You are on page 1of 6

DIESEL GENERATOR SET

PRIME
292 ekW 365 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT C15 ATAAC DIESEL ENGINE
Low Emissions Utilizes ACERT Technology
Reliable, rugged, durable design
DESIGN CRITERIA Field-proven in thousands of applications
The generator set accepts 100% rated load in one worldwide
step and meets ISO 8528-5 transient response. Four-stroke diesel engine combines consistent
performance and excellent fuel economy with
FULL RANGE OF ATTACHMENTS
minimum weight
Wide range of bolt-on system expansion
Electronic engine control
attachments, factory designed and tested
CAT GENERATOR
SINGLE-SOURCE SUPPLIER
Matched to the performance and output
Fully prototype tested with certified torsional
characteristics of Caterpillar engines
vibration analysis available
2/3 pitch minimizes harmonic distortion and
WORLDWIDE PRODUCT SUPPORT facilitates parallel operation
Caterpillar dealers provide extensive post sale Low adjustment module provides engine relief
support including maintenance and repair upon load impact and improves load acceptance
agreements and recovery time
Caterpillar dealers fill 99.7% of parts orders within UL 1446 Recognized Class H insulation
24 hours
CAT EMCP 3 SERIES CONTROL PANELS
Caterpillar dealers have over 1,600 dealer branch
Controls designed to meet individual customer
stores operating in 200 countries
needs.
The Cat SOSSM program cost effectively detects
EMCP 3 provides the option for full-featured
internal engine component condition, even the
power metering and protective relaying
presence of unwanted fluids and combustion
Segregated low voltage, AC/DC accessory box
by-products
provides single point access to accessory
connections
Options to meet UL/CSA/NFPA
Power Center provides convenient location for
control panel, optional power terminal strips and
optional circuit breakers

PRIME 292 ekW 365 kVA


50 Hz 1500 rpm 400 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet Light Duty Air filter Canister Style Air Cleaners
Air Cleaner - single stage
Dual element
Heavy duty

Cooling Radiator package mounted(50C) Radiator removal


Coolant drain line with valve terminated at edge of Radiator duct flange & guard
base
Fan and belt guards
Coolant level sight gauge
Caterpillar Extended Life Coolant
Exhaust Dry exhaust manifold Mufflers
Flanged faced outlets Manifold & Turbocharger guards
Stainless Steel Flex with split-cuff connection Elbows

Fuel Primary fuel filter with integral water separator Integral single wall and dual
Secondary fuel filters wall fuel tank bases
Fuel priming pump Manual transfer pump
Engine fuel transfer pump Fuel level switch
Flex fuel lines
Fuel cooler
Generator Self excited Permanent magnet excitation
Class H insulation CDVR with KVAR/PF control
Random Wound Internal Excitation
2/3 pitch Oversize and premium generators
R448 voltage regulator with load adjustment module Bearing/Stator temperature detection (premium
IP23 Protection generator)
3 phase sensing
Anti-condensation space heaters
Reactive droop
Power Termination Rear mounted breaker,IEC 3 pole Power Termination Strips mounted inside Power
Segregated low voltage wiring panel center
Circuit breakers, IEC 3 & 4 pole
- Circuit breaker Shunt trip
- Circuit breaker Auxillary contact
Floor standing 3 & 4 pole breakers
Governor ADEMA4 Load share module

Control Panels EMCP 3.1 (rear mounted) EMCP 3.2 & EMCP 3.3 (can be RH mounted)
Speed adjust Local annuniciator modules (NFPA 99/110)
Emergency stop pushbutton Remote annunicator modules (NFPA 99/110)
Voltage adjust Discrete I/O module
Lube Lubricating oil and filter Manual sump pump
Oil drain line with valves
Fumes disposal
Gear type lube oil pump
Mounting 8-hr Single wall fuel tank base Formed steel wide base frame
Linear vibration isolation-seismic zone 4

Starting/Charging 24 volt starting motor Jacket water heater with shut off valves
Battery with rack and cables Block heater
Ether starting aids
Battery disconnect switch
Battery chargers (5 & 10 amp)
Oversized batteries
45 amp charging alternator

General Paint - Caterpillar yellow except rails and radiators


gloss black
SAE standard rotation

2 11 April 2007 1:39 PM


PRIME 292 ekW 365 kVA


50 Hz 1500 rpm 400 Volts

SPECIFICATIONS

CAT GENERATOR CAT EMCP 3 CONTROL PANELS


Frame size................................................................ LC6114B
EMCP 3.1 (Standard)
Excitation........................................................ Self Excitation
UL/CSA/CE
Pitch.............................................................................. 0.6667
NEMA 1, IP22 enclosure
Number of poles...................................................................4
Run/Auto/Stop control
Number of bearings...................................... Single Bearing
True RMS metering, 3-phase
Number of Leads................................................................ 12
Speed Adjust
Insulation....................... UL 1446 Recognized Class H with
Vandel cover (option)
tropicalization and antiabrasion
- Consult your Caterpillar dealer for available voltages Voltage adjust
IP Rating........................................................................... IP23 Digital Indication for:
Alignment.............................................................. Pilot Shaft - RPM
Overspeed capability...................................... 125% of rated - Operating hours
Wave form Deviation (Line to Line)................................. 2% - Oil Pressure
Voltage regulator.............. 3 Phase sensing with selectible - Coolant temperature
volts/Hz - System DC volts
Voltage regulation............Less than +/- 1/2% (steady state) - L-L volts, L-N volts, phase amps, Hz
Less than +/- % (w/ 3% speed change) - ekW, kVA, kVAR,kW-hr, %kW, PF,(EMCP3.2/3.3)
Telephone influence factor............................... Less than 50 Shutdowns with common indicating light for:
Harmonic Distortion.........................................Less than 5% - Low oil pressure
- High coolant temperature
CAT DIESEL ENGINE
- Low coolant level
- Overspeed
C15 ATAAC, L-6, 4-stroke water-cooled diesel - Emergency stop
Bore.......................................................... 137.20 mm (5.4 in) - Failure to start (overcrank)
Stroke..................................................... 171.40 mm (6.75 in) Programmable protective relaying functions: (EMCP 3.2
Displacement...........................................15.20 L (927.56 in3) & 3.3)
Compression Ratio....................................................... 16.1:1 -Under and over voltage
Aspiration................................................................... ATAAC -Under and over frequency
Fuel System................................................................... MEUI - Reverse power
Governor Type................ Caterpillar ADEM control system - Overcurrent
MODBUS isolated data link (RS-485 half-duplex EMCP
3.2 & 3.3)

3 11 April 2007 1:39 PM


PRIME 292 ekW 365 kVA


50 Hz 1500 rpm 400 Volts

TECHNICAL DATA

Open Generator Set - - 1500 rpm/50 Hz/400 Volts DM8476


Low Emissions

Generator Set Package Performance


Genset Power rating @ 0.8 pf 365 kVA
Genset Power rating with fan 292 ekW
Fuel Consumption
100% load with fan 82.9 L/hr 21.9 Gal/hr
75% load with fan 61.8 L/hr 16.3 Gal/hr
50% load with fan 43.3 L/hr 11.4 Gal/hr
Cooling System1
Ambient air temperature 50 C 122 F
Air flow restriction (system) 0.12 kPa 0.48 in. water
Air flow (max @ rated speed for radiator arrangement) 558 m/min 19706 cfm
Engine Coolant capacity with radiator/exp. tank 57.8 L 15.3 gal
Engine coolant capacity 20.8 L 5.5 gal
Radiator coolant capacity 37.0 L 9.8 gal
Inlet Air
Combustion air inlet flow rate 24.9 m/min 879.3 cfm
Exhaust System
Exhaust stack gas temperature 534.3 C 993.7 F
Exhaust gas flow rate 71.1 m/min 2510.9 cfm
Exhaust flange size (internal diameter) 152.4 mm 6.0 in
Exhaust system backpressure (maximum allowable) 6.8 kPa 27.3 in. water
Heat Rejection
Heat rejection to coolant (total) 118 kW 6711 Btu/min
Heat rejection to exhaust (total) 318 kW 18085 Btu/min
Heat rejection to atmosphere from engine 67 kW 3810 Btu/min
Heat rejection to atmosphere from generator 21.0 kW 1194.3 Btu/min
Alternator2
Motor starting capability @ 30% voltage dip 745 skVA
Frame LC6114B
Temperature Rise 125 C 225 F
Emissions (Nominal)3
NOx mg/nm3 1762.1 mg/nm
CO mg/nm3 427.6 mg/nm
HC mg/nm3 12.7 mg/nm
PM mg/nm3 28.9 mg/nm
1
Ambient capability at 300m (984 ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar dealer. Air flow
restriction (system) is added to existing restriction from factory. Generator temperature rise is based on a 40 C (104 F) ambient per NEMA
MG1-32
2
Generator temperature rise is based on a 40 C (104 F) ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel
with 35 API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and
engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use
values based on a weighted cycle.

4 11 April 2007 1:39 PM


PRIME 292 ekW 365 kVA


50 Hz 1500 rpm 400 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1995 standard conditions.
CSA, IEC60034, ISO3046, ISO8528, NEMA MG 1-33, These ratings also apply at ISO3046 standard conditions.
UL508A, 72/23/EEC, 89/336/EEC, 98/37/EC Fuel rates are based on fuel oil of 35 API [16 C (60 F)]
Prime - Output available with varying load for an gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
unlimited time. Average power output is 70% of the when used at 29 C (85 F) and weighing 838.9 g/liter
prime power rating. Typical peak demand is 100% of (7.001 lbs/U.S. gal.). Additional ratings may be available
prime rated ekW with 10% overload capability for for specific customer requirements. Consult your
emergency use for a maximum of 1 hour in 12. Overload Caterpillar representative for details.
operation cannot exceed 25 hours per year. Prime power
in accordance with ISO3046. Prime ambients shown
indicate ambient temperature at 100% load which results
in a coolant top tank temperature just below the alarm
temperature.

5 11 April 2007 1:39 PM


PRIME 292 ekW 365 kVA


50 Hz 1500 rpm 400 Volts

DIMENSIONS

Package Dimensions
Note: Do not use for installation design.
Length 3822.7 mm 150.5 in See general dimension drawings for
Width 1110.0 mm 43.7 in detail (Drawing #2781056).
Height 2166.0 mm 85.28 in
Weight 3894 kg 8,585 lb

www.CAT-ElectricPower.com
2007 Caterpillar
All rights reserved.
Performance No.: DM8476
Materials and specifications are subject to change without notice.
Feature Code:: C15DEM9 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," and the
Source:: European Sourced POWER EDGE trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.
11 April 2007 9485186