You are on page 1of 5

Abhishek Garg Int. Journal of Engineering Research and Applicationswww.ijera.

com
ISSN : 2248-9622, Vol. 5, Issue 5, ( Part -3) May 2015, pp.56-60

RESEARCH ARTICLE OPEN ACCESS

Starting Time Calculation for Induction Motor.


Abhishek Garg1, Arun Singh Tomar2
Authors are working with the nuclear department of L&T construction, Chennai, 600089, India.

ABSTRACT
This Paper Presents The Starting Time Calculation For A Squirrel Cage Induction Motor. The Importance Of
Starting Time Lies In Determining The Duration Of Large Current, Which Flows During The Starting Of An
Induction Motor. Normally, The Starting Current Of An Induction Motor Is Six To Eight Time Of Full Load
Current. Plenty Of Methods Have Been Discovered To Start Motor In A Quick Time, But Due To Un-Economic
Nature, Use Are Limited. Hence, For Large Motors Direct Online Starting Is Most Popular Amongst All Due To
Its Economic And Feasible Nature. But Large Current With Dol Starting Results In A Heavy Potential Drop In
The Power System. Thus, Special Care And Attention Is Required In Order To Design A Healthy System.
A Very Simple Method To Calculate The Starting Time Of Motor Is Proposed In This Paper. Respective
Simulation Study Has Been Carried Out Using Matlab 7.8.0 Environment, Which Demonstrates The
Effectiveness Of The Starting Time Calculation.
Index Terms: - Induction Motor, Starting Time, Direct Online Starting

I. INTRODUCTION starting time calculations, but none of them compares


Motors in modern industrial systems are the outcome with the simulation software.
becoming larger due the heavy applications This paper presents the comparative study
requirement. Some are considered large even in between mathematical calculation and MATLAB
comparison to the total capacity of large industrial result of motor starting time.
power systems [2]. Starting of such large motors can
cause adverse effects to any locally connected load, II. BASICS OF INDUCTION MOTOR
other motors and also to buses, which are electrically The basic operation of induction motor is similar
remote from the point of motor starting. to transformer, where the stator acts as the primary
Ideally, a motor-starting study should be done side of transformer and the rotor as secondary of
prior to purchase of a large motor. The motor transformer as shown in figure 1. At time of starting,
manufacturer shall provide the value of starting the voltage induced in the induction motor rotor is
voltage requirement and preferred locked-rotor maximum because slip is maximum (S = 1). Since
current. A motor-starting study should be done if the the rotor impedance is low, the rotor current is
motor horsepower exceeds approximately 30% of the excessively large. Due to transformer action this
supply transformer(s) base kVA rating, if no large rotor current is reflected in the stator. This
generators are present [2]. Whereas, If generator is results in large starting current (nearly 6 to 8 times
present, and no other sources are involved, an the full-load current) in the stator at low power factor
analysis should be done whenever the motor and consequently the value of starting torque is low.
horsepower exceeds 1015% of the generator kVA This large current does not harm the motor due to
rating, depending on actual generator characteristics short duration.
[2].
Squirrel cage induction motor is most commonly X1 X2
used motor in the world due to its simple design, less r1
maintenance and simple operation. The rating of
induction motor is available from fraction of watts to
Mega-Watts. It can be used for different type of
applications based on torque speed characteristics AC r2
requirements such as constant power, constant
torque, torque increases in proportion to speed,
torque increases with the square of speed, torque
decreases in inverse proportion to speed [5].
Many conference papers have been published on
Fig.1 Basic circuit of induction motor
motor starting with various starting methods and

www.ijera.com 56|P a g e
Abhishek Garg Int. Journal of Engineering Research and Applicationswww.ijera.com
ISSN : 2248-9622, Vol. 5, Issue 5, ( Part -3) May 2015, pp.56-60

However, this large starting current will produce So if we are changing X1& X2, then starting time
large drop in line-voltage [2]. Table 1 represents the will also change. If this time is more than limit value,
minimum allowable voltage levels required, when this large current will adversely affect the other
motor starting is taken into consideration. electrical equipment connected to the same bus.
Figure 2 shows the equivalent circuit of induction
Table 1- motor.
Summary of representative critical system voltage
levels when starting motors (IEEE 399-1997)
Voltage drop location or Minimum 1 Xs 2 Xr
Rs
problem allowable m
c
voltage (%
R2/s
rated) Rc Xm
At terminals of starting motor a80%a 2
1
All terminals of other motors 71%a
that must reaccelerate
AC contactor pick-up (by 85%
standard) (see 9.8, NEMA
standards)
DC contactor pick-up (by 80%
Fig. 2 Equivalent circuit of induction motor
standard) (see 9.8, NEMA
standards)
Contactor hold-in (average of 6070%b Therefore, it is desirable and necessary to reduce
those in use) the magnitude of stator current during starting.
Solid-state control devices 90%c Several methods have been discovered to reduce the
Noticeable light flicker 3% change starting current. Some of popular starting methods
amongst all are-
1) Direct-on-line starting
(a)- Typical for NEMA design B motors only. Value
2) Stator resistance starting
may be higher (or lower) depending on actual motor
3) Autotransformer starting
and load characteristics.
4) Star-delta starting
(b)-Value may be as high as 80% for certain
5) Rotor resistance
conditions during prolonged starting intervals.
In practice, any one of the first four methods is
(c)- May typically vary by depending on available
used for starting squirrel cage motors, depending
tap settings of power supply transformer when
upon the size of the motor. But slip ring motors are
provided.)
mostly started by rotor resistance starting.
The starting torque and starting current also
depends on motor class as shown in Table 2. This
change is due to change in value of X1& X2 with III. STATOR RESISTANCE STARTING
different class of motors as shown in figure 1. In stator resistance starting, external resistances
are connected in series with each phase of stator
Table 2 winding during starting. This causes voltage drop
Empirical distribution of leakage reactance in across the resistances so that voltage available across
induction motors.( IEEE 112) motor terminals is reduced and hence the starting
Mot Description Fraction of X 1 + current. The starting resistances are gradually cut out
or X2 in steps (two or more steps) from the stator circuit as
class the motor picks up speed. When the motor attains
rated speed, the resistances are completely cut out
X1 X2
and full line voltage is applied to the rotor.
A Normal starting torque, 0.5 0.5 This method suffers from two drawbacks. First,
normal starting current the reduced voltage applied to the motor during the
B Normal starting torque, 0.4 0.6 starting period lowers the starting torque and hence
low starting current increases the accelerating time. Secondly, a lot of
C High starting torque, 0.3 0.7 power is wasted in the starting resistances.
low starting current
D High starting torque, 0.5 0.5 IV. AUTOTRANSFORMER STARTING
high slip This method also aims at connecting the
Wou Performance varies 0.5 0.5 induction motor to reduced supply at starting and
nd with rotor resistance then connecting it to the full voltage as the motor
rotor picks up sufficient speed. The tapping on the

www.ijera.com 57|P a g e
Abhishek Garg Int. Journal of Engineering Research and Applicationswww.ijera.com
ISSN : 2248-9622, Vol. 5, Issue 5, ( Part -3) May 2015, pp.56-60

autotransformer is so set that when it is in the circuit, starting time at a couple of selected values such as
65% to 80% of line voltage is applied to the motor. 90% or 85% and then plot the results on the time
At the instant of starting, the change-over switch is versus current curves for the supplied motor.
thrown to start position. This puts the System designers can use these starting times,
autotransformer in the circuit and thus reduced but it is sometimes necessary to calculate the motor
voltage is applied to the circuit. Consequently, starting times using the results of a power system
starting current is limited to safe value. When the studies for the maximum voltage dip at critical power
motor attains about 80% of normal speed, the system conditions. This method can then be used,
changeover switch is thrown to run position. This using the maximum voltage dip, to avoid application
takes out the autotransformer from the circuit and problems, set motor protective devices and perform
puts the motor to full line voltage. Autotransformer coordination studies with other protective devices on
starting has several advantages few of them are low the system.
power loss, low starting current and less radiated
heat. For large machines (over 25 H.P.), this method VII. CALCULATION USING ACCELERATION
of starting is often used. This method can be used for TORQUE AND ACCELERATION TIME
both star and delta connected motors. Figure 3 shows the torque speed curve of
induction motor. By this its clear that on application
V. STAR-DELTA STARTING of voltage speed increases from zero along-with
The stator winding of the motor is designed for torque. In starting, slip is unity and with the increase
delta operation and is connected in star during the in speed there is a gradual reduction in slip. Motor
starting period. When the machine is up to speed, the comes to rated speed which is near to its synchronous
connections are changed to delta. speed and the time taken to reach this point is called
At the instant of starting, the changeover switch starting time. By this figure 3 it is also clear that if
is thrown to Start position which connects the the gap between the motor torque and load torque is
stator windings in star. Therefore, each stator phase more motors will start very fast and this gap between
gets volts where V is the line voltage. This reduces these two torques is called acceleration torque.
the starting current. When the motor picks up speed, Calculation for acceleration torque and
the changeover switch is thrown to Run position acceleration time is given below with explanation.
which connects the stator windings in delta. Now torque
each stator phase gets full line voltage V. 30000
The disadvantage of this method is: when there
is Star-connection during starting, stator phase 25000
voltage is *times of line voltage. Consequently, 20000
starting torque is *times the value it would have with Motor torque
D-connection. This method becomes rare for a large 15000
Accelerated Load torque
motor due to large reduction in starting torque. 10000 torque Rated torque
741 rpm
VI. IMPORTANCE OF STARTING TIME 5000

Large motor over current protection is normally


set to trip prior to the locked-rotor withstand time 0 75 150 225 300 375 450 525 600 675 750 rpm
(LRWT) provided by the motor manufacturer, after S=1 S=0
the calculated motor start time. The locked-rotor
withstand time is determined by the motor designer Fig.3 torque vs. speed curve of induction motor.
based on the heating of the rotor parts for locked-
rotor condition, where the motor continuously VIII. ACCELERATION TORQUE
requires a large value of inrush current. A load can only be accelerated when the driving
At the time of starting, an induction motor draws motor provides a greater torque than the load requires
high values of current (motor is a constant impedance at that time. The difference of both of this torques is
device during the starting condition), that are very called as acceleration torque . This acceleration
close to the motors locked rotor value and remains at torque will be equal to the multiplication of moment
this value for the time required to start the motor. of inertia of motor and angular acceleration of motor.
This is the reason why the locked-rotor withstand Mathematical formula to calculate this is given in
time is used as an allowable time limit for starting the equation 1. Further this angular acceleration can
motor across the line, full voltage [2]. change in term of angular speed and time of starting.
The capability to calculate motor starting time In this case the simplified assumption is made that
for large induction motor is important in order to during acceleration period load torque is constant. By
evaluate the relative strength of the power system. calculating average load torque this assumption can
Typically the motor designer may calculate the motor
www.ijera.com 58|P a g e
Abhishek Garg Int. Journal of Engineering Research and Applicationswww.ijera.com
ISSN : 2248-9622, Vol. 5, Issue 5, ( Part -3) May 2015, pp.56-60

be fulfilled and replace the variable motor torque by a = 1.5 0


constant mean acceleration.
Acceleration torque = motor load (1) as = 0

So = 1.5 5157.86 = 7736.79


j j 2 n
= j = =
Tst 60 Tst Now by Equation (2)
jn
= (2) 30741
9.55 Tst = * = 0.3008 sec
9.557736 .79

Where (b) Acceleration (starting) time with load


= motor torque in Nm
= load torque in Nm = 1.5
= starting time in s
= angular acceleration /s2 But = at rated condition (5)
n = motor speed/min
= angular speed/s = 1.5
= mean acceleration torque in Nm
= moment of inertia in kg-m2 reduced to the motor So = 0.5
shaft
= 0.5 5157.86 = 2578.93
IX. ACCELERATION TIME
The acceleration time (starting time) tst of At load total moment of inertia in kg-
induction motor can be determined from equation 2 m2=30+19=49kg-m2
by doing some manipulations. As told above that Now by Equation (2)
time is time taken by induction motor to reach at
rated speed & rated torque at rated voltage. Now if 49741
Tst = = 1.474 sec
the mean acceleration torque and moment of 9.552578 .93
inertia are known we can easily calculate the value of
starting time. In this motor the acceleration time tst is lesser
jn than the maximum time specified by the
Starting time = = (3)
9.55 manufacturer. Unloaded motors and motors with only
little additional centrifugal masses reach their idle
The concept is demonstrated with the help of an speed very quickly. But when large centrifugal
example, as given below- masses are to be accelerated, starting times are
generally quite high. This is called heavy starting,
Example: Let an eight -pole SCIM motor with Nr which is the case, for example, in centrifuges, ball
= 741 rpm, P = 400 kW have an inertia of J = 30 mills, transport systems and large fans. These
kgm2 at no-load and have an average acceleration applications often require special motors and
torque = 1.5. (at no load),the maximum time corresponding switchgears.
specified by the manufacturer is 15 sec. If the curve of the load torqueis complex and the
Calculate motor torque is not constant, it is advantageous to
a) The starting time at no-load? divide the computation into individual zones as
b)The starting time together with driven shown in Figure 5
equipment torque with reference to motor is 19 torque
Kgm2. 30000

25000
Solution:
20000
a)Rated torque of the motor Motor torque
15000
Accelerated Load torque
9.81 Rated kW 974 Rated torque
T
T

10000 torque
motor = 741 rpm
T

Rated rpm
T
T
T

5000
T
T
T

So 0 75 150 225 300 375 450 525 600 675 750 rpm
9.81400 974 S=1
= * = 5157.86 Nm (4) S=0
741
Fig. 4 torque vs. speed curve of induction motor
But at no load when is complex.

www.ijera.com 59|P a g e
Abhishek Garg Int. Journal of Engineering Research and Applicationswww.ijera.com
ISSN : 2248-9622, Vol. 5, Issue 5, ( Part -3) May 2015, pp.56-60

Now the acceleration times for the individual calculate the starting time using acceleration torque,
zones, which take effect in the segment are motor speed and moment of inertia of an induction
computedand added up for each and every individual motor is presented and the derived results from the
speed segments. Further to this, acceleration torque calculation has been verified against the simulation
can be calculated using equation 3. study carried on MATLAB environment. Results of
Now to calculate the starting time of non-constant both the approaches are found to be in line with each
acceleration torque is given by equation 6. other.
Three-phase Induction
Acceleration time for non-constant torques REFERENCES
[1]. Abbas, M.; Majeed, M.A.A.; Kassas, M.;
In s = 9.55 (6)
Ahmad, F., "Motor starting study for a urea
Where the meaning of each is same as in equation 2, manufacturing plant," Power Engineering,
except j* n. Energy and Electrical Drives
This shows summation of all zones with (POWERENG), 2011 International
multiplication of moment of inertia and change in Conference on , vol., no., pp.1,6, 11-13 May
speed. 2011 doi: 10.1109/PowerEng.2011.6036562
[2]. IEEE Recommended Practice for Industrial
X. SIMULATION RESULT and Commercial Power System Analysis,"
Simulation study is carried out by using IEEE Std 399-1990 , vol., no., pp.1,384,
MATLAB 7.8.0 software with the same eight -pole Dec. 15 1990 doi:
SCIM motor with Nr = 741 rpm, P = 400 kW as 10.1109/IEEESTD.1990.115569
considered in the previous example. Figure 5 shows [3]. Hu Hong-ming; Mao Cheng-xiong; Ji-ming
that there is nearly six time of rated current during Lu; Yu You-xin, "The torque oscillation
motor starting which is gradually decreasing and study in the motor soft starting process with
reaches to the rated current within 1.47 sec. This time discrete variable frequency method,"
is nearly equal to the time calculated by equation 5. Electrical Machines and Systems, 2008.
Figure 6 shows the speed vs. time curve obtained by ICEMS 2008. International Conference on ,
simulation it is clear by the graph that speed is vol., no., pp.1686,1690, 17-20 Oct. 2008
increasing with time and coming to rated value in [4]. Grewal, G.S.; Pocsai, S.; Hakim, M.,
approximately 1.47 seconds, which is in line with the "Transient motor re-acceleration study in an
result calculated by the mathematical equation. integrated petrochemical facility," Industrial
and Commercial Power Systems Technical
Conference, 1997. Conference Record,
Papers Presented at the 1997 Annual
Meeting., IEEE 1997 , vol., no., pp.102,106,
11-16 May 1997 doi:
10.1109/ICPS.1997.596000
[5]. B.Venkataraman, B.Godsey, W. Premerlani,
E.Shulman, M.Thakur,
R.Midence,Fundamentals of a Motor
Thermal Model and its Applications in
Motor Protection.
Fig.5 Current Vs. Time Curve for SCIM [6]. IEEE Houston Section Continuing
Education On Demand Seminar, April 3-4,
2007
[7]. Timothy L. O'Hearn, Calculating Motor
Start Time,
[8]. IEEE Guide for Construction and
Interpretation of Thermal Limit Curves for
Squirrel-Cage Motors Over 500 Hp," IEEE
Std 620-1987 , vol., no., pp.0_1,, 1987doi:
10.1109/IEEESTD.1987.81026.
Fig. 6 Speed vs. time curve for SCIM

XI. CONCLUSIONS
In this paper the importance of induction motor
starting time has been described along-with different
type of starting methods. A mathematical formula to

www.ijera.com 60|P a g e

You might also like