(*) The rated power is defined by natural air cooling (AN). Should there be particular constraints, it may be
increased by 40 % by forced cooling addition (AF). Please consult us. (1) Others possibilities upon request,
consult us. (2) Non standard ratings available on request.
E/2
J J L I
SM100016
13
tapping
links
C
M
H
B
earthing
terminal
40 (50)
D
125 (160) D
A E
Dimensions (mm) - Lenght A 1100 1180 1260 1450 1540 1550 1600 1720 1840 2000 2070
- Width B 650 650 800 815 840 950 950 950 1195 1195 1200
- Height C 1250 1290 1430 1690 1680 1720 1880 2070 2210 2390 2610
- Roller pitch D 520 520 670 670 670 820 820 820 1070 1070 1070
- Frame width E 645 645 795 795 795 945 945 945 1195 1195 1195
- Roller diam. F 125 125 125 125 125 125 125 125 160 160 160
- Roller width G 40 40 40 40 40 40 40 40 50 50 50
Weight without enclosure (kg) 800 1000 1350 1960 2220 2500 2950 3850 4635 5450 7380
Dimensions (mm) - Lenght A 1340 1350 1440 1570 1585 1620 1655 1795 1840 2085 2260
- Width B 710 715 810 835 840 945 945 945 1195 1195 1200
- Height C 1350 1355 1465 1640 1770 1940 2080 2200 2440 2500 2540
- Roller pitch D 520 520 670 670 670 820 820 820 1070 1070 1070
- Frame width E 645 645 795 795 795 945 945 945 1195 1195 1195
- Roller diam. F 125 125 125 125 125 125 125 125 160 160 160
- Roller width G 40 40 40 40 40 40 40 40 50 50 50
Weight without enclosure (kg) 960 1060 1500 2040 2300 2640 3160 4075 4900 5800 7600
03
Cast Resin Transformers Trihal - Reduced losses
I
SM100017
13
tapping
links C
earthing
terminal (50)
40 G
D
125 (160) D
A B
The winding resin coating and the plug-in connectors dont ensure any protection against touch when the
transformer is energized. The contrator must ensure that cables and busbars are adequately supported to
prevent mechanical stresses from being imposed on the transformer terminals, busbars or bushings.
SM100019
cable support
200 mm
LV n HV
LV
200 mm
cable support
cable support
200 mm
HV
500 mm*
LV terminations HV terminations
SM100022
SM100023
70 80
23.5
23.5
40 33 33
50
15
14
33
33
33
4 x 14 4 x 14
100 160 13
50 80 40
25
35
50
4 x 14 4 x 16
50
The contrator must ensure that cables and busbars are adequately supported to prevent mechanical stresses from being
imposed on the transformer terminals, busbars or bushings.
NRJED311120EN 09-2011