1. PREIMENSIONAMIENTO DE MUROS
2. PREDIMENSIONAMIENTO DE LOSAS
H H = 20.00 cm
25 bw = 10.00 cm
3. DENSIDAD DE MUROS
Z 0.40
L t ZUSN U
S
1.00
1.00
Ap 56 N
RELACION
2.00
0.014
MUROS LA DIRECCION X
Ap 56
Densidad Minima de Muros Y
Ap 88.57 m2
Z 0.4
L t ZUSN U
S
1
1.2
Ap 56 N
RELACION
2
0.017
MUROS LA DIRECCION Y
Ap 56
METRADO DE CARGAS
H 20.00 cm
Area 88.57 m2
fc 210.00 Kg/cm2
fm 65.00 Kg/cm2
v'm 8.30 Kg/cm2
f'b 145.00 Kg/cm2
LOSA
PRIMER PISO
MUROS DE ALBAILERIA
LONGITUD
MUROS ESPESOR (m) AREA (m2)
EFECTIVA (m)
TABIQUES
VIGAS
COLUMNAS
Piso Tipico
TIPO No. b h L Peso
C1 CONFINAMIENTO 12 0.150 0.450 2.400 4.67
C2 CONFINAMIENTO 6 0.150 0.150 2.400 2.33
C3 CONFINAMIENTO 6 0.150 0.450 2.400 0.78
C4 0 0.000 0.000 2.400 0.00
2 piso
Piso Peso CM Peso CV CM+25%CV Peso/m2 1 piso
1 105.001 17.868 109.468 1.236
2 103.770 13.286 107.091 1.209
26.571 Tn
8.857 Tn
35.428 Tn
17.714 Tn
26.571 Tn
8.857 Tn
35.428 Tn
13.286 Tn
PISO Y SEGUNDO PISO
11.190 m2
2.400 m
51.024 Tn
PISO
1.231 Tn
0.154 Tn
2 piso
1 piso
0
0
0
0
0
ANLISIS SSMICO MODERADO
TABLA 1
TABLA 4
TABLA 4
ENTONCES:
Altura de piso
numero de pisos
Ct
hn
T
TABLAS C
TABLA 5 U
TABLA 7 R
R
NOTA: No se considero ningn factor de irregularidad
Z U C S
V P
R
Z 0.40
U 1.00
C 2.50
S 1.00
R 6.00
V 36.09
V 17%
Tn
Z 0.4
Tp 0.6
Tl 2.0
2.4
2
60
4.8
0.08
2.5
1.00
3
6 SISMO MODERADO
nsidero ningn factor de irregularidad
Z U C S
P
R
Vp
24.39 Tn
36.09 Tn
2) Distribucion del cortante basal
Piso h
2 5.2
1 2.6
P x h Ph
Peso P por nivel Px h
F V Vp
Peso/m2 #VALUE! #VALUE! #VALUE! #VALUE! Tn
0.00 0.000 #VALUE! #VALUE! #VALUE! Tn
= #VALUE! Tn
Tn
CALCULO DEL CENTRO
LONGITUD
MUROS ESPESOR (m) AREA (m2) ALTURA PESO
EFECTIVA (m)
LONGITUD
MUROS ESPESOR (m) AREA (m2) ALTURA PESO
EFECTIVA (m)
Xc 5.64 Yc 4.19
CALCULO DEL CENTRO DE MASA
CENTROIDE
PxX
EN X
5.85 46.78
5.79 10.49
1.75 4.19
9.92 24.02
PESOS . X
X
2.83 18.23
PESOS
8.23 13.42
11.04 16.36
0.00 0.00
X
0.00 0.00
PESOS
0.08 0.21
4.47 5.35
4.62 12.96
5.77 6.91
7.12 8.04
11.62 20.67
4.62 12.96 X = 5.63
8.21 23.02
11.62 25.04
0.08 0.17
248.80
CENTROIDE
PxY
EN Y
0.08
1.58
4.03
0.64
2.86
9.65 Y
PESOS . Y
4.03
8.08
8.08
9.76
52.04
13.17
PESOS
8.08 11.97
0.00 0.00
0.00 0.00
2.14 6.00
3.23 3.87
0.83 0.94
2.88 5.12 Y = 4.01
2.05 5.75
2.05 5.75
6.50 14.00
6.50 14.00
6.50 14.00
7.40 7.59
177.13
CENTROIDE
PxX
EN X
0.00 0.00
126.90
CENTROIDE
PxX
PESOS . Y
EN Y
Y
PESOS
5.78 31.88
Y
PESOS . Y
PESOS
1.70 7.46
6.84 28.17
6.13 32.98
2.88 0.00
2.03 10.82 Y = 4.501
0.00 0.00
111.32
CENTRO DE RIGIDECES
CENTRO DE RIGIDECES
m t
K 3
h h
4 3
L L
CONSIDERAMOS TODOS LOS MUROS COMO VOLADOS
H 2.5
MURO L (m) t (m) L*t (m2) K Y K*Y
X1 11.69 0.14 1.64 66843.21 0.08 5347.46
X2 2.65 0.14 0.37 7352.15 1.58 11616.40
X3 3.50 0.14 0.49 12636.84 4.03 50926.47
X4 3.54 0.14 0.50 12898.61 4.03 51981.40
X5 5.65 0.24 1.36 46596.13 8.08 376496.74
X6 1.43 0.24 0.34 2930.34 8.08 23677.15
X7 1.30 0.24 0.31 2279.56 8.08 18418.85
X8 0.00 0.14 0.00 0.00 0.00 0.00
X9 0.00 0.14 0.00 0.00 0.00 0.00
TOTAL 5.00 151536.85 538464.47
Ycr = 3.55
Xcr = 6.63
DISTRIBUCION DEL CORTANTE POR DESPLAZAMIENTO
Ki
VD V acumulado por piso
Ki
PRIMER PISO
Vacumulado por piso = 36.09
SEGUNDO PISO
Vacumulado por piso = 24.39
PRIMER PISO
MURO L (m) t (m) L*t (m2) K Vd
X1 11.69 0.14 1.64 66843.21 15.92
X2 2.65 0.14 0.37 7352.15 1.75
X3 3.50 0.14 0.49 12636.84 3.01
X4 3.54 0.14 0.50 12898.61 3.07
X5 5.65 0.24 1.36 46596.13 11.10
X6 1.43 0.24 0.34 2930.34 0.70
X7 1.30 0.24 0.31 2279.56 0.54
X8 0.00 0.14 0.00 0.00 0.00
X9 0.00 0.14 0.00 0.00 0.00
TOTAL 5.00 151536.85 36.09
SEGUNDO PISO
MURO L (m) t (m) L*t (m2) K Vd
X1 11.69 0.14 1.64 66843.21 10.76
X2 2.65 0.14 0.37 7352.15 1.18
X3 3.50 0.14 0.49 12636.84 2.03
X4 3.54 0.14 0.50 12898.61 2.08
X5 5.65 0.24 1.36 46596.13 7.50
X6 1.43 0.24 0.34 2930.34 0.47
X7 1.30 0.24 0.31 2279.56 0.37
X8 0.00 0.14 0.00 0.00 0.00
X9 0.00 0.14 0.00 0.00 0.00
TOTAL 5.00 151536.85 24.39
1. EXCENTRICIDADES
Exc. Terica
ex Xcr Xcm 1
2
6.626
6.626
3.553
3.553
5.638
5.638
4.185
4.185
0.988
0.988
ey Ycr Ycm
Exc. Accidental
Accidental Piso LX LY exacc
exacc 0.05 L 1
2
11.700
11.700
9.560
9.560
0.478
0.478
eyacc 0.05 L
Excentricidad X Excentricidad Y
ex + ex acc ex + ex acc (caso1)
(caso1) ex - ex acc (caso2)
ex - ex acc (caso2)
2. MOMENTOS TORSORES
Piso e Vp MT(tn.m)
1
2
1.466
1.466
36.093
24.395
52.910
35.761
MT Pe
3. CORTANTE POR TORSION
PRIMER PISO
Kd
VT M
2
(K d )
MURO K Y Ycr d Kxd Kd^2
X1 66843.21 0.08 3.553 -3.47 -232170.32 806410.33
X2 7352.15 1.58 3.553 -1.97 -14508.41 28630.28
X3 12636.84 4.03 3.553 0.48 6023.27 2870.95
X4 12898.61 4.03 3.553 0.48 6148.04 2930.42
X5 46596.13 8.08 3.553 4.53 210924.07 954778.02
X6 2930.34 8.08 3.553 4.53 13264.60 60044.13
X7 2279.56 8.08 3.553 4.53 10318.76 46709.34
X8 0.00 0.00 3.553 -3.55 0.00 0.00
X9 0.00 0.00 3.553 -3.55 0.00 0.00
MURO K X Xcr d Kxd Kd^2
Y1 16629.49 0.08 6.626 6.55 108940.41 713672.78
Y2 2853.11 4.47 6.626 2.16 6151.41 13262.68
Y3 2464.96 4.62 6.626 2.01 4944.81 9919.48
Y4 7064.56 5.77 6.626 0.86 6047.53 5176.92
Y5 16629.49 7.12 6.626 -0.49 -8214.33 4057.56
Y6 16629.49 11.62 6.626 -4.99 -83047.02 414733.63
Y7 10386.76 4.62 6.626 2.01 20836.24 41798.30
Y8 10386.76 8.21 6.626 -1.58 -16452.23 26059.70
Y9 10386.76 11.62 6.626 -4.99 -51871.09 259042.21
Y10 1934.65 0.08 6.626 6.55 12664.26 82900.76
Kd
SEGUNDO PISO
VT M
(K d 2 )
MURO K Y Ycr d Kxd Kd^2
X1 66843.21 0.08 3.553 -3.47 -232170.32 806410.33
X2 7352.15 1.58 3.553 -1.97 -14508.41 28630.28
X3 12636.84 4.03 3.553 0.48 6023.27 2870.95
X4 12898.61 4.03 3.553 0.48 6148.04 2930.42
X5 46596.13 8.08 3.553 4.53 210924.07 954778.02
X6 2930.34 8.08 3.553 4.53 13264.60 60044.13
X7 2279.56 8.08 3.553 4.53 10318.76 46709.34
X8 0.00 0.00 3.553 -3.55 0.00 0.00
X9 0.00 0.00 3.553 -3.55 0.00 0.00
Exc. Terica
ey
-0.632
-0.632
Exc. Accidental
eyacc
0.585
0.585
Excentricidad Y
+ ex acc (caso1)
- ex acc (caso2)
Vt
0.00
0.00
0.09
0.09
3.21
0.20
0.16
0.00
0.00
Vt
1.66
0.09
0.08
0.09
0.00
0.00
0.32
0.00
0.00
0.19
Vt
0.00
0.00
0.06
0.06
2.17
0.14
0.11
0.00
0.00
Vt
1.12
0.06
0.05
0.06
0.00
0.00
0.21
0.00
0.00
0.13
10. METRADO DE CARGAS PARA MUROS
10.1 METRADO DE CARGAS PRIMER NIVEL
CARGA MUERTA
LOSA+Pterminado TABIQUES TABIQUES AZOTEA
0.40 1.90 Peso P.albanileria (Ton/cm3) =
Peso (Ton)
L (m) Niveles A (m)H (m)L (m) Niveles (Ton) A (m) H (m) L (m)
1 1 16.21 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 2.21 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 14.74 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 12.46 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 9.74 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 4.12 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 2.80 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 1.65 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 2.68 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 1.51 0.14 2.40 0.00 1 0.00 0.14 1.50 0.00
1 1 5.38 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 6.60 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 1.65 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 3.72 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 3.47 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 1.61 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
1 1 0.85 0.14 2.40 0.00 1 0.00 0.14 1.00 0.00
CARGA VIVA
QUES AZOTEA SOBRECARGA
Ton/cm3) = CM (Ton/m) 0.2 CV (Ton/m)
Peso (Ton)
Niveles A (m) L (m) Niveles
1 0.00 20.14 16.21 1 1 3.24
1 0.00 3.10 2.21 1 1 0.44
1 0.00 15.92 14.74 1 1 2.95
1 0.00 13.65 12.46 1 1 2.49
1 0.00 12.99 9.74 1 1 1.95
1 0.00 4.94 4.12 1 1 0.82
1 0.00 3.55 2.80 1 1 0.56
1 0.00 3.03 1.65 1 1 0.33
1 0.00 3.27 2.68 1 1 0.54
1 0.00 2.06 1.51 1 1 0.30
1 0.00 6.25 5.38 1 1 1.08
1 0.00 7.98 6.60 1 1 1.32
1 0.00 3.03 1.65 1 1 0.33
1 0.00 4.78 3.72 1 1 0.74
1 0.00 4.53 3.47 1 1 0.69
1 0.00 2.67 1.61 1 1 0.32
1 0.00 1.35 0.85 1 1 0.17
CARGA VIVA
QUES AZOTEA AZOTEA
Ton/cm3) = CM (Ton/m) 0.15 CV (Ton/m)
Peso (Ton)
Niveles A (m) L (m) Niveles
1 0.00 20.14 16.21 1 1 2.43
1 0.00 3.10 2.21 1 1 0.33
1 0.00 15.92 14.74 1 1 2.21
1 0.00 13.65 12.46 1 1 1.87
1 0.00 12.99 9.74 1 1 1.46
1 0.00 4.94 4.12 1 1 0.62
1 0.00 3.55 2.80 1 1 0.42
1 0.00 3.03 1.65 1 1 0.25
1 0.00 3.27 2.68 1 1 0.40
1 0.00 2.06 1.51 1 1 0.23
1 0.00 6.25 5.38 1 1 0.81
1 0.00 7.98 6.60 1 1 0.99
1 0.00 3.03 1.65 1 1 0.25
1 0.00 4.78 3.72 1 1 0.56
1 0.00 4.53 3.47 1 1 0.52
1 0.00 2.67 1.61 1 1 0.24
1 0.00 1.35 0.85 1 1 0.13
11. RESISTENCIA AL AGRIETAMIENTO DIAGONAL
11.1 DATOS
v'm (ton/m2) = 80.00
%CV = 0.25
PRIMER NIVEL
MURO Vei (Ton) Mei (Ton.m) Vm1/Ve1 Vui (Ton)
Muro x1 15.92 89.86 3.00 47.76
Muro x2 1.75 9.88 3.00 5.25
Muro x3 3.10 17.51 3.00 9.30
Muro x4 3.17 17.87 3.00 9.50
Muro x5 14.31 80.78 3.00 42.93
Muro x6 0.90 5.08 3.00 2.70
Muro x7 0.70 3.95 3.00 2.10
Muro y1 7.95 44.89 2.28 18.10
Muro y2 1.17 6.62 3.00 3.52
Muro y3 1.01 5.69 3.00 3.02
Muro y4 2.77 15.61 3.00 8.30
Muro y5 6.29 35.52 3.00 18.88
Muro y6 6.29 35.52 2.88 18.10
Muro y7 4.25 23.98 2.85 12.12
Muro y8 3.93 22.19 3.00 11.79
Muro y9 3.93 22.19 2.82 11.10
Muro y10 0.93 5.22 3.00 2.78
SEGUNDO NIVEL
MURO Vei (Ton) Mei (Ton.m) Vm1/Ve1 Vui (Ton)
Muro x1 10.76 25.83 3.00 32.28
Muro x2 1.18 2.84 3.00 3.55
Muro x3 2.10 5.03 3.00 6.29
Muro x4 2.14 5.14 3.00 6.42
Muro x5 9.67 23.22 3.00 29.02
Muro x6 0.61 1.46 3.00 1.82
Muro x7 0.47 1.14 3.00 1.42
Muro y1 5.38 12.90 2.28 12.24
Muro y2 0.79 1.90 3.00 2.38
Muro y3 0.68 1.64 3.00 2.04
Muro y4 1.87 4.49 3.00 5.61
Muro y5 4.25 10.21 3.00 12.76
Muro y6 4.25 10.21 2.88 12.24
Muro y7 2.87 6.89 2.85 8.19
Muro y8 2.66 6.38 3.00 7.97
Muro y9 2.66 6.38 2.82 7.51
Muro y10 0.63 1.50 3.00 1.88
Mui (Ton.m) Pm m Refuerzo Refuerzo Refuerzo REFUERZO
269.58 23.38 14.29 No necesita No necesita No necesita No necesita
29.65 3.54 9.55 No necesita No necesita No necesita No necesita
52.52 18.86 38.50 No necesita Necesita Necesita 19.29
53.61 16.14 32.57 No necesita Necesita Necesita 19.29
242.33 14.94 11.02 No necesita No necesita No necesita No necesita
15.24 5.77 16.81 No necesita No necesita No necesita No necesita
11.86 4.11 13.17 No necesita No necesita No necesita No necesita
102.18 3.36 5.85 Necesita No necesita Necesita 19.29
19.87 3.80 15.53 No necesita No necesita No necesita No necesita
17.07 2.37 10.24 No necesita No necesita No necesita No necesita
46.83 7.33 20.14 No necesita No necesita No necesita No necesita
106.57 9.30 16.20 No necesita No necesita No necesita No necesita
102.18 3.36 5.85 Necesita No necesita Necesita 19.29
68.39 5.52 12.52 Necesita No necesita Necesita 19.29
66.56 5.22 11.84 No necesita No necesita No necesita No necesita
62.68 2.99 6.78 Necesita No necesita Necesita 19.29
15.67 1.52 7.26 No necesita No necesita No necesita No necesita
Usamos varillas de 6mm cada 2 hiladas
1.46
0.39
3/8
4.00
2.85
OK!!!
Muro X7
COLUMNA
Extrema Interna
0.00
0.00
0.00
0.00
0.00
0.00
3
0.00
#DIV/0!
0.00
#DIV/0! #DIV/0!
#DIV/0! #DIV/0!
#DIV/0! #DIV/0!
0.85 0.85
#DIV/0! #DIV/0!
20.00 20.00
14.00 14.00
280.00 280.00
0.80 0.80
#DIV/0! #DIV/0!
#DIV/0! #DIV/0!
#DIV/0! #DIV/0!
5/8 5/8
4.00 4.00
7.92 7.92
#DIV/0! #DIV/0!
0.80 0.80
0.70 0.70
#DIV/0! #DIV/0!
135.00 135.00
1.40 1.40
#DIV/0! #DIV/0!
3/8 3/8
0.71 0.71
15.00 15.00
20.00 20.00
5.90 5.90
15.83 15.83
5.00 5.00
22.00 23.00
5.00 5.00
45 45
#DIV/0!
#DIV/0!
3/8
4.00
2.85
#DIV/0!
DISEO DE LOSAS
H H =
25 bw =
PAO/
DISTANCIAS
CARA LIBRE X CARA LIBRE Y ELECCION DE ARMADO
UNIDIRECCIONAL DIAMETRO As
LOSA UNIDIRECCIONAL
20.00 cm
10.00 cm
12 1/2 3/8
10 1/2 3/8
9 3/8 3/8
12 1/2 3/8
7 3/8 3/8
12 1/2 3/8
AS+ AS- AS+ ESCOGER AS- ESCOGER REVISIN AS+ REVISIN AS-
Mu
ku
As
Usamos 2 varillas de 1/4" x lad
Vu
Vc
Vc
CARGAS ORTOGONALES - CERCO PERIMTRICO
e 0.15 m
Z 0.40
U 1.00
C1 0.60
1.40 Tn/m3
W 0.040 tn/m2
W 0.004 kg/cm2
a 2.00 m
b 3.00 m
b/a 1.50
m 0.13
Ms 21.12 kg-cm/cm
f 0.65 ok
ft 1.50
O DE COLUMNAS DE CONFINAMIENTO
0.08 tn
0.20 tn-m
10.00
0.0023
0.46 cm2
Usamos 2 varillas de 1/4" x lado
0.240 tn
11.130 tn
Vc 9.461 tn