You are on page 1of 8

TECHNICAL FEATURE|Fundamentals at Work

This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or
distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.

Part One
Radiant Heating and
Cooling Systems
BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

The use of radiant heating systems has several thousand years of history.1,2 The early
stage of radiant system application was for heating purposes, where hot air from flue gas
(cooking, fires) was circulated under floors or in walls. After the introduction of plastic
piping water-based radiant heating and cooling with pipes embedded in room surfaces
(floor, wall, and ceiling), the application increased significantly worldwide. Earlier
application of radiant heating systems was mainly for residential buildings because of
its comfort and free use of floor space without any obstruction from installations. For
similar reasons, as well as possible peak load reduction and energy savings, radiant
systems are being widely applied in commercial and industrial buildings.
This two-part article describes basic knowledge of cooling. The water temperatures are operated at very
radiant heating and cooling systems to give a principle close to room temperature, and, depending on the
understanding of the design and operation of this position of the piping, the system can take advan-
advantageous system including comfort, system load, tage of the thermal storage capacity of the building
heating/cooling capacity, installation and application of structure.
the system with examples. Figure 1 shows the available types of embedded
hydronic radiant systems. The embedded radiant sys-
Embedded Radiant Heating and Cooling System tems, except thermally active building systems (TABS),
Embedded radiant systems are used in all types of are usually insulated from the main building structure
buildings. Due to the large surfaces needed for heat (floor, wall and ceiling), and the actual operation mode
transfer, the systems work with low water tempera- (heating/cooling) of the systems depends on the heat
ture for heating and high water temperature for transfer between the water and the space.

Kwang Woo Kim, Arch.D., is a professor of architecture at Seoul National University, Seoul, South Korea, and president of Architectural Institute of Korea. Bjarne W. Olesen, Ph.D., is
director, professor, International Centre for Indoor Environment and Energy, Technical University of Denmark in Lyngby, Denmark, and vice president of ASHRAE.

28 A S H R A E J O U R N A L ashrae.org FEBRUARY 2015


TECHNICAL FEATURE

Floor Ceiling Wall TABS

FIGURE 1 Examples of water based radiant systems.3

The radiant system is defined as a system where at


least 50% of the heat transfer takes place by radiation. Btu/hft2F
Figure 2 shows the total heat transfer coefficients between 2.03
a heated-cooled surface and a room. The radiant heat 1.85 1.94 1.94 1.41
transfer is, in all cases, 5.5 W/mK (0.97 Btu/hftF). 1.67
1.50
The convective heat transfer then varies between 0.5 1.41
1.32 1.06
and 5.5 W/mK (0.09 and 0.97 Btu/hftF), depend-
1.14
ing on the surface type and on heating or cooling mode. Wall
0.97 1.23
This shows that the radiant heat transfer varies between Heating Ceiling
Cooling Floor
50% and 90% of the total heat transfer. The heat trans-
fer coefficient for cold ceiling and warm floor will vary FIGURE 2 Heat transfer coefficients between heated/cooled surface and room.4,5
between 9 and 11 W/mK (1.59 and 1.94 Btu/hftF),
depending on the temperature difference between sur-
face and room. Part 5: Installation; and
The radiant heat transfer does not directly affect the Part 6: Control.
room air temperature. The long wave radiation heats or
cools the surrounding surfaces, which then indirectly Comfort
heats or cools the room air. Occupants thermal comfort is the primary objec-
tive in radiantly heated or cooled space. To provide an
Standard for Radiant Heating and Cooling Systems acceptable thermal environment for the occupants, the
As the heat transfer process between water and room requirements for general thermal comfort shall be taken
is quite different from conventional air systems, an into account by using the index of predicted mean vote
international standard on radiant heating and cooling (PMV) or operative temperature, to, and local thermal
systems has been developed based on system design and comfort, e.g., surface temperature, vertical air tempera-
existing standards from different countries and was ture differences, radiant temperature asymmetry, draft,
published in 2012. etc.
ISO 11855, Building Environment DesignDesign, For radiant or convective systems the comfort require-
Dimensioning, Installation and Control of the Embedded Radiant ments are the same when expressed by the PMV-PPD
611
Heating And Cooling Systems, consists of six parts: index (0.5 < PMV <+0.5) or expressed as an operative
Part 1: Definition, symbols, and comfort criteria; temperature range corresponding to: 20C to 24C (68F
Part 2: Determination of the design and heating and to 75.2F) for heating season and 23C to 26C (73.4F
cooling capacity; to 78.8F) for cooling season in spaces with sedentary
12,13
Part 3: Design and dimensioning; activity.
14,15
Part 4: Dimensioning and calculation of the dynamic The operative temperature is the combined influ-
heating and cooling capacity of thermo active building ence of air temperature and mean radiant temperature.
systems; The operative temperature can be approximated with

FEBRUARY 2015 ashrae.org A S H R A E J O U R N A L 29


TECHNICAL FEATURE|Fundamentals at Work

0F 3.6F 7.2F 10.8F 14.4F 18F 0F 9F 18F 27F 36F 45F 54F 63F
Y Y
80% 80%
60% 60%
40% 40%
1 2
20% 20%

10% 10%
8% 8% 3 4
6% 6%
4% 4%

2% 2%

1% X 1% X
X=Air Temperature Difference Between Head and Feet Y=Dissatisfied X=Radiant Temperature Asymmetry Y=Dissatisfied 1=Warm Ceiling
FIGURE 3Local thermal discomfort caused by vertical air temperature difference.6 2=Cool Wall 3=Cool Ceiling 4=Warm Wall
FIGURE 4 Local thermal discomfort caused by radiant temperature asymmetry.6

the simple average of air and mean radiant temperature


in spaces with low air velocities (<0.2 m/s [39 fpm]), or 100 1
with a small difference between mean radiant tempera-
ture and air temperature (<4K, 7F). 80 0.3
The operative temperature (to) is in spaces with low air 0.2
60 50.4F
velocities determined from the following expression: 0.1
Dissatisfied (%)

Acceptability
0.0
to = 0.5(ta + tr) 40
41.4F 0.1
Where 0.2
20 32.4F
ta = air temperature F (C) 0.3
tr = mean radiant temperature F (C)
0 1.0
The occupants can maintain the same comfort level 20 30 40 50 60 70 80
with a lower air temperature in a radiantly heated Relative Humidity (%)
space, and the same comfort level with a higher air FIGURE 5 Human satisfaction with the IAQ depending on relative humidity and air
temperature.3
temperature in a radiantly cooled space in comparison
to convective heating and cooling systems. Therefore,
reduction of the energy loss due to ventilation and infil- system and vice-versa in summer. With air systems the
tration is possible while maintaining the same comfort colder window temperatures in winter will be com-
level compared with conventional heating and cooling pensated by a higher air temperature, which will result
systems. in an air temperature higher than the mean radiant
As the reference temperature for the transmission heat temperature.
loss is closer to the operative temperature than to the air For rooms with sedentary and/or standing occupants,
temperature, there will not be any significant difference the maximum permissible floor temperature for heating
of transmission heat loss between radiantly heated or is 29C (84F), and the minimum floor temperature for
cooled spaces. cooling is 19C (66F). For spaces with occupants in bare
Interestingly enough, the difference between air- and feet (bathrooms, swimming pools, dressing rooms, etc.),
mean radiant temperature is normally smaller in radi- the optimal floor temperature for comfort also depends
antly heated or cooled spaces. This is due to the fact on the floor covering material.
that in winter the windows will have a lower surface For wall heating, a maximum surface temperature
temperature than the air temperature, which is com- range of 35C to 45C (95F to 113F) is recommended.
pensated by a higher surface temperature of the radiant The maximum may depend on whether the occupants

30 A S H R A E J O U R N A L ashrae.org FEBRUARY 2015


TECHNICAL FEATURE|Fundamentals at Work

Type A and C Type B Type D Type G


1 1 1
2 2 2

5 Flooring Material
3 3
3

Joist
4 4 4

1=Floor Covering 2=Weight Bearing and Thermal Diffusion Layer (Cement Screed, Anhydrite Screed, Asphalt Screed or Wood)
3=Thermal Insulation 4=Structural Base 5=Heat Diffusion Device
FIGURE 6 Embedded radiant system types.7

may easily get contact with the surface or whether occu- for condensation and mold growth. The relationship
pants are more sensitive persons such as children or the between air temperature and humidity is one of impor-
elderly. Wall cooling is limited by the risk of condensa- tant comfort issues in radiantly cooled spaces. Where
tion and the development of a downdraft of cold air. the humidity is not controlled by the air system, as in
A vertical air temperature difference between head naturally ventilated spaces, radiant cooling capacity will
and feet of less than 3K (5.4F) is recommended. Most be limited to avoid the forming of condensation on the
heating and cooling systems will, in modern buildings, radiant surface (see section on control in Part 2 of this
normally have vertical air temperature differences article in next months Journal).
within this limit. In high ceiling spaces it is, for energy With air heating or cooling system more air has to
reasons, important to avoid large vertical temperature be circulated than the amount needed for providing
differences. This is why floor heating is especially rec- acceptable air quality. This may increase the noise level
ommended here (atrium, foyer, industrial space, etc.) in a space and also increase the risk for complaints
People are very sensitive to radiant temperature related to draft. When a part of sensible heating and/
asymmetry from a cold window and a warm ceiling. or cooling load is taken care of by a water-based radi-
Occupants may feel discomfort caused by a temperature ant system, the ventilation system may have reduced
asymmetry of 5K (9F) for warm ceiling, and a tempera- duct size and lower air velocity because it will only
ture asymmetry of 10K (18F) for walls or windows (Figure treat the air renewal for required IAQ and, if needed,
4, Page 30). The critical factor at cold surfaces (windows, dehumidification.
walls) is, however, the risk of downdraft that may cause In buildings with thermally active building systems
discomfort. (TABS) you will normally prefer to have free access to
The radiant heating and cooling system operates with the concrete surface to increase the heat transfer with
less dust transportation, as it is not a convective system, the room. This may require special solutions for the
and does not require the cleaning of heat emitters or acoustics. Acoustic panels on the ceilings and suspended
filters. With the radiant floor heating systems, carpets ceiling panels will reduce heat transfer. It will be more
16
are not necessary. Thus, the possible allergen sources of efficient to hang down vertical acoustical panels. The
emitting pollutants and a sink source can be eliminated. application of the raised floor or the thermal/acoustic
The higher mean radiant temperature in radiantly insulation in floor will decrease the upper heat flow
heated space means that the air temperature can be from the TABS, which normally is much less than the
kept lower than in convectively heated space. This has heat exchange from the ceiling.
the advantage that the relative humidity in winter may
be a little higher. Studies show that lower air tempera- Load Calculations and Heating/Cooling Capacity
ture and lower air humidity have a significant effect At a given average surface temperature and indoor
3
on perceived air quality (Figure 5 ). Due to the higher temperature (operative temperature, to), a surface
heating surface temperatures, there is less chance will deliver the same amount of heat flux to a space

32 A S H R A E J O U R N A L ashrae.org FEBRUARY 2015


TECHNICAL FEATURE|Fundamentals at Work

Structure S4 qup=112.6 Btu/h


q=0 q=0 Temperature (F)
Material
78.8
Floor Covering
=0.08 Btuin/hft2F 77
s=0.6 in.
75.2
Screed
=0.40 Btuin/hft2F 73.4
s=2.4 in.
71.6
Thermal Insulation
=0.01 Btuin/hft2F 69.8
s=1.2 in.
68
Concrete
=0.70 Btuin/hft2F 66.2
s=7.1 in.
64.4

qdown=22.3 Btu/h

FIGURE 7 Temperature distribution and cooling effect up and down for a floor system calculated by FEM software for a floor cooling system with 19C (66.2F) water tem-
peratures and 26C (78.8F) room temperature.

regardless of the embedded radiant system type. surface and the space in relation with the system type.
Therefore, it is possible to establish basic formulas or Acceptable surface temperature is determined based on
characteristic curves of heating and cooling for the all comfort considerations and the risk of condensation.
7
heating and cooling surfaces independent of the embed- Heating/cooling capacity of the systems is:
ded system types. The heat transfer between the surface
Floor heating and ceiling cooling, q = 8.92 (to tS,m )1.1;
and the space do, however, depend on the different sur-
face heat transfer coefficients (Figure 2). Wall heating and wall cooling, q = 8 (|to tS,m |);
The heat transfer between the water and surface is differ- Ceiling heating, q = 6 (|to tS,m |);
ent for each system configuration. Therefore, the estima-
tion of heating/cooling capacity of systems is very important Floor cooling, q = 7 (|to tS,m |).
for the proper system design. Two calculation methods Where
7
included in ISO 11855-2 are simplified calculation meth- to (C) is the operative temperature in the space
ods depending on the type of system, and finite element tS,m (C) is the average surface temperature
method (FEM) or finite difference method (FDM). Given The ceiling has the capacity up to 100 W/m (31.7
system types are Types A and C, Type B, Types D and G. Btu/hft) for sensible cooling and 40 to 50 W/m (12.7
The simplified calculation methods are specific for the to 15.9 Btu/hft) for heating. The floor has the capac-
given system types within boundary conditions. Based ity up to 100 W/m (31.7 Btu/hft) for heating and
on the calculated average surface temperature at given 40 W/m (12.7 Btu/hft) for sensible cooling. When
heat transfer medium temperature and space tempera- direct sunlight strikes on the floor, the sensible cooling
ture, it is possible to determine the steady state heating capacity of the floor may be more than 100 W/m (31.7
and cooling capacity. In case a simplified calculation Btu/hft). This is why floor cooling is often adopted in
method is not applicable for the considered system, spaces with large window area like airports, atria and
either two- or three-dimensional finite element or finite lobby halls.
difference method, or laboratory testing may be applied. For the thermally active building systems (TABS), the
The temperature distribution in floor cooling system, steady-state heating/cooling capacity calculation is not
calculated using FEM software, is shown in Figure 7. sufficient, and analysis with a dynamic computational
Heat exchange coefficient is the parameter that program that can predict the dynamic behavior and
determines the amount of heat transferred between performance of the system together with the building

34 A S H R A E J O U R N A L ashrae.org FEBRUARY 2015


TECHNICAL FEATURE

17,1
is needed. Several programs exist such
Energy Plus, TRNSYS and IDA-ICE.
One of the main advantages of TABS are
4

Cooling Power (Btu/h)


reduced building height. For each story, you 2
may save 500 to 600 mm (1.8 to 2 ft) of build-
1 3
ing height, which for a seven-story build-
ing amounts to an entire story and related
building materials. As no suspended ceiling
is needed to cover air ducts, significant sav-
ing of building materials is possible. It is also
possible to operate the system at 30% to 50%
lowered peak loads allowing reduced plants
1=Heat Gain 2=Power Needed for Conditioning the Ventilation Air
sizes and possible operation of heating/cool-
3=Power Needed on Water Side 4=Peak Heat Gain Reduction
ing systems with temperatures close to room
FIGURE 8 Example of peak-shaving (reducing the peak load) effect (time vs. cooling power).17
temperature, allowing increased plants effi-
ciency and use of renewable energy sources
(ground heat exchanger, evaporative cool- over 24 hours and by an air system normally over 8 to
ing, etc.). 10 hours. After the water circulation in the slab may
Thermally active building systems exploit the high have been stopped during the day and will be started
thermal inertia of the slab to perform peak shaving. The again in the evening, there will be a high peak cool-
peak shaving reduces the peak in the required cooling ing load between the heated slab and the cool water;
7
power, so that it is possible to cool the structures of the but this should not be used to size the chiller as it is a
building during a period in which the occupants are very short peak and the capacity needed will after some
absent (during nighttime in office premises). This way, minutes decrease significantly. It can be somewhat com-
the cooling can be delayed and lower nighttime electric- plicated to calculate the needed capacity on the water
ity rates can be used. At the same time, a reduction in side (chiller, heat pump); therefore, a dynamic building
the size of heating/cooling system components (includ- simulation is recommended.
ing the chiller) is possible.
During daytime, the heat is extracted from the occu- System Design
pied space by the ventilation system and stored in the Radiant system design requires determining heat-
concrete slabs. Then, during nighttime, the level of ven- ing/cooling surface area, type, pipe size, pipe spacing,
tilation is reduced and the circulation of cool water in supply temperature of the heat transfer medium, and
the slabs will remove the stored heat. design medium flow rate. The design steps are as follows
8
For the conventional air system, the space load will (ISO 11855-3 ):
be the instantaneous system load, because all the heat 1. Calculate the design heating and sensible cooling
delivered to the space is immediately removed by the load in accordance with a standard for heating and cool-
air system. For the radiant system and especially for ing load calculation based on operative temperature.
a TABS the calculated design space load should not be 2. Determine the minimum supply air quantity
used as system load. For both an air system and a TABS, needed for ventilation and dehumidification. In cooling
it is important that the room load over a 24-hour day application, calculate latent cooling and sensible cooling
(Curve 1 in Figure 8) is removed within the 24 hours, else available from supply air. Determine remaining sen-
the room will get warmer and warmer day by day if the sible cooling load to be satisfied by radiant system. Also,
weather stays the same. The difference is that with a designate or calculate the relative humidity and dew
TABS this load is removed from the space in three ways: point, because the cooling system should operate within
absorption in the concrete slab, removed by the ventila- a surface temperature range above the dew point, which
tion system and removed by the water circulating in the shall be specified depending on the respective climate
slabs. Therefore, the load is removed by a slab system conditions in the country. By limiting supply water

FEBRUARY 2015 ashrae.org A S H R A E J O U R N A L 35


TECHNICAL FEATURE|Fundamentals at Work

temperature to be maintained above TABLE 1 


System design example for panel cooling.
dew point, the risk of condensation STEP FIND EXAMPLE
can be easily avoided.
3. Determine the surface area for 0 A = 10 m2 (108 ft2), V = 30 m3 (1,059
ft3) Room is Given to be Installed with
radiant system, excluding any area Radiant System and HVAC System
covered by objects immovable or 1 Calculate Cooling Load Based on Opera-
fixed to the building structure. tive Temperature
Cooling Load (Latent) Qc,latent = 150 W (512 Btu/h)
4. Establish a maximum permis- Qc,sensible = 1,000 W (3,416 Btu/h)
Cooling Load (Sensible)
sible surface temperature and a mini-
2 Determine Minimum Supply Air Quantity VHVAC,min = 0.7 ACH = 21 CMH (12.4 CFM)
mum permissible surface tempera-
ture in consideration of the dew point. Calculate Latent Cooling Available From QHVAC,latent = Qc,latent = 150 W (512 Btu/h)
Supply Air
5. Determine the design heat flux,
including the design heat flux of pe- Sensible Cooling Available From Supply Assuming the SHF (Sensible Heat Factor) of HVAC, SHF =
Air (QHVAC,sensible / QHVAC,total) = 0.7
ripheral area and the design heat flux QHVAC,total = QHVAC,latent / (1 - SHF)
of occupied area. For the design of the = QHVAC,latent / 0.7 = 500 W (1,708 Btu/h)
cooling systems, determine the room Then, QHVAC,sensible = QHVAC,total QHVAC,latent
= 500 W 150 W = 350 W
with the maximum design heat flux.
(1,196 Btu/h) is available from
6. Determine the radiant system supply air of HVAC
such as the pipe spacing and the cov- Design the Relative Humidity
ering type, and design heating and And Dew Point RH = 50 %, Tdew = 14.8C (58.6F)
cooling medium differential temper-
ature based on the maximum design Determine Remaining Sensible Cooling
Load to be Satisfied by Radiant System Remaining Qc,sensible = Qc,sensible - QHVAC,sensible
heat flux and the maximum and = 1,000W 350 W
minimum surface temperature from = 650 W (2,220 Btu/h)
the field of characteristic curves. 3 Determine the Available Surface Area Aavailable = 5 m2 (53.8 ft2), 50% of ceiling area is available
for radiant system
7. If the design heat flux cannot
4 Establish a Minimum Permissible Tsurf,min = 17C (62.6F) is acceptable for cooled ceiling*
be obtained by any pipe spacing Surface Temperature (which is higher than dew point temperature)
alternatives for the room of design, it
5 Determine Maximum Design Heat Flux Qc,max = 99 W/m2 (31.4 Btu/hft2) is allowed for cooled
is recommended to provide supple- ceiling*
mentary heating/cooling equipment. 6 Determine Radiant System Selected Radiant System has cooling capacity of 80 W/m2
In this case, the maximum design (25.4 Btu/hft2).
heat flux for the embedded system Pipe Spacing mT = 0.2 m (8 in.)
may now occur in another room. Covering Type punched aluminum sheet
8. Determine the thermal resis- Design Cooling Medium Differential Tm = 2C (3.6F)
Temperature
tance of backside insulating layer Design heating capacity of radiant 5 m2 = 400 W (1,366 Btu/h)
and the design heating/cooling system,
medium flow rate. 7 Select Supplementary Required cooling capacity of Supplementary
9. Estimate the total length of Cooling Equipment Cooling Equipment
circuit. Qout = Remaining Qc,sensible Qdes
= 650 W 400 W = 250 W (854 Btu/h)
Hydronic radiant surface systems
8 Determine Thermal Resistance of Rcover = 0.021 m2K/W (0.12 hft2F/Btu)
are very often coupled with an air- Backside Insulating Layer m = 0.0478 kg/s (6.3 lb/min),
handling system. The air-handling Cooling Medium Flow Rate ensured of fully developed flow in pipe
system usually operates only with If the resistance of backside insulation is high, the cooling
the amount of air needed for accept- medium flow rate could be lowered.
able indoor air quality, the required 9 Estimate Total Length Of Circuit Lcir = Aavailable / mT = 5 m2 / 0.2 m = 25 m (82 ft)
IAQ standard, or amount of air *ISO 11855-2: Building environment design Design, dimensioning, installation and control of embedded radiant

needed to remove latent heat from heating and cooling systems Part 2: Determination of the design heating and cooling capacity.

36 A S H R A E J O U R N A L ashrae.org FEBRUARY 2015


TECHNICAL FEATURE

the space and control air humidity level, while the hydronic systems Part 1: Definition, symbols, and comfort criteria.
7. ISO 11855-2:2012, Building environment design - Design, dimension-
system supplies or removes the sensible heat depending on ing, installation and control of the embedded radiant heating and cooling sys-
the seasonal conditions. In the cooling mode, the air system tems Part 2: Determination of the design and heating and cooling capacity.
can play a key role in avoiding surface condensation. 8. 8. ISO 11855-3:2012, Building environment design - Design, dimen-
sioning, installation and control of the embedded radiant heating and cooling
Part 2 of this article will cover control, operation, systems Part 3: Design and dimensioning.
installation and application of the system. 9. ISO 11855-4:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling
systems Part 4: Dimensioning and calculation of the dynamic heating and
Acknowledgments cooling capacity of Thermo Active Building Systems (TABS).
This article was supported by VELUX guest professorship, and a grant 10. ISO 11855-5:2012, Building environment design - Design, dimension-
from the National Research Foundation of Korea (NRF) funded by the ing, installation and control of the embedded radiant heating and cooling
Korean government (MEST) (No. 2014-050381). systems Part 5: Installation.
11. ISO 11855-6:2012, Building environment design - Design, dimension-
References ing, installation and control of the embedded radiant heating and cooling
1. Bean, R., Olesen, B.W., Kim, K. W. 2010. History of Radiant systems Part 6: Control.
Heating & Cooling Systems, Part 1. ASHRAE Journal (1):4046. 12. ASHRAE Standard 55-2010, Thermal Environmental Conditions for
2. Bean, R., Olesen, B.W., Kim, K. W. 2010. History of Radiant Human Occupancy.
Heating & Cooling Systems, Part 2. ASHRAE Journal (2):5055. 13. ISO EN 7730-2005, Moderate thermal environmentsdetermination of
3. REHVA. 2007. Guidebook No 7: Low Temperature Heating and the PMV and PPD indices and specification of the conditions for thermal comfort.
High Temperature Cooling. 14. 2012 ASHRAE HandbookHVAC Systems and Equipment.
4. Olesen, B.W. 1997. Possibilities and limitations of radiant floor 15. ISO EN 7726-1998, Ergonomics of the thermal environment- Instru-
cooling. ASHRAE Transactions 103(1):4248. ments for measuring physical quantities.
5. Olesen, B.W., Michel, E., Bonnefoi, F., De Carli, M. 2000. Heat 16. Weitzmann, P., Pittarello, E., Olesen, B.W. 2008. The cooling
exchange coefficient between floor surface and space by floor cool- capacity of the thermo active building system combined with acous-
ing: theory or a question of definition. ASHRAE Transactions, Part I. tic ceiling. Presented at Nordic Symposium on Building Physics.
6. ISO 11855-1:2012, Building environment design - Design, dimension- 17. Olesen, B.W. 2012. Thermo active building systems using
ing, installation and control of the embedded radiant heating and cooling building mass to heat and cool. ASHRAE Journal 54(2):4452.

Advertisement formerly in this space. Advertisement formerly in this space.

FEBRUARY 2015 ashrae.org A S H R A E J O U R N A L 37

You might also like