Busduct Division

EGE, spol. s r.o.


Novohradsk 34
370 01 esk Budjovice
Czech Republic
Tel.: +420 387 764 430
Fax: +420 387 764 606
E-mail: aluobch@ege.cz
www.ege.cz

Busduct and
Aluminium
Products
Division
01

BUSDUCT SPHERE OF ACTIVITIES

DIVISION The Busduct and Aluminium Products


Division is engaged in a wide range of
activities related to producing and
installing busducts, particularly those
required by power station generator
outlets.

The history of busduct production at


EGE dates back to the early 1970s. Sin-
ce then, the division has diversified its
EGE is agroup of companies assembled in an internationally operating holding products, which now include all common
company which offers deliveries of special equipment for the power engineering busduct varieties with air insulation.
industry all over the world. EGEs global customers benefit from our over 60
years of experience and tradition in quality production, from expert and reliable Since 1971, EGE has installed more than Logistics
services, and from our flexibility in meeting customer-specific requirements. 1000 busduct units in over 500 power Site erection & supervision
plants worldwide. After-sales service & technical support
The companys strategy is to offer a full range of products and services from
technical training to after-sales service. Quality has been a key target to all of RANGE OF ACTIVITIES The Busduct Division assures installa-
EGEs activities, and the company has been certified on quality in accordance tion and commissioning as well as su-
with ISO 9001, ISO 14001, ISO 3834 and OHSAS 18001 standards. The quality Consultancy pervision by designers on building sites,
level established by these standards has been adhered to through demanding Studies maintenance, reconstruction work, and
audits which have covered the entire scope of EGEs business activities. Design repairs of busducts throughout the life
Engineering of equipment.
The parent company of EGE, spol. s r.o. primarily manufactures and supplies Technical documentation
special equipment for the energy industry. The companys main spheres of bu- Manufacture Furthermore, EGE designs and manu-
siness are three-fold: generator outlets busducts and other aluminium pro- Workshops and acceptance factures steel structures for suppor
ducts, special high-voltage electrical technology, and steel structures. tests ting busducts.
02
03

BUSDUCTS FOR GENERATOR featuring electrically shorted enclosu-


OUTLETS (IPB) res represent a standard type of large
generator outlets.
Generator busducts represent a spe
cial type of conductors capable of trans BUSDUCTS afford a great num-
EGE
mitting AC currents of high ratings and
withstanding high short-circuit currents
ber of advantages such as:
BUSDUCTS ISOLATED PHASE BUSDUCTS (IPB) WITH trIPLE
typically experienced in power plant ge- Elimination of phase-to-phase faults SUPPORTING POINT
nerator outlets. The conductors are de- Great short-circuit resistance
signed to achieve maximum operational Reduction of external magnetic fields
U* Rated current Outer dimension of Phase distance
[kV] [kA] enclosure [mm] [mm]
safety and reliability. to a minimum residual value
Elimination of Joule and hysteresis
12/28/75 2,5 14 480 960 1000 1200
Each phase conductor runs through the losses transferred to surrounding 17,5/50/110 2,5 25 540 1440 1000 1800
centre of a separate grounded sheath steel structures 24/60/125 2,5 30 640 1660 1000 2000
made of conductive and non-magnetic Limitation of difficulties with electro- 36/70/170 2,5 30 860 1820 1200 2100
material. Its position is held concent- magnetic compatibility *insulation level IEC 71-1 / power frequency withstand voltage / lightning impulse withstand voltage
ric with the enclosure by insulators. Air Protection of insulators against Busducts with a rated current up to 25 kA are designed as self-cooled IPBs, while
gaps are allowed between the enclosu- unfavourable ambient conditions busducts above 25 kA are designed as forced cooled. The Double Tube conductor
res of lateral and central phase conduc- with air insulation can be used for the current value of 25 to 30 kA. EGE is licensed
tors, thus separating the phase conduc- Shielding the conductors inside the en from Siemens PG for the production of this type of conductor.
tors and the enclosure from each other. closures completely ensures attendant
In the instance of a single-phase failure, safety. Maintenance is minimized. The ISOLATED PHASE BUSDUCTS (IPB) WITH SINGLE SUPPORTING POINT
ionized air cannot deteriorate the insu- busducts are interconnected with con-
lation capability of the other phases and ductive links at both ends. This results U* Rated current Outer dimension of Phase distance
[kV] [kA] enclosure [mm] [mm]
short them out. in connected enclosures forming a sha-
ding coil with induced current flowing 7,2/20/60 2,5 4 270 360
Shorted enclosures exert a significant lengthways through its full cross sec 12/28/75 2,5 4 300 400
shielding effect on the time-variable tion. This current almost amounts to that * insulation level IEC 71-1 / power frequency withstand voltage / lightning impulse withstand voltage
magnetic fields of adjacent conductors, flowing through the phase conductors, EGE offers busducts with a single supporting point which can fully substitute Non Seg-
thus diminishing electro-dynamic forces but its phase direction is inverse. There regated Phase Busducts (NSPB). The main advantage over NSPB is a better screening
EGE impacting upon conductors and conse- fore, the magnetic field outside the effect of the enclosure by encapsulating each phase separately. Busducts with a single
quently upon insulators during short- enclosures is compensated to a low supporting point are used for heavy workloads in many power plants around the world.
BUSDUCTS -circuit transients. Generator busducts residual value.
Non-Segregated and Segregated Phase Busducts (NSPB, SPB)

U* Rated current Outer dimension of Phase distance


[kV] [kA] enclosure [mm] [mm]
7,2/20/60 1,5 5 710 290 1130 430 180 320
12/28/75 1,5 5 830 410 1250 550 210 350
17,5/38/95 1,5 5 910 470 1410 610 250 390
* insulation level IEC 71-1/power frequency withstand voltage/lightning impulse withstand voltage
Calculated for ambient temperature of 40C and atmospheric pressure up to
1000 m above sea level without the effect of the sun.
04
05
PRODUCTION Applicable standards

Technical preparation of production


complies with the following standards:
IEEE C37.23 (Standard for Metal En
closed Bus and Calculation Losses)
IEC 60071-1 (Insulation coordination,
part 1: Definitions, principles, and rules)
IEC 60071-2 (Insulation coordination,
part 2: Application guide)
IEC 61439 Low-voltage switchboards
DESIGN AND ENGINEERING EC 62271 High-voltage switchgears
and control gears
EGE has a team of specialised electrical IEC 60865-1 (Short circuit currents. Sawing machines with circular and
and mechanical engineers experienced Calculation of effects, part 1: Defini band saw tools
in designing and engineering generator tions and calculation methods) Numerically controlled (NC) oxygen
busducts, using modern, highly sophi- BS 159 (High-voltage busbars and cutters enabling plane figures to be cut
sticated and computerised methods. busbar connection) using both oxygen and plasma
A team of experts is ready to respond C SA standard C22.2 Metal Enclosed Drilling and pressing NC automated
flexibly to any technical requirement of High Voltage Busways machines
a customer as related to a particular  SN EN ISO 3834 Welding process Bending machines and tilting press
project. Earthing diagram The busducts are designed to meet the Roll bending machine for bending bars
List of materials EU directive on electromagnetic compa- and sheets
THE TECHNICAL DOCUMENTATION List of modules tibility 2004/108/EC. All products are Machine tools for cut-machining
PROCESS Manufacturing documentation also in accordance with other EU legisla- Power sources for MIG and WIG inert
Operational and technological tive requirements. gas welding and special welding opera-
Preliminary layout procedures tions
Technical documentation for approval Welding procedure specification PRODUCTION CAPACITY EGE Preliminary preparative blasting of sur-
Operation and maintenance manuals Erection procedures faces
Erection procedures Operation and maintenance manuals Three manufacturing halls - two in the Surface finishing and hot dip galvanization
Process of approval List of consumables Czech and one in the Slovak Republic Paint spray boxes for painting busducts
Manufacturing drawings Packing lists Complete production facilities - ware- Test shops for electrical equipment
As-built documentation As-built documentation houses, packing and shipping services testing
List of spare parts ERP systems and IT networks associa- High voltage laboratory for transport
standard technical ted to the production unit testing
documentation models and calculations
MANUFACTURING MACHINERY TESTS PERFORMED
Site layout SW Mathcad for IPB AND EQUIPMENT
TechnicAL DO- Civil drawings including load calculation SW ANSYS for IPB, NSPB a SPB Type tests
Drawings of detailed connections to SW Autocad Shearing
machines capable of separa- Factory routine tests
CUMENTATION equipment SW Inventor ting metal sheets On-site tests
06
07

MATERIAL FOR busduct attenuation of dynamic impacts during MATERIAL busduct components

PRODUCTION short-circuit transients.


AND Aluminium connection terminals of
conductors are silver-plated. Conduc-
Conductors are manufactured of pressed T-branches, vertical, and horizontal tors are fixed in the proper position by
tubes, or rolled, bent Al 99.5 EN 485.2 elbows are designed according to pro- components supporting cast resin or porcelain insu-
aluminium sheets, or, alternatively, Cu ject-specific requirements, site condi lators, removable from the outside of
E57 copper tubes, encapsulated in alu- tions, and the number of devices connec the enclosure. Axial thermal dilatation
minium Al 99.5 EN 485.2 coaxial enclo- ted to the generator busducts. of conductors is ensured by flexible
sures. links made of aluminium if welded within manufacturer tests the insulators
The degree of protection of the route the conductors, or of copper if installed according to IEC 60660 standards.
The conductor is held concentric inside corresponds to IP 65 according to EN at the connection terminals. This design eliminates the need to take
the enclosure by three support insu- 60529. Flexible connections of conduc- measures by cold energizing.
lators. New, replacement insulators tors and enclosures allows for the use Rubber compensators allow axial di-
can be easily installed. In their stan of busducts in areas with higher seis- latation and flexible connection of the The overpressure system or dehydra-
dard form cast resin is used as a base mic activity. enclosure. Transport units are ma- ting breathers preventing condensa-
material thus allowing for a greater nufactured at a maximal length of 11 tion inside the busducts are available
creepage distance. This epoxy material NSPB conductors are made of stamped meters. The final welding is performed upon customer request or based on
substantially reduces water condensa- aluminium tubes Al 99, 5 EN 485.2 on site according to the Welding Pro- site conditions. In locations affected
tion levels due to its low thermal creep or copper E-57. Additional insulation cedures, which are part of the Erection by the sun, we supply protective sun
MATERIAL conductivity. layers on the conductors can be pro- Manual. shields.
posed as an option. Conductors are
AND The insulators feature a spring- enclosed in a rectangular aluminium Supporting insulators are designed Supporting steel structures can be
mounted head, allowing for both radial casing made of aluminium sheets Al with a long creepage distance and are included in delivery as hot dip galvani-
components and axial dilatation in addition to the 99.5 EN 485.2. made of cast resin or porcelain. The zed or painted.
08
09

GENERATOR CONNECTION GENERATOR CIRCUIT BREAKER


(GCB) CONNECTION
Generator busducts are usually connec
ted to a generator through removable Connections to generator circuit brea
half shells housing with silver-plated kers can either be designed as a rigid
contact surfaces. This allows for a flexi
ble and dismountable connection of the
or flexible connection depending on site
conditions. Should a rigid connection be CONNECTIONS MAIN TRANSFORMER CONNECTION

conductor as well as providing easy chosen, enclosures are directly welded Busduct enclosures are connected to a
access to connection terminals and in- to GCB casings. A flexible connection main transformer body using two flan-
stalled devices; this is especially useful involves a circuit breaker flange being ged half shells bolted together which are
for carrying out maintenance and im- affixed by a rubber compensator which fixed to busduct enclosures by rubber
provements. Interface boxes and exis is connected to a busduct enclosure compensators thus allowing thermal
ting sections of conductors are designed and conductively bridged by aluminium and mechanical dilatation. The rubber
to facilitate the replacement of bus joints. The connection is designed in ac- compensators are bridged by alumi
hings or even of the entire machine if ne cordance with the specific type of the nium links in one or three phases in
cessary. On customer request, infrared circuit breaker utilized. Conductors are order to maintain the conductivity of
thermometers can be added to the con- connected to GCB terminals using flexi the enclosures. Earthing is carried out UNIT TRANSFORMER CONNECTION
nection terminals of larger generators. ble silver-plated copper joints. in accordance with a grounding diagram.
Branch busduct enclosures are connec-
GENERATOR NEUTRAL POINT GENERATOR CIRCUIT BREAKER CONNECTION TO INSTRUMENT ted to unit transformers using two flan-
CONNECTION STEEL PLATFORM CUBICLES ged half shells bolted together or are
fixed using rubber compensators that
Generator neutral point boxes are spe- EGE also supplies the calculation, design Connection to instrument cubicles is fa- allow for thermal and mechanical dila-
cifically designed for the type of gene and manufacture of a steel platform un- cilitated using two flanged half shells bol- tation. The entire system is designed
rator used. They are equipped with ope der a generator circuit breaker made ted together which are fixed to busduct for easy erection on site and for the
nings for easy erection and maintenance according to the type of the circuit brea enclosures by rubber compensators, simplification of the future maintenance
on site. Inter-phase star connection is ker in use, site conditions, the civil ar- permitting thermal and mechanical di- of flexible silver-plated copper joints con
done using flat copper bars fixed with rangement, and the customers specific latation. The entire system is designed necting silver-plated aluminium termi-
insulators to neutral point box casings, requirements. The standard surface for easy erection on site and to simplify nals at connection points on both sides.
or using a special E-shaped aluminium treatment method is hot dip galvanisa- future maintenance. The rubber com- Rubber compensators are bridged by
tube fixed by insulators to a neutral tion. The steel support platform under pensators are bridged by aluminium aluminium links in one or three phases
point box. Neutral point boxes are fixed a generator circuit breaker can be ship links in order to preserve the conductivi- in order to maintain the conductivity of
to generator casings by a flanged bolt ped together with the delivery of gene ty of enclosures. Earthing occurs at only enclosures. Earthing is carried out in
CONNECTIONS connection. rator busducts. one place. accordance with a grounding diagram.
10
11

CONNECTION POINTS

Connection terminals are shaped sil-


WALL WALL PENETRATION STEEL STRUCTURES SUPPORTING
BUSDUCTS
ver-plated aluminium plates which are
welded to a conductor. These terminals PENETRATION, To pass generator busducts through
a wall, we use split wall penetration The support structures are designed
are equipped with holes for connecting
silver-plated copper expansion links to SUN SHIELDS, plates made of aluminium. A silicone
sealing is used to seal the resultant in-
according to customer requirements.
The supporting structures are primarily
relevant devices. All the conductors of terface gap. Single fire compartments composed of HEA and HEB steel beams
transport units are shaped and made SUPPORTING are separated from each other with with zinc hot dip galvanized or painted
ready for connecting and easy welding special material with the required fire surface treatment.
on site. Bolted connections, as well as STEEL resistance.
all other current carrying points, are SADDLES AND ATTACHMENTS TO
fastened together with rust-proof, non- STRUCTURES SUN SHIELDS ENCLOSURES
-magnetic steel nuts and bolts.
in between enclosures. Dilatation Sun shields are installed in areas of high Busduct enclosures are welded to fixed
CONDUCTOR AND ENCLOSURE couplings for both conductors and en solar activity, especially in tropical and or movable saddle points whose steel
DILATATION
CONNECTION closures are welded and require no main
tenance under operational conditions.
subtropical territories. Their function
is to reflect sun radiation and decrease
base plates are welded to support
structure cross-beams. The entire as-
The longitudinal dilatation of conductors Enclosure movement in a desired direc- the temperature of encapsulated bus- sembly can be adjusted to fit a support
COMPONENTS, is compensated for by flexible links made tion is facilitated by an array of fixed and ducts. Sun shields are produced from structure, and its total height can also
of thin aluminium sheets. The dilatation sliding support feet welded to the steel shaped aluminium sheeting which is fi- be modified. This height adjustment is
TERMINALS, of an enclosure is enabled by the use of support structures. Dilatation is further xed to busduct enclosures. A substitute necessary on site due to building to-
compensators made of specially for- secured by rubber compensators fitted for sun shields is to make conductors lerances. Saddles are insulated from
DILATATION med aluminium sheets which are welded at the ends of transformer connections. and enclosures from thicker material. steel supports.
12
13

DEVICE FOR USE IN HAZARDOUS AUXILIARIES Short Circuiting Device

LOCATION In the generator route, the Short Cir-


cuiting Device serves for testing and
For connection of the busducts to the setting the protection of the gene-
hydrogen-cooled generators EGE de- rator. It also serves as a single-pole,
signs and supplies equipment for hyd- mechanically controlled earthing. The
rogen leak detection and ventilation shorting device design allows for a
assembly to ensure safe operation of load of 8 kA for a period of 30 minu-
busducts in accordance with ATEX di- AIR PRESSURE REDUCING BOX tes, or 12 kA for a period of 15 minu-
rective 94/9/EC. tes at the rated voltage 24 kV or 36 kV.
As an alternative, we can offer a pres
DEHYDRATING BREATHERS surised air distribution system fed with DRAINAGE EQUIPMENT
treated air or recommend that a com- Voltage transformers
The internal space of busducts is sepa- pressor be furnished with an air pres Should water condensation be present, Current transformers
rated from ambient influences based on sure reduction box connected through it is captured by the drainage equipment Surge arresters
the level of protection defined by equip- piping to busduct enclosures. Pressure and drained out of the system through High voltage cubicles
ment. Changes in air volume caused by at the inlet to the reduction box may be an outlet at the lowest point of a genera- Remote infrared measurement
alterations in temperature during the up to 10 Bars. Slight overpressure pre- tor busduct unit. system
day and night are compensated for by vents the entry of air moisture and dust Grounding transformers

AUXILIARIES, air passing through a silica gel breather


which dries the air flowing to busducts
particles from the surrounding atmo-
sphere and ensures a suitable environ-
AUXILIARY EQUIPMENT Switchboard cubicles
Temporary grounding devices
to prevent the condensation inside. The ment inside the busducts. The pressure According to customer requirements,
OVERPRESSU- dehydrating breathers are of a type com reduction box can be accessorised with EGE can supply additional instruments EGE is ready to deliver auxiliary devices
monly used in conjunction with trans remote signalling of operational sta- and equipment with generator busducts and equipment including the adaptation
RE SYSTEMS formers or similar machines. tuses to a control room. such as: of busducts for their installation.
14
15

PACKING packing for land transport

AND LOGISTIC Particularly for delivery across Europe,


busducts are specially packed and pre-
pared for transport by land haulage.
Transport units are packed in wooden
crates to prevent them from being da-
maged during delivery. Assembly ma-
terials for site erection are packed and
UTILIZATON OF NSPB & SPB well protected in wooden boxes.
CONTAINER PACKING
Non-segregated phase and segregated PACKING FOR OCEAN SHIPPING
phase busducts with air insulation are At the customers request, EGE is able
designed as specified by ANSI C37.23 Packing for overseas delivery is done to transport busducts in containers.
for the transmission of medium cur according to international standards for The busducts inside are packed as
rents. The insulation level follows IEC ocean shipping. Items are packed in woo- transport units in wooden crating, pre-
60071-1 in the range up to 17.5 kV. IEC den boxes and material is well protected venting any damage during delivery.

NON-SEGREGA- standards 60298 and 60694 are valid


for each proposed design.
against movement, humidity, dust, and
salty air. Wooden boxes can be stored TRANSPORT
on site for several months without any
TED & SEGREGA- Non-segregated phase busducts are damage occurring to the equipment in- EGE can provide for the transport of
generally designed for medium voltage circuits of large generators is also pos side. Materials used when erecting are goods to the site or port of export based
TED PHASE circuits of switch stations, auxiliary sible. NSPB can be installed without separately packed and carefully signed on valid Incoterms conditions. Shipment
circuits, and outlets of small AC gene- other setup in places not protected for in accordance with packing lists and from EGE can either be by road haulage
BUSDUCTS rators. Application for DC excitation against the weather. technical documentation. or via a factory railway.
16

assembly

The divisions experienced assembly


teams are capable of carrying out bus-
duct assembly and other power con-
structions throughout the world. EGE
possesses all the certification, authori-
zation, tools and devices necessary to
conduct assembly work. The company
regularly organises training sessions
for employees and enables them to EGE employees. The supervisors are
monitor the latest trends while main- well informed on the specific project re-
taining a high quality of the work per- quirements and assist throughout the
formed. The EGE staff is able to pro- installation process, including dielec-
vide the entire assembly of busducts, tric stregth tests and pressure tests.
including commissioning. These specialists ensure that the in-
stallation is carried out in accordance
SUPERVISING with the technical documentation and
assembly, assembly procedures. As-built docu-
Supervision on the sites of busduct in- mentation based on their reports is
SUPERVISING stallation worldwide is performed by prepared after the installation.