FULLYAUTOMATICSTARDELTASTARTER USERMANUAL

Qualityfeaturesforconvenientoperation:

FullyAutomatic:ThemotorstartsinStarwhenthegreenSTARTbuttonispressed.ChangeovertoDELTAisautomaticafter10to20secs,controlled
byanadjustableelectronictimerincorporatedinthestarter.

Construction:

ASDshaveoneIncomingmainswitch(TPN)withHRCfusesfollowedbythreecontrolfuses&sixindicatinglamps:ThreelampsRed,Yellow,Bluefor
threephases,OneAmberforTrip&OneAmberforOverloadindication.TherearethreepowercontactorsMAIN,STAR,DELTA.Thethermaloverload
relayissuitablywiredandinterconnectedwiththeMAINcontactor.

Overloadprotection:

Thetriplepolebimetallicthermaloverloadrelayisofhandresettype.Itunmistakableindicatedoverload.Atemperaturecompensationdevice
preventstherelayfrombeingaffectedbyvariationinambienttemperature.Overloadrelaysetting

Phasefailure,Phaseunbalanceprotection:

TheVSPD2phasefailurerelayactsinPhaseFailure,Unbalance,PhaseSequence.IthasAuto/Manual/RemoteResetandanAdjustableUnbalance
Setting,2COoutputRelay.Itprotectsthemotorincaseofphasefailure,phaseunbalance.

PushButton:
IlluminatedSTART,STOPpushbuttonaremountedonthefrontofthestarterpanel.

Earthing:
Separateearthbusbarisprovidedinthepanel.

DosandDontsforStarterPanel:
Dos:

1. Beforeinstallationcheckforanyloosenessinthewiredcomponentsofthepanel.
2. Checkthesupplyvoltagefromwheretheincomingsupplytothestarteristobegiven.Thesupplyvoltagemustnotfallbelow415+10%V.
3. AlwaysoperatethehandleofthemainswitchinOneGo.
4. IfthetimeofSTARtoDELTAconversionhappensquicklythenadjustthetimesettingofthetimerto10seconds.
5. Ifthemotordoesntstartatthefirsttimetheninterchangethewiringatterminals2&3ofVSPD2.
6. Alwaysconnecttheneutralproperlywitheverystarterpanel.
7. AlwaysearththebodyofthestarterpanelatthebothsidesindicatedforEarthing.
8. Ifthemotortripsagain&againthendisconnectthemotor&startthestarterwithoutload,ifitwithstandsindeltathencheckthemotorfor
possibleoverloading.

Donts:
1. Neveroperatethestarterpanelbyopeningthefrontdoor.
2. DontchangethewiringofthepanelwithoutconsultingwithElectricalDepartmentoffactory.

TROUBLESHOOTING

1)MotorworksinStar.HoweveritdoesnotworkproperlyIn Checkifonlythreewiresarebeingterminatedinterminalbox
Deltaandrefusestotakeload. ofmotor.Sixwiresshouldbeconnectedtostarter.Ifshorting
linksarepresenttheyshouldberemoved.
2)MotorstartswithdifficultyinStarortripswhenadditional ReducetimedelayfromStartoDeltaincaseitiskeptvery
loadispresent, long.
3)MotorworksinStar.HoweverstopswhenDeltaconnection Possiblyduetolowsystem voltage.
comeson.
3)Eventhoughallsixwireshavebeenconnected,motorstops Deltaconnectionfrommotorisimproper
wheninDelta,

4)MotorstopswheninDelta,startertripsandfuseblows. Lowsystemvoltage.Star/Deltaconnectioninstarterwrongly
connected.


Publicationno.T264.01

CONTROLFUSES
FUSESWITCHUNIT

PHASEFAILURERELAYVSPD2

I/CCABLETOBE
TERMINATEDHERE
WITHNEUTRAL 3NOSPOWERCONTACTOR
CONNECTION

MOTORO/G
TERMINAL THERMALOVERLOADRELAY

FULLYAUTOMATICSTARDELTASTARTER INSIDEVIEW