You are on page 1of 24

LIME_PLC_08AUG2013 / Program_Block (OB1)

Block: Program_Block
Author:
Created: 06/26/2013 03:00:16 pm
Last Modified: 10/29/2013 04:04:49 pm

Symbol Var Type Data Type Comment


TEMP
TEMP
TEMP
TEMP

PROGRAM COMMENTS
Network 1 Network Title
Network Comment

HL_3:I3.1 BUNK_HI_LVL:Q0.0

Symbol Address Comment


BUNK_HI_LVL Q0.0 BUNKER LEVEL HIGH
HL_3 I3.1 LEVEL SWITCH 3

Network 2

BUNK_HI_LVL:Q0.0 SYS_HLTY:Q3.2
/

Symbol Address Comment


BUNK_HI_LVL Q0.0 BUNKER LEVEL HIGH
SYS_HLTY Q3.2 SYSTEM HEALTHY

1 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 3
FOR FLASHING FAULT ON PANEL ON MOTOR TRIP

CFAN1_TRP :I0.4 FAULT_1:M0.0

CFAN2_TRP :I2.6

CRUSHER_TRP:I1.0

RAL1_TRP :I0.6

RAL2_TRIP :I3.0

Symbol Address Comment


CFAN1_TRP I0.4 BIN VENT FAN 1 SILO TRIP
CFAN2_TRP I2.6 BIN VENT FAN 2 TRIP
CRUSHER_TRP I1.0 LIME CRUSHER TRIP
FAULT_1 M0.0 MOTOR FAULT
RAL1_TRP I0.6 RAL1 TRIP
RAL2_TRIP I3.0 RAL2 TRIP

2 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 4
FOR FLASHING FAULT ON PANEL ON VALVE OPEN/CLOSE FAILURE

DPTVENT_O~:M0.4 FAULT_2:M0.1
S OUT
RS
DPTVENT_CL~:M0.5

MAT_IN_V1_~:M0.6

MAT_IN_V1_~:M0.7

MAT_IN_V2_~:M1.0

MAT_IN_V2_~:M1.1

MAT_OUT_O~:M1.2

MAT_OUT_CL~:M1.3

T53
R1

Symbol Address Comment


DPTVENT_CLS_FAIL M0.5 DPT VENT FAILED TO CLOSE
DPTVENT_OPN_FAIL M0.4 DPT VENT FAILED TO OPEN
FAULT_2 M0.1 MATERIAL VALVE FAULT
MAT_IN_V1_CLS_FAIL M0.7 MATERIAL INLET VALVE V1 FAILED TO CLOSE
MAT_IN_V1_OPN_FAIL M0.6 MATERIAL INLET VALVE V1 FAILED TO OPEN
MAT_IN_V2_CLS_FAIL M1.1 MATERIAL INLET VALVE V2 FAILED TO CLOSE
MAT_IN_V2_OPN_FAIL M1.0 MATERIAL INLET VALVE V2 FAILED TO OPEN
MAT_OUT_CLS_FAIL M1.3 MATERIAL OUTLET V/V FAILED CLOSE
MAT_OUT_OPN_FAIL M1.2 MATERIAL OUTLET V/V FAILED OPEN

Network 5

FAULT_2:M0.1 FLT2_FL_TMR:T52
IN TON

+10 PT 100 ms

Symbol Address Comment


FAULT_2 M0.1 MATERIAL VALVE FAULT
FLT2_FL_TMR T52 FAULT 2 FLASH TIMER

3 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 6

FLT2_FL_TMR:T52 T53
IN TOF

+10 PT 100 ms

Symbol Address Comment


FLT2_FL_TMR T52 FAULT 2 FLASH TIMER

Network 7

DFV_PR_HI:I2.3 LINE_BLK:T56
IN TON

+1800 PT 100 ms

Symbol Address Comment


DFV_PR_HI I2.3 DFV PRESSURE HIGH
LINE_BLK T56 LINE BLOCK TIMER

Network 8
FOR FLASHING FAULT ON PANEL ON LINE BLOCK

LINE_BLK:T56 FAULT_3:M0.3
S OUT
RS
T55
R1

Symbol Address Comment


FAULT_3 M0.3 LINE BLOCK
LINE_BLK T56 LINE BLOCK TIMER

Network 9

FAULT_3:M0.3 T54
IN TON

+10 PT 100 ms

Symbol Address Comment


FAULT_3 M0.3 LINE BLOCK

4 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 10

T54 T55
IN TOF

+50 PT 100 ms

Network 11
SYSTEM FAULT LAMP INDICATION ONLY

FAULT_1:M0.0 SYS_FLT:Q3.3

FAULT_2:M0.1

FAULT_3:M0.3

Symbol Address Comment


FAULT_1 M0.0 MOTOR FAULT
FAULT_2 M0.1 MATERIAL VALVE FAULT
FAULT_3 M0.3 LINE BLOCK
SYS_FLT Q3.3 SYSTEM FAULT

Network 12

EMG_ON:I3.6 EMG_STP:Q3.0

Symbol Address Comment


EMG_ON I3.6 EMERGENCY PUSH BUTTON PRESSED
EMG_STP Q3.0 EMERGENCY STOP INDICATION

5 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 13

CFAN1_OND:T40 SYS_STR_BIT:Q4.5 CFAN1_ON_C~ :Q0.3


S OUT
RS
EMG_STP:Q3.0
R1

SYS_STP:I4.0
/

HL_3:I3.1

Symbol Address Comment


CFAN1_ON_CMD Q0.3 CFAN 1 ON COMMAND
CFAN1_OND T40 CFAN 1 ON DELAY
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_3 I3.1 LEVEL SWITCH 3
SYS_STP I4.0 SYSTEM STOP
SYS_STR_BIT Q4.5 SYSTEM START BIT

Network 14

CFAN2_ON:I2.5 CFAN1_OND:T40
IN TON

+50 PT 100 ms

Symbol Address Comment


CFAN1_OND T40 CFAN 1 ON DELAY
CFAN2_ON I2.5 BIN VENT FAN 2 RUN FEEDBACK

6 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 15

CFAN2_OND:T41 CFAN2_ON_C~ :Q2.3


S OUT
RS
EMG_STP:Q3.0
R1

SYS_STP:I4.0
/

HL_3:I3.1

Symbol Address Comment


CFAN2_ON_CMD Q2.3 CFAN 2 ON COMMAND
CFAN2_OND T41 CFAN 2 ON DELAY
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_3 I3.1 LEVEL SWITCH 3
SYS_STP I4.0 SYSTEM STOP

Network 16

CFAN1_ON:I0.3 CRUSHER_ON~:T42
IN TON

+100 PT 100 ms

Symbol Address Comment


CFAN1_ON I0.3 BIN VENT FAN 1 RUN FEEDBACK
CRUSHER_OND T42 CRUSHER ON DELAY

7 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 17

CRUSHER_ON~:T42 CRUSHER_O~:Q0.5
S OUT
RS
EMG_STP:Q3.0
R1

SYS_STP:I4.0
/

HL_2:I2.4

HL_3:I3.1

MAT_IN_V1_O~:I1.3
/

MAT_IN_V2_O~:I1.5
/

Symbol Address Comment


CRUSHER_ON_CMD Q0.5 LIME CRUSHER ON COMMAND
CRUSHER_OND T42 CRUSHER ON DELAY
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_2 I2.4 LEVEL SWITCH 2
HL_3 I3.1 LEVEL SWITCH 3
MAT_IN_V1_OPN I1.3 MATERIAL INLET V/V V1 OPEN FEEDBACK
MAT_IN_V2_OPN I1.5 MATERIAL INLET V/V V2 OPEN FEEDBACK
SYS_STP I4.0 SYSTEM STOP

Network 18

CRUSHER_ON:I0.7 RAL1_OND:T43
IN TON

+50 PT 100 ms

Symbol Address Comment


CRUSHER_ON I0.7 LIME CRUSHER RUN FEEDBACK
RAL1_OND T43 RAL 1 ON DELAY

8 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 19

RAL1_OND:T43 RAL1_ON_CM~ :Q0.4


S OUT
RS
EMG_STP:Q3.0
R1

HL_2:I2.4

SYS_STP:I4.0
/

CRUSHER_ON:I0.7
/

HL_2:I2.4

Symbol Address Comment


CRUSHER_ON I0.7 LIME CRUSHER RUN FEEDBACK
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_2 I2.4 LEVEL SWITCH 2
RAL1_ON_CMD Q0.4 RAL 1 ON COMMAND
RAL1_OND T43 RAL 1 ON DELAY
SYS_STP I4.0 SYSTEM STOP

Network 20

RAL2_ON:I2.7 CFAN2_OND:T41
IN TON

+100 PT 100 ms

Symbol Address Comment


CFAN2_OND T41 CFAN 2 ON DELAY
RAL2_ON I2.7 RAL2 RUN FEEDBACK

9 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 21

SYS_STR_BIT:Q4.5 RAL2_ON_CM~ :Q2.4


S OUT
RS
EMG_STP:Q3.0
R1

SYS_STP:I4.0
/

BFSC_RDY :M1.6
/

Symbol Address Comment


BFSC_RDY M1.6
EMG_STP Q3.0 EMERGENCY STOP INDICATION
RAL2_ON_CMD Q2.4 RAL 2 ON COMMAND
SYS_STP I4.0 SYSTEM STOP
SYS_STR_BIT Q4.5 SYSTEM START BIT

10 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 22

SYS_STR_BIT:Q4.5 CON_ON_CMD:Q3.1
S OUT
RS
EMG_STP:Q3.0
R1

SYS_STP:I4.0
/

HL_3:I3.1

LINE_BLK:T56

CFAN1_ON:I0.3
/

CFAN2_ON:I2.5
/

DPTVENT_O~:M0.4

DPTVENT_CL~:M0.5

MAT_IN_V1_~:M0.6

MAT_IN_V1_~:M0.7

MAT_IN_V2_~:M1.0

MAT_IN_V2_~:M1.1

MAT_OUT_O~:M1.2

MAT_OUT_CL~:M1.3

Symbol Address Comment


CFAN1_ON I0.3 BIN VENT FAN 1 RUN FEEDBACK
CFAN2_ON I2.5 BIN VENT FAN 2 RUN FEEDBACK
CON_ON_CMD Q3.1 CONVEYING ON COMMAND

11 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

DPTVENT_CLS_FAIL M0.5 DPT VENT FAILED TO CLOSE


DPTVENT_OPN_FAIL M0.4 DPT VENT FAILED TO OPEN
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_3 I3.1 LEVEL SWITCH 3
LINE_BLK T56 LINE BLOCK TIMER
MAT_IN_V1_CLS_FAIL M0.7 MATERIAL INLET VALVE V1 FAILED TO CLOSE
MAT_IN_V1_OPN_FAIL M0.6 MATERIAL INLET VALVE V1 FAILED TO OPEN
MAT_IN_V2_CLS_FAIL M1.1 MATERIAL INLET VALVE V2 FAILED TO CLOSE
MAT_IN_V2_OPN_FAIL M1.0 MATERIAL INLET VALVE V2 FAILED TO OPEN
MAT_OUT_CLS_FAIL M1.3 MATERIAL OUTLET V/V FAILED CLOSE
MAT_OUT_OPN_FAIL M1.2 MATERIAL OUTLET V/V FAILED OPEN
SYS_STP I4.0 SYSTEM STOP
SYS_STR_BIT Q4.5 SYSTEM START BIT

Network 23

MAT_IN_V2_O~:I1.5 DPTVENT_O~:Q0.6
S OUT
RS
HL_2:I2.4
R1

LINE_BLK:T56

DFV_PR_HI:I2.3

CFAN1_ON:I0.3
/

Symbol Address Comment


CFAN1_ON I0.3 BIN VENT FAN 1 RUN FEEDBACK
DFV_PR_HI I2.3 DFV PRESSURE HIGH
DPTVENT_ON_CMD Q0.6 DPT VENT OPEN/CLOSE COMMAND
HL_2 I2.4 LEVEL SWITCH 2
LINE_BLK T56 LINE BLOCK TIMER
MAT_IN_V2_OPN I1.5 MATERIAL INLET V/V V2 OPEN FEEDBACK

Network 24

DPTVENT_O~:Q0.6 T44
IN TON

+300 PT 100 ms

Symbol Address Comment


DPTVENT_ON_CMD Q0.6 DPT VENT OPEN/CLOSE COMMAND

12 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 25

T44 DPTVENT_OPN:I1.1 DPTVENT_O~:M0.4


/

Symbol Address Comment


DPTVENT_OPN I1.1 DPT VENT VALVE OPEN FEEDBACK
DPTVENT_OPN_FAIL M0.4 DPT VENT FAILED TO OPEN

Network 26

DPTVENT_O~:Q0.6 T45
/ IN TON

+300 PT 100 ms

Symbol Address Comment


DPTVENT_ON_CMD Q0.6 DPT VENT OPEN/CLOSE COMMAND

Network 27

T45 DPTVENT_CLS:I1.2 DPTVENT_CL~:M0.5


/

Symbol Address Comment


DPTVENT_CLS I1.2 DPT VENT VALVE CLOSE FEEDBACK
DPTVENT_CLS_FAIL M0.5 DPT VENT FAILED TO CLOSE

Network 28

MAT_IN_V2_O~:I1.5 MAT_IN_V1_~ :Q0.7


S OUT
RS
EMG_STP:Q3.0
R1

HL_2:I2.4

CON_ON_CMD:Q3.1
/

Symbol Address Comment


CON_ON_CMD Q3.1 CONVEYING ON COMMAND
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_2 I2.4 LEVEL SWITCH 2
MAT_IN_V1_ON_CMD Q0.7 MATERIAL INLET V1 OPEN/CLOSE COMMAND
MAT_IN_V2_OPN I1.5 MATERIAL INLET V/V V2 OPEN FEEDBACK

13 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 29

MAT_IN_V1_~:Q0.7 T46
/ IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_IN_V1_ON_CMD Q0.7 MATERIAL INLET V1 OPEN/CLOSE COMMAND

Network 30

T46 MAT_IN_V1_O~:I1.3 MAT_IN_V1_~ :M0.6


/

Symbol Address Comment


MAT_IN_V1_OPN I1.3 MATERIAL INLET V/V V1 OPEN FEEDBACK
MAT_IN_V1_OPN_FAIL M0.6 MATERIAL INLET VALVE V1 FAILED TO OPEN

Network 31

MAT_IN_V1_~:Q0.7 T47
IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_IN_V1_ON_CMD Q0.7 MATERIAL INLET V1 OPEN/CLOSE COMMAND

Network 32

T47 MAT_IN_V1_C~:I1.4 MAT_IN_V1_~ :M0.7


/

Symbol Address Comment


MAT_IN_V1_CLS I1.4 MATERIAL INLET V/V V1 CLOSE FEEDBACK
MAT_IN_V1_CLS_FAIL M0.7 MATERIAL INLET VALVE V1 FAILED TO CLOSE

14 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 33

CON_ON_CMD:Q3.1 MAT_IN_V2_~ :Q1.0


S OUT
RS
EMG_STP:Q3.0
R1

SYS_FLT:Q3.3

HL_2:I2.4

SYS_STP:I4.0
/

AIR_PUR_ON~ :Q2.0

DFV_PR_HI:I2.3

Symbol Address Comment


AIR_PUR_ON_CMD Q2.0 PURGE VALVE OPEN/CLOSE COMMAND
CON_ON_CMD Q3.1 CONVEYING ON COMMAND
DFV_PR_HI I2.3 DFV PRESSURE HIGH
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_2 I2.4 LEVEL SWITCH 2
MAT_IN_V2_ON_CMD Q1.0 MATERIAL INLET V2 OPEN/CLOSE COMMAND
SYS_FLT Q3.3 SYSTEM FAULT
SYS_STP I4.0 SYSTEM STOP

Network 34

MAT_IN_V2_~:Q1.0 T48
/ IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_IN_V2_ON_CMD Q1.0 MATERIAL INLET V2 OPEN/CLOSE COMMAND

15 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 35

T48 MAT_IN_V2_O~:I1.5 MAT_IN_V2_~ :M1.0


/

Symbol Address Comment


MAT_IN_V2_OPN I1.5 MATERIAL INLET V/V V2 OPEN FEEDBACK
MAT_IN_V2_OPN_FAIL M1.0 MATERIAL INLET VALVE V2 FAILED TO OPEN

Network 36

MAT_IN_V2_~:Q1.0 T49
IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_IN_V2_ON_CMD Q1.0 MATERIAL INLET V2 OPEN/CLOSE COMMAND

Network 37

T49 MAT_IN_V2_C~:I2.0 MAT_IN_V2_~ :M1.1


/

Symbol Address Comment


MAT_IN_V2_CLS I2.0 MATERIAL INLET V/V V2 CLOSE FEEDBACK
MAT_IN_V2_CLS_FAIL M1.1 MATERIAL INLET VALVE V2 FAILED TO CLOSE

16 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 38

HL_2:I2.4 MAT_OUT_O~:Q1.1
S OUT
RS
DFV_PR_HI:I2.3

CON_ON_CMD:Q3.1
/ R1

DFV_PR_HI:I2.3
/

EMG_STP:Q3.0
/

Symbol Address Comment


CON_ON_CMD Q3.1 CONVEYING ON COMMAND
DFV_PR_HI I2.3 DFV PRESSURE HIGH
EMG_STP Q3.0 EMERGENCY STOP INDICATION
HL_2 I2.4 LEVEL SWITCH 2
MAT_OUT_ON_CMD Q1.1 MATERIAL OUTLET VALVE OPEN/CLOSE COMMAND

Network 39

MAT_OUT_O~:Q1.1 T50
IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_OUT_ON_CMD Q1.1 MATERIAL OUTLET VALVE OPEN/CLOSE COMMAND

Network 40

T50 MAT_OUT_OPN:I2.1 MAT_OUT_O~:M1.2


/

Symbol Address Comment


MAT_OUT_OPN I2.1 MATERIAL OUTLET V/V OPEN FEEDBACK
MAT_OUT_OPN_FAIL M1.2 MATERIAL OUTLET V/V FAILED OPEN

17 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 41

MAT_OUT_O~:Q1.1 T51
/ IN TON

+300 PT 100 ms

Symbol Address Comment


MAT_OUT_ON_CMD Q1.1 MATERIAL OUTLET VALVE OPEN/CLOSE COMMAND

Network 42

T51 MAT_OUT_CLS:I2.2 MAT_OUT_CL~:M1.3

Symbol Address Comment


MAT_OUT_CLS I2.2 MATERIAL OUTLET V/V CLOSE FEEDBACK
MAT_OUT_CLS_FAIL M1.3 MATERIAL OUTLET V/V FAILED CLOSE

18 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 43

MAT_IN_V1_C~ :I1.4 MAT_IN_V2_C~:I2.0 DFV_PR_HI:I2.3 DPTVENT_CLS:I1.2 MAT_OUT_OPN:I2.1

EMG_STP:Q3.0
43.A

CON_ON_CMD:Q3.1
/

SYS_STP:I4.0
/

AIR_PUR_ON~:Q2.0
S OUT
RS

43.A R1

Symbol Address Comment


AIR_PUR_ON_CMD Q2.0 PURGE VALVE OPEN/CLOSE COMMAND
CON_ON_CMD Q3.1 CONVEYING ON COMMAND
DFV_PR_HI I2.3 DFV PRESSURE HIGH
DPTVENT_CLS I1.2 DPT VENT VALVE CLOSE FEEDBACK
EMG_STP Q3.0 EMERGENCY STOP INDICATION
MAT_IN_V1_CLS I1.4 MATERIAL INLET V/V V1 CLOSE FEEDBACK
MAT_IN_V2_CLS I2.0 MATERIAL INLET V/V V2 CLOSE FEEDBACK
MAT_OUT_OPN I2.1 MATERIAL OUTLET V/V OPEN FEEDBACK
SYS_STP I4.0 SYSTEM STOP

19 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 44

MAT_OUT_CLS:I2.2 AIR_IN_ON_C~ :Q2.5


S OUT
RS
DFV_PR_HI:I2.3
/

Q4.3
/ R1

CON_ON_CMD:Q3.1
/

DFV_PR_HI:I2.3

Symbol Address Comment


AIR_IN_ON_CMD Q2.5 AIR INLET VALVE OPEN/CLOSE COMMAND
CON_ON_CMD Q3.1 CONVEYING ON COMMAND
DFV_PR_HI I2.3 DFV PRESSURE HIGH
MAT_OUT_CLS I2.2 MATERIAL OUTLET V/V CLOSE FEEDBACK

Network 45

Q4.3 AIR_KNF_ON~:Q2.1
S OUT
RS
Q4.3
/ R1

CON_ON_CMD:Q3.1
/

DFV_PR_HI:I2.3
/

Symbol Address Comment


AIR_KNF_ON_CMD Q2.1 AIR KINFE VALVE OPEN/CLOSE COMMAND
CON_ON_CMD Q3.1 CONVEYING ON COMMAND
DFV_PR_HI I2.3 DFV PRESSURE HIGH

20 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 46
PULSE TIMER BIT FOR AIR KNIFE & AIR INLET VALVES

DFV_PR_HI:I2.3 MAT_OUT_OPN:I2.1 Q4.3


S OUT
RS
T38
R1

Symbol Address Comment


DFV_PR_HI I2.3 DFV PRESSURE HIGH
MAT_OUT_OPN I2.1 MATERIAL OUTLET V/V OPEN FEEDBACK

Network 47

T37 T38
IN TOF

+20 PT 100 ms

Network 48

Q4.3 T37
IN TON

+20 PT 100 ms

Network 49

SYS_STR:I3.7 SYS_STR_BIT:Q4.5
S OUT
RS
SYS_STP:I4.0
/ R1

EMG_STP:Q3.0

Symbol Address Comment


EMG_STP Q3.0 EMERGENCY STOP INDICATION
SYS_STP I4.0 SYSTEM STOP
SYS_STR I3.7 SYSTEM START
SYS_STR_BIT Q4.5 SYSTEM START BIT

21 / 24
LIME_PLC_08AUG2013 / Program_Block (OB1)

Network 50

BFSC1_ON:V100.0 DIV_POS_1 :I3.2 BFSC1_RDY :M1.4

Symbol Address Comment


BFSC1_ON V100.0 BFSC 1 RUN FEEDBACK
BFSC1_RDY M1.4
DIV_POS_1 I3.2 DIVERTER POSITION 1

Network 51

BFSC2_ON:V100.1 DIV_POS_2 :I3.3 BFSC2_RDY :M1.5

Symbol Address Comment


BFSC2_ON V100.1 BFSC 2 RUN FEEDBACK
BFSC2_RDY M1.5
DIV_POS_2 I3.3 DIVERTER POS 2

Network 52

RAL2_ON_CM~ :Q2.4 LIME_STON~:V102.0

Symbol Address Comment


LIME_STONE_RUN V102.0
RAL2_ON_CMD Q2.4 RAL 2 ON COMMAND

Network 53

BFSC2_ON:V100.1 DIV_POS_2 :I3.3 BFSC_RDY :M1.6

BFSC1_ON:V100.0 DIV_POS_1 :I3.2

Symbol Address Comment


BFSC1_ON V100.0 BFSC 1 RUN FEEDBACK
BFSC2_ON V100.1 BFSC 2 RUN FEEDBACK
BFSC_RDY M1.6
DIV_POS_1 I3.2 DIVERTER POSITION 1
DIV_POS_2 I3.3 DIVERTER POS 2

22 / 24
LIME_PLC_08AUG2013 / SBR_0 (SBR0)

Block: SBR_0
Author:
Created: 06/26/2013 03:00:16 pm
Last Modified: 10/29/2013 03:50:47 pm

Symbol Var Type Data Type Comment


EN IN BOOL
IN
IN_OUT
OUT
TEMP

SUBROUTINE COMMENTS
Network 1 Network Title
Network Comment

23 / 24
LIME_PLC_08AUG2013 / INT_0 (INT0)

Block: INT_0
Author:
Created: 06/26/2013 03:00:16 pm
Last Modified: 10/29/2013 03:50:47 pm

Symbol Var Type Data Type Comment


TEMP
TEMP
TEMP
TEMP

INTERRUPT ROUTINE COMMENTS


Network 1 Network Title
Network Comment

24 / 24