You are on page 1of 14

Section 9

Air Cooled Exchangers

An air-cooled exchanger is used to cool fluids Fin construction types are tension-wrapped, em-
with ambient air. Several articles have been pub- bedded, extruded, welded, and plate. The applica-
lished describing in detail their application and eco- tion of each type is a matter of agreement between
nomic analysis. (See Bibliography at the end of this manufacturers, contractors and users, depending on
section.) This section describes the general design of the temperatures and other conditions of the service.
air cooled exchangers and presents a method of ap-
proximate sizing. Base tube diameters are % in. to 1% in. OD with
fins from ?4 in. to 1 in. high, spaced
- - from 7 to ll/in..
ARRANGEMENT AND MECHANICAL DESIGN providing an extended finned surface of 12 to 25 tknei
the outside surface of the base tubing. Tubes are
Figs. 9-1 and 9-2 show typical elevation and plan

-views of horizontal air-cooled exchangers as com-


i,
monly manufactured in the U. S. The basic com-
ponents are one or more tube bundles served by one
usually arranged on triangular pitch with the fin
tips of adjacent tubes touching or separated by from
1/16 in. to f/4 in. Matching of the tube bundle to the
fan system and the heat transfer requirements usually
or more axial flow fans, fan drivers, speed reducers, results in the bundle having depth of 3 to 8 rows of
and an enclosing and supporting structure. fintubes, with 4 rows the most typical.
Air-cooled exchangers are classed as forced draft A I-in. OD tube is the most popular diameter and
when the tube bundle is located on the discharge side the most common fins are in.or in. high. The
of the fan* and as induced draft when the tube data presented here are for 1 in. OD tubes with M in
bundle is located on the suction side of the fan. high fins, fins,,in. (designated as 9) and in:
Coolers are regularly manufactured in tube lengths high fins, fins,,in. (designated as %
from 6 ft to 50 ft and in bay widths from 4 ft to
30 ft. Use of longer tubes usually results in a less
costly design compared to using shorter tubes. AIR-SIDE CONTROL
Fan size range is from 3 f t to 28 ft diameter, how- Air-cooled exchangers are sized to operate at
ever, 14 ft to 16 ft diameter is the maximum diameter warm (summer) air temperatures. Seasonal varia-
normally used. Fan drivers may be electric motors, tion of the air temperature can result in over-cooling
steam turbines, hydraulic motors, or gas-gasoline en- which may be undesirable. One way to control the
gines. Usually a speed reducer, such as a v-belt drive amount of cooling is by varying the amount of air
or reduction gear box is necessary to match the flowing through the tube bundle. This can be ac-
driver output speed to the relatively slow speed of complished by using multiple motors, 2-speed motors,
the .axial flow fan. Fan tip speeds are normally hydraulic variable-speed drives, louvers on the face
12,000 fpm or less. U. S. practice is to use v-belt of the tube bundle, or automatically variable pitch
drives up to about 30 bhp and gear drives at higher fans.
power. Individual driver size is usually limited to
50 hp. Staging of fans or fan speeds may be adequate
for systems which do not require precise control of
Two-fan bays are popular, since this provides a process temperature or pressure. Louvers will pro-
degree of safety factor against fan or driver failure vide a full range of air quantity control. They may
and also a method of control by fan staging. Fan be operated manually, or automatically operated by
coverage is the ratio of the projected area of the fan a pneumatic or electric motor controlled by a remote
to the face area of bundle or bundles served by the temperature or pressure sensor on the process stream.
fan. Good practice is to keep this ratio above 0.40 Louvers used with constant speed fans do not reduce
whenever possible because higher ratios improve air fan power requirements.
distribution across the face of the tube bundle. Face
area is the plan area of the heat transfer surface Auto-variable-pitch fans are normally provided
available to air flow at the face of the bundle or with pneumatically operated blade pitch adjustment
bundles. which may be controlled from a remote sensor. Blade
pitch is adjusted to provide the required amount of
The heat-transfer device is the tube bundle which air flow to maintain the process temperature or pres-
is an assembly of side frames, tube supports, headers, sure at the cooler. The required blade angle de-
and fintubes. Aluminum fins are normally appliod creases as ambient air temperature drops and this
to the tubes to provide an extended surface on thtx conserves fan power. Efydraulic variable speed drives
air side, in order to compensate for the relatively reduce fan speed when less air flow is required and
low heat transfer coefficient of the air to the tube. can also conserve fan power.
Extreme variation in air temperature such as en-
countered in northern climates may make additional
steps necessary. Ducts and louvers can be arranged
to recirculate warm discharge air through the tube
bundle in varying amounts to temper the ambient
air. Very elaborate systems may be necessary when
designing a cooler for a high pour point liquid in a
cold climate. This may include louvers and ducts for
full air recirculation, use of auto pitch fans, and a
steam coil for heating the system at startup.

Thermal Design
The basic equation to be satisfied is the same as
given in Section 8, Shell & Tube Exchangers:

Normally Q is known, U and AT, are calculated,


and the equation is solved for A. The ambient air
temperature to be used will either be known from
available plant data or can be selected from the sum-
mer dry bulb temperature data given in Section 11,
Cooling Towers. A complication arises in calculating
the LMTD because the air quantity is a variable, and
therefore the air outlet temperature is not known. 1
i'
The procedure given here starts with a step for
approximating the air-temperature rise. After the
air-outlet temperature has been determined, the
corrected log mean temperature difference is cal-
culated in the manner described in the shell & tube
section, except that the MTD correction factors to
be used are from Figs. 9-3 and 9-4, which have been
developed for the cross-flow situation existing in air
cooled exchangers.
Fig. 9-3 is for one tube pass. It is also used for
multiple tube passes if passes are side by side. Fig.
9-4 is for two tube passes and is used if the tube
passes are over and under each other. A MTD cor-
rection factor of 1.0 is used for four or more tube
passes, if passes are over and under each other. A
correction factor of 1.0 may be used as an approxi-
mation for three passes, although the factor will be
slightly lower than 1.0 in some cases.
The procedure for the thermal design of an sir
cooler consists of assuming a selection and then
proving it to be correct. The typical overall heat
__
transfer coefficients given in Fig. 9-5 are used to '4
approximate the heat transfer area required. The
heat transfer area is converted to a bundle face area
using Fig. 9-6 which lists the amount of extended
surface available per square foot of bundle face area
for two specific fintubes on two different tube pitches
for 3, 4, 5, and 6 rows. After assuming a tube length,
Fig. 9-6 is also used to ascertain the number of tubes.
Both the tube side and air side mass velocities are
now determinable.
The tube side film coefficient is calculated from
Figs. 9-7 and 9-8. Fig 9-9 gives the air-side film
coefficient based on outside extended surface. Since
all resistances must be based on the same surface, it
is necessary to multiply the reciprocal of the tube-
side film coefficient and tube-side fouling factor by
the ratio of the outside surface to inside surface. This
results in an overall transfer rate based on extended
surface, designed as U,. The equation for overall method has been selected for use in the example
heat transfer rat.e is therefore: which follows. The air-film coefficient in Fig. 9-9
and the air static pressure drop in Fig. 9-10 are
only for 1 in. OD tubes with % in. high fins, 10 fins
per inch on 214 in. triangular pitch. Refer to Bibliog-
raphy Nos. 2, 3, and 5 for information on other fin
configurations and spacings.
The basic equation will then yield a heat transfer
area in extended surface, A, and becomes: The minimum fan area is calculated in Step 16
using the bundle face area, number of fans, and a
minimum fan coverage of 0.40. The calculated area
is then converted to a diameter and rounded up to
The overall heat transfer rate could also be cal- the next available fan size. The air-side static pres-
culated by converting all film coefficients to resist- sure is calculated from Fig. 9-10, and the fan
ances based on the outside bare tube surface using total pressure is estimated using gross fan area in
the surface ratios for the inside surface and the Step 20. Finally, fan horsepower is calculated in
extended surface to the outside bare tube surface. Step 21 assuming a fan efficiency of 70%, and driver
In this method the overall heat transfer is Ub, horsepower is estimated by assuming a 92%-efficient
and the resultant heat transfer area is the outside speed reducer.
bare tube surface A,. The basic equation to be solved
would be: PROCEDURE FOR ESTIMATING TRANSFER
SURFACE, PLOT AREA, AND HORSEPOWER

Either method is equally valid and each is used Procedure and example
extensively by thermal design engineers. Fig. 9-5 Required data for hot fluid
gives typical overall heat transfer coefficients based
on both extended surface and outside bare surface, so Name and phase: 48' API hydrocarbon liquid
either method may be used. The extended-surface (Text cont'd. p. 9-7)

LIST OF SYMBOLS

A, = inside surface of tube, sq f t Q = heat transferred, BTU/hr

-A, = outside bare tube surface, sq ft U = over-all heat transfer coefficient, BTU/hr/
sq ft/OF.
A, = outside extended surface of tube, sq ft W = flow rate, lb/hr
A, = tube inside cross-sectional area, sq in. P = viscosity of fluid at average fluid tem-
(Fig. 8-17) perature, centipoise

C, = specific heat at average temperature, = viscosity of fluid at average tube wall


BTU/lb/OF. temperature, centipoise
h, = tube side film coefficient based on inside
D, = inside tube diameter, in. tube area, BTU/hr/sq ft/OF.
Do = outside tube diameter, in. h, = shell side film coefficient based on outside
tube area BTU/hr/sq ft/OF.
ij D, = density ratio r., = fouling resistance (fouling factor)
Fa = total face area of bundles, sq ft rl = fluid film resistance (reciprocal of film
coefficient)
G = mass velocity, lb/sq ft/sec
r, = metal resistance
-
G, = air face mass velocity, lb/hr/sq f t face area += viscosity gradient correction = p/PW

k = thermal conductivity, BTU/hr/sq ft/ = fluid density, lb/cu ft


( OF-ft)
AP = pressure drop, psi
L = length of tube, ft
AT, = corrected mean temperature difference
LMTD = mean temperature difference. See Fig. 8-1
N = number of rows of tubes in direction of Subscripts:
flow a = airside
NT = number of tubes t = tube side
Np = number of tube passes- s = shell side
FIG. 9-2 I

Typical plan views of air coolers ',.-./

r Bay w~dth-
b

I
Un~tw~dth

/-

Tube
length

<--A

One-fan bay with Two one-fan boys w~th


3 tube bundler 4 tube bundles

Bay width -- Unit w~dth

I
A
i b
,0--.
c-**
#;$\
4
/ \ \ \ /'.
I
\ \/
'.-.A'

TIrbe Tube
l e19th
~ w e - - - - - - - - length ----------- --- - - - - - -
/--\

'r.9.
---4/ -*-c/

I
!

Two-fan bay with Two two-fan bays with


2 tube bundles 6 tube bundles

Courtesy the Rainey Corp.


*

FIG. 9-3
MTD correction factors Typical tube layouts
Inlet Inlet
1 pass-cross flow
Both fluids unmixed
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Nomenclature: ~ 0 0 0 0 0 0 ~ ~ ~ 0 0 0
TI =inlet temperature, tube side
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Tr=outlet temperature, tube side -
tI = inlet temperature, air side
Outlet Outlet
t2 =outlet temperature, air side

1.0

0.9

.-
b

2 0.8
-
.-S
V
?
ij
V

0.7

0.6

0.5
0 0.1 0.2 03 0.4 0.5 0.6 0.7 0.8 09 1.0
P
R= -
TI- Tr
tr- tl
P= -
tr- 11
TI- t~
Courtesy the Ro~neyCarp
I
Physical properties & avg temp: Avg. T = 200°F. Flow quantity: W, = 273, 000 lb/hr
Cp = .55 BTU;lb°F. F = .51 cp Temp in & out: T, = 250°F. T, = 150°F.
k = .0766 BTU/hr/Sq ft OF/ft. Fouling factor r,,, = .001
(From this Data Book) Allowable pressure drop: AP, = 5 psi
Heat load: Q = 15, 000,000 BTU/hr.
Required data for air
Ambient temp: t, = 100°F.
FIG. 9-5
Elevation : Sea level
Typical overall heat-transfer coefficients
Basic assumptions
for air coolers
Type: Forced draft
Service Fintube Fintube: 1 in. OD with % in. high fins
ys i n by 9 % in. by 10
Tube pitch: 2% in. triangular
1. Water & water solutions
First trial
u,, u, u, ux
Engine jacket water (r, = .001) 1 10 - 7.5 130 -6.1 1. Pick approx. overall transfer
Process water (rf = .002) 95-6.5 110-5.2 coefficient for Fig. 9-5: U, = 4.2
50-50 Ethyl glycol-water (rf = .001) 90 - 6.2 105 -
4.9 2. Approximate air temp. rise:
50-50 Ethyl glycol-water (rf = .002) 80 - 5.5 95 -
4.4

2. Hydrocabon liquid coolers


Viscosity C p U, U,
0.2 85 -
5.9
'kJ 0.5 75 -
5.2
1.O 65 - 4.5
2.5 45-3.1
4.0 30 -
2.1 3. Calc. CMTD:
6.0 20 -
1.4
Hydrocarbon 250 150
10.0 10-0.7

3. Hydrocabon gas coolers


Air - -
152 f-- 100
98 50
Pressure, psig U, U, Ub U,
AT,,, = 72 x 1.00 = 72OF.
50 30-2.1 35-1.6
100 35 -
2.4 40 - 1.9 (Assume 3 or more passes)
300 45 - 3.1 55 -2.6
500 55 -
3.8 65 -3.0 4. Calc. required surface
750 65 -
4.5 75 -3.5
1000 75 - 5.2 90 -4.2 Q
A, =
4. Air and flue-gas coolers (U,) (ATn1)
Use one-half of value given for hydrocabon gas coolers 15,000,000
A, = = 49,700 sq f t
5. Steam condensers 4.2 x 72
(Atmospheric przssure & above)
w u, ux Ub u; 5. Calc, face area utiag APSF factor from Fig.
Pure steam (rf = .0005) 125-8.6 145-6.8 9-6:
Steam with non-condensables 60 4.1 - 70 -3.3
6. HC condensers FIG. 9-6
Pressure, psig Ub Ux Ub Ur Fintube data for I-in. OD tubes
0" range 85 -5.9 100 - 4.7 Fin height by Fins/inch % in by 9 % in. by 10
10" range 80 -
5.5 95 -4.4
25' range 75 -
5.2 90 -4.2 APF 3.80 5.58
60' range 65 -
4.5 75 -3.5 AR 14.5 21.4
100' & over range 60 -
4.1 70 - 3.3 Tube Pitch 2 in.4 21A in. A 2 % in. A 2'/2 in. A
APSF (3 rows) 68.4 60.6 89.1 80.4
7. Other condensers
(4 rows) 91.2 80.8 118.8 107.2
Ub u, Ub u, (5 rows) 114.0 101.0 148.5 134.0
Ammonia 110 -7.6 130 - 6.1 (6 rows) 136.8 121.2 178.2 160.8
Freon 12 65 -4.5 75 -3.5
Notes: APF is area/ff o f fintube in sq ft. AR is area ratio of
Note: U b is overall rate based on bare tube area and U, ir overall firrtrtbe ronrparrJ to tbe cxtrrior area of 1 in. OD bare tribe wbicb
rate bared on extended surface. bas 0.262 sq f t / f t . APSF is arra per sq ft of bundle face area.
Ax 419
F;, = ---- Width = -= 14.0 f t
APSF 30
49,700 (Assume 30-ft-long tubes)
F:, = = 419 sq ft (Assume 4 rows)
118.8 7. Calc. no. tubes using APF factor from Fig. 9-6:

6. Calc. unit width by assuming a tube length.


Fa
Width = -
L

FIG. 9-8
Physical property factor for hydrocarbons

2 . . . : . .. ... .. .. .../. ... . ....,.........


. _ .: . . . . . . . . . . . . . .
. . .
. -..-.. .. .. I:
: : : : : L;,!:::: ::::::;:. :..:;: :.. :
...
. . .. . . .
.
. .!.
,.. . ., . . . . . . . . . . .
-. _. . . , ........................ --
....; ..-. . . . . . . . . .
...I:-
A

.
. . A , . . .

. .
)... . . . .
.!,.. .
.
.
.
. . . . . . . -1;
. .
: .. : . : . :. . . -... .....
'- " . ,........,- . ...! . . . . . . . . . . . . . . . . . . . . . . . Courtesy The Oil and Gor Journal
. " ' "LIL"" .
o.ol a s e
. -
I 2 4
7 890.1 2
5 4 0 e 7 . .
1 .O 2
a 4 s e 7 . 9 10
Vircorily, cp

_I
-
8. Calc. tubeside mass velocity by assuming
number of passes and reading A, from Fig.
8-17 for a 1 in. OD x 16 BWG tube.

.04 x 273,000 x 3
FIG. 9-9 G, = = 186 lb/sec/sq f t
Air film coefficient 297 x .5945
(Assume 3 pass)

9. Calc. tubeside pressure drop using equation


from Fig. 9-11 and from Fig. 9-12:
-- f YLN,,
AP, = - BN,
-
+
- -

.a3 #
,t ' " --. -.' ' (0.0024) (14.5) (30) (3)
I

=
AP~
0.98
+ (0.25) (3)

Air face mass velocity, = 4.0 psi 1


Ib/hr-sq f t face area
10. Calc. modified Reynolds No.

&
! ,

11. Calc. tubeside film coefficient e u u a t i o ~from


I .- + FIG. 9-10
Air static-pressure drop from Fig. 9-8:
0.20

0.15

u"
0.10
3
0.09
0.87
0.08
2
-0 12. Calc. air quantity:
g 0.07
3
la)
a 0.06
==a
0.05 b
0.04
C
. -.- i
13. CalG air face . q ..
~_velocit@
--, - .
0.03 - ' w.- 2-
1,OOo 2,000 3,000 4,000 G, 5 - = lb/hr/sq f t face area
Air face mass velocity, Fa
Ib/hr-sq ft face area

14. Read airside film coefficient from Fig. 9-9:


h,, = 9.0
Courtesy the Rainey Corp.
L 15. Calc. overall transfer coefficient
-- - ,-- --- -- - .-- - - - - - - . --..- -

You might also like