COMPLETION CERTIFICATE

We certify that the installation detailed below has been installed by us and tested and that to
the best of our knowledge and belief it complies with Indian Electricity Rules 1956, as well as
Indian Standard Code of Practice for Electrical Wiring and Fittings in buildings (IS 732 1963)
issued by the Indian Standard Institution.

Ref: C.E.I.G./E.I. Letter No. : KM.1639/CEIG/D3/Drawing/2011 Dt. 23.12.2011

1. Electrical Installation at : M/S. AMTEK AUTO LIMITED.,


RNS-21, Sipcot Industrial Growth Center,
Oragadam, Vadakkupattu Village, Sriperumpudur TK
Kanchipuram-Dist, Pin-602 105.

2. Voltage and system of supply : 433V, 3Ph, 4 Wire systems

a) Particulars of work : As per the Enclosure


b) If the work involves installation of
Overhead lines and / or underground
Cable : Under ground cable.

c) Earthing
1. Description of earthing electrodes : 40 mm Dia. GI. Pipe.

2. No. of earth electrodes : 18Nos

3. Size of earth wire / flat : 50x6 mm Cu. Flat.


40x6 mm Cu. Flat.
25x3 mm Cu. Flat.
50x6 mm GI. Flat.
8SWG & 10SWG Cu Wire.
d) Test results
1. Insulation resistance for the whole
Installation
(i) Between Conductors : Above 100 Meg. Ohms.
(ii) Between each Conductor and
Earth : Above 100 Meg. Ohms.

2. Resistance of earthing Electrodes : 4 Ohms.

3. Maximum earthing resistance of


Installation : 0.5 Ohms.

Signature of Supervisor Signature of contractor


Name of Supervisor: Name and address of the contractor
D.SIVAKUMAR M/S Siva Energy Infrastructure P Ltd.,
No.18/27, Pillaiyarkoil 4th Street,
Ekkattuthangal, Chennai- 600 032
LICENCE NO: -C 26648 LINCENCE NO. EA-2621
Valid up to: 17.02.2013. Valid up to: 07.02.2012.