PAGE 1

HVAC Consultancy Services FILE SAVED:HL-Workstation Area-S&M, R0


DATE :
COOLING AND HEATING LOAD ESTIMATION FOR SUMMER & MONSOON OUTSIDE CONDITIONS
Summer 110F DB 75F WB
Project Monsoon 95F DB 83F WB
Address INSIDE CONDITIONS
Architects 75F DB 55% RH
Space FRESH AIR REPLENISHMENT
Floor AS PER ASHARE NORMS
TOTAL HT F\CEILING HT
10'
Size Sft x ht ft 0 Cu.ft

ITEM AREA SUN GAIN OR t FACTOR BTUs/HOUR


SUMMER MONSOON SUMMER MONSOON
01. SOLAR GAIN

Glass N 14 11 0.56 0 0
Glass E 12 11 0.56 0 0
Glass S 12 13 0.56 0 0
Glass W 164 165 0.56 0 0
Glass NW 123 100 0.56 0 0
Glass NW (B/off) 123 100 0 0 0
Glass SW 100 127 0.56 0 0
Glass SW(B/off) 100 127 0 0 0
Glass NE 12 11 0.56 0 0
Glass SE 12 11 0.56 0 0
Glass SE(B/off) 12 11 0 0 0
Sky Light 123 107 0.9 0 0

02. TRANS. GAIN

Wall N 21 8 0.32 0 0
Wall E 35 22 0.32 0 0
Wall S 33 20 0.32 0 0
Wall W 29 16 0.32 0 0
Wall NW 23 10 0.32 0 0
Wall SW 31 18 0.32 0 0
Wall NE 27 14 0.32 0 0
Wall SE 35 22 0.32 0 0
All Glass
Single 0 35 22 1.13 0 0
Partn Glass 25 12 1.13 0 0
Partn.Wall 27 12 0.4 0 0
Partn.Wall (Stairs) 27 12 0.4 0 0
Partn.Wall (Toilet & ahu) 22 10 0.4 0 0
Floor 30 15 0.4 0 0
Ceiling 30 15 0.4 0 0

03. INFILTRATION AND OUTSIDE AIR

Infiltration (Cfm) 35 20 1.08 0 0


Outside Air (Cfm) 35 20 0.14 1.08 0 0

04. INTERNAL HEAT GAIN

People pax 280 0 0


Equipment kw 3413 0 0
Light (flu) watts 0 1.25 3.413 0 0

1
PAGE 2
Light (inc) watts 0 3.413 0 0
Appliances sft 560 0 0
Meals pax 30 0 0

ROOM SENSIBLE HEAT GAIN SUB TOTAL 0 0

Supply Supply Fan Motor Total


Duct Duct 5.50% '12.5%
Heat Gain 3 % Leakage Loss 4%
Add 12.5% on above sub total Summer 0 0.125 0
Monsoon 0 0.125 0

05. TOTAL ROOM SENSIBLE HEAT 0 0

06. LATENT HEAT GAIN

INFILTRATION AND OUTSIDE AIR

Infiltration (Cfm) 0.68 0 0


Outside Air (Cfm) 0 4 82 0.14 0.68 0 0
gr/lb gr/lb
INTERNAL HEAT GAIN

People 0 pax 270 0 0


Appliances 0 sft 140 0 0
Meals 0 pax 30 0 0

ROOM LATENT HEAT GAIN SUB TOTAL 0 0

Supply Loss Total


Duct Infiltration 3.5% 0
Leakage Loss 4%
Add 7.5% on above sub total Summer 0 0.075 0
Monsoon 0 0.075 0

07. TOTAL ROOM LATENT HEAT 0 0

08. ROOM TOTAL HEAT 0 0


Summer Monsoon

SENSIBLE HEAT FACTOR #DIV/0! 0.000


INDICATED ADP 55 55
SELECTED ADP 56 56
DEHUMIDIFIED RISE 16.34 16.34

09. DEHUMIDIFIED CFM 0 0

10. RETURN AIR HEAT GAIN

TRANS. GAIN

Wall N 23 8 0.32 0 0
Wall E 37 22 0.32 0 0
Wall S 35 20 0.32 0 0
Wall W 31 16 0.32 0 0
Wall NW 25 10 0.32 0 0
Wall SW 33 18 0.32 0 0
Wall NE 29 14 0.32 0 0
Wall SE 37 12 0.32 0 0
Partn.Wall 28 13 0.4 0 0
Roof 54 39 0.16 0 0
Ceiling 30 15 0.4 0 0
2
PAGE 3

RETURN AIR HEAT GAIN SUB TOTAL 0 0

Add 12.5% on above sub total Summer 0 0.125 0


Monsoon 0 0.125 0

11. TOTAL RETURN AIR HEAT GAIN 0 0

12. OUTSIDE AIR HEAT GAIN

Sensible 0 35 20 0.86 1.08 0 0


Latent 0 4 82 0.86 0.68 0 0

13. ROOM TOTAL HEAT 0 0

14. GRAND TOTAL HEAT SUB TOTAL 0 0

Return duct/ Return Duct/ Total


Space Space '5%
Heat Gain 2 % Leakage Loss 3%
Add 5% on above sub total Summer 0 0.05 0
Monsoon 0 0.05 0

15. GRAND TOTAL HEAT 0 0

16. AC LOAD IN TR 0.0 0.0

17. REHEAT :

ROOM SENSIBLE HEAT 0

ROOM TOTAL HEAT 0

SELECTED ESHF (SUMMER) 0.00

REHEAT (BTU's/HOUR) 0

REHEAT LOAD (TR) 0

REHEAT (KW) 0

ULTIMATE AC LOAD (TR) 0.0

17. EQUIPMENT SELECTION :

18. CHECK FIGURES : SUMMER MONSOON

SFT/TR #DIV/0! 0.0


CFM/SFT #DIV/0! #DIV/0!

19. ASSUMPTIONS/REMARKS

20. REFRIGERATION LOAD ON ACCOUNT OF OUTSIDE AIR ONLY BY INTRODUCING HRV

Sensible 0 33 18 1 1.08 0 0
Latent 0 1 68 1 0.68 0 0

OUTSIDE AIR HEAT GAIN TOTAL 0 0

21. AC LOAD (TR, ON ACCOUNT OF FRESH AIR ONLY) 0.0 0.0


ON FOLLOWING RETURN AIR CONDITIONS

22. SAVING IN AC LOAD (TR)


(BY INCORPORATING ERW HAVING EFFICIENCY AS 60% 0.0 0.0
AND RETURN AIR AS 70% OF SUPPLY AIR)

23. AC LOAD USING HRV (TR) 0.0 0.0

3
PAGE 4

SAVING IN REFRIGERATION LOAD HAS BEEN BASED ON FOLLOWING RETURN AIR CONDITIONS
TO ERW THROUGH INSULATED DUCTS :

a. Temperature : 77 F DBT
b. RH : 60%
c. Gr/lb : 84

REVISIONS

No. Date Revision Details By