TLK 38 1
1.1
1.2
2
2.1
INSTRUMENT DESCRIPTION
GENERAL DESCRIPTION
FRONT PANEL DESCRIPTION
PROGRAMMING
FAST PROGRAMMING OF SET POINT
2.2 SELECTION OF CONTROL STATE AND PARAMETER
PROGRAMMING
MICROPROCESSOR-BASED 2.3
2.4
PARAMETER PROGRAMMING LEVELS
CONTROL STATES
DIGITAL 2.5
3
ACTIVE SET POINT SELECTION
INFORMATION ON INSTALLATION AND USE
TEMPERATURE CONTROLLER 3.1
3.2
PERMITTED USE
MECHANICAL MOUNTING
3.3 ELECTRICAL CONNECTIONS
3.4 ELECTRICAL WIRING DIAGRAM
4 FUNCTIONS
4.1 MEASURING AND VISUALIZATION
4.2 OUTPUTS CONFIGURATION
4.3 ON/OFF CONTROL
4.4 NEUTRAL ZONE ON/OFF CONTROL
4.5 SINGLE ACTION PID CONTROL
4.6 DOUBLE ACTION PID CONTROL
4.7 AUTO-TUNING AND SELF-TUNING FUNCTIONS
4.8 REACHING OF SET POINT AT CONTROLLED SPEED
AND AUTOMATIC COMMUTATION BETWEEN TWO
SET POINTS
4.9 SOFT-START FUNCTION
4.10 ALARMS OUTPUTS FUNCTIONS
4.11 LOOP BREAK ALARM FUNCTION
ADVANCED THERMOELECTRIC 4.12
4.13
FUNCTION OF KEY U
PARAMETERS CONFIGURATION BY KEY01
toll-free 1(866) 665-5434 5 PROGRAMMABLE PARAMETERS TABLE
(603) 888-2467 6 PROBLEMS , MAINTENANCE AND GUARANTEE
6.1 ERROR SIGNALLING
6.2 CLEANING
sales@electracool.com 6.3 GUARANTEE AND REPAIRS
7 TECHNICAL DATA
7.1 ELECTRICAL DATA
7.2 MECHANICAL DATA
7.3 MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING
7.4 FUNCTIONAL DATA
7.5 MEASUREMENT RANGE TABLE
7.6 INSTRUMENT ORDERING CODE
1 - INSTRUMENT DESCRIPTION
9 - Led Shift index: indicates that the process value is lower than
the one programmed on par. AdE.
10 - Led = Shift index: indicates that the process value is within "O P L O "
the range [SP+AdE ... SP-AdE]
11 - Led + Shift index: indicates that the process value is higher
than the one set on par. AdE.
2 - PROGRAMMING
To enter the menu ConF select the option ConF, press the key
2 .1 - FAST PROGRAMMING OF THE SET POINT P and the display will show 0.
This procedure permits rapid programming of the active Set Point At this request, enter, using keys UP and DOWN, the number
and possibly the alarm thresholds (see par 2.3) reported on the last page of this manual and push key P.
Push key P, then release it and the display will visualise SP nIf an incorrect password is entered, the instrument exit from
(where n is the number of the Set Point active at that moment) programming mode.
alternatively to the programmed value. If the password is correct, the display will visualise the code
To modify the value, press UP key to increase it or the DOWN identifying the first group of parameters ( ]SP ) and with keys UP
key to decrease it. and DOWN it will be possible to select the desired group of
These keys change the value one digit at a time but if they are parameters.
pressed for more than one second, the value increases or Once the desired group of parameters has been selected, the code
decreases rapidly and, after two seconds in the same condition, theidentifying the first parameter of the selected group will be
changing speed increases in order to allow the desired value to be visualised by pushing the P key.
reached rapidly. Again using the UP and DOWN keys, it is possible to select the
Once the desired value has been reached, by pushing key P it is desired parameter and, if the key P is pressed, the display will
possible to exit by the fast programming mode or it is possible to alternatively show the parameters code and its programming value,
visualise the alarm thresholds (see par. 2.3). which can be modified by using the UP or DOWN keys.
To exit the fast Set programming it is necessary to push key P, Once the desired value has been programmed, push key P once
more: the new value will be memorised and the display will show
after the visualisation of the last Set Point, or alternatively, if no key
only the code of the selected parameter.
is pressed for approx. 15 seconds, the display will return to normal
functioning automatically. By using the UP or DOWN keys, it is then possible to select a
new parameter (if present) and modify it as described above.
2.2 - SELECTION OF THE CONTROL STATE AND PARAMETER To select another group of parameters, keep the UP or DOWN
key pressed for approx. 2 sec., afterwards the display will return to
PROGRAMMING
visualise the code of the group of parameters.
By pushing key "P" and holding it down for approx. 2 sec. it is
Release the key and by using the UP and DOWN keys, it will be
possible to enter into the main selection menu.
possible to select a new group.
Using the "UP" or DOWN keys, it is then possible to roll over the
To exit the programming mode, no key should be pressed for
selections:
approx. 20 seconds, or keep the UP or DOWN pressed until exit
"OPEr" to enter into the operating parameters menu
from the programming mode is obtained.
TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 2
Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com
The programming and exit modes for the OPEr menu are the CONTROL OFF (OFF) The instrument can be swapped into the
same as those described for menu ConF with the difference that OFF state, i.e. the control and the relative outputs are
to access the men "OPEr" the Password is not required. deactivated.
The alarm outputs are instead working normally.
BUMPLESS MANUAL CONTROL (OPLO) By means of this
option it is possible to manually program the power percentage
given as output by the controller by deactivating automatic control.
When the instrument is swapped to manual control, the power
Hold for
2 sec.
percentage is the same as the last one supplied and can be
modified using the UP and DOWN keys.
Hold for
2 sec.
Hold
Longer As in the case of automatic control, the programmable values
range from H100 (+100%) to C100 (-100%).
To return to automatic control, select "rEG" in the selection menu.
If it is desired an automatic cycle from the power on instead it is Note: In all the examples that follow is made reference to the alarm
necessary to program the par. "nSP" = 2, to program the two Set AL1. Naturally the operation of the other alarms results analogous.
Point values "SP1" and "SP2" and naturally to program the par.
"SLor", "dur.t" and "SLoF" with the desired values. Have now access at the group ]AL1, and program on par.
In this case at the end of the cycle all the ramps won't be more OAL1 , to which output the alarm signal has to be sent.
active. The alarm functioning is instead defined by parameters :
"AL1t " - ALARM TYPE
PV "Ab1" - ALARM CONFIGURATION
[U n it] AL1 - ALARM THRESHOLD
d u r .t
SP1 AL1L - LOW ALARM THRESHOLD (for band alarm) OR
SLoF
SLor MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high
SP2
alarm)
AL1H - HIGH ALARM THRESHOLD (for band alarm) OR
AUTO
MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high
t im e [ m in .]
change
S et
alarm)
HAL1 - ALARM HYSTERESIS
Examples with starts from values lower than SP and with
AL1d - ALARM ACTIVATION DELAY (in sec.)
decreasing of SP.
Note: In case of PID control, if Auto-tuning is desired whilst the "AL1i" - ALARM BEHAVIOUR IN THE EVENT OF
ramp function is active, this will not be carried out until the tuning MEASUREMENT ERROR
TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 7
Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com
The number to be set, which will correspond to the function desired,
"AL1t" ALARM TYPE : the alarm output can behave in six is obtained by adding the values reported in the following
different ways. descriptions :
LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the ALARM BEHAVIOUR AT SWITCH ON: the alarm output may
process value goes below the alarm threshold set on parameter behave in two different ways, depending on the value added to par.
"AL1 and will be deactivated when it goes above the value Ab1.
[AL1+HAL1]. +0 = NORMAL BEHAVIOUR: The alarm is always activated when
With this mode is possible to program the minimum and the there are alarm conditions.
maximum set of AL1 by AL1L and AL1H parameters. +1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched
HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the on, the instrument is in alarm condition, the alarm is not activated. It
process value goes higher than the alarm threshold set on will be activated only when the process value is in non-alarm
parameter "AL1" and will be deactivated when it goes below the conditions and then back in alarm conditions.
value [AL1 - HAL1]. PV
PV PV
tim e
AL1 O N O N
HAL1 +0
HAL1 o ff o ff
AL1 Ab1 O N
+1 o ff o ff
ON ON time ON ON time
OUT OUT exemple with absolute low alarm
AL1 off off off AL1 off off off ALARM DELAY: the alarm output may behave in two different
ways depending on the value added to par. Ab1.
LoAb HiAb +0 = ALARM NOT DELAYED: The alarm is immediately activated
LodE = DEVIATION LOW ALARM: The alarm is activated when the when the alarm condition occurs.
process value goes below the value [SP + AL1] and will be +2 = ALARM DELAYED: When the alarm condition occurs, delay
deactivated when it goes above the value [SP + AL1 + HAL1]. counting begins, as programmed on par. AL1d (expressed in
With this mode is possible to program the minimum and the sec.) and the alarm will be activated only after the elapsing of that
maximum set of AL1 by AL1L and AL1H parameters. time.
HidE = DEVIATION HIGH ALARM: The alarm is activated when the ALARM LATCH: : the alarm output may behave in two different
ways depending on the value added to par. Ab1.
process value goes above the value [SP + AL1] and will be
deactivated when it goes below the value [SP + AL1 - HAL1]. + 0 = ALARM NOT LATCHED: The alarm remains active in alarm
conditions only.
With this mode is possible to program the minimum and the
maximum set of AL1 by AL1L and AL1H parameters. + 4 = ALARM LATCHED: The alarm is active in alarm conditions
and remains active even when these conditions no longer exist,
PV PV until the correctly programmed key U, (USrb=Aac) has been
pushed.
SP
P V
HAL1
AL1
-AL1
HAL1 SP
AL1
ON ON ON ON tim e
OUT time OUT time
O N
AL1 off off off AL1 off off off +0 o ff o ff
A b1 O N
LodE HidE
+4 o ff
LHAb = ABSOLUTE BAND ALARM: The alarm is activated when
the process value goes under the alarm threshold set on parameter exemple with absolute high alarm
"AL1L" or goes higher than the alarm threshold set on parameter ALARM AKNOWLEDGEMENT: : the alarm output may behave in
"AL1H" and will be deactivated when it goes below the value [AL1H two different ways depending on the value added to par. Ab1.
- HAL1] or when it goes above the value [AL1L + HAL1]. + 0 = ALARM NOT AKNOWLEDGED: The alarm always remains
LHdE = DEVIATION BAND ALARM: The alarm is activated when active in alarm conditions.
the process value goes below the value [SP + AL1L] or goes above + 8 = ALARM AKNOWLEDGED: The alarm is active in alarm
than the value [SP + AL1H] and will be deactivated when it goes conditions and can be deactivated by key U if properly
below the value [SP + AL1H - HAL1] or when it goes above the programmed (USrb=ASi), and also if alarm conditions still exist.
value [SP + AL1L + HAL1]. ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION
PV
ALARMS ONLY): the alarm output may behave in two different
PV
AL1H ways, depending on the value added to par. Ab1.
HAL1 HAL1 +0 = NORMAL BEHAVIOUR: The alarm is always activated when
AL1H
SP there are alarm conditions.
- AL1L
AL1L
HAL1 HAL1 +16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,
when Set Point change, the instrument is in alarm condition, the
alarm is not activated. It will be activated only when the process
ON ON time ON ON time value is in non-alarm conditions and then back in alarm conditions.
OUT OUT
AL1 off off off AL1 off off off
"AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
LHAb LHdE ERROR: This allows one to establish how the alarm have behave
in the event of a measurement error (yES=alarm active; no=alarm
deactivated).
"Ab1" - ALARM CONFIGURATION: This parameter can assume a
value between 0 and 31.
TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 8
Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com
4.11 - LOOP BREAK ALARM FUNCTION device while if it results green blinking or red blinking this means
All the parameters referring to the Loop Break alarm function are that it has not been loaded any valid configuration on the device .
contained in the group ]LbA. 5) press the button placed on the device.
The Loop Break alarm is available on all the instruments, which 6) observe the indication led : after having pressed the button, the
intervenes when, for any reason (short-circuit of a thermocouple, led becomes red and therefore, at the end of the data transfer, it
thermocouple inversion, load interruption), the loop control is becomes green.
interrupted. 7) now it is possible to disconnect the device.
First of all, it is necessary to establish to which output the alarm has To transfer the configuration loaded on the device onto an
to correspond. instrument of the same family (DOWNLOAD), it is necessary to
To do this it is necessary to set the parameter relative to the output proceed in the following way:
to be used (O1F , O2F) in the group ]Out, programming the 1) position both dip switch of KEY 01 in the ON mode.
parameter as : 2) connect the device to an instrument TLK having the same
= ALno if the alarm output has to be ON when the alarm is active features of the one from which has been downloaded the desired
while it is OFF when the alarm is not active. configuration, plugging the special connector.
= ALnc if the alarm output has to be ON when the alarm is not 3) verify that the instrument or the device are supplied
active while it is OFF when the alarm is active. 4) observe the indication led on the device KEY 01: it has to result
= ALni if the alarm output has to be ON when the alarm is not green, because if the led results green blinking or red blinking, this
active, while it is OFF when the alarm is active but with reverse led means that on the device it has not been downloaded any valid
indication (led ON= alarm OFF). configuration and therefore its useless to continue.
Enter group ]LbA and program which output the alarm signal 5) if the les results green, press the button placed on the device.
has to be addressed to on par. OLbA,. 6) observe the indication led : after having pressed the button, the
The Loop Break alarm is activated if the output power remains at led becomes red and therefore, at the end of the data transfer, it
the 100% of the value for the time programmed on par. "LbAt" becomes green.
(expressed in sec.). 7) now it is possible to disconnect the device.
To avoid false alarms, the value of this parameter has to be set Instrument supplied and device not supplied
considering the time the plant takes to reach the Set point when the SUPPLY
measured value is a long distance from it (for example at the plant
start-up).
On alarm intervention, the instrument visualizes the message
LbA and behaves as in the case of a measurement error giving a
power output as programmed on par. OPE (programmable in the
group ]InP).
To restore normal functioning after the alarm, select the control
mode OFF and then re-program the automatic control (rEG)
after checking the correct functioning of probe and actuator.
To exclude the Loop Break alarm, set OLbA = OFF. Instrument supplied from the device
28
0..20 mA
SEnS = 0.20
OUT1 - = + OUT2
4..20 mA
64 SEnS = 4.20
min. 15 mm
0 ... 50 mV
SEnS = 0.50
0 ... 60 mV
71 SEnS = 0.60
29
0 ... 5 V
RECOMMENDED
PANEL CUTOUT SEnS = 0.5
1 ... 5 V
SEnS = 1.5
0 ... 10 V
SEnS = 0.10
2 ... 10 V
BRACKETS
TYPE 2 SEnS = 2.10
TLK38 a b c d ee f
31
a : POWER SUPPLY
43
F = 12 VAC/VDC
L = 24 VAC/VDC
BRACKET
TYPE 1 H = 100... 240 VAC
b : INPUT
C = thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100)
E = thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC)
I = normalized signals 0/4..20 mA
PANEL + GASKET
R = Relay
PANEL + GASKET
MAX 12 mm
MAX 29 mm
d : OUTPUT OUT2
R = Relay
O = VDC for SSR
- = None
ee: SPECIAL CODES
7.4 - FUNCTIONAL FEATURES f: SPECIAL VERSIONS
Control: ON/OFF, ON/OFF Neutral Zone, PID single Action, PID
double action.
Measurement range: according to the used probe (see range table)
Display resolution: according to the probe used 1/0,1/0,01/0,001 TLK 38 PASSWORD = 381
TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 12