Professional Documents
Culture Documents
Equipment Inspected Running Motor Motor Motor Ambient Motor Motor Vibration Oil Fan & Terminal Cleanliness LCS Earthing Snapshot Comments
ID By Status Temp DE Temp NDE Temp Body Temp Vibration Vibration Reading Leakage Cover Cover Condition (If any)
DE NDE (mm/sec)
481FN1 Swarup Running 51 44 42 32 1.1 Double OK
(COOLER Nayak Earthing
ESP
FAN)
481RV1 Swarup Running 37 34 38 31 1.1 Double OK
(COOLER Nayak Earthing
ESP
RAL)
481RV2 Swarup Running 41 39 45 29 0 Single OK
(COOLER Nayak Earthing
ESP
RAL)
481RV3 Swarup Running 35 34 38 29 0 Double Gland
(COOLER Nayak Earthing not
ESP proper.
RAL)
481DR2(DRAG
Swarup Running No
CHAIN Nayak access
COOLER to motor.
ESP TO
DDPC)
www.gocanvas.com Emulator-1501753213736
Inspection Route Monday-1
Equipment Inspected Running Motor Motor Motor Ambient Motor Motor Vibration Oil Fan & Terminal Cleanliness LCS Earthing Snapshot Comments
ID By Status Temp DE Temp NDE Temp Body Temp Vibration Vibration Reading Leakage Cover Cover Condition (If any)
DE NDE (mm/sec)
461GD3 Swarup Running 42 38 40 37 4 Double OK
(GRATE Nayak Earthing
DRIVE)
461FNJ Swarup Not Double OK
(SEAL Nayak Running Earthing
AIR FAN)
461FNK Swarup Not Single OK
(COOLER Nayak Running Earthing
BRG
COOLING
FAN)
461GD1 Swarup Running 41 39 41 34 Double OK
(GRATE Nayak Earthing
DRIVE)
441FN5 Swarup Running 43 36 41 32 2.8 Single Motor
(NOSE Nayak Earthing NDE
RING side
FAN) vibration
6mm/s
441FN6 Swarup Not Double OK
(NOSE Nayak Running Earthing
RING
FAN)
452BL2(JETSwarup Running 44 33 42 31 2.6 Double OK
AIR Nayak Earthing
BLOWER)
452BL1 Swarup Not Double OK
(JET AIR Nayak Running Earthing
BLOWER)
461GD2 Swarup Running 39 38 38 35 OK
(GRATE Nayak
DRIVE)
451FN2 Swarup Not Double OK
(PRIMARY Nayak Running Earthing
AIR FAN)
451FN1 Swarup Running 42 35 41 33 11 Double 11mm/s
(PRIMARY Nayak Earthing vibration
AIR FAN) on
higher
side.
461CC1 Swarup Running 38 32 39 31 0 Double OK
(HAMMER Nayak Earthing
CRUSHER)
www.gocanvas.com Emulator-1501753213736
Inspection Route Monday-1
Equipment Inspected Running Motor Motor Motor Ambient Motor Motor Vibration Oil Fan & Terminal Cleanliness LCS Earthing Snapshot Comments
ID By Status Temp DE Temp NDE Temp Body Temp Vibration Vibration Reading Leakage Cover Cover Condition (If any)
DE NDE (mm/sec)
441MD1 Swarup Running 41 39 45 30 Double OK
(KILN Nayak Earthing
MAIN
DRIVE)
441LP1 Swarup Running 39 33 40 28 6 Single 6mm/s
(KILN Nayak Earthing motor
LUB) DE side
vibration
on
higher
side.
441LP2 Swarup Not Double OK
(KILN Nayak Running Earthing
LUB)
441HD1 Swarup Not Double OK
(KILN Nayak Running Earthing
HYDRAULIC)
441HD2 Swarup Not Double OK
(KILN Nayak Running Earthing
HYDRAULIC)
461DB3 Swarup Running 34 30 30 28 3 Double LCS to
Nayak Earthing be
covered.
www.gocanvas.com Emulator-1501753213736
Inspection Route Monday-1
Equipment Inspected Running Motor Motor Motor Ambient Motor Motor Vibration Oil Fan & Terminal Cleanliness LCS Earthing Snapshot Comments
ID By Status Temp DE Temp NDE Temp Body Temp Vibration Vibration Reading Leakage Cover Cover Condition (If any)
DE NDE (mm/sec)
461FN1 Swarup Way to
Nayak motor
blocked
461RV1 Swarup Way to
Nayak Motor
blocked.
461DB4 Swarup Running 48 33 36 33 12 Double LCS
(CLINKER Nayak Earthing maintenance
SILO required
TOP)
461PA2(DDPC-2)
Swarup Running 36 32 38 31 1.2 Double OK
Nayak Earthing
471FN2 Swarup Running 40 35 39 32 2.7 Double LCS to
Nayak Earthing be
covered.
www.gocanvas.com Emulator-1501753213736
Inspection Route Monday-1
Equipment Inspected Running Motor Motor Motor Ambient Motor Motor Vibration Oil Fan & Terminal Cleanliness LCS Earthing Snapshot Comments
ID By Status Temp DE Temp NDE Temp Body Temp Vibration Vibration Reading Leakage Cover Cover Condition (If any)
DE NDE (mm/sec)
461PA4 Swarup Running No
(DDPC-4) Nayak access
due to
clinker
accumulation
www.gocanvas.com Emulator-1501753213736