RPLC PROJECT

Sheet 2 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

CURRENT L1 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


1

CURRENT L2 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


2

CURRENT L3 (A) AO x x ETHERNET =D06+R06 Grid Incomer A0


3

VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D06+R06 Grid Incomer A0


4

ACTIVE POWER (MW) AO x x ETHERNET =D06+R06 Grid Incomer A0


5

REACTIVE POWER (MVAR) AO x x ETHERNET =D06+R06 Grid Incomer A0


6

POWER FACTOR AO x x ETHERNET =D06+R06 Grid Incomer A0


7

FREQUENCY AO x x ETHERNET =D06+R06 Grid Incomer A0


8

ENERGY CONSUMPTION (MWH) AO x x ETHERNET =D06+R06 Grid Incomer A0


9

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


10

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


11

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D06+R06 Grid Incomer A0


12

MAIN PROTECTION LP1 ON TEST DO x x HARDWIRED =D06+R06 Grid Incomer A0


13

BACKUP PROTECTION LP2 PROTECTION ON TEST DO x x HARDWIRED =D06+R06 Grid Incomer A0


14

MAIN PROTECTION LP1 UNAVAILABLE DO x x x HARDWIRED =D06+R06 Grid Incomer A0


15

BACKUP PROTECTION LP2 UNAVAILABLE DO x x x HARDWIRED =D06+R06 Grid Incomer A0


16

OVERCURRENT TRIP 51 DO x x x ETHERNET =D06+R06 Grid Incomer A0


17

EARTH FAULT TRIP 51N DO x x x ETHERNET =D06+R06 Grid Incomer A0


18

DIRECT TRANSFER TRIP SENT 87L DO x x x ETHERNET =D06+R06 Grid Incomer A0


19

DIRECT TRANSFER TRIP RECEIPT 87L DO x x x ETHERNET =D06+R06 Grid Incomer A0


20

SYNCHRO CHECK START 25 DO x x ETHERNET =D06+S1 Grid Incomer A0


21

+R06 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D06+R06 Grid Incomer A0


22

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0


23
RPLC PROJECT

Sheet 3 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0


24

CIRCUIT BREAKER OPEN STATUS Q0 DO x x HARDWIRED =D06+S1 Grid Incomer A0


25

CIRCUIT BREAKER CLOSED STATUS Q0 DO x x HARDWIRED =D06+S1 Grid Incomer A0


26

GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D06+S1 Grid Incomer A0


27

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
28

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
29

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
30

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D06+S1 Grid Incomer A0
31

BB DISCONNECTOR OPEN STATUS Q1 DO x x HARDWIRED =D06+S1 Grid Incomer A0


32

BB DISCONNECTORCLOSED STATUS Q1 DO x x HARDWIRED =D06+S1 Grid Incomer A0


33

HIGH SPEED EARTHING SWITCH OPEN STATUS Q8 DO x x HARDWIRED =D06+S1 Grid Incomer A0
34

HIGH SPEED EARTHING SWITCH CLOSED STATUS Q8 DO x x HARDWIRED =D06+S1 Grid Incomer A0
35

LINE DISCONNECTOR OPEN STATUS Q9 DO x x HARDWIRED =D06+S1 Grid Incomer A0


36

LINE DISCONNECTOR CLOSED STATUS Q9 DO x x HARDWIRED =D06+S1 Grid Incomer A0


37

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D06+S1 Grid Incomer A0


38

ISOLATING LINK Q6 IN DO x x HARDWIRED =D06+S1 Grid Incomer A0


39

ISOLATING LINK Q6 OUT DO x x HARDWIRED =D06+S1 Grid Incomer A0


40

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


41

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


42

MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
43

MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
44

BB DISCONNECT SWITCH Q1 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


45

BB DISCONNECT SWITCH Q1 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


46
RPLC PROJECT

Sheet 4 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

MAINTENANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
47

MAINTENANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
48

HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
49

HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0
50

LINE DISCONNECT SWITCH Q9 OPEN COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


51

LINE DISCONNECT SWITCH Q9 CLOSE COMMAND DI x x x HARDWIRED =D06+S1 Grid Incomer A0


52

CURRENT L1 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


53

CURRENT L2 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


54

CURRENT L3 (A) AO x x ETHERNET =D08+R08 Grid Incomer B0


55

VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D08+R08 Grid Incomer B0


56

ACTIVE POWER (MW) AO x x ETHERNET =D08+R08 Grid Incomer B0


57

REACTIVE POWER (MVAR) AO x x ETHERNET =D08+R08 Grid Incomer B0


58

POWER FACTOR AO x x ETHERNET =D08+R08 Grid Incomer B0


59

FREQUENCY AO x x ETHERNET =D08+R08 Grid Incomer B0


60

ENERGY CONSUMPTION (MWH) AO x x ETHERNET =D08+R08 Grid Incomer B0


61

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


62

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


63

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D08+R08 Grid Incomer B0


64

MAIN PROTECTION LP1 ON TEST DO x x HARDWIRED =D08+R08 Grid Incomer B0


65

BACKUP PROTECTION LP2 PROTECTION ON TEST DO x x HARDWIRED =D08+R08 Grid Incomer B0


66

MAIN PROTECTION LP1 UNAVAILABLE DO x x x HARDWIRED =D08+R08 Grid Incomer B0


67

BACKUP PROTECTION LP2 UNAVAILABLE DO x x x HARDWIRED =D08+R08 Grid Incomer B0


68

OVERCURRENT TRIP 51 DO x x x ETHERNET =D08+R08 Grid Incomer B0


69
RPLC PROJECT

Sheet 5 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

EARTH FAULT TRIP 51N DO x x x ETHERNET =D08+R08 Grid Incomer B0


70

DIRECT TRANSFER TRIP SENT 87L DO x x x ETHERNET =D08+R08 Grid Incomer B0


71

DIRECT TRANSFER TRIP RECEIPT 87L DO x x x ETHERNET =D08+R08 Grid Incomer B0


72

SYNCHRO CHECK RUNNING 25 DO x x ETHERNET =D08+R08 Grid Incomer B0


73

+R08 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D08+R08 Grid Incomer B0


74

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0


75

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0


76

CIRCUIT BREAKER OPEN STATUS Q0 DO x x HARDWIRED =D08+S1 Grid Incomer B0


77

CIRCUIT BREAKER CLOSED STATUS Q0 DO x x HARDWIRED =D08+S1 Grid Incomer B0


78

GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D08+S1 Grid Incomer B0


79

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
80

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
81

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
82

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D08+S1 Grid Incomer B0
83

BB DISCONNECTOR OPEN STATUS Q1 DO x x HARDWIRED =D08+S1 Grid Incomer B0


84

BB DISCONNECTORCLOSED STATUS Q1 DO x x HARDWIRED =D08+S1 Grid Incomer B0


85

HIGH SPEED EARTHING SWITCH OPEN STATUS Q8 DO x x HARDWIRED =D08+S1 Grid Incomer B0
86

HIGH SPEED EARTHING SWITCH CLOSED STATUS Q8 DO x x HARDWIRED =D08+S1 Grid Incomer B0
87

LINE DISCONNECTOR OPEN STATUS Q9 DO x x HARDWIRED =D08+S1 Grid Incomer B0


88

LINE DISCONNECTOR CLOSED STATUS Q9 DO x x HARDWIRED =D08+S1 Grid Incomer B0


89

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D08+S1 Grid Incomer B0


90

ISOLATING LINK Q6 IN DO x x HARDWIRED =D08+S1 Grid Incomer B0


91

ISOLATING LINK Q6 OUT DO x x HARDWIRED =D08+S1 Grid Incomer B0


92
RPLC PROJECT

Sheet 6 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


93

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


94

MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
95

MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
96

BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


97

BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


98

HIGH SPEED EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
99

HIGH SPEED EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
100

HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
101

HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0
102

LINE DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


103

LINE DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D08+S1 Grid Incomer B0


104

BUS BAR VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D07+R07 Bus A VT


105

BUS BAR VOLTAGE L1-L3 (V) AO 0-230kV x x ETHERNET =D07+R07 Bus B VT


106

TRIP CIRCUIT 1 MONITORING 74 DO x x x HARDWIRED =D07+R07 Bus coupler BT


107

TRIP CIRCUIT 2 MONITORING 74 DO x x x HARDWIRED =D07+R07 Bus coupler BT


108

SYNCHROCHECK START 25 DO x x ETHERNET =D07+R07 Bus coupler BT


109

CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


110

CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


111

GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D07+S1 Bus coupler BT


112

MAINTENANCE EARTHING SWITCH Q51 OPEN STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT
113

MAINTENANCE EARTHING SWITCH Q51 CLOSED STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT
114

BB DISCONNECTOR Q1 OPEN STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT


115
RPLC PROJECT

Sheet 7 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

BB DISCONNECTOR Q1 CLOSED STATUS BT A DO x x HARDWIRED =D07+S1 Bus coupler BT


116

MAINTENANCE EARTHING SWITCH Q52 OPEN STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT
117

MAINTENANCE EARTHING SWITCH Q52 CLOSED STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT
118

BB DISCONNECTOR Q10 OPEN STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT


119

BB DISCONNECTOR Q10 CLOSED STATUS BT B DO x x HARDWIRED =D07+S1 Bus coupler BT


120

CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D07+S1 Bus coupler BT


121

CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D07+S1 Bus coupler BT


122

MAINTENANCE EARTHING SWITCH Q51 OPEN COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT
123

MAINTENANCE EARTHING SWITCH Q51 CLOSE COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT
124

BB DISCONNECTOR Q1 OPEN COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT


125

BB DISCONNECTOR Q1 CLOSE COMMAND BT A DI x x x HARDWIRED =D07+S1 Bus coupler BT


126

MAINTENANCE EARTHING SWITCH Q52 OPEN COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
127

MAINTENANCE EARTHING SWITCH Q52 CLOSE COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT
128

BB DISCONNECTOR Q10 OPEN COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT


129

BB DISCONNECTOR Q10 CLOSE COMMAND BT B DI x x x HARDWIRED =D07+S1 Bus coupler BT


130

+R07 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D07+R07 Bus coupler BT


131

SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


132

SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D07+S1 Bus coupler BT


133

EARTHING SWITCH ON BUSBAR Q15 OPEN STATUS DO x x HARDWIRED =D05+S1 Bus A


134

EARTHING SWITCH ON BUSBAR Q15 CLOSED STATUS DO x x HARDWIRED =D05+S1 Bus A


135

EARTHING SWITCH ON BUSBAR Q15 OPEN COMMAND DI x x x HARDWIRED =D05+S1 Bus A


136

EARTHING SWITCH ON BUSBAR Q15 CLOSE COMMAND DI x x x HARDWIRED =D05+S1 Bus A


137

EARTHING SWITCH ON BUSBAR Q16 OPEN STATUS DO x x HARDWIRED =D09+S1 Bus B


138
RPLC PROJECT

Sheet 8 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

EARTHING SWITCH ON BUSBAR Q16 CLOSED STATUS DO x x HARDWIRED =D09+S1 Bus B


139

EARTHING SWITCH ON BUSBAR Q16 OPEN COMMAND DI x x x HARDWIRED =D09+S1 Bus B


140

EARTHING SWITCH ON BUSBAR Q16 CLOSE COMMAND DI x x x HARDWIRED =D09+S1 Bus B


141

MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D07+S1 Bus coupler BT


142

OVERCURRENT PROTECTION ON TEST DO x x HARDWIRED =D07+R07 Bus coupler BT


143

87B PROTECTION ON TEST DO x x HARDWIRED =D07+R07 Bus coupler BT


144

OVERCURRENT PROTECTION ON UNAVAILABLE DO x x x HARDWIRED =D07+R07 Bus coupler BT


145

87B PROTECTION UNAVAILABLE DO x x x HARDWIRED =D07+R07 Bus coupler BT


146

LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D07+R07 Bus coupler BT


147
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D02+R02
148 MS-XFR-604A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D02+R02
149 MS-XFR-604A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D02+R02
150 MS-XFR-604A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D02+R02
151 MS-XFR-604A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D02+R02
152 MS-XFR-604A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D02+R02
153 MS-XFR-604A
TRANSFORMER
+R02 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D02+R02
154 MS-XFR-604A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D02+S1
155 MS-XFR-604A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D02+S1
156 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D02+S1
157 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D02+S1
158 MS-XFR-604A
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D02+S1
159 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D02+S1
160 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D02+S1
161 MS-XFR-604A
RPLC PROJECT

Sheet 9 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D02+S1
162 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D02+S1
163 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D02+S1
164 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D02+S1
165 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D02+S1
166 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D02+S1
167 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D02+S1
168 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D02+S1
169 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D02+S1
170 MS-XFR-604A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
171 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D02+S1
172 MS-XFR-604A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
173 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D02+S1
174 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
175 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D02+S1
176 MS-XFR-604A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
177 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D02+S1
178 MS-XFR-604A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
179 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D02+S1
180 MS-XFR-604A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D02+S1
181 MS-XFR-604A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D02+R02
182 MS-XFR-604A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D02+S1
183 MS-XFR-604A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D02+R02
184 MS-XFR-604A
RPLC PROJECT

Sheet 10 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D02+R02
185 MS-XFR-604A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D02+R02
186 MS-XFR-604A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D02+R02
187 MS-XFR-604A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D03+R03
188 MS-XFR-603A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D03+R03
189 MS-XFR-603A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D03+R03
190 MS-XFR-603A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D03+R03
191 MS-XFR-603A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D03+R03
192 MS-XFR-603A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D03+R03
193 MS-XFR-603A
TRANSFORMER
+R03 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D03+R03
194 MS-XFR-603A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D03+S1
195 MS-XFR-603A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D03+S1
196 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D03+S1
197 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D03+S1
198 MS-XFR-603A
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D03+S1
199 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D03+S1
200 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D03+S1
201 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D03+S1
202 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D03+S1
203 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D03+S1
204 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D03+S1
205 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D03+S1
206 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D03+S1
207 MS-XFR-603A
RPLC PROJECT

Sheet 11 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D03+S1
208 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D03+S1
209 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D03+S1
210 MS-XFR-603A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
211 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D03+S1
212 MS-XFR-603A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
213 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D03+S1
214 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
215 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D03+S1
216 MS-XFR-603A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
217 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D03+S1
218 MS-XFR-603A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
219 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D03+S1
220 MS-XFR-603A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D03+S1
221 MS-XFR-603A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D03+R03
222 MS-XFR-603A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D03+S1
223 MS-XFR-603A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D03+R03
224 MS-XFR-603A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D03+R03
225 MS-XFR-603A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D03+R03
226 MS-XFR-603A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D03+R03
227 MS-XFR-603A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D04+R04
228 MS-XFR-602A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D04+R04
229 MS-XFR-602A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D04+R04
230 MS-XFR-602A
RPLC PROJECT

Sheet 12 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D04+R04
231 MS-XFR-602A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D04+R04
232 MS-XFR-602A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D04+R04
233 MS-XFR-602A
TRANSFORMER
+R04 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D04+R04
234 MS-XFR-602A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D04+S1
235 MS-XFR-602A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D04+S1
236 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D04+S1
237 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D04+S1
238 MS-XFR-602A
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D04+S1
239 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D04+S1
240 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D04+S1
241 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D04+S1
242 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D04+S1
243 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D04+S1
244 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D04+S1
245 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D04+S1
246 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D04+S1
247 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D04+S1
248 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D04+S1
249 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D04+S1
250 MS-XFR-602A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
251 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D04+S1
252 MS-XFR-602A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
253 MS-XFR-602A
RPLC PROJECT

Sheet 13 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D04+S1
254 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
255 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D04+S1
256 MS-XFR-602A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
257 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D04+S1
258 MS-XFR-602A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
259 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D04+S1
260 MS-XFR-602A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D04+S1
261 MS-XFR-602A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D04+R04
262 MS-XFR-602A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D04+S1
263 MS-XFR-602A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D04+R04
264 MS-XFR-602A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D04+R04
265 MS-XFR-602A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D04+R04
266 MS-XFR-602A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D04+R04
267 MS-XFR-602A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D05+R05
268 MS-XFR-601A
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D05+R05
269 MS-XFR-601A
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D05+R05
270 MS-XFR-601A
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D05+R05
271 MS-XFR-601A
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D05+R05
272 MS-XFR-601A
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D05+R05
273 MS-XFR-601A
TRANSFORMER
+R05 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D05+R05
274 MS-XFR-601A
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D05+S1
275 MS-XFR-601A
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D05+S1
276 MS-XFR-601A
RPLC PROJECT

Sheet 14 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D05+S1
277 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D05+S1
278 MS-XFR-601A
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D05+S1
279 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D05+S1
280 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D05+S1
281 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D05+S1
282 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D05+S1
283 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D05+S1
284 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D05+S1
285 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D05+S1
286 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D05+S1
287 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D05+S1
288 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D05+S1
289 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D05+S1
290 MS-XFR-601A
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
291 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D05+S1
292 MS-XFR-601A
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
293 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D05+S1
294 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
295 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D05+S1
296 MS-XFR-601A
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
297 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D05+S1
298 MS-XFR-601A
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
299 MS-XFR-601A
RPLC PROJECT

Sheet 15 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D05+S1
300 MS-XFR-601A
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D05+S1
301 MS-XFR-601A
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D05+R05
302 MS-XFR-601A
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D05+S1
303 MS-XFR-601A
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D05+R05
304 MS-XFR-601A
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D05+R05
305 MS-XFR-601A
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D05+R05
306 MS-XFR-601A
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D05+R05
307 MS-XFR-601A
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D09+R09
308 MS-XFR-601B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D09+R09
309 MS-XFR-601B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D09+R09
310 MS-XFR-601B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D09+R09
311 MS-XFR-601B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D09+R09
312 MS-XFR-601B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D09+R09
313 MS-XFR-601B
TRANSFORMER
+R09 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D09+R09
314 MS-XFR-601B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D09+S1
315 MS-XFR-601B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D09+S1
316 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D09+S1
317 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D09+S1
318 MS-XFR-601B
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D09+S1
319 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D09+S1
320 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D09+S1
321 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D09+S1
322 MS-XFR-601B
RPLC PROJECT

Sheet 16 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D09+S1
323 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D09+S1
324 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D09+S1
325 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D09+S1
326 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D09+S1
327 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D09+S1
328 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D09+S1
329 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D09+S1
330 MS-XFR-601B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
331 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D09+S1
332 MS-XFR-601B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
333 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D09+S1
334 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
335 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D09+S1
336 MS-XFR-601B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
337 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D09+S1
338 MS-XFR-601B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
339 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D09+S1
340 MS-XFR-601B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D09+S1
341 MS-XFR-601B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D09+R09
342 MS-XFR-601B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D09+S1
343 MS-XFR-601B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D09+R09
344 MS-XFR-601B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D09+R09
345 MS-XFR-601B
RPLC PROJECT

Sheet 17 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D09+R09
346 MS-XFR-601B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D09+R09
347 MS-XFR-601B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D10+R10
348 MS-XFR-602B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D10+R10
349 MS-XFR-602B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D10+R10
350 MS-XFR-602B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D10+R10
351 MS-XFR-602B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D10+R10
352 MS-XFR-602B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D10+R10
353 MS-XFR-602B
TRANSFORMER
+R10 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D10+R10
354 MS-XFR-602B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D10+S1
355 MS-XFR-602B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D10+S1
356 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D10+S1
357 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D10+S1
358 MS-XFR-602B
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D10+S1
359 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D10+S1
360 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D10+S1
361 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D10+S1
362 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D10+S1
363 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D10+S1
364 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D10+S1
365 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D10+S1
366 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D10+S1
367 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D10+S1
368 MS-XFR-602B
RPLC PROJECT

Sheet 18 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D10+S1
369 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D10+S1
370 MS-XFR-602B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
371 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D10+S1
372 MS-XFR-602B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
373 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D10+S1
374 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
375 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D10+S1
376 MS-XFR-602B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
377 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D10+S1
378 MS-XFR-602B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
379 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D10+S1
380 MS-XFR-602B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D10+S1
381 MS-XFR-602B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D10+R10
382 MS-XFR-602B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D10+S1
383 MS-XFR-602B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D10+R10
384 MS-XFR-602B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D10+R10
385 MS-XFR-602B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D10+R10
386 MS-XFR-602B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D10+R10
387 MS-XFR-602B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D11+R11
388 MS-XFR-603B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D11+R11
389 MS-XFR-603B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D11+R11
390 MS-XFR-603B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D11+R11
391 MS-XFR-603B
RPLC PROJECT

Sheet 19 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D11+R11
392 MS-XFR-603B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D11+R11
393 MS-XFR-603B
TRANSFORMER
+R11 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D11+R11
394 MS-XFR-603B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D11+S1
395 MS-XFR-603B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D11+S1
396 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D11+S1
397 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D11+S1
398 MS-XFR-603B
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D11+S1
399 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D11+S1
400 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D11+S1
401 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D11+S1
402 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D11+S1
403 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D11+S1
404 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D11+S1
405 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D11+S1
406 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D11+S1
407 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D11+S1
408 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D11+S1
409 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D11+S1
410 MS-XFR-603B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
411 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D11+S1
412 MS-XFR-603B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
413 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D11+S1
414 MS-XFR-603B
RPLC PROJECT

Sheet 20 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
415 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D11+S1
416 MS-XFR-603B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
417 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D11+S1
418 MS-XFR-603B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
419 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D11+S1
420 MS-XFR-603B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D11+S1
421 MS-XFR-603B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D11+R11
422 MS-XFR-603B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D11+S1
423 MS-XFR-603B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D11+R11
424 MS-XFR-603B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D11+R11
425 MS-XFR-603B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D11+R11
426 MS-XFR-603B
TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D11+R11
427 MS-XFR-603B
TRANSFORMER
TRIP CIRCUIT MONITORING 1 74 DO x x x HARDWIRED =D12+R12
428 MS-XFR-604B
TRANSFORMER
TRIP CIRCUIT MONITORING 2 74 DO x x x HARDWIRED =D12+R12
429 MS-XFR-604B
TRANSFORMER
LOCKOUT RELAY OPERATED 86 DO x x x HARDWIRED =D12+R12
430 MS-XFR-604B
TRANSFORMER
OVERCURRENT TRIP 51 DO x x x ETHERNET =D12+R12
431 MS-XFR-604B
TRANSFORMER
EARTH FAULT TRIP 51N DO x x x ETHERNET =D12+R12
432 MS-XFR-604B
TRANSFORMER
87L TRIP 87L DO x x x ETHERNET =D12+R12
433 MS-XFR-604B
TRANSFORMER
+R12 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D12+R12
434 MS-XFR-604B
TRANSFORMER
SELECTOR SWITCH POSITION REMOTE STATUS DO x x HARDWIRED =D12+S1
435 MS-XFR-604B
TRANSFORMER
SELECTOR SWITCH POSITION LOCAL STATUS DO x x HARDWIRED =D12+S1
436 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSED STATUS DO x x HARDWIRED =D12+S1
437 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN STATUS DO x x HARDWIRED =D12+S1
438 MS-XFR-604B
TRANSFORMER
GENERAL LOCKOUT SF6 DO x x x HARDWIRED =D12+S1
439 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN STATUS DO x x HARDWIRED =D12+S1
440 MS-XFR-604B
RPLC PROJECT

Sheet 21 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BB DISCONNECTOR Q1 CLOSED STATUS DO x x HARDWIRED =D12+S1
441 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN STATUS DO x x HARDWIRED =D12+S1
442 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSED STATUS DO x x HARDWIRED =D12+S1
443 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN STATUS DO x x HARDWIRED =D12+S1
444 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSED STATUS DO x x HARDWIRED =D12+S1
445 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN STATUS DO x x HARDWIRED =D12+S1
446 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSED STATUS DO x x HARDWIRED =D12+S1
447 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN STATUS DO x x HARDWIRED =D12+S1
448 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSED STATUS DO x x HARDWIRED =D12+S1
449 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 OPEN COMMAND DI x x x HARDWIRED =D12+S1
450 MS-XFR-604B
TRANSFORMER
CIRCUIT BREAKER Q0 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
451 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 OPEN COMMAND DI x x x HARDWIRED =D12+S1
452 MS-XFR-604B
TRANSFORMER
BB DISCONNECTOR Q1 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
453 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 OPEN COMMAND DI x x x HARDWIRED =D12+S1
454 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q51 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
455 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 OPEN COMMAND DI x x x HARDWIRED =D12+S1
456 MS-XFR-604B
TRANSFORMER
MANTEINANCE EARTHING SWITCH Q52 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
457 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 OPEN COMMAND DI x x x HARDWIRED =D12+S1
458 MS-XFR-604B
TRANSFORMER
TRANSFORMER DISCONNECTOR Q9 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
459 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 OPEN COMMAND DI x x x HARDWIRED =D12+S1
460 MS-XFR-604B
TRANSFORMER
HIGH SPEED EARTHING SWITCH Q8 CLOSE COMMAND DI x x x HARDWIRED =D12+S1
461 MS-XFR-604B
TRANSFORMER
CURRENT L2 (A) AO x x ETHERNET =D12+R12
462 MS-XFR-604B
TRANSFORMER
MASTER INTERLOCK OVERRIDE DO x x HARDWIRED =D12+S1
463 MS-XFR-604B
TRANSFORMER
MAIN PROTECTION TP1 ON TEST DO x x HARDWIRED =D12+R12
464 MS-XFR-604B
TRANSFORMER
BACKUP PROTECTION TP2 ON TEST DO x x HARDWIRED =D12+R12
465 MS-XFR-604B
TRANSFORMER
MAIN PROTECTION TP1 UNAVAILABLE DO x x x HARDWIRED =D12+R12
466 MS-XFR-604B
RPLC PROJECT

Sheet 22 of 22
Rev E

SIGNAL LIST Doc. No. V-SIE-EL001-COMMON-074

FUNCTION
Function Signal Signal Ethernet / Equipment
Item N Tag N Service Equipment Label Remark
Code Type Range Hardwired Address
I R C A T

TRANSFORMER
BACKUP PROTECTION TP2 UNAVAILABLE DO x x x HARDWIRED =D12+R12
467 MS-XFR-604B
+P00 PANEL AC FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
468
ANNUNCIATOR PANEL 1 -F091 FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
469
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-604A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
470
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-603A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
471
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-602A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
472
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-601A ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
473
125VCC DISTRIBUTION TO LINE A FROM PAL ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
474
125VCC DISTRIBUTION TO BUSBAR COUPLER ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
475
ANNUNCIATOR PANEL 2 -F092 FEEDER FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
476
125VCC DISTRIBUTION TO LINE B FROM PAL ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
477
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-601B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
478
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-602B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
479
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-603B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
480
125VCC DISTRIBUTION TO TRANSFORMER MS-XFR-604B ON FAULT DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
481
ANNUNCIATOR PANEL 1 UNAVAILABLE DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
482
ANNUNCIATOR PANEL 2 UNAVAILABLE DO x x x HARDWIRED =D00+P00 ANNUNCIATOR PANEL
483

Note: Maintenance network switch shall be provided for diagnostic and troubleshooting in PSCS.
Alarm signals from GIS are sent to PSCS hardwired from LCCs clasified like "alarm" on this list

TOTAL DI DO AI AO HARDWIRED ETHERNET

134 305 28 404 63