TIMER TOP 948

GENERAL

FUNCTION: A – Delay on Make


Ab – Delayed Single Shot
B – Single Shot
C – Delay on Break
D – Repeat Cycle, OFF time first
Di – Repeat Cycle, ON time first
H – Interval
T – On Delay w/ Memory

TIME RANGES: 99.99 s 999.9 s


9999 s 99 min 59 s
99.99 min 999.9 min
9999 min 99 h 59 min
9999 hrs 999.9 hrs
Note: The 99.99 s time range is not available
in the Repeat Cycle Mode

- Simultaneous and constant display of the current value and pre-selection


value (internal battery, minimum life span 10 years at 20°C)
- Up count (Up) or down count (Down) display
- 8 A, 250 VAC relay output (10 A UL)
- Power supply: 24 VAC/DC, 110 VAC, or 220 VAC (tolerance + 10 % - 15 %)
- Front panel protection rating NEMA 4 (IP 56)
- 8 pin or 11 pin plug configuration
- Input types: contact voltage or static (PNP)
High level: 4-30 Vdc
Low level: 0-1 Vdc

1/7
Note:
The display only appears when the timer is switched on.
Warning:
Once the timer is set, the selected function starts as soon as the timer
returns to run mode; nevertheless, for security reasons, no function is
possible with the 2-5 contact open.

DISPLAY 1: Modes of Operation


2: Active Output Display
3: Current Value Display
4: Timing Range Unit
5: Decimal Point
6: CHECK mode
7: Preset Value
8: Pre-selection Display
9: RESET Active Display
10: Input Active Display
11: Increment Digital Values
12: PROG Mode button
13: Parameter Selection
14: RESET in RUN Mode
ENTER in CONFIG or
PROG modes
End of CHECK mode
USER PRECAUTIONS
The cables carrying the power supply and the bables to the input circuits must be separated
from one another. It is imparative to connect the supply (2-10 or 2-11) before applying voltage
to the control inputs (start or reset). In industrial environments where there are high levels of
electromagnetic interference, there are certain ways of counterin this interference:
• Sheild the conductors by connecting their shield to the 0 V of the counter.
• Protecting the output devices:
1. AC outputs: 100MΩ, 0.1µf RC circuit across terminals of coil.
2. DC output: diode across terminals of coil
A minimum amount of ventilation must be provided.
Important:
The input circuits must be galvanically isolated from the timer supply. However,
galvanic isolation is not necessary if:
• The supply is AC and the input is by contact closure.
• The timer and the sensor have the same supply.

2/7
CONFIGURATION

CONFIG / RUN

CONFIG.

Parameter
CONFIG
selection

PR

Function A, Ab, b, C
d(La), di(L), CONFIG
Ht b Ent
MODE

PR

Memory in YES, NO
case of CONFIG
power failure YES Ent
MEMO

PR

Direction of UP, dn
timing CONFIG
UP Ent
COUNT

3/7
PR

Calibration of 999.9s,
T ON and/or 99.99s, CONFIG
T OFF 99h59m, … 99 . 99S Ent
CALIB

PR

Parameter YES, NO
protection CONFIG
YES Ent
SECU

PR

Select 4 digit code


Security CONFIG
Code 2345 Ent

Select digit Increment value

PR

End of
Configuration CONFIG
YES Ent
SECU

PR

NOTE:
At the end of the operation, the “ENT” key must be pressed to validate the parameters,
then reset (RST), local or remote after transferring from config to run mode.

4/7
PROG.

Modification of
PROG
unprotected
parameters

PR

Modify
T ON and/or PROG
T OFF 2345 Ent
0004

Select digit Increment value

PR

End of
programming PROG
Ent Ent

PR

CHECK
CHECK
Press both buttons simultaneously

Press PR to check parameters


MODE Ent

PR

RUN

5/7
MODES OF OPERATION

6/7
DIMENSIONS AND ASSEMBLY

WIRING DIAGRAMS

88 857 800

7/7