Professional Documents
Culture Documents
ON
OIL & NATURAL GAS CORPORATION
GAS PROCESSING PLANT
HAZIRA, SURAT (GUJARAT)
BY
ARPIT DIXIT
B.TECH (ELECTRICAL ENGINEERING) 2013-17
NIT, SRINAGAR
10/12/2015 - 08/01/2016
AKNOWLEDGEMENT
I wish to thank OIL AND NATURAL GAS CORPORATION LIMITED
Hazira Plant for allowing me to attend the vocational training
programme at their premises and for providing all the needful
facilities required for the completion of the entire program. I
would also like to express our sincere gratitude towards
Mr.S.V.Acharya - Chief Engineer - In-charge Training Programme
for providing us with an opportunity to undergo training
programme in ONGC Hazira Plant.
I would also like to thank our mentor Mr. ROHIT SIR AND Mr. B K
GUPTA for their continuous guidance and for enlightening us with
his vital knowledge throughout the programme. Working under
their guidance has been an honor and a fruitful learning
experience.
I express my deepest gratitude to those who have helped and
encouraged me in various ways in carrying out this training
program. I would like to extend my thanks and would like to
acknowledge the ONGC personnel for sharing their valuable
knowledge.
INTRODUCTION TO HAZIRA PLANT
In recent past the natural gas acquired an increased importance by virtue of its
usage as the substitute of coal, petrol and diesel as fuel in the industrial boilers
and furnace. This natural gas being rich in propane and butane i.e., rich in
compounds such as C3 and C4 compounds gives straight run LPG .
Some of the gas fields in India are producing sour Natural gas which are required
to be subjected to special treatment for the removal of hydrogen supplied which
is very poisonous in nature. The isolated carbon condensate are also associated
with sour natural gas which when processed can yield sour LPG which is again
undesirable for usage so this requires an additional treatment for making it sweet
(free from H2S) marketable and safe for use.
This is all what is taken care off in HGPC( Hazira Gas Processing Complex) receives
the sour natural gas in varying amount through the subsea pipeline through the
subsea reservoir. The gas is received in the gas receiving stations, called the slug
catcher where the gas and the slug(containing hydrocarbon condensate ,moisture
such as corrosion inhibitors) are separated .The gas and the condensate are
routed through different streams for their further processing .The gas stream
after the removal of H2S and moisture yield dry and sweet gas which after dew
point depression is sent through the HBJ pipeline to the different receiving
stations. Where as the condensate after processing yields LPG and another
product called NGL.(Naphtha) which in turn produces kerosene and
ARN(Aromatic Rich Naphtha).
To carry out all these operation the major units which are installed in HGPC area
as ;
1. Gas Terminal .
2. Gas Sweetening Unit.
3.Gas Dehydration Unit.
4.Due Point Depression.
5.Sulphur Recovery Unit.
6.Condensate Fractionation Unit.
7.LPG recovery.
8.Kerosene Recovery Unit.
Hazira plant is self contained for all the utilities and offsite facilities such as
Cogeneration power, steam cycles water system, air system , inert gas system,
effluent treatment plants, product storage and dispatch etc. required for safe and
smooth facilities.
DEWPOINT DEPRESSION :
The dehydrated gas from GDU trains first passes through gas-gas exchanger and
cooled to about 15-degree. This gas is further cooled to about 5-degree . In a
chiller with the help of propane refrigerant in closed circulation cycle. The chilling
temp. Control valve, which regulates the gas flow through chiller and operates at
a present temp. value in automatic mode. The cooled gas condensate at 5-degree.
goes to a filter separator where the liquid and gases are separated the
condensate is pumped to LPG plant surge drum(for condensate feed to
distillation column). The cooled gas from the top passes through gas-gas
exchangers where the chillness of the gas is exchanged with the incoming gas
from GDU. The gas then flows out to Gas Authority OF India (GAIL) for
transportation of sweet natural gas to Hazira-Bijapur-Jagdishpur.
Like any electric motor, a 3-phase induction motor has a stator and a rotor. The
stator carries a 3-phase winding (called stator winding) while the rotor carries a
short-circuited winding (called rotor winding). Only the stator winding is fed
from 3-phase supply. The rotor winding derives its voltage and power from the
externally energized stator winding through electromagnetic induction and
hence the name. The induction motor may be considered to be a transformer
with a rotating secondary and it can, therefore, be described as a transformer
type
AC machine in which electrical energy is converted into mechanical
energy.
Advantages
-
Construction
A 3-phase induction motor has two main parts (i) stator and (ii) rotor. The rotor
is separated from the stator by a small air-gap which ranges from 0.4 mm to 4
mm, depending on the power of the motor. The parts are as follows :
1. Stator
2. Rotor
The rotor, mounted on a shaft, is a hollow laminated core having slots on its
outer periphery. The winding placed in these slots (called rotor winding) may be
one of the following two types:
(i) Squirrel cage type
(ii) Wound type
WOUND ROTOR
Types of atmosphere :
Open
Dusty or closed
Gaseous/hazardous
Knowledge of atmosphere helps in correct selection of motor i.e. Weather proof
type, totally enclosed type, drip proof type or screen protected etc.
Duty cycle Rating (S1 to S7): It gives the measure and quick insight about
the operational time , characteristics of sudden or continuous loads being
attached to the shaft and lastly whether the motor will be operated with
normal start and stop calibrations or erratic start and stops.
1. Voltage
1. Undervoltage
2. Overvoltage
3. Unbalance in 3-phase
4. Single phasing
5. Voltage surges
2. Frequency
1. Low frequency
2. High frequency
3. Environmental conditions
4. Mechanical problems
1. Seized bearings
2. Incorrect alignment/foundation levelling
3. Incorrect fixing of coupling
4. High vibration mounting
5. External shock due to load
5. Condition at location
1. Poor ventilation
2. Dirt accumulation
3. Exposure to direct sunlight
All the motors encounter few or several of these abnormalities during the course
of their service lives. Consideration of listed abnormal conditions at design stage
greatly helps to minimize the effects of abnormal conditions to maintain a
consistent performance.
TROUBLESHOOTING:
ROTOR BAR CRACKS: cracked rotor bar develop more severe high
resistance connections .These high resistance connections require the
current to increase in the nearby bars to supply the torque required to start
up and operation of the motor. During the start up very high temperature is
developed around the crack or open bar causing potential damage to rotor
bar and stator insulation.
GROWLER TESTING is the most common method to analyse the rotor bars
of a SCIM .growler is a coil wrapped around a metal core with AC power
applied to the coil. The coil is placed next to the rotor .The magnetic field
generated by the coil induces a current In the rotor bar. A piece of this
metal is placed on the top of the rotor bar. If the bar is broken the
alternating voltage at the location of the break will cause the thin piece of
metal to vibrate.
VOLTAGE TESTING METHOD : approximately 25 percent of the operating
voltage is fed across a single phase of three phase motor. An ammeter is
placed in line with test circuit to indicate any current fluctuation while
turning the rotor manually . A broken rotor bar will cause an increase in the
stator winding impedance as it passes under the single energized phase.
This will decrease in the current seen on the ammeter for each rotation.A
fluctuation of current of >5-10% in the current is generally considered
unacceptable.
ROTOR PROPOSITY: This is generally more common in cast rotor.it causes
imbalance In rotor fields which will develop into high vibration resulting
into bearing damage. Un-identified and un-corrected rotor will continue to
cause bearing failure over and over again.
ROTATION : Mostly the motors used are bi directional however ensure that
rotation is in conformity with the directional arrow marks shown on the
name plate or as required by driven equipment.
BEARING TEMPERATURE RISE AND SLEEVING: Bearing temperature should
be carefully monitored .If the temperature rise is excessive a thorough
investigation should be made before it is operated again. As detectors are
placed on the shaft of the rotor give the measure of the bearing
temperature which should be within the permissible limits and when the
rate of temperature rise is less than 1 degree per half an hour the bearing
temperature is considered to be stabilized. And if it exceeds 95 degrees the
motor should be stopped immediately.
Moisture protection is very important to be maintained by means of
external and internal heaters such that the temperature of motor is
maintained about 3 degree above dew point.
Any abnormal noise or vibration should be noted immediately with the
detectors and corrected accordingly. Increased vibration ca be indicative of
a change in balance due to mechanical failure of rotor part,stator winding
problem or a change in motor alignment
CONDITION MONITORING
Rolling element bearings are critical components in induction motors and
monitoring their condition is important to avoid failures. Several condition
monitoring techniques for the bearings are available. Out of these, stator current
monitoring is a relatively new technique. Vibration, stator current . a common
mode of failure of an induction motor is the bearing failure followed by stator
winding and rotor bar failures. The bearing failure increases the rotational friction
of the rotor. Even under normal operating conditions of balanced load and good
alignment, fatigue failure begins with small fissures, located below the surfaces of
the raceway and rolling elements, which gradually propagate to the surface
generating detectable vibrations and increasing noise levels. Continued stressing
causes the fragments of the material to break loose producing localized fatigue
phenomena known as flaking or spalling. Electric pitting or cracks due to excessive
shock loading are common in induction machines when used for heavy loads.
The widespread application of rolling element bearings in both industry and
commercial life require advanced technologies to efficiently and effectively
monitor their health status. There are many condition monitoring methods used
for detection and diagnosis of rolling bearings.
In fact, large electrical machine systems are often equipped with mechanical
sensors, which are primarily vibration sensors such as proximity probes. However,
these are delicate and expensive. Various researchers have suggested that stator
current monitoring can provide the same indications without requiring access to
the motor. This technique utilises results of spectral analysis of the stator current
or supply current of an induction motor for the diagnosis [1].A detailed review of
different vibration and acoustic methods, such as vibration measurements in time
and frequency domains, sound measurement, the SPM and the AE technique for
condition monitoring of rolling bearings .
AE is the phenomena of transient elastic wave generation due to a rapid release
of strain energy caused by structural alteration in a solid material under
mechanical or thermal stresses. Generation and propagation of cracks are among
the primary sources of AE in metals. AE transducers are designed to detect the
very high frequency (450 kHz) stress waves that are generated when cracks
extend under load. The most commonly measured AE parameters are peak
amplitude, counts and events of the signal. Counts involve counting the number
of times the amplitude exceeds a preset voltage level in a given time and gives a
simple number characteristic of the signal. An event consists of a group of counts
and signifies a transient wave. The shock pulses caused by the impacts in the
bearings initiate damped oscillations in the transducer at its resonant frequency.
Measurement of the maximum value of the damped transient gives an indication
of the condition of rolling bearings. Low-frequency vibrations in the machine,
generated by sources other than rolling bearings, are electronically filtered out.
The maxim normalized shock value is a measure of the bearing condition. Shock
pulse meters are simple to use so that semiskilled personnel can operate them.
They give a single value indicating the condition of the bearing straightaway,
Instrumentation
Vibrations were measured with the help of a piezoelectric accelerometer Bruel
and Kjaer (B&K) type 4366having un damped natural frequency of 39 kHz. The
output of the accelerometer was fed to the B&K charge amplifier 2635 connected
to Ono Sokki CF 3200 portable fast Fourier transform analyzer. The schematic
diagram of the current sensor(working on Hall effect) in series with motor supply
line
The Hall element located in the air gap of the magnetic circuit converts the
magnetic field generated by the primary current into a proportional Hall voltage.
The magnetic field produced by the primary current generates a highly linear
magnetic flux in the air gap of the magnetic circuit, which in turn induces a
proportional Hall voltage in the Hall element. The voltage is then electronically
amplified resulting in an output voltage that is highly proportional to the primary
current up to the final value of the measuring range. The current sensor is
supplied with 715V from the power supply unit for 15min before taking the
measurements.
Measurement conditions
The measurements were carried out from no load to full load (27 kg) for the
induction motor bearing with an increment of 5 kg. The motor was run at
constant speed of 1440 rpm. Three healthy bearings were used to check the
repeatability of the measurements. Inner race defect was simulated by a circular
hole of diameter varying from 250 to 1500 mm in the outer race of the same
bearing (in steps of 250 mm successively after each measurement) by spark
erosion technique.
RESULTS AND DISCUSSIONS
CO GENERATION PLANT
What is co generation ??
By definition, in lay mans language cogeneration is on site generation of 2
quantities and the most prevalent example of co-gen is generation of electric
power and heat as a byproduct simultaneously which is used up efficiently for
various processes going on in the hazira plant.
ROLE OF CO GENERATION PLANT
The role of co generation plant is to meet the energy requirements in the form of
electricity and steam. For meeting electricity needs ,power supply has been taken
from Gujarat electricity board at 66kv through 2 feeders each capable of meeting
the full load requirement .The importance of natural gas for petrochemical
industries ,fertilizers, and LPG for domestic cooking was for seen at that time and
it was this future outlook which led to this conception of own power generation
through CPP as reliable source of power .Since steam was one of the inputs used
for the processing of the gas idea of having 2 Gas Turbine based CPPs units along
with Heat Recovery Steam Generators was conceived and implemented .
With increase of processing capacity from 28 million cm^3 to 42 million cm^3
both steam as well as power demands went up and the third GT+ HRSG was
erected and commissioned .This has further added to the reliability of power to
the complex.
OPERATIONAL PHILOSOPHY:
Initially the system used to be connected with the grid till third GTG unit was
commissioned .But such a system had a serious draw back that our system too
used to collapse along with Gujarat electricity board (GEB) in case of grid faults
.After commissioning of third GTG ,our reliability has gone up and we started to
run the system in isolated mode ie. taking power from GEB when it was
absolutely necessary .We even reduced our contract demand from 8 MVA saving
cost on demand charges .Subsequently, 66kv protection systems was upgraded
using state of the art numeric control relays which operated within few cycles.
After this, the system used to isolate itself from the grid in case of grid faults
without affecting the operation of the plant .This gave us a shot in the arm and
we even started exporting surplus power to GEB . Today we are always connected
to the grid and exchanging power with the grid .A surplus power of 15.7 MVA is
being wheeled to sister ONGC plants thereby saving 4.5 crore rupees to the
corporation which would otherwise have been paid to GEB by mehsana asset
towards purchase of power. Still surplus power left is sold to GEB at a cost of rs
2.190 per unit as per their requirement.
Their is even a load shedding scheme which operates and sheds the load beyond
16 MW when either only one source is available or there is a severe fault leading
to predetermined high level of rate of change of frequency (df/dt). Such ascheme
saves the plant from complete black out situation, a thing of the past.
ACCESSORY GEAR : The accessory gear is used to connect the turbine shaft
at starting device to compressor end through hydraulic torque convertor
which is used when the GT is initially in the off mode and we need some
high initial torque to start it which is done with the help of synchronous
motors and gear box.
AIR INLET SYSTEM: inlet air enters the compartment and flows in the duct
with built in acoustical silencers and trash screen , to the inlet plenum
before entering the turbine compressor.
TURBINE: In the turbine section, the hot gases are converted into shaft
horse power .It is in two stages . In the first stage (high pressure) wheel and
the second (low pressure) wheel are bolted together to make up a single
unit. The first stage and the second stage nozzles direct the flow of hot
gases on the turbine blades .
PARALLELED WITH THE GRID : Here the GTs need to be set in the droop
mode of operation and they are connected to each other in parallel
such that the utility grid will determine the generator frequency ,speed
and voltage .In cogeneration and in industries the GT can not change up
its frequency but can slightly vary their terminal voltage . Its features
are as follows :
1. more/less fuel will raise /lower the generator active power.
2. more/less excitation will raise/lower the generator reactive
power.
3. Grid determines the frequency ,speed and voltage .
4. The difference between the total plant load and the generator
output power will be imported or exported .
5. engine fuel control options : droop speed control only.
6. excitation current control options: droop voltage control, VAR
control, PF control .
7. control room is responsible to keep the imported /exported
power or power factor constant.
PARALLELED WITHOUT THE GRID : HERE ,all the GTs are connected to
each other but not with the grid ,so one GT should be in isochronous
mode and (it will take care of the load variations and will maintain the
frequency at 50 Hz) and other GTs need to be in the droop mode .Its
features as follows :
1. more/less fuel will raise/lower the generator active power and the bus
frequency.
2. more/less excitation will raise /lower the generator reactive power and
the bus voltage .
3. The total plant load determines the sum of the power of all generators.
4. engine fuel control option: droop speed control .
5. power management system keeps the bus frequency and voltage
constant ,while sharing the load .
BOILERS:
KTI
1986 BABCOK WATER HP 20T/HR 36.7 SATURATED
HITACHI,JAPAN TUBE
LP 105T/HR 8.2 SATURATED
From the table it is very evident that there are 5 water tube boilers and 3 gas fire
boilers. The total high pressure steam capacity is 107T/HR ,total medium pressure
steam capacity is 110T/HRS and total low pressure steam capacity is 315T/HRS.
Out of the three HRSGs , HRSG3 is designed for only HP steam but it has a
provision of dumping from HP steam to MP steam and LP steam .
OPERATION OF HRSG:
Heat recovery and Steam Generators also known as HRSGs can be either
operated in GT+S mode , FD mode or only GT mode .GT+S mode is selected
when heat given out as an exhaust by GT is not enough to generate desired
quantity of steam at desired pressure .FD mode operation is selected only
when GT mode is not available due to maintenance or shut down. Diverter
damper diverts the GT exhaust to the boiler for GT+s mode or to the
atmosphere for open cycle operation. For safety of boiler protections of low
drum level, loss of flame, drum level to D/D close etc have been provided.
These protections are checked before taking the boiler into operation .
controls are done through PLC.
POWER DISTRIBUTION: Power from all the 3 GTs and grid is fed into
the main 11kv substation-1 . From substation-1 power is distributed to 18
different substations. Power is consumed at 11 kv, 6.6 kv and 415 volts
depending on the capacity of the drive . the total production of all the GTs is
60 Mega Watts out of which 32 mega watts is consumed in the plant itself in
feeding the different processing sections and the rest 28 mega watts of power
is exported to the Gujarat Electricity Board and to the sister ongc plants
depending upon the requirement. The distribution of power within the various
sub stations will be discussed in the sub stations category .
SUBSTATION
Presently ,ONGC Hazira plant consists of 18 substations from SS-1 to SS-18 with
substation 17 under the process of reconstruction . The power distribution to
various process units depending upon the operating voltage of the equipments
is done through these substations through adequate protections with the help
of power fuses , circuit breakers and protective relays for the various
abnormalities that can sprout up under the process of continuous operation
and environmental disturbances. As per the single line diagram it is evident
that power after generation from the co generation plant from the 5 sources
(3 GTs and 2 supply lines from GEBs ) where power from GEB is provided
through a 66kv bus line which is stepped down to 11kv with the help of step
down transformers TR-101 and TR-102 , is sent to firstly at substation 1 from
where further distribution for reduced voltages of 6.6kv and 415v bus lines is
supplied through transformers that reduce it from 11 to various ranges of
voltages for operating the equipments .Depending upon the voltages , not all
the substations have same voltage bus line feeding the loads connected to
them instead substations 2, 3,4 ,16,18 have 6.6kv bus bars , substation 14 has
both 11kv and 6.6kv bus bars and all of them come under the category of HT
substations .LT substations include 5,6,7,8,9,10,11,12,13,15,17(reconstruction)
as they have bus bars at working voltage of 415volts . These transformers are
known as incomers and feed the bus line of the corresponding substation
which is not a single line instead consists of 2 or 3 parts joined together with
the help of bus couplers which help to shut down particular section of loads
connected to the bus and even help to supply the part of the loads connected
to the failed incomer and even provides facility for the maintenance of a
particular part of the bus and prevents disruptions in continuous operation of
the plant
Substations have varying installations of breakers (HT or LT) , bus couplers ,
direct online starters , battery chargers , relays , fuses and contactors for the
efficient supply of power from source to the equipments and continuous
supervision and monitoring of the various equipments installed in the field as
in case of any abnormalities the relays attached to the motors send a signal to
the control room from where a signal is sent to the sub station which cut off
the supply to that very equipment until the repair work has been done .Hence
sub stations in ONGC Hazira plant gives a deep insight in the switchgear and
protection section of the power system analysis and implementation.
A direct on line (DOL) or across the line starter applies the full line voltage to the
motor terminals, the starters or cubicle locations, can usually be found on an ELO
drawing. This is the simplest type of motor starter. A DOL motor starter also
contains protection devices, and in some cases, condition monitoring. Smaller
sizes of direct on-line starters are manually operated; larger sizes use an
electromechanical contactor (relay) to switch the motor circuit. Solid-state direct
on line starters also exist. A direct on line starter can be used if the high inrush
current of the motor does not cause excessive voltage drop in the supply circuit.
The maximum size of a motor allowed on a direct on line starter may be limited
by the supply utility for this reason. For example, a utility may require rural
customers to use reduced-voltage starters for motors larger than 10 kW.
DOL starting is sometimes used to start small water pumps, compressors, fans
and conveyor belts. In the case of an asynchronous motor, such as the 3-phase
squirrel-cage motor, the motor will draw a high starting current until it has run up
to full speed. This starting current is typically 6-7 times greater than the full load
current. To reduce the inrush current, larger motors will have reduced-voltage
starters or variable speed drives in order to minimize voltage dips to the power
supply. A starter contains two DOL circuitsone for clockwise operation and the
other for reversing starter can connect the motor for rotation in either direction.
Such a counter-clockwise operation, with mechanical and electrical interlocks to
prevent simultaneous closure. For three phase motors, this is achieved by
swapping the wires connecting any two phases. Single phase AC motors and
direct-current motors require additional devices for reversing rotation.
A DOL can be used if the high inrush current of the motor does not cause does not
cause excessive voltage drop in the supply circuit . The maximum size of the
motor allowed on a DOL starter may be limited by the supply utility for this
reason. for example, a utility may require rural customers to use reduced voltage
starters for motors larger than 10kw .
It is generally used only for small motors otherwise it needs more protection
devices to be incorporated due to the high values of the operating voltages
involved. Contactors and bi metallic relays are two main components of a DOL
starter. In contactor there is an electromagnet where a current is passed through
the coil around the electromagnet such that it gets magnetized and the plunger is
pulled and the contacts are restored . Now to quench the spark produced due to
contact a long path is provided so that the arc length is increased and the spark
gets quenched . In BMR two different metals having different heat capacities are
used .So at same temperature their expansions are different and hence works as a
relay for the DOL.
CONTACTOR :
CONSTRUCTION:
A contactor has three components. The contacts are the current carrying part
of the contactor. This includes power contacts, auxiliary contacts, and contact
springs. The electromagnet (or "coil") provides the driving force to close the
contacts. The enclosure is a frame housing the contact and the electromagnet.
Enclosures are made of insulating materials like Bakelite, Nylon 6, and
thermosetting plastics to protect and insulate the contacts and to provide some
measure of protection against personnel touching the contacts. Open-frame
contactors may have a further enclosure to protect against dust, oil, explosion
hazards and weather.
Magnetic blowouts use blowout coils to lengthen and move the electric arc. These
are especially useful in DC power circuits. AC arcs have periods of low current,
during which the arc can be extinguished with relative ease, but DC arcs have
continuous high current, so blowing them out requires the arc to be stretched
further than an AC arc of the same current. The magnetic blowouts in the
pictured Albright contactor (which is designed for DC currents) more than double
the current it can break, increasing it from 600 A to 1,500 A.
A basic contactor will have a coil input (which may be driven by either an AC or DC
supply depending on the contactor design). The coil may be energized at the
same voltage as a motor the contactor is controlling, or may be separately
controlled with a lower coil voltage better suited to control by programmable
controllers and lower-voltage pilot devices. Certain contactors have series coils
connected in the motor circuit; these are used, for example, for automatic
acceleration control, where the next stage of resistance is not cut out until the
motor current has dropped.
OPERATING PRINCIPLE:
Unlike general-purpose relays, contactors are designed to be directly connected
to high-current load devices. Relays tend to be of lower capacity and are usually
designed for both normally closed and normally open applications. Devices
switching more than 15 amperes or in circuits rated more than a few kilowatts are
usually called contactors. Apart from optional auxiliary low current contacts,
contactors are almost exclusively fitted with normally open ("form A") contacts.
Unlike relays, contactors are designed with features to control and suppress the
arc produced when interrupting heavy motor currents.
Because arcing and consequent damage occurs just as the contacts are opening or
closing, contactors are designed to open and close very rapidly; there is often an
internal tipping point mechanism to ensure rapid action.
Rapid closing can, however, lead to increase contact bounce which causes
additional unwanted open-close cycles. One solution is to have bifurcated
contacts to minimize contact bounce; two contacts designed to close
simultaneously, but bounce at different times so the circuit will not be briefly
disconnected and cause an arc.
A slight variant has multiple contacts designed to engage in rapid succession. The
first to make contact and last to break will experience the greatest contact wear
and will form a high-resistance connection that would cause excessive heating
inside the contactor. However, in doing so, it will protect the primary contact
from arcing, so a low contact resistance will be established a millisecond later.
Another technique for improving the life of contactors is contact wipe; the
contacts move past each other after initial contact in order to wipe off any
contamination.
ARC SUPPRESSION:
Without adequate contact protection, the occurrence of electric current arcing
causes significant degradation of the contacts, which suffer significant damage.
An electrical arc occurs between the two contact points (electrodes) when they
transition from a closed to an open (break arc) or from an open to a closed (make
arc). The break arc is typically more energetic and thus more destructive.
The heat developed by the resulting electrical arc is very high, ultimately causing
the metal on the contact to migrate with the current. The extremely high
temperature of the arc (tens of thousands of degrees Celsius) cracks the
surrounding gas molecules creating ozone, carbon monoxide, and other
compounds. The arc energy slowly destroys the contact metal, causing some
material to escape into the air as fine particulate matter. This activity causes the
material in the contacts to degrade over time, ultimately resulting in device
failure. For example, a properly applied contactor will have a life span of 10,000
to 100,000 operations when run under power; which is significantly less than the
mechanical (non-powered) life of the same device which can be in excess of 20
million operations.
Most motor control contactors at low voltages (600 volts and less) are air break
contactors; air at atmospheric pressure surrounds the contacts and extinguishes
the arc when interrupting the circuit. Modern medium-voltage AC motor
controllers use vacuum contactors. High voltage AC contactors (greater than 1000
volts) may use vacuum or an inert gas around the contacts. High Voltage DC
contactors (greater than 600V) still rely on air within specially designed arc-chutes
to break the arc energy. High-voltage electric locomotives may be isolated from
their overhead supply by roof-mounted circuit breakers actuated by compressed
air; the same air supply may be used to "blow out" any arc that forms.
BUS COUPLER :
A bus coupler is a device meant to help users switch between two or more
computer buses on the fly. Unlike other bus switching methods, in which the
computers must be shut off to avoid electrical problems, a bus coupler allows
users to change buses without going through this process. There are two main
types of bus couplers, in-line and box; while each can be used in most systems, all
are meant for slightly different applications. This device is useful for networks, or
computers with multiple buses, because users sometimes will need different
buses for processing certain problems or functions.
The primary task of a bus coupler is to help users switch between different buses
on a network. This task normally takes a relatively long time, because the power
has to be turned off, the other bus has to be confirmed as safe, the computer has
to start back up and the buses have to power up. With a coupler, this switch is
made within seconds, without having to go through all the other steps.
When a bus coupler is used, it also makes bus switching safer. If the bus is
improperly switched, even if users go through the longer process, then there is a
chance that an arc will be made and the resulting electricity can damage the
systems or injure users. A coupler is able to balance this, and the bus switch
occurs without any change in power.
Bus couplers come in two builds: in-line and box. Both bus coupler types are
similarly connected to buses, and they can be used with most systems. The
difference is that the box type tends to be heavier and bigger, but make it simpler
to find problems with the electricity; in-line couplers are lighter but tend to offer
fewer connections and cannot withstand much force without breaking. Unless
weight or size is an issue, there should be no problems using one coupler in place
of another.
Aside from making bus switching safer, a bus coupler helps users function quickly
with networks. One bus system usually will have different hardware
configurations that make it better for one function over another, and being able
to switch between different configurations quickly can help increase processing
time. Networks normally will only need this device or computers set up with
several bus configurations, because consumer computers commonly have just
one bus configuration, making this device useless with them.
FUSES :
In electronics and electrical engineering, a fuse is a type of low resistance resistor
that acts as a sacrificial device to provide overcurrent protection, of either the
load or source circuit. It s essential component is a metal wire or strip that melts
when too much current flows through it, interrupting the circuit that it connects.
Short circuits, overloading, mismatched loads, or device failure are the prime
reasons for excessive current. Fuses can be alternative to circuit breakers.
CONSTRUCTION OF FUSES :
The fuse element is made of zinc, copper, silver, aluminum or alloys to provide
stable and predictable characteristics. The fuse ideally would carry its rated
current indefinitely, and melt quickly on a small excess. The element must not be
damaged by minor harmless surges of current, and must not oxidize or change its
behavior after possibly years of service.
The fuse elements may be shaped to increase heating effect. In large fuses,
current may be divided between multiple strips of metal. A dual-element fuse
may contain a metal strip that melts instantly on a short-circuit, and also contain a
low-melting solder joint that responds to long-term overload of low values
compared to a short-circuit. Fuse elements may be supported by steel or
nichrome wires, so that no strain is placed on the element, but a spring may be
included to increase the speed of parting of the element fragments.
The melting point and specific resistance of different metals used for fuse wire
1. Fuse
2. Fuse wire
3. Minimum Fusing Current : It is minimum value of current due to
which fuse melts.
4. Current Rating of Fuse : It is maximum value of current due to which
fuse does not get melt.
5. Fusing Factor : This is the ratio of minimum fusing current and current
rating of fuse.
6. Therefore, fusing factor = Minimum fusing current / current rating of
fuse.
7. The value of fusing factor is always more than 1.
8. Prospective Current in Fuse: Before melting, the fuse element has to
carry the short circuit current through it. The prospective current is
defined as the value of current which would flow through the fuse
immediately after a short circuit occurs in the network.
9. Melting Time of Fuse or Pre-arcing Time of Fuse: This is the time taken
by an fuse wire to be broken by melting. It is counted from the instant,
the over current starts to flow through fuse, to the instant when fuse
wire is just broken by melting.
10.Arcing Time of Fuse: After breaking of fuse wire there will be an arcing
between both melted tips of the wire which will be extinguished at the
current zero. The time accounted from the instant of arc initiated to
the instant of arc being extinguished is known as arcing time of fuse.
11. Operating Time of Fuse : When ever over rated current starts to flow
through a fuse wire, it takes a time to be melted and disconnected, and
just after that the arcing stars between the melted tips of the fuse wire,
which is finally extinguished. The operating time of fuse is the time gap
between the instant when the over rated current just starts to flow
through the fuse and the instant when the arc in fuse finally
extinguished. That means operating time of fuse = melting time + arcing
time of fuse.
Current carrying capacity of a fuse wire depends upon numbers of factors like,
what material used for it, what are the dimension of it, i.e. diameter and length,
size and shape of terminals used to connect it, and the surrounding.
FUSE LAW :
Fuse law determines the current carrying capacity of a fuse wire. The law can be
established in the following way. At steady state condition that is when fuse carry
normal current without increasing its temperature to the melting limit. That
means at this steady state condition, heat generated due to current through fuse
wire is equal to heat dissipated from it.
HIGH RUPTURING CAPACITY (HRC) FUSES :
high rupturing capacity (HRC) fuses are short-circuit current limiting with low
rated minimum breaking current ,low switching over voltages . HRC high voltage
fuses are used to protect transformers, capacitor banks, cable networks and
overhead lines against short-circuits. ABB HRC HV fuses protect switchgears from
thermal and electromagnetic effects of heavy short-circuit currents by limiting the
peak current values (cut-off characteristics) and interrupting the currents in
several milliseconds. HRC fuse or high rupturing capacity fuse- In that type of
fuse, the fuse wire or element can carry short circuit heavy current for a known
time period. During this time if the fault is removed, then it does not blow off.
The enclosure of HRC fuse is either of glass or some other chemical compound.
This enclosure is fully air tight to avoid the effect of atmosphere on the fuse
materials. The ceramic enclosure having metal end cap at both heads, to which
fusible silver wire is welded. The space within the enclosure, surrounding the fuse
wire or fuse element is completely packed with a filling powder. This type of fuse
is reliable and has inverse time characteristic, that means if the fault current is
high then rupture time is less and if fault current is not so high then rupture time
is long.
CIRCUIT BREAKER :
A circuit breaker is an automatically operated electrical switch designed to
protect an electrical circuit from damage caused by overload or short circuit. Its
basic function is to detect a fault condition and interrupt current flow. Unlike a
fuse, which operates once and then must be replaced, a circuit breaker can be
reset (either manually or automatically) to resume normal operation. Circuit
breakers are made in varying sizes, from small devices that protect an individual
household appliance up to large switchgear designed to protect high voltage
circuits feeding an entire city.
OPERATION:
All circuit breaker systems have common features in their operation. Although
details vary substantially depending on the voltage class, current rating and type
of the circuit breaker.
The circuit breaker must detect a fault condition; in low voltage circuit breakers
this is usually done within the breaker enclosure. Circuit breakers for large
currents or high voltages are usually arranged with protective relay pilot devices
to sense a fault condition and to operate the trip opening mechanism. The trip
solenoid that releases the latch is usually energized by a separate battery,
although some high-voltage circuit breakers are self-contained with current
transformers, protective relays and an internal control power source.
Once a fault is detected, the circuit breaker contacts must open to interrupt the
circuit; some mechanically-stored energy (using something such as springs or
compressed air) contained within the breaker is used to separate the contacts,
although some of the energy required may be obtained from the fault current
itself. Small circuit breakers may be manually operated, larger units have
solenoids to trip the mechanism, and electric motors to restore energy to the
springs.
The circuit breaker contacts must carry the load current without excessive
heating, and must also withstand the heat of the arc produced when interrupting
(opening) the circuit. Contacts are made of copper or copper alloys, silver alloys
and other highly conductive materials. Service life of the contacts is limited by the
erosion of contact material due to arcing while interrupting the current.
Miniature and molded-case circuit breakers are usually discarded when the
contacts have worn, but power circuit breakers and high-voltage circuit breakers
have replaceable contacts.
INSTRUMENT TRANSFORMERS :
How will you measure AC currents and voltages of very high magnitude? You will
need the measuring instruments having higher range, which literally mean huge
instruments. Or there's another way, using the transformation property of AC
currents and voltages. You can transform the voltage or current down with a
transformer whose turns ratio is accurately known, then measuring the stepped
down magnitude with a normal range instrument. The original magnitude can be
determined by just multiplying the result with the transformation ratio. Such
specially constructed transformers with accurate turns ratio are called as
Instrument transformers. These instruments transformers are of two types - (i)
Current Transformers (CT) and (ii) Potential Transformers (PT).
Current Transformers (CT):
Current transformers are generally used to measure currents of high magnitude.
These transformers step down the current to be measured, so that it can be
measured with a normal range ammeter. A Current transformer has only one or
very few number of primary turns. The primary winding may be just a conductor
or a bus bar placed in a hollow core (as shown in the figure). The secondary
winding has large number turns accurately wound for a specific turns ratio. Thus
the current transformer steps up (increases) the voltage while stepping down
(lowering) the current.
Now, the secondary current is measured with the help of an AC ammeter. The
turns ratio of a transformer is NP / NS = IS / IP
BATTERY CHARGER :
A battery charger comprises of rectifier and a tapped transformer ,DC supply
required for charging is obtained from the battery charger .Along with this service
rectifier feeding the load where control DC supply is required for control system .
connect the positive terminal of the charger to positive terminal of the battery
and same for the negative. During the normal use current leaves the positive
terminal and enters through negative terminal while during the charging mode
current enters through positive terminal and leaves from negative terminal .In
generating substation , the DC auxiliary power sources is required for protecting
systems and for control systems. This supply is usually 110 v DC or 220v DC and
obtained from storage battery system.
The batteries are placed in a well ventilated battery room .The battery cells are
placed on the raised wooden rocks. The DC busses are generally supported on the
ceiling or the side walls on the epoxy insulator support .The dc busses are flat
copper sections. The connections are made by soldering by flame of gas. The bus
bars from battery rooms are brought out to DC board by means of asbestos
cement slabs. The lead acid batteries in the room should be kept on the trickle
charge by means of the battery charger kept connected to the dc bus bars.
SPECIFICATIONS OF A STEP DOWN TRANSFORMER
:
COMPONENTS OF UPS:
RECTIFIER : Rectifier represents the input stage and transforms the alternating
voltage of the power line in continuous voltage .The functions carried out by
rectifier are the following :
powering the inverter with direct supply
charging the battery automatically
MICROPROCESSOR: controls the entire system.
BATTERY: Provides the reserve energy for powering the load when there is no
power input to the UPS .For different versions it may be housed inside the UPS in
a compartment at the side or in a supplementary cabinet.
INVERTER : This is the output stage .Converts direct voltage from the rectifier or
battery into stabilized sinusoidal alternating voltage. It is always in operation and
the load connected to the output of the UPS is always powered .
BYPASS: The bypass device allows synchronized ,automatic or manual passage in
zero time of the power of the protected line load (inverter output) to unprotected
line(by-pass-line).
SWMB: Non automatic switch for maintenance .Closing SWMB and opening all
the other switches allows maintenance operations inside the unit safely while
keeping the load powered .There is no power inside the equipment .
EMI FILTERS : One filter is connected before rectifier and one after inverter . The
filter connected in rectifier does not allow high frequency components in rectifier
, other does not allow up and down fluctuations.
CONCLUSION
India is one of the fastest growing economies in the world and is all set to become
a major economic as well as technical super power of this century. The industrial
and process industries of India face stiff competition from their international
counterparts . to meet this ever growing challenge , India needs to boost its fuel
and power supplies and its effective and productive utilization .
Hazira plant at present generates approximately 60 MW of electric power ,out of
which 32 MW is consumed within the plant for the various processes to keep
going without interruption and the remaining 28 MW of power is supplied to GEB
.It also processes the sour gas recieved from south bassein gas fields to produce
LPG, Naphtha, super kerosene oil, ATF, sulphur etc. These useful fuels and
chemicals are then supplied to various industries . This plant is also strategically
placed at Surat , major industrial port near Arabian Sea. Its proximity to Bombay
High and many neighbouring industries plays a major role in making this plant key
element in development of Indian Industries.