Description Transformer unit Spare Transformers
II.
Transformer Asset name and ---
Asset Code number.
1 Capacity HV: 25MVA IV LV 25MVA
2 Voltages: HV: 220000/3 kV IV: LV: 11000 kV
3 Rated Current: HV: 196 IV: LV: 2272.7
4 Vector group YNd1
5 Type of Cooling OFWF
6 Percentage Impedance HV-IV 12.8% HV-LV IV-LV
7 Guaranteed Temp. rise in Oil/ Wdg 450 C, 550 C
8 Serial No. and Year of make T09836/1 Year2010
relays
A.6.1 Is the relay contacts intact
Any corrosion for Alarm &trip
A.6.2
contacts
A.6.3 Method of glanding of cable
Any chance of water entry in to
A.6.4
terminal box
How frequently TB checked
A.6.5
/gasket changed
A.7 Leakage
Is it gasket leakage or welding NA
A.7.1
leakage
A.7.2 How frequent leakage is checked When leakage noticed
A.7.3 How frequent action taken As per the severity of the problem
B Tank
B.1 General condition of tank
B.2 Normal tank or bell tank Normal tank
B.3 Completely welded tank Yes
B.4 Any re welding done on the tank How and when -No
B.5 Locking arrangement of No
transformer wheels
C Conservator tank
Condition of /MOLG of main Ok
C.1
conservator
C.2 Make of /MOLG SukrutUdyog
C.3 Are MOLG replaced NO
C.4 Any difficulty in reading the Is reading correct-Yes
gauge
C.5 How often transformer topped up When required
C.6 How often MOLG terminal Monthly
box/contacts checked
C.7 Whether air cell is provided Condition of air cell-NA
C.8 How air cells condition checked. NA
C.9 Any problem with topping up of NA
transformer or vacuuming of the
transformer with air cell
C.10 Any intention in providing air cell NO
in normal type conservator.
C.11 Any other remarks No
D Conservator for OLTC No
Condition of prismatic oil level
D1 gauge/ OK Visible
when
Condition of WTI Capillary
H3 sensor/capillary/switches
/repeater/etc
Switch Settings and functions R
H4
ph
Switch Settings and functions Y
H5
ph
Switch Settings and functions B
H6
ph
Date of last calibration of WTI & Not available
H7
result
H8 How often contacts checked? Monthly
H9 Any remarks
I Oil Temperature Indicator
I1 Make of relay/indicator Precimeasure and control pvt ltd
Is relay/indicator replaced , if so NO
I2
when
Condition of OTI Capillary
I3 sensor/capillary/switches
/repeater/etc
I4 Switch Settings and functions
Date of last calibration of OTI & -
I5
result
I6 How often contacts checked? Monthly
I7 Any remarks
8
J Radiators Not available
Are radiators tank mounted or
J1
separately mounted
If separately mounted , provided
J2
with expansion joints
J3 Functioning of non-return valve
Is the arrangement of cooler
J4
proper for effective maintenance
J5 No. of radiators on each bank
Condition of radiators and make
J6
of radiator
How often Radiators cleaned,
method of cleaning of radiators, Is
J7
cleaning possible without
shutdown?
J8 Any radiator added , or replaced
Intention to add radiators in
J9
future
O Marshalling kiosk
General /physical conditions
O1
including painting.
O2 Condition of hinges/handles
Working of space heater &
O3
Thermostat
Whether all dummy gland holes
O4
are properly sealed?
Status of cubicle indication bulb
O5
and socket.
Any remarks
O6
P Cooling Fans
P1 No. of fans in each group
Make and type and ratings of the
P2
fans
General working and appearance
P3
of fans
P4 Operation of all fans in
Independent mode
Working of fans in auto mode
P5 and actual temperature of
switching.
Auto starting of standby fans on
P6
failure of Service fans
P7 Current taken by fans (average)
P8 Whether bird guards are provided
P9 How often fans are cleaned /
Whether fans were replaced ,
P10
cause /last replaced
P11 Any remarks
Q Cooling Pumps
No. of pumps in each group
Q1
Q2 Make and type of pumps
Q3 Whether pumps are replaced
General working and appearance
Q4
of pumps
Working of pumps in auto mode
Q5 and actual temperature of
switching.
Auto starting of standby pumps
Q6
on failure of Service pumps
Q7 Current taken by pumps (average)
Q8 How often pumps are checked
Is transformer shutdown essential
Q9 for pump replacement/
maintenance
Q10 Any other remarks
R Bushing CT
R1 No. of bushing WTI CTs HV IV LV - 1
Is protection class CT cores No
R2
provided
R3 Ratio
Condition of terminal connection OK. No Leak
R4
fixture and any oil leak
Sec. current measurement Primary Current applied :
R5
Sec. Current measured :
R6
W Protection
Whether Main-1 & Main-2
W1
Differential protections provided
HV and LV REF protection
W2
Provided
O/C & E/f protection with high
W3
set are provided on HV & LV
W4 Over flux protection
Whether busbar protection is
W5
available
Whether LBB protection is
W6
provided for Trfr. CBs
Condition of Protection panel &
W7
Accessories
Whether all trouble trip wired to
W8
Master trip
(before summer)
Z3.31 Checking of auto starting of Pump will start when switch on the machine
cooler pumps and fans
Z3.32 Checking of auto starting of na
cooler pumps and fans
Z3.33 checkingof all remote no
indications (WTI and tap
position indicator)
andtop up oil pockets, if
required.
Z3.34 Electricalchecking/testing of no
pressure relief device, buchholz
relay, OLTCsurge
relay/checking of alarm/ trip
replacement of the gaskets of
the terminal box.
Z3.35 checking/testing of buchholz yes
relay by oil draining
Z3.36
Z3.37 physical verification of oil in yes
conservator tank
Z3.38 checking the inter trip from HV yes
to LV
Z3.39 checking the inter trip from LV yes
ref to HV
Z3.40 Checking of the actual tripping
of CB on the operation of all
relays on HV &LV