Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS -PT #19-SITE #303-BLG

Room Area And Volume


Space Name & No. Width Length Height Volume
TOILETS & WASHES G-12 7.70 4.91 2.90 109.6
GHANGING (1931-G23) 2.30 2.00 2.50 11.5

EF-01

TOILETS & WASHES G-25 5.00 5.00 2.50 62.5


CHANGING (1931-G24) 2.30 2.00 2.50 11.5

EF-01

GARBAGE (1931-G26) Based on negative Pressure of (- 10%)


EF-02

JANITOR (1931-G35) 3.20 2.00 4.60 29.4


EF-03

ELEC. ROOM (1931-G12 & G34) 2.80 2.70 4.60 34.8


EF-04

CHEMICALS ST.(1931-G11) 2.80 2.70 4.60 34.8


EF-05

CENTERAL COOKING (1931-G40) Q= L X 930 L\s = 7.2 X 930 = 2890 L/S


KEF-01 9 KEF-01 EACH

CENTERAL COOKING (1931-G40) Q = 0.95 X Q = 0.95 X 6696 = 6361 L/S


KMF-01 9 KMF-01 EACH

PASTRY (1931-G18) Q= L X 930 L\s = 3.2 X 930 = 2976 L/S


KEF-02

PASTRY (1931-G18) Q = 0.95 X Q = 0.95 X 2976 = 2827 L/S


KMF-02

TRAY&PAN (1931-G16) Q= L X 930 L\s = 1.5 X 930 = 1395 L/S


KEF-03

PASTRY (1931-G18) Q= 0.95 X Q = 0.95 X 1395 = 1325 L/S


KMF-03

DRY CLEANING (1931-G01-G02-G13-G05) AIR VOLUME REQUIRE FOR FRESH AIR =


FAF-01

STAFF DINING (1931-G03) AIR VOLUME REQUIRE FOR FRESH AIR =


FAF-02
Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS -PT #19-SITE #303-BLG
Room Area And Volume
Space Name & No. Width Length Height Volume

STAFF DINING (1931-G23) AIR VOLUME REQUIRE FOR FRESH AIR =


FAF-02

OFFICE (1931-G08, 09) AIR VOLUME REQUIRE FOR FRESH AIR =


FAF-03

OFFICE (1931-G27,28) AIR VOLUME REQUIRE FOR FRESH AIR =

FAF-03

FOOD INSPECTOR (1931-G21,22) AIR VOLUME REQUIRE FOR FRESH AIR =

FAF-03
FLOW RATE CALCULATIONS -PT #19-SITE #303-BLG 1931
Fan Selection Data
No. of Air Air flow rate
12 370
8 30
400
SAY 240 LPS

12 210
8 30
240
SAY 240 LPS

Based on negative Pressure of (- 10%) 111


SAY 110 LPS

8 70
SAY 70 LPS

12 120
SAY 120 LPS

8 80
SAY 80 LPS

Q= L X 930 L\s = 7.2 X 930 = 2890 L/S 6696


9 KEF-01 EACH SAY 6696 LPS

Q = 0.95 X Q = 0.95 X 6696 = 6361 L/S 6361


9 KMF-01 EACH SAY 6361 LPS

Q= L X 930 L\s = 3.2 X 930 = 2976 L/S 2976


SAY 2976 LPS

Q = 0.95 X Q = 0.95 X 2976 = 2827 L/S 2827


SAY 2827 LPS

Q= L X 930 L\s = 1.5 X 930 = 1395 L/S 1395


SAY 1395 LPS

Q= 0.95 X Q = 0.95 X 1395 = 1325 L/S 1325


SAY 1325 LPS

AIR VOLUME REQUIRE FOR FRESH AIR = 280


SAY 280 LPS

AIR VOLUME REQUIRE FOR FRESH AIR = 80


SAY 80 LPS
FLOW RATE CALCULATIONS -PT #19-SITE #303-BLG 1931
Fan Selection Data
No. of Air Air flow rate

AIR VOLUME REQUIRE FOR FRESH AIR = 78


SAY 80 LPS

AIR VOLUME REQUIRE FOR FRESH AIR = 40


SAY 40 LPS

AIR VOLUME REQUIRE FOR FRESH AIR = 40


SAY 40 LPS

AIR VOLUME REQUIRE FOR FRESH AIR = 40


SAY 40 LPS