ANALISIS DE FLUJO DE POTENCIA

CASO BASE
CASO BASE DEL SISTEMA
BARRAS

Name In Folder Nom.L-L Volt. Ul, Magnitude u, Magnitude U, Angle General Load, Active Power General Load, Reactive Power

kV kV p.u. deg MW Mvar


BB N1 380 387.6 1.02 0 0 0
BB1 N2 110 106.5885 0.9689859 -3.032879 35 18.891
BB2 N2 110 106.5885 0.9689859 -3.032879 35 18.891
BB1 N3 110 106.1461 0.9649643 -2.800074 10 5.123152
BB2 N3 110 106.1461 0.9649643 -2.800074 10 5.123152
BB N4 110 101.5414 0.9231036 -4.836645 96.4 59.74334
BB N5 10 10 1 -150.5875 0 0
BB N6 10 10 1 -150.5875 0 0

GENERADORES
Name Terminal Terminal Bus Active Reactive Apparent Par.no. App.Pow. u, Power Positive-Sequence-
T. Power Power Power Magnitude Factor Voltage, Magnitude
StaCubic Busbar MW Mvar MVA MVA p.u. p.u.
G1 N5 BB PV 30 6.819903 30.76542 1 46.55 1 0.9751208 0.952381
G2 N6 BB PV 30 6.819903 30.76542 1 210 1 0.9751208 0.6349206
TRANSFORMADORES
Tap 1,
Tap 1, Tap 1,
u, u, Curren Reactive
Nam HV- LV- Min. Max. Active Active Reactive Reactive Apparen Apparen Losses
HV-Side LV-Side Magnitud Magnitud Loading t -Losses
e Side Side Positio Positio Power Power Power Power t Power t Power (total)
e e Positio (total)
n n
n

StaCubi Busba StaCubi Busba HV-Side LV-Side in HV-Side LV-Side HV-Side LV-Side LV-Side HV-Side HV-Side in HV-Side
%
c r c r in p.u. p.u. in MW in MW in Mvar in Mvar in MVA in MVA MW in Mvar

- -
0.968985 77.1427 84.3259 82.5822 112.022 118.028 8.61839
T1 N1 BB N2 BB2 1.02 0 -9 9 84.1327 73.9638 0.1931979
9 4 8 6 2 4 8
8 6
-
0.964964 53.8394 6.81990 30.7654 30.4445 0.0699981 1.24646
T2 N3 BB1 N5 BB 1 0 -9 9 -29.93 30 5.57343
3 9 3 2 1 1 5
8
-
0.964964 53.8394 6.81990 30.7654 30.4445 0.0699981 1.24646
T3 N3 BB1 N6 BB 1 0 -9 9 -29.93 30 5.57343
3 9 3 2 1 1 5
8

LINEAS

Gener Gener
Gener Gener
Capacit al al
u, u, Reacti Appar al al Reacti Appar
Na Termi Termi Termi Termi Loadi ive Active Losses Load, Load, Active Losses Losses
Magnit Magnit ve ent Load, Load, ve ent
me nal i nal i nal j nal j ng Loadin Power (load) Reacti Reacti Power (total) (total)
ude ude Power Power Active Active Power Power
g ve ve
Power Power
Power Power
Termi Termi Termi Termi Termi Termi Termi Termi Termi Termi Termi
Termin Termin Termi Termi
StaCu Busba StaCu Busba nal i nal i nal i nal i nal j nal i nal j nal j nal j nal i nal j
al i in al j in % Mvar nal i in nal j in
bic r bic r in in in in in in in in in in in
p.u. p.u. MVA MVA
MW Mvar MW MW MW Mvar Mvar MW Mvar MW MW
10.63
L1 N2 BB1 N3 BB2 0.969 0.965 0.480 -4.128 9.182 10.067 0.021 35.000 10.000 18.891 5.123 4.149 -9.605 10.463 0.021 0.021
8
10.63
L2 N2 BB1 N3 BB2 0.969 0.965
8
0.480 -4.128 9.182 10.067 0.021 35.000 10.000 18.891 5.123 4.149 -9.605 10.463 0.021 0.021
38.36 - -
L3 N2 BB1 N4 BB 0.969 0.923
0
1.226 29.831 22.128 37.142 0.744 35.000 96.400 18.891 59.743
29.087 21.370
36.094 0.744 0.744
36.91 - -
L4 N2 BB1 N4 BB 0.969 0.923
7
1.753 27.558 14.581 31.178 0.853 35.000 96.400 18.891 59.743
26.705 14.767
30.516 0.853 0.853
49.91 - -
L5 N3 BB1 N4 BB 0.965 0.923
9
0.915 41.561 25.235 48.622 0.954 10.000 96.400 5.123 59.743
40.607 23.606
46.970 0.954 0.954
OBSERVACIONES

De los datos en la tabla de barras se nota en el N4 que como U<0.95 la tensin es de lama calidad
Es necesario mejorar la calidad en la barra esto se puede hacer elevando la tensin en el nodo 3, o cambiando los valores p. u.
De los generadores, o implementando controles de subestacin etc