EN 54-16

en Installer checklist
EN 54-16 Table of Contents | en 3

Table of contents
1 Emergency Sound System 4
2 List of authorized end-users 6
3 EN 54-16 7
3.1 4 General requirements 7
3.2 5 General requirements for indications 9
3.3 6 The quiescent condition 11
3.4 7 The voice alarm condition 11
3.5 8 Fault warning condition 14
3.6 10 Voice alarm manual control (option with requirements) 21
3.7 11 Interface to external control device(s) (option with requirements) 23
3.8 12 Emergency microphone(s) (option with requirements) 23
3.9 13 Design requirements 24
3.10 14 Additional design requirements for software controlled VACIE 38
3.11 15 Marketing 44
3.12 16 Tests 44

Installer checklist 21-Sep-2015 | 01 |


4 en | Emergency Sound System EN 54-16

1 Emergency Sound System


BOSCH has made a great effort for the design and manufacturing of the components and also
supplies all documentation that enables the assembly of a safe and high quality emergency
unit in accordance with EN 54-16. BOSCH has made up this list of requirements, based on the
standard, which needs to be filled in and subsequently signed off by both parties. The signed
paper has the nature of a certificate and can have significant meaning in the case of a legal
investigation of the liability issue for personal injuries.

The safety of the system in accordance with EN 54-16 in an alarm and emergency
application does not only depend on component safety, but also highly on the installation
engineer and the operator. For example, the sound pressure level of the system depends
on the installation. Moreover, the system should only be installed and operated by
qualified personnel.
Modifications of the system should only be executed by authorized persons in accordance
with the safety concept and need to be registered in the system documentation.
If EN 54-16 devices and non-EN 54-16 devices (e.g. a CD player for background music) are
assembled in one cabinet, it must be marked which devices belong to EN54-16 and which
devices do not.
Only use a UPS compliant to the current standards and legislation in combination with
the PAVIRO System.
The end-user must maintain a journal for the system.
The installer is responsible for security measures to prevent improper use of the system.
BOSCH refuses any liability for damage that might result from non-observance of these
instructions.
The installer has to ensure that he uses certified firmware running on the devices.
Information, which firmware versions are applicable can be seen at the web page.

Notice!
The EN 54-16 is a standard referring to products, for an installation the project-depending
country-specific standards must be observed.

21-Sep-2015 | 01 | Installer checklist


EN 54-16 Emergency Sound System | en 5

Herewith the undersigned states that he/she has processed for him/her applicable
requirements, as specified in this document, in an adequate way and has confirmed this fact
by signing the right most column of each requirement.

Installer End-User
Name _____________________ Name _____________________
Signature _____________________ Signature _____________________
Date _____________________ Date _____________________
Place _____________________ Place _____________________

The installer is only allowed to affix a VACIE label on the applied cabinet of a PAVIRO system,
wherein the controller has been installed, after the installer has completed, dated and signed
the checklist for EN 54-16 and has clearly indicated on the VACIE label the year in which the
VACIE label actually has been affixed on the cabinet. A copy of the completed checklist is to
be returned to the regional Bosch office. To ensure compliance to classification IP30 of EN
60529, make sure that the selected cabinet is compliant, and also pay attention to cable
glands, ventilation grilles and connection to the wall. Keep in mind that access to the
controlling and indicating equipment (e.g. PVA-15CST) is access level 2 (protected by a lock)
and that the rear of the equipment is access level 3 (protected by a different or additional
lock).
Racks that are allowed within this EN54-16 system certification are listed on the original
certificate. Please refer to this certificate to ensure the correct rack is used and refer to the
manufacturer's site, instructions for use and sales technicians for information on correct IP30
compliant mounting and accessories that are needed to safeguard all aspects of the selected
rack. The installer must ensure that all open areas and holes of the used racks which do not
comply with IP30 are closed. Use compatible cable glands, climate control, etc. Calculate
ample climate control (temperature dependent ventilation) for the rack and charger(s). Order
the fan pack with thermal control.

Installer checklist 21-Sep-2015 | 01 |


6 en | List of authorized end-users EN 54-16

2 List of authorized end-users

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

Name: _____________________________ Name: _____________________________

21-Sep-2015 | 01 | Installer checklist


EN 54-16
3 EN 54-16

3.1 4 General requirements


Clause/Requirement EN 54-16:2008 Compliance Signature

4 General requirements

4.1 General

4.1.1 If an optional function with requirements is The following optional functions, with requirements, are
included in the VACIE, then all the included in PAVIRO from software Version IRIS-Net
corresponding requirements shall be met. V3.0.0 upwards
Audible warning (7.3)
Phased evacuation (7.5)
Manual silencing of the voice alarm condition
(7.6.2)
Installer checklist

Manual reset of the voice alarm condition (7.7.2)


Voice alarm condition output (7.9)
Indication of faults related to the transmission path
to the CIE (8.3)
Indication of fault related to voice alarm zones (8.4)
Voice alarm manual control (10)
Emergency microphone(s) (12)
Redundant power amplifiers (13.14)
The following optional functions with requirements are
not included in PAVIRO and are not used:
Delay(s) to entering the voice alarm condition (7.4)
Output to fire alarm devices (7.8)
Disabled condition (9)
Interface to external control device(s) (11)

4.1.2 If functions other than those specified in The installer has to ensure that additional functions like

EN 54-16 | en
this European Standard are provided, they background music do not influence compliance. For
21-Sep-2015 | 01 |

shall not jeopardize compliance with any other functions such as announcements, chimes or
requirements of this European Standard. stored messages the priority must be observed.

7
21-Sep-2015 | 01 |

8
Clause/Requirement EN 54-16:2008 Compliance Signature

4.2 Combined VACIE and CIE No signature

en | EN 54-16
necessary in this line.

When the VACIE and CIE are combined they No signature


may share common indications, manual necessary in this line.
controls and outputs (see Annex F). In this
case, the following shall apply:

a) a single fault in the CIE shall not adversely The installer has to ensure to configure the system
affect the mandatory functions of the VACIE; accordingly.

b) indication(s) and manual control(s) of the Indications and controls are not shared.
voice alarm condition shall be clearly
identifiable, with the exception of the
optional audible warning.

4.3 Power supply


Installer checklist

Power supply equipment, external or It is the responsibility of the installer to use power
included in the VACIE, shall comply with the supplies and battery charging equipment in accordance
requirements of EN 54-4. with EN 54-4. The installer has to ensure that the
NOTE The power supply may be shared with capacity of power supplies operates with sufficient
that of the fire detection and fire alarm headroom.
system. The power supply may be shared with that of a fire
detection system, but when operated with a battery the
fire detection and the fire alarm system must be
included into the capacity calculation.

EN 54-16
EN 54-16
3.2 5 General requirements for indications
Clause/Requirement EN 54-16:2008 Compliance Signature

5.1 Display and functional conditions

5.1.1 The VACIE shall be capable of The emergency CALL STATIONs indicate the "voice
unambiguously indicating the following alarm condition" (must be configured) with the red
functional conditions, as described in LED (Alarm) and the "fault warning condition" with
Clauses 6 to 9: the yellow LED (Fault). If both LED are off the
quiescent condition; system is in the "quiescent condition" and the green
voice alarm condition; LED (Power) must be on.
fault warning condition; The PAVIRO system does not support the
disablement condition (option with disablement condition.
requirements) The installer has to ensure that the system provides
the required indications. This can be solved e.g. by
including a CALL STATION.
Installer checklist

5.1.2 The VACIE shall be capable of being The PAVIRO system is capable of being No signature necessary in
simultaneously in any combination of the simultaneously in the voice alarm condition and in this line.
following functional conditions on different the fault warning condition.
voice alarm zones:
voice alarm condition;
fault warning condition;

5.2 Indications displays

All mandatory indications shall be clearly Mandatory indications are clearly identifiable by No signature necessary in
identifiable, except where otherwise system default. this line.
specified in this European Standard.

5.3 Indication on alphanumeric displays

EN 54-16 | en
21-Sep-2015 | 01 |

9
21-Sep-2015 | 01 |

10
Clause/Requirement EN 54-16:2008 Compliance Signature

Where an alphanumeric display is used to The LC display of the emergency CALL STATIONs

en | EN 54-16
display indications relating to different indicates status conditions and fault details of the
functional conditions these may be system.
displayed at the same time. However, for If a fault occurs in the system, the faults are
each functional condition there shall be only displayed automatically. The information related to
one window, in which all of the information emergency has precedence over the faults
relating to that functional condition is information.
grouped. Note: See chapter 8.

5.4 Indication of the supply of power

5.4.1 A visible indication shall be given by means Each PAVIRO system component has a green power No signature necessary in
of a separate discrete light-emitting LED. The LED is on when the component is supplied this line.
indicator while the VACIE is supplied with with power.
power.

5.4.2 Where the VACIE is distributed in more than Each PAVIRO system component has a green power No signature necessary in
Installer checklist

one cabinet, an indication of supply of LED. The LED is on when the component is supplied this line.
power to each distributed cabinet shall be with power.
given at that point.

5.5 Additional indications

Where additional indications are provided, All of the additional indications are clearly identified No signature necessary in
they shall be clearly identifiable and shall (description in the User manuals of the PAVIRO this line.
not override the primary indication of the system); since the fault warning indication and the
VACIE. voice alarm indication always do have separate
indicators, the primary indications are not
overridden. The display of the CALL STATION offers
a menu that is also used for other indications than
indication of the voice alarm and/or fault warning
condition. The Installation and User Instructions of
the PAVIRO system CALL STATIONs clearly
identifies the other indications of the menu. The
other menus do not override the emergency and
faults information.

EN 54-16
EN 54-16
3.3 6 The quiescent condition
Clause/Requirement EN 54-16:2008 Compliance Signature

6 The quiescent condition

Any kind of system information may be All of the additional indications are clearly identified No signature necessary in
displayed during the quiescent condition. (description in the User manuals of the PAVIRO this line.
However, no indications shall be given which system); since the fault warning indication and the
could be confused with indications used in the voice alarm indication always do have separate
voice alarm condition indicators, the primary indications are not
fault warning condition overridden.
the disablement condition (option with
requirements).

3.4 7 The voice alarm condition


Clause/Requirement EN 54-16:2008 Compliance Signature
Installer checklist

7.1 Reception and processing of fire signals

7.1.1 The VACIE shall be capable of receiving and The installer has to ensure the maximum 3 second
processing alarm signals from the CIE or from delay time is observed.
manual control on the VACIE or both, and Note: Task Engine Debounce/Timer/Supervision
causing the appropriate voice alarm outputs to Block
be activated within 3 s or on expiry of any delay
period (see 7.4).

7.1.2 The mandatory indications and or outputs shall The PAVIRO system offers 100 discrete priorities.
not be falsified by multiple alarm signals Correct configuration assures that mandatory
received simultaneously from the CIE and/or indications, and outputs behave consistently when
manual controls. multiple alarm signals are received simultaneously
from the CIE and/or manual controls.

EN 54-16 | en
21-Sep-2015 | 01 |

11
21-Sep-2015 | 01 |

12
Clause/Requirement EN 54-16:2008 Compliance Signature

7.1.3 Where the VACIE and CIE are in separate PAVIRO is an autonomous subsystem that can

en | EN 54-16
cabinets, failure of the transmission path operate without connection to the CIE. The effect
between the CIE and the VACIE shall not result of the failure of the transmission path between
in any loss of control or any change of state of the CIE and the PAVIRO system is limited to fault
the VACIE. reporting and losing interaction between the CIE
and the PAVIRO system. The installer has to
ensure that a fault of the transmission path starts
or stops an alarm signal/alarm message.

7.2 Indication of the voice alarm condition

7.2.1 The presence of a voice alarm condition shall be No signature


indicated on the VACIE, without prior manual necessary in this line.
intervention, by:

a) a visible indication by means of a separate A voice alarm condition is indicated on the PAVIRO
discrete light emitting indicator (the General system by a red LED (Alarm) indicator on all
Installer checklist

Voice Alarm Activated indicator) and emergency CALL STATIONs. The installer has to
ensure to configure the alarm condition
accordingly.

b) a visible indication for each activated voice The red zone LED's on the emergency CALL
alarm zone where manual controls are provided STATION indicates activated voice alarm zones
(see 10.2);

NOTE This may be by means of separate discrete No signature


indicators or an alphanumeric display as necessary in this line.
specified in 13.8.

7.3 Audible warning (option with requirements) The emergency CALL STATION uses for audible
warning a different frequency than for fault
warning. Audible warning has a higher priority
than fault warning.
Note: Regarding the sound pressure level see
requirement 13.10.2.

7.5 Phased evacuation (option with requirements)

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

The VACIE may have a provision to phase the Phased evacuation is possible by using different
warning signals to the emergency loudspeaker control contacts from CIE. Every contact
zones. The facility shall be configurable at repesents an emergency zone. The installer has to
access level 3. There may be provision to switch ensure to configure the correct settings at the
on and switch off the phased evacuation PVA-4CR12 "PAGINGS" dialog. If a system needs
sequence by means of a manual operation at the provision to switch on and switch off the
access level 2 (see Annex A for information on phased evacuation sequence by means of a
access levels). manual operation the installer has to configure the
Task Engine accordingly. We suggest to label the
button with "P-EVAC OFF".

7.6 Silencing of the voice alarm condition

7.6.1 Silencing of the voice alarm condition from the No signature


CIE necessary in this line.

7.6.1.1 Where the voice alarm condition has been Voice alarm triggered from the CIE can also be
Installer checklist

triggered from the CIE, the VACIE shall respond silenced from the CIE. The installer has to ensure
appropriately to a silence instruction from the to configure the system according the
CIE. requirement.

7.6.1.2 The silencing procedure may allow for the The silencing will be done immediately or after
completion of messages in the process of being being broadcasted.
broadcast.

7.6.2 Manual silencing of the voice alarm condition

It may be possible to manually silence the voice The installer has to configure the system
alarm message from the VACIE at access level 2. accordingly.
In this case, following manual silencing, it shall
be possible to re-activate the voice alarm
message at access level 2.

7.7 Reset of the voice alarm condition

EN 54-16 | en
21-Sep-2015 | 01 |

7.7.1 Reset of the voice alarm condition from the CIE No signature
necessary in this line.

13
21-Sep-2015 | 01 |

14
Clause/Requirement EN 54-16:2008 Compliance Signature

Where the voice alarm condition has been The installer has to ensure that a separate input

en | EN 54-16
triggered from the CIE, the VACIE shall respond from the CIE is configured for resetting the alarm
appropriately to a reset instruction from the CIE. condition.

7.7.2 Manual reset of the voice alarm condition No signature


(option with requirements) necessary in this line.

7.7.2.1 It shall be possible to reset the voice alarm The installer has to ensure to configure a separate
condition from the VACIE at access level 2 by CALL STATION button to reset the voice alarm
means of a separate manual control. This control condition. This manual reset function must have a
shall be used only for reset and may be the same higher priority than the CIE contact.
as that used for reset from the fault warning
condition.

7.7.2.2 Following a reset operation, the indication of the After a reset operation, the PAVIRO system will
correct functional condition corresponding to immediately indicate the functional condition it is
any received signals shall either remain or be re- currently in. It will also immediately respond to
Installer checklist

established within 20 s. received signals that will bring it into another


functional condition. The installer has to ensure
not to add to much delay.

7.9 Voice alarm condition output (option with


requirements)

The VACIE may have provision for transmitting a The installer has to ensure that the PAVIRO system
signal that is in the voice alarm condition. In this transmits a signal that it is in the voice alarm
case, it shall activate the output only in the voice condition via control output contact which has to
alarm condition. be configured.

3.5 8 Fault warning condition


Clause/Requirement EN 54-16:2008 Compliance Signature

8 Fault warning condition

8.1 Reception and processing of fault signals

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

8.1.1 The VACIE shall enter the fault warning When the PAVIRO system receives a supervision
condition when signals are received which, fault signal (i.e. detects a fault in the system), the
after any necessary processing, are fault warning condition is entered. The installer has
interpreted as a fault. to ensure that faults are configured accordingly.

8.1.2 The VACIE shall be capable of The installer has to ensure to include only fault
simultaneously recognizing all of the faults messages into the fault handling.
specified in 8.2 and, if provided, in 8.3 The PAVIRO system is capable of recognizing all of
unless this is prevented by: its system faults simultaneously. The PAVIRO system
the presence of an alarm output signal is able to recognize faults in a voice alarm zone even
on the same voice alarm zone when there is an alarm output signal on the zone.

8.1.3 The VACIE shall enter the fault warning The PAVIRO system recognizes and reports all faults
condition within 100 s of the occurrence of within the time defined in EN 54.The installer has to
any fault, or the reception of a fault signal or ensure that faults are configured accordingly.
within another time as specified in this
Installer checklist

European Standard or in other parts of EN


54.

8.2.1 The presence of faults in specified functions No signature necessary in


shall be indicated on the VACIE without this line.
prior manual intervention. The fault warning
condition is established when the following
are present:

a) a visible indication by means of a The PAVIRO system provides a visible indication


separate light emitting indicator (the general when it is in the fault warning condition via the
fault warning indicator); yellow LED (Fault) of the emergency CALL
STATIONs, and via the yellow front panel LED
(Fault) of the PAVIRO CONTROLLER.

b) a visible indication for each recognized The PAVIRO system offers visual indication of
fault as specified in 8.2.4, and 8.2.5, 8.2.6, individual faults at the LC display or via additional

EN 54-16 | en
8.2.7, if provided, and 8.3; LEDs on emergency CALL STATIONS.
21-Sep-2015 | 01 |

15
21-Sep-2015 | 01 |

16
Clause/Requirement EN 54-16:2008 Compliance Signature

c) an audible indication, as specified in 8.4. The PAVIRO system provides an audible fault

en | EN 54-16
indication when it is in the fault warning condition
via sounder at the emergency CALL STATION. In
case of CALL STATION fault it additionally indicates
the fault warning condition via sounder at the
PAVIRO CONTROLLER.

8.2.2 If the indication is on an alphanumeric No signature necessary in


display, which cannot simultaneously this line.
indicate all of the faults because of its
limited capacity, at least the following shall
apply:

a) the presence of fault indications which The first line shows the total quantity of active
have been suppressed shall be indicated; faults, the other lines indicate fault details.

b) suppressed fault indications shall be The next error is displayed each time you press the No signature necessary in
Installer checklist

capable of being displayed by means of a (ESC) fault button. After the last error, the display this line.
manual operation at access level 1 or 2 begins again from the beginning.
which interrogates only fault indications.

8.2.3 The following faults shall be indicated by No signature necessary in


means of separate light emitting indicators this line.
and/or an alphanumeric display:

a) an indication at least common to any The installer has to ensure that all Power faults are
power supply fault resulting from: indicated on the LCD of the emergency CALL
1) a short circuit or an interruption in a STATION.
transmission path to a power supply (item L
of Figure 1 of EN 54-1), where the power
supply is contained in a different cabinet
from that of the VACIE, and
2) the power supply faults as specified in EN
54-4;

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

b) an indication at least common to any The installer has to ensure that all Ground faults
earth fault of less than 50 k which is from the amplifier outputs are indicated on the LCD
capable of affecting a mandatory function, of the emergency CALL STATION.
and which is not otherwise indicated as a
fault of a supervised function;

c) an indication of the rupture of any fuse Every rupture of a fuse or the operation of a
within the VACIE, or the operation of any protected device that affects a mandatory function
protective device within the VACIE which is will result in a fault since the mandatory functions
capable of affecting a mandatory function in are supervised.
the fire alarm condition;

d) an indication of any short circuit or The installer has to ensure that the transmission
interruption, at least common to all paths between the cabinets are supervised if the
transmission paths between parts of the cabinets used for one system are not mounted in
VACIE contained in more than one cabinet, one room.
Installer checklist

which is capable of affecting a mandatory


function and which is not otherwise
indicated as a fault of a supervised function.

Note: These indications from 8.2.3 may be No signature necessary in


suppressed during the fire alarm condition. this line.

8.2.4 The following faults shall be indicated at No signature necessary in


least by means of the general fault warning this line.
indicator:

a) any short-circuit or interruption in a voice The installer has to ensure that the transmission
alarm transmission path between parts of paths between the cabinets are supervised if the
the VACIE contained in more than one cabinets used for one system are not mounted in
cabinet even where the fault does not affect one room.
a mandatory function;

EN 54-16 | en
b) any short-circuit or interruption in the The installer has to ensure that the supervision of
21-Sep-2015 | 01 |

voice alarm transmission path to the the emergency CALL STATION microphone is
emergency microphone capsule, if provided; activated.

17
21-Sep-2015 | 01 |

18
Clause/Requirement EN 54-16:2008 Compliance Signature

c) any short-circuit or interruption in the The installer has to ensure that the loudspeaker

en | EN 54-16
voice alarm transmission path between the lines are permanently supervised by one of the
VACIE and loudspeakers even where the following options:
fault does not affect the operation of PLN-1EOL
loudspeakers. PVA-1WEOL
Permanent impedance measurement

d) any short-circuit or interruption in the The installer has to ensure that the path to fire
transmission path between the VACIE and alarm devices are supervised.
fire alarm devices when used. Note: E.g. with supervised control inputs.

e) failure of any power amplifier. The installer has to ensure that the supervision of
the amplifiers is activated.

8.3 Indication of faults related to the


transmission path to the CIE (option with
requirements)
Installer checklist

The VACIE may have provision for an The installer has to ensure that the path to the CIE
indication of faults related to the is supervised.
transmission path to the CIE. In this case, Note: E.g. with supervised control inputs.
the shortcircuit or interruption of the
transmission path to the CIE shall be
indicated by means of a separate light
emitting indicator and/or an alphanumeric
display.

8.4 Indication of faults related to voice alarm


zones (option with requirements)

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

The VACIE may have provision for an The PAVIRO system is able to indicate each
indication of faults related to voice alarm loudspeaker zone failure at the emergency CALL
zones. In this case the short-circuit or STATION display by indicating the zone number. The
interruption of a voice alarm transmission installer has to ensure that each amplifier may only
path between the VACIE and the be part of one voice alarm zone.
loudspeakers in that zone shall be indicated
by means of a separate light emitting
indicator per zone and/or an alphanumeric
display.

8.5 System fault

A system fault is a fault as specified in 14.4 No signature necessary in


or 14.6 in the case of software controlled this line.
VACIE. A system fault may prevent
requirements of this European Standard,
Installer checklist

other than those specified below, from


being fulfilled. In the event of a system fault
at least the following shall apply:

a) a system fault shall be visibly indicated by The installer has to ensure that the DEL button on
means of the general fault warning indicator the emergency CALL STATION needs to be
and a separate light emitting indicator on configured as system fault reset. The yellow LED of
the VACIE. These indications shall not be this button indicates a system fault. The button
suppressed by any other functional needs to be clearly marked being related to system
condition of the VACIE and shall remain until fault.
a manual reset and/or another manual Note: We recommend to label the system fault key:
operation at access level 2 or 3; System Fault

b) a system fault shall be audibly indicated. The Installer has to enable the sounder of the
This indication may be capable of being emergency CALL STATION. The sounder can be
silenced. silenced by pressing the fault (ESC) button.

EN 54-16 | en
8.6 Audible indication
21-Sep-2015 | 01 |

19
21-Sep-2015 | 01 |

20
Clause/Requirement EN 54-16:2008 Compliance Signature

8.6.1 The audible indication of faults required in The sounder in the emergency CALL STATION which No signature necessary in

en | EN 54-16
8.2 shall be capable of being silenced is used for failure indication can be silenced by this line.
manually at access level 1 or 2 at the VACIE. pressing the fault (ESC) button.
The same manual operation may be used as
for silencing the voice alarm condition.

8.6.2 The audible indication shall be silenced If the PAVIRO system is reset from the fault warning No signature necessary in
automatically if the VACIE is automatically condition, the sounder is automatically silenced. this line.
reset from the fault warning condition.

8.6.3 If previously silenced, the audible indication The sounder used for audible indication starts No signature necessary in
shall resound for each newly recognized sounding again every time a new failure occurs. this line.
fault.

8.7 Reset of fault indications

8.7.1 Indications of faults as required in 8.2 shall No signature necessary in


Installer checklist

be capable of being reset this line.

a) automatically when faults are no longer The indication of faults is reset automatically when No signature necessary in
recognized, and/or faults are no longer recognized. this line.

b) by a manual operation at access level 2. Reset of system fault can be carried out via
dedicated configured CALL STATION button.

8.7.2 Following reset as specified in 8.7.1, the PAVIRO fault indication will remain or be re- No signature necessary in
indication of the correct functional established within 20 s. this line.
conditions corresponding to any received
signals shall either remain or be re-
established within 20 s.

8.8 Transmission of the fault warning condition

The VACIE shall have provision for There is a fixed defined potential free output
transmitting, by means of at least general contact at the PAVIRO CONTROLLER (Ready Relais
fault signal, all faults specified in 8. This on Control Output Connector) which gives a
fault signal shall also be given if the VACIE is collective fault signal. This contact is also active
de-energized. when the system is de-energized

EN 54-16
EN 54-16
3.6 10 Voice alarm manual control (option with requirements)
Clause/Requirement EN 54-16:2008 Compliance Signature

10.1 General requirements

The VACIE may have provision for manually Note: We recommend to label the voice alarm No signature necessary in
activating the voice alarm output condition. manual control key: Start Alarm this line.
If a voice alarm output control facility is
provided the following shall apply:

a) a manual control which causes a voice The Installer has to ensure to configure access level
alarm output condition to be given shall only 2 for the manual control.
be accessible at access level 2 and

b) it shall be possible to activate each voice The Installer has to ensure to configure the system
alarm zone individually and/or in group(s) of accordingly.
voice alarm zones;
Installer checklist

c) the manual activation of a voice alarm PAVIRO will prevent mandatory indications. No signature necessary in
zone shall not prevent the mandatory this line.
indications and outputs to other voice alarm
zones.

10.2 Indication of the voice alarm zones in an


activated condition

The indication for the voice alarm condition No signature necessary in


in the voice alarm zone(s) associated with this line.
each manual control shall be available
without any manual action and shall not be
suppressed. This indication shall be by
means of

a) a separate light emitting indicator (the The voice alarm condition is indicated on the
General Voice Alarm Output activated PAVIRO system by a red indicator on the emergency

EN 54-16 | en
indicator), and CALL STATIONs (the alarm LED). The installer has
21-Sep-2015 | 01 |

to ensure to configure the emergency CALL


STATIONs accordingly.

21
21-Sep-2015 | 01 |

22
Clause/Requirement EN 54-16:2008 Compliance Signature

b) a separate light emitting indicator and/or A separate light emitting indicator is available for No signature necessary in

en | EN 54-16
alphanumeric display for each voice alarm each voice alarm zone and/or group(s) of voice this line.
zone and/or an indication for group(s) of alarm zones.
voice alarm zones.

NOTE These indicators may not necessarily No signature necessary in


indicate which emergency message is being this line.
broadcast in each voice alarm zone.

10.3 Indication of the voice alarm zones in fault


condition

The indication for the fault condition which No signature necessary in


would prevent the generation and this line.
transmission of the voice alarm signal to the
voice alarm zone(s) associated with each
manual control shall be available without
Installer checklist

any manual action and shall not be


suppressed. This indication shall be by

a) a separate light emitting indicator (the The fault condition is indicated on the PAVIRO
general fault indicator), and system by a yellow indicator on all emergency CALL
STATIONs (the fault LED).

b) an indication for each voice alarm zone Individual faults for each voice alarm zone are
and/or an indication for defined group(s) of indicated at the emergency CALL STATION display.
zones. The installer has to ensure to configure the system
accordingly.

EN 54-16
EN 54-16
3.7 11 Interface to external control device(s) (option with requirements)
Clause/Requirement EN 54-16:2008 Compliance Signature

The VACIE may have provision for interfacing to external Not supported No signature necessary in this
control devices(s) such as standardized user interfaces line.
required by local regulations.
a) the interface shall allow only access level 1 and 2
functions;
b) the mandatory functions of the VACIE shall not be
overridden;
c) any short circuit, interruption or earth fault in the
transmission path to the external device(s) shall:
1) not prevent the mandatory function of the VACIE and
2) be indicated on the VACIE, at least by means of the
general fault warning indicator.
NOTE The external control devices should comply with
Installer checklist

available local codes, European Standards or national


standards.

3.8 12 Emergency microphone(s) (option with requirements)


Clause/Requirement EN 54-16:2008 Compliance Signature

The VACIE may have provision for emergency No signature necessary in this
microphone(s). In this case the emergency line.
microphone(s) shall have

a) priority over all inputs, including pre-recorded An emergency microphone can be configured from 0
messages, (lowest priority) to 100 (highest priority). The
installer has to ensure that the priority of the
emergency microphone is higher than the priorities
of other signals including pre-recorded messages.
Higher priorities overrule lower priorities in case of

EN 54-16 | en
resource or destination conflicts. Calls with the
21-Sep-2015 | 01 |

same priority operate on first come first serve basis.

23
21-Sep-2015 | 01 |

24
Clause/Requirement EN 54-16:2008 Compliance Signature

b) an emergency microphone control to open the The Installer has to ensure to configure access level

en | EN 54-16
microphone channel, at access level 2; 2 for the emergency microphone.

c) where a pre-announcement attention drawing A emergency CALL STATION has an LC display No signature necessary in this
signal is provided, an indicator adjacent to the which indicates an active pre-chime. If the pre- line.
microphone shall show when the signal has chime signal has finished, the display shows
finished and live speech can commence, and "announcement".
Note: Pre-announcement signal is mixed with live
speech.

d) when the emergency microphone control is The sounder of the CALL STATION will be switched
operated, any audible indication that might off automatically when a call is made. The installer
interfere with the use of the microphone shall be has to ensure to switch off any loudspeaker near
automatically muted. the emergency microphone.

e) where the VACIE has provision for the An emergency microphone can be configured from 0
connection of more than one emergency (lowest priority) to 100 (highest priority). Higher
Installer checklist

microphone, they shall be configurable for priorities overrule lower priorities in case of
priority at access level 3 or 4 and only one resource or destination conflicts. Calls with the
emergency microphone shall be active at any one same priority operate on first come first serve basis.
time

3.9 13 Design requirements


Clause/Requirement EN 54-16:2008 Compliance Signature

13.1 General requirements and manufacturers


declarations

13.1.1 The VACIE shall comply with the design No signature necessary
requirements of this clause, where relevant to in this line.
the technology used. Some requirements can
be verified by testing. Others can only be
verified by inspection of the design and its
accompanying documentation because of the
impracticability of testing all of the possible

EN 54-16
combinations of functions and of establishing
the long-term reliability of the VACIE.
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

13.1.2 In order to assist the process of design No signature necessary


inspection, the manufacturer shall declare the in this line.
following in writing:

a) that the design has been carried out in The BOSCH development department responsible No signature necessary
accordance with a quality management for development/maintenance of the PAVIRO system in this line.
system which incorporates a set of rules for - part of the EVI Audio GmbH - works according to
the design of all elements of the VACIE; ISO 9001.

b) that the components of the VACIE have The components of the PAVIRO system operate No signature necessary
been selected for the intended purpose and within their specification within the specified in this line.
are expected to operate within their environmental conditions (Class 3k5 of EN
specification when the environmental 60721-3-3:1995 + A2:1997). It is the responsibility
conditions outside the cabinet of the VACIE of the installer that other parts of the system, e.g.
comply with Class 3k5 of EN 60721-3-3:1995 + the 19-racks, comply with this requirement.
A2:1997.
Installer checklist

13.2 Documentation

13.2.1 The manufacturer shall prepare installation The PAVIRO user manuals and the installer checklist No signature necessary
and user documentation which shall be are provided. in this line.
submitted to the testing authority together
with the VACIE. This shall comprise at least
the following:

a) a general description of the equipment, The user manual of the PAVIRO CONTROLLER No signature necessary
including a list of contains a general description of the PAVIRO in this line.
1) the optional functions with requirements of system. The installer checklist (this document)
this European Standard, describes all functions related to EN 54-16.
2) the functions relating to other parts of EN
54, and
3) the ancillary functions not required by this
European Standard;

EN 54-16 | en
21-Sep-2015 | 01 |

25
21-Sep-2015 | 01 |

26
Clause/Requirement EN 54-16:2008 Compliance Signature

b) technical specifications of the inputs and The inputs and outputs for audio and control are No signature necessary

en | EN 54-16
outputs of the VACIE, sufficient to permit an described in the user manual including the technical in this line.
assessment of the mechanical, electrical, and data, system functions, configuration instructions,
software compatibility with other components compliancy to standards.
of the system (e.g. as described in EN 54-1),
including where relevant
1) the power requirements for recommended
operation,
2) the maximum number of voice alarm zones,
3) information concerning the connection of
emergency microphones,
4) the maximum and minimum electrical
ratings for each input and output,
5) information on the communication
parameters employed on each transmission
Installer checklist

path,
6) recommended cable parameters for each
transmission path, and
7) fuse ratings;

c) specified means to limit the consequences The user manual describes all means to limit the No signature necessary
of fault (see 13.5.2); consequences of fault. in this line.

d) configuring and commissioning Configuration instruction are included in the user No signature necessary
instructions; manual and IRIS-Net software help file, in this line.
commissioning instructions are in this checklist.

e) operating instructions; Operating instructions are included in the user No signature necessary
manual in this line.

f) maintenance information. Maintenance information of the PAVIRO system is No signature necessary


included in the user manual. in this line.

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

13.2.2 The manufacturer shall prepare design All of the mentioned design documentation is No signature necessary
documentation that shall be submitted to the available as for inspection by testing authorities. in this line.
testing authority together with the VACIE. This
documentation shall include drawings, parts
lists, block diagrams, circuit diagrams and a
functional description to such an extent that
compliance with this European Standard may
be checked and that a general assessment of
the mechanical and electrical design is made
possible.

13.3 Mechanical design requirements

13.3.1 The cabinet of the VACIE shall be of robust The emergency CALL STATION complies with this
construction consistent with the method of requirement. The installer has to ensure for
installation recommended in the implementing this requirement for 19-units, by
Installer checklist

documentation. It shall meet at least means of using a correct 19- frame, meeting at
classification IP30 of EN least classification IP30 of EN 60529:1991+A1:2000.
60529:1991+A1:2000.

13.3.2 All interconnections and settings inside the The installer has to ensure to install the system in a
cabinet shall be accessible at level 3. compliant rack with restricted access to the rear
panels.

13.3.3 The VACIE may be housed in more than one The mandatory controls and indicators are located
cabinet. If the documentation shows that the on the emergency CALL STATION.
cabinets may be installed in locations
distributed within the protected premises,
then all of the mandatory manual controls and
indicators shall be on one cabinet or on
cabinets declared to be only suitable for
mounting adjacent to each other.

EN 54-16 | en
21-Sep-2015 | 01 |

27
21-Sep-2015 | 01 |

28
Clause/Requirement EN 54-16:2008 Compliance Signature

13.3.4 All mandatory manual controls and light The emergency CALL STATION has paper slots

en | EN 54-16
emitting indicators shall be clearly labeled to below each of its programmable buttons. The
indicate their purpose. The labels shall be installer has to ensure providing proper labels that
legible at 0.8 m distance in an ambient light fit into these paper slots and implement this
intensity from 100 lux to 500 lux. requirement.

13.3.5 The terminations for transmission paths and All terminations for transmission paths are clearly No signature necessary
the fuses shall be clearly labeled. labeled on all of the PAVIRO system elements (near in this line.
the relevant connectors).

13.4 Electrical and other design requirements

13.4.1 The processing of signals shall give the Signals within the PAVIRO system have a configured
highest priority to the voice alarm condition. priority. The installer has to ensure to give the voice
alarm signals the highest priority.

13.4.2 Transitions between the main and the standby Transition between the main and standby power No signature necessary
Installer checklist

power sources shall not change any sources does not change any of the indications in this line.
indications and/or the state of any outputs, and/or state of any outputs of the PAVIRO system,
except those relating to the power supplies. except for the fault warning indication in order to
report the failure of a power source.

13.4.3 If the VACIE has provision for disconnecting or The installer has to ensure that these items are only No signature necessary
adjusting the main or the standby power accessible at access level 3 or 4. in this line.
source, this shall only be possible at access
level 3 or 4.

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

13.5 Integrity of transmission paths

13.5.1 A fault in any voice alarm transmission path The PAVIRO system has the following voice alarm
between the VACIE and other components of transmission paths between itself and other parts of
the voice alarm system shall not affect the the voice alarm system:
correct functioning of the VACIE or of any transmission path between CIE and PAVIRO
other voice alarm transmission path. system via input contact,
transmission path between FPA5000 and
PAVIRO via Ethernet,
transmission path between PAVIRO system and
the loudspeaker(s),
transmission path between PAVIRO controller
and emergency PAGING STATION.
If there is a fault in the transmission path between
the CIE and an input contact of the PAVIRO system,
Installer checklist

the configured action of the input contact will not


be automatically activated or deactivated. The
correct functioning of the PAVIRO system or of any
other voice alarm transmission path is therefore not
affected. The fault will be reported.
If there is a fault in the transmission path between
the PAVIRO system, i.e. the amplifier outputs and
the loudspeaker(s), the loudspeaker(s) will not be
able to produce the intended audio signal. However
the fault will not affect the correct functioning of
the PAVIRO system or any other voice alarm
transmission path. The fault will be reported, only.

13.5.2 A short circuit or an interruption in the The installer has to make sure to install the system
transmission path to the loudspeaker(s) shall accordingly.
not affect more than one voice alarm zone for

EN 54-16 | en
longer than 100 s following the occurrence of
21-Sep-2015 | 01 |

the fault.

29
21-Sep-2015 | 01 |

30
Clause/Requirement EN 54-16:2008 Compliance Signature

13.5.3 A single short circuit or an interruption in any We recommend to install the emergency CALL

en | EN 54-16
voice alarm transmission path between STATION inside of the cabinet. In case of
distributed cabinets of a VACIE shall not interruption of the transmission path to the
prevent the activation of a voice alarm output emergency CALL STATION the CONTROLLER will
condition to more than one voice alarm zone activate the system fault condition.
for longer than 100 s following the occurrence
of the fault.

13.5.4 If the VACIE is designed to be used with a If a 19-cabinet (rack) or adjacent cabinets provide
power supply (item L of Figure 1 of EN 54-1) enough space for the battery and/or charger, the
contained in a separate cabinet, then an installer can install the complete PSE (power supply
interface shall be provided for at least two equipment) as referred in EN 54-4 in one cabinet. In
voice alarm transmission paths to the power that case this requirement is not applicable.
supply, such that a short circuit or an In case the installer installs the backup part of the
interruption in one does not affect the other. PSE (battery and charger) in a separate cabinet,
Installer checklist

PAVIRO provides a separate DC-backup connection


on the PAVIRO units (Amplifiers). This implies that a
PAVIRO installation will always have two separate
power paths to the power supply: one for mains and
one for DC backup. Both will not influence each
other. For parts that do have only 24V DC
connectors (e.g. PAVIRO CONTROLLER), the PSE
needs to be in the same rack. It is the responsibility
of the installer to let the installation comply with
this requirement.

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

13.6 Accessibility of indications and controls

Four access levels shall be provided on the The Installer has to ensure to configure access
VACIE, from access level 1 (most accessible) levels described below.
to access level 4 (least accessible). Manual Access level 1 is intended for operational users of
controls at a given access level shall not be the PAVIRO system. It provides direct operational
accessible at a lower access level. The access to the unrestricted functionality of the
following shall apply: PAVIRO system via:
Input contacts of system components that have
level 1 functionality
The front panel menu of system components
(LED indications, acknowledge button)
A non emergency CALL STATION
Access level 2 is intended for advanced operational
users of the PAVIRO system. It provides operational
Installer checklist

access to the system after gaining access to a


physical part of the system. Access level 2 is
enforced for the access level 1 access points by
means of physical access control, which restricts
access to persons that possess the physical access
device (e.g. key, access card, et cetera).
Input contacts with physical access control; the
system components offering the input contacts
are located in a room/cabinet that is not
generally accessible
A emergency CALL STATION with physical
access control over the lock key. The key
switch has to be connected so the key can be
removed in locked position only. Use pin 1 and
pin 2 of the key switch.
A emergency CALL STATION with physical

EN 54-16 | en
access control; the CALL STATION is located in
21-Sep-2015 | 01 |

a room/cabinet that is not generally accessible

31
21-Sep-2015 | 01 |

32
Clause/Requirement EN 54-16:2008 Compliance Signature
Access level 3 is intended for installers and/or

en | EN 54-16
configurators of the PAVIRO system. It provides
access for hardware configuration and installation
of the PAVIRO system after physical access to the
rear of the rack
Physical access control by means of installing
the system elements in a restricted
environment, such as placing the 19-units in a
19-rack with key lock. This type of access can
be used for physical diagnosis of the system,
e.g. inspect interconnections.
Access level 4 is intended for maintenance
personnel of the PAVIRO system. It provides
software configuration and firmware upgrade of the
PAVIRO system components after logical
Installer checklist

identification. This level of access is offered


through:
The IRIS-Net PC software. At access level 4,
specialized configuration software is needed.

a) all mandatory indications shall be visible at All mandatory indications are placed on the
access level 1 without prior manual emergency CALL STATION. The installer has to
intervention (e.g. the need to open a door); ensure to mount the emergency CALL STATION on a
suitable place. If the CALL STATION is installed in a
cabinet with a front door, the door must be a glass
door.

b) manual controls at access level 1 shall be The installer has to ensure to enable access level 1
accessible without special procedures; controls without special procedures.

c) indications and manual controls that are All PAVIRO indications (LEDs, equipment connected
mandatory at access level 1 shall also be to output contacts, front panel indication, LC
accessible at access level 2; display) and manual controls (input contacts, CALL
STATION buttons) that are accessible at access
level 1 are also be accessible at access level 2.

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

d) entry to access level 2 shall be restricted The installer has to ensure to enable access level 2
by a special procedure; controls with special procedures.

e) entry to access level 3 shall be restricted Entry to access level 3 is restricted by limiting
by a special procedure, differing from that for access to the rear of the rack. Correct configuration
access level 2; and installation (physical access control) will ensure
that the special procedure differs from that of
access level 2. The system administrator should
define different users in IRIS-Net. The installer
should ensure that the physical access procedure
differs from that of the physical access procedure of
access level 2.

f) the entry to access level 4 shall be The IRIS-Net PC software. At access level 4, a
restricted by special means which are not part password is needed.
of the VACIE.
Installer checklist

NOTE Further access levels are permitted


provided that they are distinct from the
access levels described in this standard.

13.7 Indications by means of light-emitting


indicators

13.7.1 Mandatory indications from light emitting The emergency CALL STATION fulfills the
indicators shall be visible in an ambient light requirements.
intensity up to 500 lux, at any angle up to The installer has to ensure to put the emergency
22.5 from a line through the indicator CALL STATION on a place where the requirements
perpendicular to its mounting surface are met also. E.g. installation behind a class door.
at 3 m distance for the general No dark glass. Avoid installation on top or bottom of
indications of functional condition, the rack.
at 3 m distance for the indication of the
supply of power,

EN 54-16 | en
and
21-Sep-2015 | 01 |

at 0.8 m distance for other indications.

33
21-Sep-2015 | 01 |

34
Clause/Requirement EN 54-16:2008 Compliance Signature

13.7.2 If flashing indications are used, both the on The emergency CALL STATION fulfils the No signature necessary

en | EN 54-16
period and the off period shall be greater than requirements in this line.
or equal to 0.25 s, and the frequencies of
flash shall not be less than
1 Hz for voice alarm indications, and
0.2 Hz for fault indications.

13.8 Indications on alphanumeric displays

13.8.1 If an alphanumeric display consists of The LCD of the emergency CALL STATION does not No signature necessary
elements or segments, the failure of one of consists of elements or segments. in this line.
these shall not affect the interpretation of the
displayed information.

13.8.2 If an alphanumeric display is used to display The display of the emergency CALL STATION is used No signature necessary
mandatory indications, it shall be clear and for indicating the different statuses. Therefore each in this line.
unambiguous. displayed information has a separate term.
Installer checklist

13.8.3 Mandatory indications on an alphanumeric The emergency CALL STATION fulfills the
display shall be legible for at least one hour requirements and the indication stays on as long as
following the display of a new indication of the system is in the corresponding condition.
the voice alarm condition and at least 5 The installer has to ensure to put the emergency
minutes for fault or disablement conditions, at CALL STATION on a place there the requirements
0,8 m distance, in ambient light intensities are met also. E.g. installation behind a glass door.
from 5 to 500 lux, at any angle from the No dark glass. Avoid installation on top or bottom of
normal to the plane of the display up to the rack.
22.5 when viewed from each side, and
15 when viewed from above and below.

13.9 Indication colors

13.9.1 The colors of the general and specific No signature necessary


indications from light emitting indicators shall in this line.
be

a) red for indications of voice alarms; The alarm LED of the emergency CALL STATIONs is No signature necessary
on (red) when the system is in the voice alarm in this line.

EN 54-16
condition.
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

b) yellow for indications of fault warnings The Fault LED of the emergency CALL STATIONs is No signature necessary
on (yellow) when the system is in the fault warning in this line.
condition.

c) green for the indication that the VACIE is All light emitting indicators of the PAVIRO system No signature necessary
supplied with power. that indicate power supply are green. in this line.

NOTE Where voice alarm automatic message No signature necessary


status indicators are provided, it may be in this line.
advantageous to indicate the difference
between evacuation and alert messages. In
this case, red will be used for emergency
messages and yellow may be used for alert
messages.

13.9.2 The use of different colors is not necessary for The LCD used in the emergency CALL STATION No signature necessary
indications on alphanumeric displays. does not use different colors for indications. in this line.
Installer checklist

However, if different colors are used for


different indications, the colors used shall be
as specified in 13.9.1.

13.10 Audible indications

13.10.1 Audible indicators shall be part of the VACIE. The sounder in the emergency CALL STATION will No signature necessary
The same device may be used for voice alarm be used for both indications. in this line.
zone activated and fault warning indications.

13.10.2 The minimum sound pressure level, measured The emergency CALL STATION fulfills the
under anechoic conditions at a distance of 1 requirements.
m, with any access door(s) on the VACIE The installer has to ensure to put the emergency
closed, shall be CALL STATION on a place where the requirements
60 dBA for the voice alarm condition, and are met also. E.g. installation behind a glass door.
50 dBA for the fault warning condition.

EN 54-16 | en
13.11 Indicator testing
21-Sep-2015 | 01 |

35
21-Sep-2015 | 01 |

36
Clause/Requirement EN 54-16:2008 Compliance Signature

All mandatory visible and audible indicators PAVIRO provides an LED test via the menu on the No signature necessary

en | EN 54-16
shall be testable by a manual operation at emergency CALL STATION at access level 1. This in this line.
access level 1 or 2. indicator test is a local test.
When activated all indications on that emergency
CALL STATION and all its connected emergency
CALL STATION EXTENSIONS are switched on to
visually and audible check the indicators.

13.12 Audio performance

13.12.1 Output power The output power of the amplifier elements of the No signature necessary
The VACIE output power shall be as declared PAVIRO system are specified in the data sheets and in this line.
by the manufacturer. user manuals.

13.12.2 Signal-to-noise ratio The A-weighted signal-to-noise ratio of the PAVIRO No signature necessary
The VACIE shall have an A-weighted signal-to- amplifiers is specified in the data sheets and in the in this line.
noise ratio of at least 45 dB (see IEC manuals. The signal-to-noise ratio is above 100 dB.
Installer checklist

60268-1). The complete signal chain from microphone to


loudspeaker is compliant to this clause.

13.12.3 Frequency response The default settings of the audio filters in IRIS-Net
The frequency response of the VACIE shall fit ensure the correct frequency response of all sound
within the nonshaded area in Figure 1 for paths. If the default settings are edited in IRIS-Net,
sound sources without microphone(s) (e.g. the installer has to ensure that the frequency
message store) and Figure 2 for sound response still fits within the non-shaded area in
sources with microphone(s). Figure 1 and 2.
NOTE The frequency response limits exclude
loudspeakers.
NOTE A bandwidth of 400 Hz to 4 kHz is
sufficient to achieve acceptable intelligibility
in some acoustic environments. However, a
higher frequency limit may be necessary to
achieve acceptable intelligibility in more
difficult acoustic environments due, for
example, to the masking effect caused by

EN 54-16
reverberation and/or ambient noise.
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

13.13 Message store(s)

Pre-recorded messages shall be stored in non- The pre-recorded messages are digitally stored on a
volatile memory that retains the messages EEPROM/Flash in uncompressed format (PCM, 16-
when all power sources are removed. bit). This EEPROM/Flash retains the messages when
NOTE The use of tapes or magnetic or optical all power sources are removed.
data disks for the storage of emergency
messages is not acceptable at the time of
drafting this European Standard (see Annex
C)

13.14 Redundant power amplifiers

13.14.1 The VACIE may have provision for at least one No signature necessary
spare power amplifier. In this case: in this line.

a) in the event of the failure of a power The installer has to ensure to configure spare
Installer checklist

amplifier, the faulty amplifier shall be capable amplifier switching accordingly.


of being replaced automatically with a spare
amplifier withing 10 s of the fault being
detected;
NOTE: This can be achieved, for example, by
switching or by permanently connected
parallel amplifiers.

b) the spare power amplifier(s) shall have at The installer has to ensure to include a spare
least the same functionality and output power amplifier with at least the same output power.
as the replaced amplifier.

13.14.2 Every fault of an amplifier shall be indicated The installer has to ensure to enable supervision on
by the general fault warning indicator as the spare amplifier.
specified in 8.2

13.14.3 Supervision of the spare amplifier(s) shall be Supervision on spare amplifiers works with both No signature necessary

EN 54-16 | en
maintained during the functional condition conditions. in this line.
21-Sep-2015 | 01 |

whilst the VACIE is powered by either the


mains or standby power supplies.

37
21-Sep-2015 | 01 |

38
en | EN 54-16
3.10 14 Additional design requirements for software controlled VACIE
Clause/Requirement EN 54-16:2008 Compliance Signature

14.1 General requirements and manufacturers


declarations

In order to fulfill requirements of this The PAVIRO system is controlled by compliant No signature necessary
European Standard the VACIE may contain software. in this line.
elements which are controlled by software. In
this case, the VACIE shall comply with the
requirements of Clause 13 and this clause
where relevant to the technology used.

14.2 Software documentation


Installer checklist

EN 54-16
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

14.2.1 The manufacturer shall prepare Design and development documents have been No signature necessary
documentation that gives an overview of the provided and approved by certification authority. in this line.
software design, which shall be submitted to
the testing authority together with the VACIE.
This documentation shall be in sufficient
detail for the design to be inspected for
compliance with this European Standard and
shall comprise at least the following:
a) functional description, using a clear
methodology appropriate to the nature of the
software, e.g. graphical representations of the
system design, data flows and control flows
and of the main program flow, including:
1) a brief description of each module and the
tasks it performs,
Installer checklist

2) the way in which the modules interact,


3) the way in which the modules are called,
including any interrupt processing, and
4) the overall hierarchy of the program;
b) a description of which areas of memory are
used for the various purposes (e.g. the
program, site specific data and running data);
c) a description of how the software interacts
with the hardware of the VACIE.
Where dynamic memory management is
employed, a separation shall be implemented
between the program, site specific data and
running data and this shall be described in
connection with the method of memory
allocation.

EN 54-16 | en
21-Sep-2015 | 01 |

39
21-Sep-2015 | 01 |

40
Clause/Requirement EN 54-16:2008 Compliance Signature

14.2.2 The manufacturer shall prepare and maintain Documents have been inspected and approved by No signature necessary

en | EN 54-16
detailed design documentation. This need not certification authority. in this line.
be submitted to the testing authority but shall
be available for inspection in a manner which
respects the manufacturer's rights of
confidentiality.
This documentation shall comprise at least
the following:
a) a description of each module of the
program, as it is implemented in the source
code of the program, containing:
1) the name of the module, and
2) the identification of the author(s);
b) the source code listing, including all global
and local variables, constants and labels used,
Installer checklist

and sufficient comment for the program flow


to be recognized;
c) details of any software tools used in the
preparation of the program (e.g. high level
design tools, compilers, assemblers).

14.3 Software design

In order to ensure the reliability of the VACIE PAVIRO is built on a modular structure. No signature necessary
the following requirements for software Not relevant, there is no manually or automatically in this line.
design shall apply: generated data.
a) the software shall have a modular PAVIRO is equipped with a watchdog which will
structure; signalize a deadlock and automatically carry out a
b) the design of the interfaces for manually reset.
and automatically generated data shall not
permit invalid data to cause an error in the
program execution;
c) the software shall be designed to avoid the
occurrence of a deadlock in the program flow.

EN 54-16
14.4 Program monitoring (see also Annex C)
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

14.4.1 The execution of the program shall be Upon activation of a watchdog, a fault is reported No signature necessary
monitored as under 14.4.2 or 14.4.3. If after restart of the failing component. A system fault in this line.
routines associated with the main functions of is indicated when entering the fault condition.
the program are no longer executed, either or Upon activation of a watchdog, a fault is reported
both of the following shall apply: after restart of the failing component indicating the
a) the VACIE shall indicate a system fault (as failing component.
in 8.3);
b) the VACIE shall enter the fault warning
condition and indicate faults of affected
supervised functions (as in 8.2.3, 8.2.4, 8.3,
8.4 and 8.5), where only these functions are
affected.

14.4.2 If the program executes in one processor, the All processors used in the PAVIRO system are either No signature necessary
execution of the routines in 14.4.1, it shall be guarded by a hardware watchdog or are monitored in this line.
Installer checklist

monitored by a monitoring device as in 14.4.4. by a processor that is guarded by a hardware


watchdog.

14.4.3 If the program executes in more than one The network controller is responsible for monitoring No signature necessary
processor, the execution of the routines in all processors in the system. Upon failure of one of in this line.
14.4.1 shall be monitored in each processor. A the processors, either due to a watchdog failure or
monitoring device as in 14.4.4 shall be due to a communication failure a fault is generated.
associated with one or more processors, and Failure of the network controller itself will cause the
at least one such processor shall monitor the system fault output contact to be de-activated to
functioning of any processor not associated indicate a system fault.
with such a monitoring device.

14.4.4 The monitoring device of 14.4.2 and 14.4.3 All components that have a processor have an No signature necessary
shall have a time-base independent of that of external watchdog. in this line.
the monitored system. The functioning of the
monitoring device, and the signaling of a fault
warning, shall not be prevented by a failure in

EN 54-16 | en
the execution of the program of the
21-Sep-2015 | 01 |

monitored system.

41
21-Sep-2015 | 01 |

42
Clause/Requirement EN 54-16:2008 Compliance Signature

14.4.5 In the event of a system fault as specified in Safe state is included at all components. No signature necessary

en | EN 54-16
14.4.1 a) or 14.6, those parts of the VACIE in this line.
affected shall enter a safe state not later than
the indication of the system fault. This safe
state shall not result in the false activation of
mandatory outputs.

14.5 The storage of programs and data (see also


Annex C)

14.5.1 All executable code and data necessary to According to the datasheet of the memory more No signature necessary
comply with this European Standard shall be than 10 years. in this line.
held in memory that is capable of continuous,
unmaintained, reliable operation for a period
of at least 10 years.

14.5.2 For the program, the following requirements No signature necessary


Installer checklist

shall apply: in this line.

a) the program shall be held in non-volatile The program is stored in a non-volatile memory. No signature necessary
memory, which can only be written to at Configuring requires access level 4. in this line.
access level 4, and

b) it shall be possible to identify the version Version reference can be read out at access level 3. No signature necessary
reference or references of the program at in this line.
access level 3. The version reference or
references shall be in accordance with the
documentation of 14.2.1.

14.5.3 For site-specific data, including emergency No signature necessary


message(s), the following requirements shall in this line.
apply:

a) the alteration of site specific data shall only Responsibility of the installer to maintain site data.
be possible at access level 3 or 4;

b) the alteration of site specific data shall not The configuration is a data set that cannot alter the No signature necessary

EN 54-16
affect the structure of the program; program itself in this line.
EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

c) if stored in read-write memory, there shall There is an EEPROM/Flash which holds No signature necessary
be a mechanism which prevents the memory configuration and program data. This is copied to in this line.
being written to during normal operation at RAM, this RAM is used during operation. The
access level 1 or 2, such that its contents are EEPROM/Flash is supervised.
protected during a failure in program
execution;

d) It shall be possible to either read or With specialized software at access level 3 the No signature necessary
interrogate the site specific data at access configuration can be read out. in this line.
level 2 or 3, or the site specific data shall be
given a version reference that shall be
updated when each set of alterations is
carried out.

e) If the site specific data has a version No version reference. No signature necessary
reference, it shall be possible to identify this in this line.
Installer checklist

at access level 2 or 3.

14.6 Monitoring of memory contents

The contents of the memories containing the There is a checksum on this data which is checked No signature necessary
site specific data shall be automatically every 1 hour. in this line.
checked at intervals not exceeding 1 h. The
checking device shall signal a system fault if a
corruption of the memory contents is
detected.

EN 54-16 | en
21-Sep-2015 | 01 |

43
21-Sep-2015 | 01 |

44
3.11 15 Marketing

en | EN 54-16
Clause/Requirement EN 54-16:2008 Compliance Signature

The VACIE shall be marked with the No signature necessary in this


following information, line.
which shall be legible at access level 1:

a) the number of this European Standard; Marking the PAVIRO system with the number of this
European standard (which is legible at access level 1) is
the responsibility of the installer, since the installer will
have to install and configure the system properly in order
to let the installation comply with this standard.

b) the name or trademark of the The name BOSCH is visible on each unit of the PAVIRO
manufacturer or supplier; system. It is the responsibility of the installer to ensure
that this name is legible at access level 1 for all system
elements.
Installer checklist

c) the type number or other designation of The type number of each unit of the PAVIRO system is
the VACIE. present on the unit itself. The installer is responsible for
ensuring that this type number is legible at access level
1.

It shall be possible to identify a code or The serial numbers of each unit gives information about
number that identifies the production the production period. This serial number is visible on
period of the VACIE at access level 1 or 2 or the type number plate of each unit of the PAVIRO system.
3. The installer is responsible for ensuring that this type
number plate is identifiable at access level 1, 2 or 3.

NOTE Where Annex ZA.3 covers the same No signature necessary in this
requirements as this clause, the line.
requirements of this clause are met.

3.12 16 Tests
All applicable tests are carried out in an accredited test lab.

EN 54-16
Bosch Security Systems B.V.
Torenallee 49
5617 BA Eindhoven
The Netherlands
www.boschsecurity.com
Bosch Security Systems B.V., 2015