they refer
only to the switchgear itself, legal specifications must also be observed; see subclause 7.5 of IEC
61936-1 [22].
Points absolutely to be taken into account are:
- Wall clearances and minimum dimensions for free areas for operating and assembly activities
(manufacturer)
- Minimum space for operation and installation to manufacturers instructions
- Minimum width of operating and assembly aisles
- Minimum width and maximum permissible length of escape routes
- Direction of pressure release (internal fault)

500 mm
Operating aisle 800 mm
Exit

Switchgear assembly

Erection or service Escape route 20 m


aisle 500 mm

Figure H-3: Arrangement of switchgear to IEC 61936-1

The following must be taken into account when switchgear is transported and installed:
Dimensions of the (door) openings in the switchgear room and access paths, load bearing capac-
ity of access paths, including lifting equipment (elevators).
Size, weight, and packaging of the transportation unit(s).
The switchgear and its components must be protected against local climatic conditions before the
final installation and commissioning if it is in temporary storage over a long period.

H 5.4 Additional aspects


There are no fixed rules for many of the selection criteria; decisions are rather made on the basis of
the operator's or designer preferences.

104 Siemens AG 12E3


Switchgear configuration

- The ratio of switch panels to circuit-breaker panels may be a criterion for the type of switchgear
design. The dominant switch type can sway the decision. On the other hand this is no clear rule;
there are circuit-breaker units available that are made up almost exclusively of switches and vice
versa.

- Operating procedures defined by the operator are closely related to the secondary equipment.
Decision-making criterion here is whether or not the switchgear can feature the relevant func-
tions which may include:
- Actuating equipment (switching levers, instrument displays, locks)
- Interlocks
- Integration in other (production) processes in the company

- The devices required for protection, control (automation, communication), measurement, and
metering functions govern the scope of the secondary equipment. The design must ensure that
this equipment can be installed properly (e.g. instrument transformer in the primary section, de-
vices in the low-voltage compartment). If remote control is used, the design concept must ac-
commodate this by providing motorized drive mechanisms for the switchgear, for example. The
higher the design category, the greater the design scope.

H6 Electrical and mechanical reserves


Reserves are provided to handle expected or planned requirements of the plant operator. A design
equipped with mechanical and electrical reserves is "overdimensioned" when it is first put into op-
eration, although it can be extended at a later stage. Which options is the design to offer?
- Panel extension
- Loss of service contuity during work on the switchgear
- Space for installing replacement instrument transformers or additional cores
- Options for installing secondary devices in the low-voltage compartment
- Options for retrofitting control or automation devices
- Options for retrofitting motorized drive mechanisms
- Planned increase of the short-circuit current
- Increase of operating currents in the feeder circuits and busbars

Siemens AG 12E3 105


Switchgear configuration

H7 Insulation medium

Selection variable Key influencing factors

Air insulation AIS* Ambient room conditions: temperature change, humid-


ity, pollution, salt, corrosive gases
Gas insulation GIS*
Type of operating site
Installation location (space requirements)
Fire protection requirements (fire load)
* AIS: "air insulated switchgear" Altitude
GIS: "gas insulated switchgear" Switching frequency and switching device lifetime

Table H-9: Criteria for the selection of the insulating medium

In technical jargon the abbreviation AIS for air insulated switchgear is common as well as GIS for
gas insulated switchgear. Instead of gas, the standard [23] uses the neutral term fluid for all gaseous
(except for ambient air) and liquid media. GIS in the medium voltage range are seldom purely gas-
insulated switchgear. With hybrid designs e.g. only the switching compartment is gas-insulated
while the busbar is embedded in solid insulation. Nevertheless they are accepted as GIS. Encapsu-
lated plug-in cable connections are a common feature of all GIS designs.
The table below compares the main features of systems with the two types of insulation. Which of
these features is the switchgear to be configured to have?

Feature AIS GIS


Enclosure Metal enclosure Metal enclosure, the primary section is
hermetically sealed
Climate Suitable for normal conditions Suitable for extreme conditions
Upgraded degree of protection (IP) In extreme conditions, only the
for harsh ambient conditions or secondary equipment needs protec-
measures taken in the service room tion.
Humidity and condensation in con- Inert atmosphere minimizes exter-
junction with pollution layers can re- nal influences on the primary sec-
duce insulation Remedy: heater in tion; in humid conditions, heater in
switchgear panel low-voltage compartment only
Maintenance Maintenance required (e.g. cleaning) Primary section does not need to be
maintained
Accessibility Easy access to all components Access to components in primary sec-
tion not required / not possible
Switching Highly suitable for switching duties Not suitable for switching duties with
frequency with high number of make-break opera- high number of make-break operations
tions Frequent access for mainte- (exception: switchgear panels with
nance contactor)

106 Siemens AG 12E3


Switchgear configuration

Feature AIS GIS


Dimensions Larger dimensions than GIS Compact design, which allows greater
(above rated voltages > 12 kV) flexibility during installation
Installation at May require a higher rated voltage (in- No measures required, even if the
altitude > 1000 m sulation level) or use of surge arresters connections are fully encapsulated
(cable plug connectors)

Table H-10: Characteristic features of air- and gas-insulated switchgear

Medium voltage Gis work at gas pressures between 50 kPa and 100 kPa in (hermetically) sealed
pressure systems according to [1]. No gas must be refilled during the life time of at least 35 years.
Because of this, as a rule, the operators of such switchgear are not concerned by the legal require-
ment of the EU Council Regulation on fluorinated gases [24]. GIS do not fall under the EU Council
Directive on pressure equipment [25]; because of the low gas pressure of only 300 kPa.
Gas insulation has many benefits, although nearly all requirements can also be fulfilled with air
insulation. In addition, certain areas of application are better suited to air-insulated systems, where
operational aspects, like accessibility or maintainability with simple means, are in the foreground.

H8 Design of the isolating distance

Selection variable Key influencing factors


Withdrawable unit / truck Switching frequency
Disconnector (built in) Component lifetime
Operational requirements
(access to cable terminals)

Table H-11: Key factors for the isolating distance

H 8.1 Accessibility
The type isolating distance can only be selected for air-insulated systems. If loads with a high
switching frequency are connected to a switchgear system, a switch in a withdrawable unit (truck) is
preferred because this enables it to be accessed quickly and easily for maintenance purposes or if it
needs to be replaced at the end of its service life.
Even if the cable terminals for the switchgear panel needs to be readily accessible (e.g. voltage tests
on cables), a withdrawable unit can still be a better solution than a fixed unit because more room is
available for working on the switchgear panel once the unit has been removed. How easily the cable
can be accessed depends on the type of partition; see section H 10.

Siemens AG 12E3 107


Switchgear configuration

H 8.2 Voltage tests on cables


If a cable cannot or must not be disconnected and dismantled from the switchgear, it must be con-
sidered that the isolating distance is dielectrically stressed with the sum of test voltage on the cable
and the power-frequency voltage on the busbar22; see U, Figure H-4. In some cases practically no
safety margin is left to the withstand capability of the isolating distance if the busbar side is still live
when the cable test voltage is applied.

UN Two other aspect need be considered:


- during a DC test on paper-insulated cables
U the isolating distance is stressed with a pul-
sating voltage, which is not covered by a
corresponding rating;
- if temporary or transient overvoltages
(e.g. during earth fault) occur on the busbar
side during the cable test, the rated insula-
UTest tion level of the isolating distance may be
exceeded.

Figure H-4: Voltage test on cables, example with a switch panel

If withdrawable switching devices realise the isolating distance, this issue is not relevant since the
withstand capability of the isolating distance is high enough rather the clearance to other parts of
the switchgear may be critical.
In case of fixed mounted switchgear designs the rated cable test voltages Uct (a.c.) or Uct (d.c.) of
the switchgear assembly shall correspond to the test values of the cable connected. Otherwise the
cable test voltage should be subject to agreement between manufacturer and user, if the cable can-
not be dismantled.

H 8.3 Switching frequency


For switchgear with double busbars, see also section H 3.3 regarding operational aspects when fre-
quent busbar switchover is required.

22
Other parts of the switchgear which remain connected to the cable are stressed with the cable test voltage as well.

108 Siemens AG 12E3


Switchgear configuration

H9 Enclosure

Selection variable Key influencing factors


Degree of protection (IP) Ambient conditions
Internal fault qualification Personnel protection
- A or B Type of operating site
-F/L/R Building
- Test current and duration
Pressure absorber
Pressure relief duct

Table H-12: Key factors for the enclosure

H 9.1 Degree of protection


According to the IEC standard of switchgear assemblies [23] a minimum degree of protection of IP
2X is required. In the market higher degrees of protection IP 3XD or IP 4X are usual. These two
degrees of protection are identical with respect to shock-hazard protection but differ with respect to
protection against ingress of solid foreign bodies (1st numeral).
Water protection is not specified for systems operating under normal conditions inside buildings.
For harsh environment the degree of protection can be upgraded on request; e.g. up to IP 51.
Requirements regarding ventilation/cooling and protection against ingress of solid foreign bodies
are contrarily! Switchgear at large rated currents and high ambient temperature can hardly suit both
requirements. The degree D for protection against electric shock, however, can always be ar-
chieved.
IP 3 X D
1st digit Additional letter

2nd digit
Foreign bodies Shock protection Water protection Shock protection*
0 non-protected unprotected 0 non-protected
1 50 mm back of hand 1 vertically dripping A back of hand
2 12.5 mm finger 2 dripping 15 tilted B finger
3 2.5 mm tool 3 spraying C tool
4 1.0 mm wire 4 splashing D wire
5 dust-protected wire 5 jetting
6 dust-tight wire 6 powerful jetting * is specified if degree of
protection is higher than
7 temporary immersion specified with 1st digit
8 continuous immersion

Figure H-5: IP codes [26]

Siemens AG 12E3 109


Switchgear configuration

H 9.2 Internal arc classification


This qualification specifies the type of accessibility of the operating site and the parts of the system
that are qualified with respect to internal faults (e.g. IAC A FLR 25 kA 1s).
A applies to switchgear in closed electrical operating areas, accessible only for authorized
and qualified personnel
B applies to switchgear at publicly accessible locations (higher severity of test)
F / L / R designate the accessible, classified sides of the switchgear that have been tested for resis-
tance to internal faults (front, lateral, rear).

Medium-voltage switchgear is generally tested for accessibility type A. Only complete, factory-
assembled stations (transformer/load-center substations) are tested for type B. Standard systems do
not need to be tested according to type B because they are always integrated in additional (station)
housing in areas that can be accessed by the public.

The qualified accessible sides F / L / R must be in accordance with the type of installation in the
service room. "FL" is sufficient for a wall-mounted installation, while "FLR" is required for a free-
standing installation (all sides can be accessed during operation). Non-classified sides of a free-
standing switchgear installation must be made inaccessible, for example by means of barriers.

H 9.3 Pressure absorbers and pressure relief ducts


With certain switchgear designs, pressure absorbers are available for low short-circuit currents
(< 20 kA). If an internal fault occurs, they reduce the pressure in the service room.
- Using pressure absorbers can help protect the building fabric, particularly in older buildings.
A pressure relief duct can channel the internal fault gases out of the switchgear room, thereby pro-
tecting the service room from the pressure wave and smoke.

Notes:
The service room must always be taken into account when measures to provide protection against
internal faults are elaborated:
- Calculation of the dynamic pressure in the service room, which the architect/structural engineer
can use to determine the stress on the building fabric.
- Pressure relief outlets with a sufficiently large cross-section or pressure relief duct.
Further requirements are defined in IEC 61936-1 [22]. Other regional legal building regulations
may also apply.

110 Siemens AG 12E3


Switchgear configuration

H 10 Compartments

Selection variable Key influencing factors


Loss of service continuity category Operating procedures
(compartmentalization) - Operation, work activities
- LSC 1 - Maintenance requirements
- LSC 2 Servicing / maintenance
- LSC 2A (component lifetime)
- LSC 2B
Operator regulations
Access control by means of:
- Interlock Personnel training
- Work instruction + lock Shock-hazard protection during work ac-
- Tool tivities
Non-accessible compartment Switchgear space requirements
Partition class
- PM (metal)
- PI (plastic)

Table H-13: Key factors for the compartment design

H 10.1 General selection criteria


The decision regarding the type of partition depends on the requirements of the operator.
- Which recurring operating procedures require access to compartments?
(e.g. changing the HRC fuse, reading short-circuit indicators, making adjustments)
- What servicing and maintenance work intervals are planned?
- Which system components must remain live even while servicing / maintenance work is being
carried out within a compartment?
- Is shock-hazard protection during servicing / maintenance work to be achieved by means of me-
tallic / non-metallic partitions?
- What level of training is required for personnel? Is shock-hazard protection to be permanently or
realized automatically or manually?
- How much space is available for the installation of the switchgear?

H 10.2 Loss of service continuity category


The loss of service continuity category (LSC) defines the possibility to keep other compartments
and/or functional units energised when opening a main circuit compartment. The LSC category
does not describe ranks of reliability or of personnel protection.
LSC 1 This category offers the least availability and does not include partitions between the bus-
bars or adjacent panels. When work is carried out in the interior the busbar section or at
least the adjacent panels must be de-energised.

Siemens AG 12E3 111


Switchgear configuration

LSC 2 This category includes an isolating distance and partitions to the busbar and adjajent pan-
els so that they can remain energised if the cable / connection compartment is open.
LSC 2A This category means that the panel has besides the busbar several accessible com-
partments. If either compartment is opened, busbar and adjacent panel can remain ener-
gised since an isolating distance and a partition to the busbar compartment is built-in.
LSC 2B In this category (known as "metal clad") the switchgear features an isolating distance and
partition between busbar and switch or circuit-breaker as well as between switch or cir-
cuit-breaker and cable terminal. Busbar and adjacent panels as well as the cables in the
connection compartment may remain live if the panel is opened.

Selection aspects
LSC 1 is advisable if the operations permit to shut down parts of or even the whole switchgear
installation for work or maintenance. The dead state provides safest work conditions.
LSC 2 makes it possible to open a panel without shutting down the busbar section or the whole
switchgear installation. With LSC 2 category switchgear only the cable / connection
compartment is accessible, most gas-insulated switchgear belong to this category.
LSC 2A This option is recommended if quick and easy access to the cable terminal or transform-
ers is required (on a regular basis too).
The systems are more compact than those in category LSC 2B.
When the switch is accessed, the cable must be disconnected from the power supply
(supply cable or reverse voltage from the load).
A door interlock with the earthing switch is recommended.
Due to the potential hazard mentioned, using systems with loss of service category LSC
2A makes more stringent demands regarding the training that staff working on the system
require.

LSC 2B Systems in this category offer the highest level of "in-built" shock-hazard protection, al-
though this means that the components can be more difficult to access.
The systems are larger than those in category LSC 2A.
In conjunction with interlock-controlled access, these systems are also suitable for per-
sonnel who do not work with high-voltage systems on a regular basis.

The loss of service continuity categories:


- Do not differentiate between permanently installed and temporary partitions (covers, removable
shutters etc. that are present only temporarily);
- Are intended for systems with accessible compartments and are, therefore, applicable to gas-
insulated systems only if they have accessible compartments other than busbar and cable / con-
nection compartment.
- Do not describe the partition for providing protection against an internal fault in an adjacent
room, but only the shock-hazard protection against live, adjacent parts 5. Safety Rules for Car-
rying Out Work [31].

Beyond technical characteristics, preferences of the operator can influence the decision for LSC 2,
2A or 2B.

112 Siemens AG 12E3


Switchgear configuration

H 10.3 Access control


While the compartment for the busbar in nearly all system designs can only be opened with a spe-
cial tool (tool-based accessible compartment), the switch and cable compartment can be opened
in one of two ways:

- Interlock-controlled access
With this method, shock-hazard protection is ensured automatically because the door / flap to the
compartment can only be opened when all the primary circuit components inside have been
short-circuited and earthed.

- Process-based access
With this method, the manufacturer must equip the compartments with locking devices. The op-
erator is responsible for ensuring that access to the compartment is regulated by means of a work
instruction. If the instruction is not observed, personnel risk coming into contact with live parts!

Provided a choice exists, operators must decide according to their own requirements. Interlock-
controlled access is recommended due to the high level of inherent safety.

Again, as for the LSC category, preferences of the operator influence the choice of access control.

H 11 Feeder circuit components

Selection variable Key influencing factors


Cable connection Operating and short-circuit current
- Sealing end: standard / plug Switching duty
- Number of cables
- Cable cross-sections Underground / overhead cables
Surge arrester Altitude
Voltage transformer Line protection
- Earth fault winding (if required) Control
Current transformer Measurement, metering
- Core number and data
Neutral-point earthing
Core-balance transformer
(cable-type current transformer)
Earthing switch Operating procedures
- Class E0
- Class E1, E2

Table H-14: Key factors for the feeder circuit components

At the configuration stage, it is important to remember that many different components need to be
installed in the limited space available on the switchgear panel.

Siemens AG 12E3 113


Switchgear configuration

H 11.1 Cable connections


The operating and short-circuit current determine the number and cross-section of the cables to be
connected. In many cases, operators have standardized the cross-sections used in their companies.
This has to be taken into account particularly with multiple cable connections for large operation
currents.

H 11.2 Instrument transformers


In order to keep the spatial size and the electrical data as small as possible, instrument transformers
should be selected accurately adapted to power consumption of the secondary devices to be con-
nected. Digital protection relays feature a power consumtion of less than 1 VA. Hence 2.5 VA or 5
VA rated output of the instrument transformers suffice in most cases, since the losses along the sec-
ondary cables are small as well due to the low burden. Overdimensioning which is quite common
practice, unfortunately may even be counterproductive, because instrument transformers measure
within their accuracy class not until a burden23 of at least 25 % of the rated output [32], [33].
In many cases a separate measuring core is dispensable if an operational measurement at > 1 % ac-
curacy is acceptable. In the range of normal currents CT protection cores transduce with satisfactory
accuracy. CT of class 5P feature a current error of approximately 1 %, which may slightly increase
at lower currents so that in average the overall accuracy is in the order of 3 %.

Voltage transformers (VT) in networks with an isolated neutral point should be equipped with a
earth fault winding (da-dn winding, formerly "e-n winding"). Damping resistors are connected to
the winding; see section I 1.

H 11.3 Earthing switches


Class E0 devices are standard earthing switches with no short-circuit making capacity. Class E1 or
E2 switches can switch two times or five times onto a voltage that is present [21]. Earthing switches
E1 / E2 are safe even if unintentional switching faults occur.

H 11.4 Surge arresters


Surge arresters also need space in the connection compartment. Therefore, depending on the switch-
ing duty, it must be determined whether the feeder should be fitted with overvoltage protection; see
section B. Under certain conditions it may be more functional to mount the surge arrester within the
panel instead of at the load to be protected; e.g. with motors.

23
According to the standards other minimum values of the burden may be agreed on for CT < 15 VA [32] rated output
and for VT < 10 VA [33] rated output.

114 Siemens AG 12E3


Switchgear configuration

H 12 Busbar / metering panel components

Selection variable Key influencing factors


Instrument transformer Line protection and measurement
Earthing switch Operating procedures
- Class E0
- Class E1, E2
Surge arrester

Table H-15: Key factors for the busbar components

The aspects that were taken into account for the feeder circuit components also apply here (see sec-
tion H 11).
- Components that have a direct electrical connection with the busbar can be installed in meter-
ing panels along with current and voltage transformers.

The following alternatives are available that do away with the need for a metering panel:
a) With certain system designs, earthing switches for the busbar can also be housed in incoming
feeder units, bus section panels, or bus coupler panels.
b) With certain system designs, instrument transformers can be installed directly in the busbar
compartment.
c) Surge arresters can also be installed in switchgear panels that are always connected to the bus-
bar, generally in the incoming feeder unit. If a busbar has more than one connected infeed, each
incoming feeder unit has a set of arresters. This solution can be more cost effective than instal-
lation on the busbar.

Siemens AG 12E3 115


Switchgear configuration

H 13 Electronic secondary equipment

H 13.1 Electromagnetic compatibility (EMC)


If the secondary system of the medium voltage switchgear is equipped with electronic components,
the electromagnetic compatibility (EMC) of these components must be specified. On the one hand
there is susceptible electronics operating close to high-voltage circuits so that sufficient immunity
has to be specified. On the other hand electronic devices themselves are a source of potential inter-
ference and disturbance whose compatibility with the environment must be ensured. In addition, the
installation must comply with the legal requirements of the EU Council Directive on EMC [34].
Not all equipment of the secondary system of switchgear has to be included in the specification,
though. Relevant to EMC are oly susceptible devices or those which cause emitted interference.
Devices without electronic components or circuits which neither respond to electromagnetic inter-
ference nor cause emissions are considered as benign equipment [35], i.e. non-critical regarding
EMC. The table below lists examples of benign equipment.

EMC relevant equipment EMC benign equipment (non critical)


Protection relay Cables, terminal blocks, plugs
Equipment for control, interlocks and Auxiliary, position and signalling switches
switchgear interlocking Miniature circuit-breaker, fuses
Equipment for measurement, metering, Resistive loads without automatic switch-
including measuring transducers ing device (heaters with no controls)
Monitoring and communication equipment Batteries, accumulators
Voltage detection system Passive components (capacitors,
Motorized drive mechanisms filament lamps etc.)
(with collector motors)

Table H-16: Benign equipment regarding EMC

H 13.2 EMC requirements on the switchgear


IEC/EN 62271-1 [1] provides the basic EMC requirements regarding emission and immunity for
switchgear. The requirements refer only to the secondary system (low-voltage system) which con-
tains electronic components.
The primary system (high-voltage part) is exempted from EMC requirements since its high-
frequency emissions (caused by corona effects) are considered as negliglible in the voltage range
below 123 kV. Switching operations cause only occasional electromagnetic disturbances whose
duration lies within the range of milliseconds. The frequency of occurrence, the levels and the im-
plications of these interference emissions are considered part of the usual electromagnetic environ-
ment of high-voltage switchgear. Therefore no emission test and proof is required.
The same applies to switching devices (without electronic components) in the secondary system.
CISPR 14 [36], dealing with interference emissions in sensitive domestic areas, exempts single
switching operations from the proof of the compliance with radio interference limits.

116 Siemens AG 12E3


Switchgear configuration

H 13.3 EMC requirements on electronic equipment


Since a EMC routine test on the complete high-voltage switchgear is not possible, the individual
components must fulfil minimum requirements so that they cooperate without unduly interference
in the secondary system.
As a rule most of the devices and components comply with the specifiaction of their relevant prod-
uct standard. However, not all components were designed to operate in a high-voltage environment.
Thus it must be thoroughly checked whether electronics complies with the immunity required for
switchgear installations. Table H-17 summarises the tests and requirements, subdivided into devices
and components with or without interface to high-voltage circuits.
Component with interface to high-voltage circuits means that it is connected via an instrument
transformer or a coupling electrode to an HV conductor. Those components may face more severe
disturbances and should thus be tested for higher immunity. In contrast to this a component with-
out interface to high-voltage is only interconnected with other secondary equipment.
A guideline for EMC specifications is given by the standard of protection relays IEC/EN 60255-26
[37]. In one document it compiles all the requirements which might be applicable. However, not all
of them are relevant for every component. Which specifications the devices or components must
meet is determined by electromagnetic phenomena prevailing in the installation, which in turn de-
pend on
- the type of the existing interfaces (e.g. ports for analogue or binary signals, power ports,
auxiliary supply);
- the type and length of cables to be connected
- the installation situation, i.e. enclosures, shielding;
- the electrical and spatial environment.

For devices and components without interface to high-voltage circuits the immunity specifications
of industrial environment suffice, supplemented with typical disturbance phenomena which appear
at switching operations.

EMC Electronic devices and components


with interface to HV circuits without interface to HV circuits
Emission IEC/EN 60255-26 IEC/EN 61000-6-4
Tables 1 and 2 Tables 1 to 3
IEC-CISPR 11
group 1, class A
Immunity IEC/EN 60255-26 IEC/EN 61000-6-2
Tables 3 to 7 Tables 1 to 4
IEC/EN 61000-4-12
100 kHz, Table 1, Level 3
IEC/EN 61000-4-18
100 kHz and 1 MHz,
Table 1, Level 3 with note a

Table H-17: EMC specifications for electronics in high-voltage switchgear

Siemens AG 12E3 117


Switchgear configuration

H 13.4 Legal EMC requirements


Switchgear installations intended for the European market must comply with the essential require-
ments and the specific requirements for fixed installations set by the EU Council Directive on
EMC [34]; summarised in Table H-18.

Switchgear (fixed installations) Specific apparatus for fixed installations


Compliance with the essential requirements Compliance with the essential
regarding emission and immunity requirements not necessary
no conformity assessment required no conformity assessment required
no CE marking required no CE marking required
EMC documentation Instructions for EMC-correct installation

Table H-18: Requirements of the EU Council Directive on EMC

There is an exemption for electronic components of the secondary system that this kind of equip-
ment stand alone does not need to comply with the essential requirements since in the end EMC is
only relevant to the complete switchgear installation. However, this is not the optimum. On the one
hand the switchgear manufacturer is dependent on using equipment with defined electromagnetic
characteristic in order to ensure the EMC of the whole installation. And on the other hand only the
component manufacturer has the knowledge to reliably evaluate the EMC characteristic of its
equipment. Thus it is recommendable as far as available to use only EMC type tested low-
voltage equipment, with the accompanying EC declaration of conformity and the CE mark.
Switchgear installations need accompanying EMC documentation, which confirms that the installa-
tion and their components is designed, manufactured and installed according to the state of the art
regarding EMC. This EMC documentation may consist of the items listed in the table below.

Switchgear Electronic secondary equipment


- Installation instructions - Installation instructions
(assembly, connections, commissioning) - EC declaration of conformity (CE mark)
- Operating instructions
- for non CE-marked electronic products:
(including maintenance instructions) documentation, for example EMC type test
- List of applicable standards reports

Table H-19: Example for EMC documentation

Medium voltage switchgear itself neither requires conformity assessment nor CE marking.

118 Siemens AG 12E3


Standards

I APPENDIX

I1 Damping relaxation oscillations

I 1.1 Relaxation oscillations (ferroresonance)


Relaxation oscillations can occur in applications with single-pole, inductive voltage transformers in
certain network configurations, such as short underground or overhead line distances (low capaci-
tance between conductor and earth):

Neutral-point earthing Risk of relaxation oscillations


Effectively (solidly) earthed None
Resistance earthed None
Compensated (Petersen coil) Slight
Insulated High

Switching operations, earth faults, or other non-linear occurrences in the network can cause relaxa-
tion oscillations that are associated with high overvoltages and can subject the equipment to ex-
treme dielectric and thermal stress; voltage transformers are especially at risk. The oscillations satu-
rate the core causing considerable iron loss (sometimes indicated by a loud drone). As a result,
thermal overload and flashovers can destroy the transformers and, in turn, damage the switchgear.

L1
L2
L3
a a a

n n n
da da da

dn dn dn max. I
RD
110 V

typical values I: 4 / 6 / 8 A

Relaxation oscillations can be damped by installing resistors on the earth fault windings connected
to the open triangle ("e-n winding"). The choice of resistor depends on the thermal limit rating (or
rated long-time current) of the da-dn winding in the voltage transformer. Since a earth fault always
affects the entire galvanically-connected network, specific measures must be taken to protect the
entire network against earth faults (this includes damping resistors). In many cases, however, gen-
eral measures can be sufficient.

Siemens AG 12E3 119


Appendix

I 1.2 Standard values for damping resistors


Standard values for the resistors are provided in the table below. The choice of resistor depends on
the thermal limiting output (or rated long duration current) of the da-dn winding in the voltage
transformer.

da-dn winding of voltage transformer Damping resistance


Thermal limiting output Rated long duration current 24
75 W 4A 25 ohms / 500 W
100 W 6A 25 ohms / 500 W
150 W 8A 12.5 ohms 25 / 1 kW

If these standard values cannot be used, other values can be calculated.

I 1.3 Calculating the damping resistance


The damping resistance can be determined from the specifications on the rating plate of the voltage
transformer.
Specifications: Rated thermal limiting out put Ssr for 8 hours
Secondary rated voltage Usr of the da-dn winding (formerly "e-n winding")
Required: Lowest damping resistance value RD
Power loss (load-carrying capacity) of the damping resistor

The resistor must be rated in such a way that neither it nor the voltage transformer are overloaded,
even if an earth fault occurs.

I 1.4 Formula, symbols and indices


U Voltage D Damping
S Apparent power r Rated value
P Active power s Secondary
R Resistance V Power loss

I 1.5 Standard, uninterrupted line operation


Voltage at the output of a single da-dn winding: U2 = Usr (rated voltage)
100
Example: secondary rated voltage U 2 r = V
3
Voltage on the open triangle: U = 0 V (due to symmetrical, uninterrupted operation)

24
The term rated long duration currentis still in frequent use, although current standards use the term rated thermal
limiting output . Both terms are synonymous, however.
25
Two 25 ohm resistors (parallel)

120 Siemens AG 12E3


Standards

Line voltage Voltage on da-dn winding


L2 L3
L3
U 3 V
0/

UL1
10
Uninterrupted
operation UL
2
L1 Uda-dn = 0 V

L2 L3
)V
0/3
10 U
3( eL
3
Operation with 1,1 Ue
L2
U

L3
Ue
e L2

earth fault in L1
110 V
L1 da dn

I 1.6 Operation with earth fault


Values at the output of a single da-dn winding:

[F1] Voltage U se = 1.1 3 U sr = 1.9 U sr Factors:


1.1 Voltage increase at fault
S sr location
[F2] Current I se = 1.9 I sr = 1.9
U sr 3 Earth fault factor
1.,9 Rated voltage factor26
[F3] Apparent power S se = U se I se = 1.9 2 S sr 1.9 = 1.1 x 3

F2: with a constant load resistance, the 1.9 x voltage on the winding results in 1.9 x current if a
earth fault occurs.
The rated thermal limiting output S2r refers to uninterrupted operation. It is a rated value, although it
does not reflect the actual load-carrying capacity of the winding. In practice, the earth fault winding
can handle 3.6 x the rated thermal limiting output over a period of 8 hours.

Values at the terminals for the da-dn windings connected to the "open" triangle:

[F4] Voltage ( )
U = 3 1.1 3 U sr = 3.3 U sr Typical value for Usr:
100
3
V

S sr
[F5] Apparent power S = 3.3 U sr 1.9 = 6.3 S sr
U sr

[F6] Current I = I se Maximum permissible value

26
Rated voltage factor: multiple of the primary rated voltage for which a voltage transformer must fulfill the thermal
requirements for a defined stress time interval.

Siemens AG 12E3 121


Appendix

I 1.7 Damping resistance


The resistance value can be calculated using [F4] and [F5]:
U 2 U2
[F7] Resistance RD = 3 sr
S S sr
RD and PV are the mini-
(3.3 U sr ) 2 mum permissible values
[F8] Power loss PV
RD

I 1.8 Sample calculations


Specifications on the rating plate of a voltage transformer:
- Rated secondary voltage of the earth fault winding Usr 100 V / 3
- Rated thermal limiting output Ssr 100 VA
(same as the former "rated long-time current" specification) 6A)
=> Damping resistance RD (acc. to F7) 19.2
Load-carrying capacity PV (acc. to F8) 630 W |19.2

A 25 ohm resistor is used as standard; load-carrying capacity 500 W or higher.

Sources for Appendix I 1


- Documents from Peter Dorsch and Dr. Kerstin Kunde
- IEC 60044-2 / VDE 0414-2

122 Siemens AG 12E3


Standards

I2 RC-circuitry for protection of MV equipment


Some switching duties require RC circuitry for surge protection in order to protect the windings of
susceptible equipment against the effects of high-frequency switching transients. There is the possi-
bility that switching operations may initiate internal resonance oscillations inside the equipment
which can lead to dielectric overstress within the windings. Those internal overvoltages cannot be
suppressed by surge arresters at the terminals. Hence resonant oscillations must be avoided from the
first. RC elements are applied to:
- compensating coils (shunt reactors)
- furnace transformers
- equipment with insulation level below the standardised ratings
- old equipment with unknown insulation capability
- equipment which is frequently subjected to dielectric stress in normal service
(in this case the RC elements prevent against early ageing)
It is always necessary to match the RC circuitry to the individual system configuration. The follow-
ing exemplification may be used in order to estimate budget prices; by no means it can be used as a
general design.

RC-circuits form a bypass for high frequency currents (and voltages) in that the transients are di-
verted to earth instead of reaching the equipment to be protected. The RC installation at the load is
most economical since the capacitance of the surge capacitor then is smallest. Installation with
small line-earth capacitance on the busbar side require an additional protection circuit at the busbar.

C N RN CRC Capacitance of the RC-circuitry


(C) RRC Resistance of the RC-circuitry
CK Line to earth capacitance of the
Busbar

Load cable (or bar)


Cable (bar) ZK Surge impedance of the cable
CK Z K (or bar)
CRC CN Capacitance on the feeding side
RN Resistance on the feeding side
(B) RRC (A)

Figure I-1: RC circuitry for susceptible equipment

RC-circuits at the load (A)


With longer cables (> 50 m), the RC-circuits are installed directly at the load terminals. Typical
ratings are CRC 3 CK and RRC = 1 2 ZK .
RC-circuits cannot prevent switching transients, but the RC-circuits damp the travelling wave and
prevent the refraction ("reflection") at the load-side cable terminals, where the RC-circuits divert
the HF transients to earth (bypass).

Siemens AG 12E3 123


Appendix

RC-circuits at the load side of the circuit-breaker (B)


If CK is small (< 50 m cable), no distinct travelling wave effects occur depending on the effective
inductance (length of busbar, c.t. cores) between supply and load side. The RC-circuits are installed
close to the circuit-breaker. Typical ratings are CRC 6 CK and RRC > ZK .
The RC-circuitry archives an aperiodic damping of the HF equalising currents in case of a re-
ignition during switching off. Thus only one re-ignition may occur; in this manner voltage escala-
tion by repetitive re-ignitions is prevented.

RC-circuits at the busbar side (C)


Only with small phase-to-earth capacitance, i.e. if few cables or cables of short length are connected
to the busbar, the RC-circuits increase the phase-earth capacitance (replication of additional cables).
The capacitor forms a bypass for HF transients to earth, and travelling waves become spacially iso-
lated at the system side. The resistor R replicates the surge impedance of a cable and damps the
transient currents.

I3 Installation of overvoltage protection devices


Surge arresters and RC-circuits shall protect equipment against transient, steep fronted overvoltages
(high rate-of-rise). In order to ensure full effectiveness of the protection devices, the inductance of
the connections shall be minimal. This means the feeding and earthing cables must be as short as
possible.

With RC circuits is most important for the effectiveness to use low-inductance RC elements, cables
and earthing conductors. This is best achieved by using bifilar windings for the capacitors and
Schniewindt strips as resistors. Preferably capacitors and resistors should be installed in a common
housing. RC elements must be insulated to the upper standardised value of the rated lightning im-
pulse withstand voltage which corresponds to the relevant maximum operating and rated voltage.

Low-inductance connections should have a time constant not higher than L / R 50 ns; where L is
the total inductance of the RC element and the earth conductor, R is the resistance of the RC ele-
ment. Low-inductance earthing is in most cases achieved by providing several earthing conductors
leading to various points of the plant earth (e.g. to the earthing point of the cable shields). Copper
conductors satisfying the earthing specifications for HV installations > 1 kV [22] must be used for
earthing. The minimum cross-section is A = 16 mm. The individual conductors should be as short
as possible.

124 Siemens AG 12E3


Standards

I4 Overvoltage factors (Definition)


Overvoltages usually are indicated as a factor which represents as a multiple of the operating volt-
age line-to-earth as reference value.

U [p.u.] Unipolar overvoltage factor k


U unipolar
k=
Uunipolar Ubipolar 2
LE U m
1 3
t
-1 Bipolar overvoltage factor k
U bipolar
k'=
2
U m
3

Um Maximum operating (network) voltage (line-line)


ULE Operating (network) voltage line-earth Um/3

Siemens AG 12E3 125


Appendix

I5 Abbreviations, Symbols and Formula Variables


Symbol Variable Device / Network* Unit
U Voltage, general kV
Ur Rated voltage Device kV
UN Network voltage Network kV
Um Maximum voltage permissible for a device Device kV
UL Rated (reseal) voltage (gapped arrester) kV
Uc Continuous operating voltage (MO arrester) kV
Ur Rated voltage (MO arrester) kV
UC Capacitor voltage kV
Up Basic Insulation Level Device kV
Ud Power-frequency withstand voltage kV
I Current, general kA
Ir Rated current A
Ist Starting current Device A
Ith Short time withstand current Device kA
Ik Sustained symmetrical short circuit current Network kA
I"k Initial peak symmetrical short circuit current Network kA
Ip Peak current peak value (first half wave) Network kA
Ima Rated short circuit making current (peak value) Device kA
Ie / Is Closing current (peak value) Device kA
I1 Rated mainly active load-breaking current Gert A
I2a; I2b Rated closed-loop breaking current Gert A
I3 Rated no-load transformer breaking current Gert A
I4a Rated cable-charging breaking current Gert A
I4b Rated line-charging breaking current Gert A
I6a Rated earth fault breaking current Gert A
Itransfer Transfer current Netz A
Ir-transfer Rated transfer current Gert A
Imin Minimum operating (clearance) current of HRC fuse Gert A
ID Let through (cut off) current of HRC fuse kA
S Apparent power, general kVA; MVA
QC Capacitor reactive power kVar; MVar
SMot Motor apparent power kVA; MVA
Time constant, general ms
tL Arcing time (HRC fuse) s
tm Melting (pre-arcing) time (HRC fuse) s
tth Short circuit duration Device s
T0 Opening time Device s
Device / Network indicates whether the symbol or variable relates to network or device characteristics. Since the
various standards sometimes use different symbols, repetition is also sometimes unavoidable.

126 Siemens AG 12E3


Standards

I6 Diagram Symbols

Transformer Current transducer (c.t.)

Circuit-breaker Voltage transducer (v.t.)

Disconnector (isolator) Surge arrester / limiter

Contactor Spark gap

Switch Fuse-link

Switch-disconnector Capacitor

Earthing switch Resistor

Make proof earthing switch Reactance

Compensation coil (shunt reactor),


short-circuit limiting reactor

Siemens AG 12E3 127


Standards

J RELEVANT STANDARDS AND REGULATIONS


The following list names the most important standards or specifications; it is structured according to
Statutory regulations for medium-voltage equipment
Generic standards for switching devices and switchgear
Product standards for switching devices
Product standards for switchgear and accessories
Generally, the IEC standards concur with the relevant national standards. A standard uses the sym-
bols customary in the respective technical field. It is consequently possible for the same physical
variable to be differently designated.

J1 Statutory regulations for medium-voltage equipment

International Germany Title ( English / German )

BGV A3 Unfallverhtungsvorschrift Elektrische Anlagen und Betriebsmittel


BGV B11 Unfallverhtungsvorschrift Elektromagnetische Felder
BGV A8 Unfallverhtungsvorschrift Sicherheits- und Gesundheitsschutzkenn-
zeichnung am Arbeitsplatz
1999/519/EC 27 Council recommendation of 12 July 1999 on the limitation of exposure
of the general public to electromagnetic fields (0 Hz to 300 GHz)
26. BImSchV EMVU-Verordnung 26. Verordnung zur Durchfhrung des Bundes-
Immissionsschutzgesetzes (Verordnung ber elektromagnetische Fel-
der - 26. BlmSchV) Vom 16. Dezember 1996
2004/108/EC 28 Directive 2004/108/EC of the European Parliament and of the Council
of 15 December 2004 on the approximation of the laws of the Member
States relating to electromagnetic compatibility
EMVG Gesetz ber die elektromagnetische Vertrglichkeit von
Betriebsmitteln
BGI 766 Instandsetzungsarbeiten an elektrischen Anlagen auf Brandstellen
BGI 559 Handlungsanleitung zur Anpassung von Hochspannungsanlagen
- DIN VDE 0101 (05/89) -

Note on BGV29: Accident prevention regulations issued by the statutory industrial accident insur-
ance institutions (Berufsgenossenschaften: BGs) are legally binding, according to
the 7th code of social law, 15.
Note on BGI30: BG information describes typical solutions for applying BG regulations. Unlike
UVV rulings, BG information does not have to be obligatorily applied.

27
An EU Council Recommendation need not obligatorily be implemented in applicable law in EU member states. In
Germany this has taken place in the form of 26. BImSchV.
28
An EU Directive must be implemented in national law in EU member states. However, only respective national legis-
lation is legally binding.
29
BGV = BG regulation
30
BGI = BG information

128 Siemens AG 12E3


Standards

J2 Generic standards for switching devices and switchgear


=> Listed according to the number of the international standard

International German Title ( English / German )


standard standard

EN 50110 Operation of electrical installations


VDE 0105-100 31 Betrieb von elektrischen Anlagen
IEC 60071 Insulation coordination
VDE 0111 Isolationskoordination
IEC 60376 Specification and acceptance of new sulphur hexafluoride
VDE 0373-1 Bestimmung fr neues Schwefelhexafluorid SF6
IEC 60480 Guide to the checking of SF6 taken from electrical equipment
VDE 0373-2 Prfung von aus elektrischen Gerten entnommenem SF6
IEC 60529 Degrees of protection provided by enclosures (IP Code)
VDE 0470-1 Schutzarten durch Gehuse (IP-Code)
IEC 62271-1 High-voltage switchgear and controlgear Common specifications
VDE 0671-1 Gemeinsame Bestimmungen fr Hochspannungs-Schaltgerte
IEC 60865 Short-circuit currents - Calculation of effects
VDE 0103 Kurzschlustrme Berechnung der Wirkung
IEC 60909 Short-circuit current calculation in three-phase a.c. systems
VDE 0102 Kurzschlustrme in Drehstromnetzen
IEC 62271-303 High-voltage switchgear and controlgear - Use and handling of sulphur
hexafluoride (SF6)
VDE 0671-303 Hochspannungs-Schaltgerte und -Schaltanlagen - Teil 303: Gebrauch
von und Umgang mit Schwefelhexafluorid (SF6)
IEC 61936-1 Power installations exceeding 1 kV ac
VDE 0101-1 Starkstromanlagen mit Nennwechselspannungen ber 1 kV
EN 50522 Earthing of power installations exceeding 1 kV
VDE 0101-2 Erdung von Starkstromanlagen mit Nennwechselspannungen > 1 kV

31
Part 1 of EN 50110 contains minimum requirements applicable in all CENELEC countries. The respective currently
valid safety requirements for the individual countries are described in national addenda. In Germany, the details of
Parts 1 and 100 (VDE 0105-1 and -100) are significant.

Siemens AG 12E3 129


Standards

J3 Product standards for switching devices


=> Listed according to the number of the international standard

International German Title ( English / German )


standard standard

IEC 60044 Instrument transformers


VDE 0414 Mewandler
IEC 60099 Surge arresters
VDE 0675 berspannungsableiter
IEC 60282 High-voltage fuses - Current-limiting fuses
VDE 0670-4 Hochspannungssicherungen Strombegrenzende Sicherungen
IEC 60644 Specification for high-voltage fuse-links for motor circuit applications
VDE 0670-401 Anforderungen an Hochspannungs-Sicherungseinstze fr Motor-
stromkreise
IEC 60787 Application guide for the selection of fuse-links of high-voltage fuses
for transformer circuit applications
VDE 0670-402 Wechselstromschaltgerte fr Spannungen ber 1 kV Auswahl von
strombegrenzenden Sicherungseinstzen fr Transformatorstromkreise
IEC 62271-100 High-voltage switchgear and controlgear - High-voltage alternating-
current circuit-breakers
VDE 0671-100 Hochspannungs-Wechselstrom-Leistungsschalter
IEC 62271-102 High-voltage switchgear and controlgear - High-voltage alternating
current disconnectors and earthing switches
VDE 0671-102 Wechselstromtrennschalter und Erdungsschalter
IEC 62271-103 High-voltage switches - Part 1: Switches for rated voltages above 1 kV
and less than 52 kV
VDE 0671-103 Hochspannungs-Lastschalter Teil 1: Hochspannungs-Lastschalter fr
Bemessungsspannungen ber 1 kV und unter 52 kV
IEC 62271-105 High-voltage alternating current switch-fuse combinations
VDE 0671-105 Hochspannungs-Lastschalter-Sicherungs-Kombinationen
IEC 62271-106 High-voltage alternating current contactors and contactor-based motor-
starters
VDE 0671-106 Hochspannungs-Wechselstrom-Schtze und -Motorstarter
mit Schtzen
IEC 62271-110 High-voltage alternating current circuit-breakers -
Inductive load switching
VDE 0671-110 Hochspannungs-Schaltgerte und -Schaltanlagen
Schalten induktiver Lasten

130 Siemens AG 12E3


Standards

J4 Product standards for switchgear and accessories


=> Listed according to the number of the international standard

International German Title ( English / German )


standard standard

EN 50181 Plug-in type bushings above 1 kV up to 36 kV and from 250 A to


1,25 kA for equipment other than filled transformers
DIN EN 50181 Steckbare Durchfhrungen ber 1 kV bis 36 kV und von 250 A bis
1,25 kA fr Anlagen anders als flssigkeitsgefllte Transformatoren
EN 50187 Gas-filled compartments for a.c. switchgear and controlgear for rated
voltages above 1 kV and up to and including 52 kV
VDE 0670-811 Gasgefllte Schottrume fr Wechselstrom-Schaltgerte und Schalt-
anlagen mit Bemessungsspannungen > 1 kV bis einschlielich 52 kV
IEC 61219 Live working Earthing or earthing and short-circuiting equipment
using lances as a short-circuiting device Lance earthing
VDE 0683-200 Arbeiten unter Spannung Erdungs- oder Erdungs- und Kurzschlie-
vorrichtung mit Stben als kurzschlieendes Gert Staberdung
IEC 61230 Live working Portable equipment for earthing or earthing and short-
circuiting
VDE 0683-100 Arbeiten unter Spannung Ortsvernderliche Gerte zum Erden oder
Erden und Kurzschlieen
IEC 61243-1 Life working Voltage detectors
Capacitive type to be used for voltages exceeding 1 kV a.c
VDE 0682-411 Arbeiten unter Spannung Spannungsprfer
Kapazitive Ausfhrung fr Wechselspannungen ber 1 kV
IEC 61243-5 Live working - Voltage detectors
Voltage detecting systems (VDS)
VDE 0682-415 Arbeiten unter Spannung Spannungsprfer
Spannungsprfsysteme (VDS)
IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages
above 1 kV and up to and including 52 kV
VDE 0671-200 Metallgekapselte Wechselstrom-Schaltanlagen fr Bemessungsspan-
nungen ber 1 kV bis einschlielich 52 kV
IEC 62271-201 A.C. insulation-enclosed switchgear and controlgear for rated voltages
above 1kV and up to and including 38 kV
VDE 0671-201 Isolierstoffgekapselte Wechselstrom-Schaltanlagen fr Bemessungs-
spannungen ber 1 kV bis einschlielich 52 kV
IEC 62271-202 High-voltage/low-voltage prefabricated substations
VDE 0671-202 Fabrikfertige Stationen fr Hochspannung/Niederspannung

Siemens AG 12E3 131


Standards

K REFERENCES AND FURTHER READING

[1] IEC 62271-1: 2007-10


High-voltage switchgear and controlgear Part 1: Common specifications
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[2] IEC 60034-15: 2009-03


Rotating electrical machines Part 15: Impulse voltage withstand levels of form-wound
stator coils for rotating a.c. machines
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[3] Luxa A., Priess A.


Switching of Motors During Start-Up
Siemens, Power Engineering & Automation VII (1985),
Special Issue Medium Voltage Technology (ISBN 3-8009-384-80)

[4] Luxa A.
Metechnische und rechnerische Untersuchung von multiplen Wiederzndungen
beim Schalten von Motoren mit Vakuumschaltern
Dissertation, Fachbereich Elektrotechnik, Technische Universitt Berlin, 1987

[5] Siemens AG, Berlin:


3EE Surge Arresters, 3EF Surge Limiters, Medium-Voltage Equipment Catalog
HG 21 2007, Order No. E50001-K1521-A101-A1-7600

[6] IEC 60076-3: 2000-03


Power transformers Part 3: Insulation levels, dielectric tests and external clearances in air
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[7] IEC 62271-100: 2008-04


High-voltage switchgear and controlgear Part 100: Alternating-current circuit-breakers
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[8] IEC 62271-103: 2011-06


High-voltage switches
Part 1: Switches for rated voltages above 1 kV and less than 52 kV
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[9] IEC 60871-1: 2005-07


Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V
Part 1: General
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[10] Schultz W.
Schalten von Kondensatorbatterien
Siemens-Bericht, TS 138 J 139/g 10.17, Mrz 1969

[11] Test Report TVS 2631E


Paralleling of Capacitor Banks
Siemens AG, Berlin, 1987-09

132 Siemens AG 12E3


Standards

[12] Report of performance 437-06


Back-to-back capacitor bank switching current tests
KEMA Arnhem, Nederlands, 2006-12

[13] Report of performance 438-06


Back-to-back capacitor bank switching current tests
KEMA Arnhem, Nederlands, 2006-12

[14] IEC 60099-5:2000-03


Surge arresters Part 5: Selection and application recommendations
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[15] Hinrichsen, V.
Metal-Oxide Surge Arrester Fundamentals
Siemens AG, Berlin, 2001

[16] IEC 60071-2: 1996-12


Insulation co-ordination Part 2: Application guide
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[17] IEC/TR 60815-1: 2008-10


Selection and dimensioning of high-voltage insulators intended for use in polluted condi-
tions Part 1: Definitions, information and general principles
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[18] IEC 60664-1: 2007-04


Insulation coordination for equipment within low-voltage systems
Part 1: Principles, requirements and tests
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[19] Zentgraf, L.
Niederspannungs-Schaltgertekombinationen
VDE-Schriftenreihe 28, VDE Verlag GmbH, Berlin

[20] IEC 61439-1: 2009-01


Low-voltage switchgear and controlgear assemblies Part 1: General rules
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[21] IEC 62271-102: 2003-08


High-voltage switchgear and controlgear
Part 102: Alternating current disconnectors and earthing switches
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[22] IEC 61936-1: 2010-08


Power installations exceeding 1 kV a.c. Part 1: Common rules
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[23] IEC 62271-200: 2003-11


High-voltage switchgear and controlgear Part 200: AC metal-enclosed switchgear and
controlgear for rated voltages above 1 kV and up to and including 52 kV
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

Siemens AG 12E3 133


Standards

[24] Regulation (EC) No 842/2006 of the European Parliament and of the Council
of 17 May 2006 on certain fluorinated greenhouse gases
http://eur-lex.europa.eu/

[25] Directive 97/23/EC of the European Parliament and of the Council of 29 May 1997 on the
approximation of the laws of the Member States concerning pressure equipment
http://eur-lex.europa.eu

[26] IEC 60529: 2001-02


Degrees of protection provided by enclosures (IP code)
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[27] IEC/TR 60787: 2007-03


Application guide for the selection of high-voltage current-limiting fuse-links
for transformer circuits
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[28] DIN VDE 670-402: 1988-05 (VDE 0670-402)


Wechselstromschaltgerte fr Spannungen ber 1 kV
Auswahl von strombegrenzenden Sicherungseinstzen fr Transformatorstromkreise
VDE Verlag GmbH, Berlin

[29] IEC 60076-5: 2006-02


Power transformers Part 5: Ability to withstand short circuit
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[30] IEC 62271-105: 2002-08


High-voltage switchgear and controlgear
Part 105: Alternating current switch-fuse combinations
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[31] EN 50110-1: 2004-11


Operation of electrical installations
CENELEC, 17 Avenue Marnix, B-1000 Brussels

[32] IEC 60044-1: 2003-02


Instrument transformers Part 1: Current transformers
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[33] IEC 60044-2 : 2003-02


Instrument transformers Part 2: Inductive voltage transformers
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[34] Directive 2004/108/EC of the European Pariament and of the Council of 15 December
2004 on the approximation of the laws of the Member States relating to electromagnetic
compatibility and repealing Directive 89/336/EEC
http://eur-lex.europa.eu

[35] Guide for the EMC Directive 2004/108/EC


22nd February 2007
http://ec.europa.eu/enterprise/electr_equipment/emc/directiv/dir2004_108.htm

134 Siemens AG 12E3


Standards

[36] IEC CISPR 14: 2009-02


Electromagnetic compatibility Requirements for household appliances, electric tools and
similar apparatus Part 1: Emission
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[37] IEC 60255-26: 2008-07


Measuring relays and protection equipment
Part 26: Electromagnetic compatibility requirements
IEC Central Office, 3 rue de Varemb, CH-1211 Geneva 20

[38] Mller, A.
Anforderungen der EMV-Richtlinie an Hochspannungsschaltanlagen
ew - das magazin fr die energie wirtschaft, Jg.107 (2008), Heft 9
VWEW Energieverlag GmbH, Frankfurt am Main

Siemens AG 12E3 135

You might also like