TheworddemanditselfsaysthemeaningofDemandFactor.Theratioofthemaximumcoincidentdemandofasystem,orpart
ofasystem,tothetotalconnectedloadofthesystem.

Demand Factor = Maximum demand / Total connected load

Forexample,anoversizedmotor20Kwdrivesaconstant15KwloadwheneveritisON.Themotordemandfactoristhen15/20
=0.75=75%.
DemandFactorisexpressasapercentage(%)orinaratio(lessthan1).

Demand factor is always < =1.

DemandFactorisalwayschangewiththetimetotimeorhourstohoursofuseanditwillnotconstant.
Theconnectedloadisalwaysknownsoitwillbeeasytocalculatethemaximumdemandifthedemandfactorforacertainsupply
isknownatdierenttimeintervalsandseasons.
Thelowerthedemandfactor,thelesssystemcapacityrequiredtoservetheconnectedload.

Calculation:

(1)AResidenceConsumerhas10NosLampof400WbutatthesametimeItispossiblethatonly9NosofBulbsareusedatthe
sametime.HereTotalConnectedloadis1040=400W.Consumermaximumdemandis940=360W.DemandFactoofthisLoad
=360/400=0.9or90%.
(2)OneConsumerhave10lightsat60KweachinKitchen,theloadis60Kwx10=600KW.ThiswillbetrueonlyifAlllightsare
TurnsONthesametime(Demandfactor=100%or1)
ForthisConsumeritisobservedthatonlyhalfofthelightsbeingturnedONatatimesowecansaythatthedemandfactoris0.5
(50%).Theestimatedload=600KwX0.5=300Kw.

Use of demand factors:

FeederconductorsshouldhavesucientAmpereCapacitytocarrytheload. TheAmpereCapacitydoesnotalwaysbeequalto
thetotalofallloadsonconnectedbranchcircuits.
Thisfactormustbeappliedtoeachindividualload,withparticularattentiontoelectricmotors,whichareveryrarelyoperatedat
fullload.
AsperNationalElectricalCode(NEC)demandfactormaybeappliedtothetotalload.Thedemandfactorpermitsafeeder
ampearcitytobelessthan100percentofallthebranchcircuitloadsconnectedtoit.
DemandfactorcanbeappliedtocalculatethesizeofthesubmainwhichisfeedingaSubpanelorafixedloadlikeamotoretc.If
thepanelhavetotalloadof250kVA,consideringaDemandfactorof0.8,wecansizethefeedercablefor250x0.8=200kVA.
Demandfactorsforbuildingstypicallyrangebetween50and80%oftheconnectedload.
Inanindustrialinstallationthisfactormaybeestimatedonanaverageat0.75formotors.
Forincandescentlightingloads,thefactoralwaysequals1.

Demand Factor For Industrial


Load

TextBookofDesignofElect.InstallationJain

ElectricalLoad DemandFactor

1NoofMotor 1

Upto10NosofMotor 0.75

Upto20NosofMotor 0.65

Upto30NosofMotor 0.6

1 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Upto40NosofMotor 0.5

Upto50NosofMotor 0.4

Demand Factor

TextBookofDesignofElect.InstallationJain

Utility DemandFactor

Oce,School 0.4

Hospital 0.5

AirPort,Bank,Shops, 0.6

Restaurant,Factory, 0.7

WorkShop,Factory(24Hr 0.8
Shift)

ArcFurnace 0.9

Compressor 0.5

Handtools 0.4

InductanceFurnace 0.8

Demand Factor

SaudiElectricityCompanyDistributionStandard

Utility DemandFactor

Residential 0.6

Commercial 0.7

Flats 0.7

Hotel 0.75

Mall 0.7

Restaurant 0.7

Oce 0.7

School 0.8

CommonAreainbuilding 0.8

PublicFacility 0.75

StreetLight 0.9

IndoorParking 0.8

OutdoorParking 0.9

Park/Garden 0.8

Hospital 0.8

Workshops 0.6

WareHouse 0.7

Farms 0.9

FuelStation 0.7

Factories 0.9

2 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Demand Factor

TextBookofPrincipalofPowerSystemV.K.Mehta

Utility DemandFactor

ResidenceLoad(<0.25KW) 1

ResidenceLoad(<0.5KW) 0.6

ResidenceLoad(>0.1KW) 0.5

Restaurant 0.7

Theatre 0.6

Hotel 0.5

School 0.55

SmallIndustry 0.6

Store 0.7

MotorLoad(upto10HP) 0.75

MotorLoad(10HPto20HP) 0.65

MotorLoad(20HPto100HP) 0.55

MotorLoad(Above100HP) 0.50

DiversityFactorisratioofthesumoftheindividualmaximumdemandsofthevarioussubcircuitofasystemtothemaximum
demandofthewholesystem.

Diversity Factor = Sum of Individual Maximum Demands / Maximum Demand of


the System.

DiversityFactor=Installedload/Runningload.

The diversity factor is always >= 1.

DiversityFactorisalways>1becausesumofindividualmax.Demands>Max.Demand.
Inotherterms,DiversityFactor(0to100%)isafractionofTotalLoadthatisparticularitemcontributedtopeakdemand.70%
diversitymeansthatthedeviceoperatesatitsnominalormaximumloadlevel70%ofthetimethatitisconnectedandturned
ON.
Itisexpressedasapercentage(%)oraratiomorethan1.
Ifweusediversityvaluein%thanitshouldbemultiplywithLoadandifweuseinnumericalvalue(>1)thanitshouldbe
dividedwithLoad.
DiversityoccursinanoperatingsystembecauseallloadsconnectedtotheSystemarenotoperatingsimultaneouslyorarenot
simultaneouslyoperatingattheirmaximumrating.Thediversityfactorshowsthatthewholeelectricalloaddoesnotequalthe
sumofitspartsduetothistimeInterdependence(i.e.diverseness).
Ingeneraltermswecansaythatdiversityfactorreferstothepercentoftimeavailablethatamachine.70%diversitymeansthat
thedeviceoperatesatitsnominalormaximumloadlevel70%ofthetimethatitisconnectedandturnedON.
ConsidertwoFeederswiththesamemaximumdemandbutthatoccuratdierentintervalsoftime.Whensuppliedbythesame
feeder,thedemandonsuchislessthesumofthetwodemands.Inelectricaldesign,thisconditionisknownasdiversity.
Diversityfactorisanextendedversionofdemandfactor.Itdealswithmaximumdemandofdierentunitsatatime/Maximum
demandoftheentiresystem.
Greaterthediversityfactor,lesseristhecostofgenerationofpower.
Manydesignersprefertouseunityasthediversityfactorincalculationsforplanningconservatismbecauseofplantloadgrowth
uncertainties.Localexperiencecanjustifyusingadiversityfactorlargerthanunity,andsmallerserviceentranceconductorsand
transformerrequirementschosenaccordingly.
Thediversityfactorforallotherinstallationswillbedierent,andwouldbebaseduponalocalevaluationoftheloadstobe
appliedatdierentmomentsintime.Assumingittobe1.0may,onsomeoccasions,resultinasupplyfeederandequipment
ratingthatisratherlargerthanthelocalinstallationwarrants,andanoverinvestmentincableandequipmenttohandletherated
loadcurrent.Itisbettertoevaluatethepatternofusageoftheloadsandcalculateanacceptablediversityfactorforeach
particularcase.

Calculation:

OneMainFeederhavetwoSubfeeder(SubFeederAandSubFeederB),SubFeederAhavedemandatatimeis35KWandSub

3 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

FeederBhavedemandsatatimeis42KW,butthemaximumdemandofMainFeederis70KW.
TotalindividualMaximumDemand=35+42=77KW.
MaximumDemandofwholeSystem=70KW
SoDiversityfactorofTheSystem=77/70=1.1
Diversityfactorcanshootupabove1.

Use of diversity factor:

TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionorsubdistributionboard).
Diversityfactoriscommonlyusedforacompleteacoordinationstudyforasystem.Thisdiversityfactorisusedtoestimatethe
loadofaparticularnodeinthesystem.
DiversityfactorcanbeusedtoestimatethetotalloadrequiredforafacilityortosizetheTransformer
Diversityfactorshavebeendevelopedformainfeederssupplyinganumberoffeeders,andtypically1.2to1.3forResidence
Consumerand1.1to1.2forCommercialLoad.1.50to2.00forpowerandlightingloads.
Note:Reciprocaloftheaboveratio(willbemorethan1)alsoisusedinsomeothercountries.
Diversityfactorismostlyusedfordistributionfeedersizeandtransformeraswellastodeterminethemaximumpeakloadand
diversityfactorisalwaysbasedonknowingtheprocess.Youhavetounderstandwhatwillbeonoroatagiventimefor
dierentbuildingsandthiswillsizethefeeder.Notefortypicalbuildingsdiversityfactorisalwaysone.Youhavetoestimateor
haveadatarecordstocreate24hoursloadgraphandyoucandeterminethemaximumdemandloadfornodethenyoucan
easilydeterminethefeederandtransformersize.
Thediversityfactorofafeederwouldbethesumofthemaximumdemandsoftheindividualconsumersdividedbythe
maximumdemandofthefeeder.Inthesamemanner,itispossibletocomputethediversityfactoronasubstation,atransmission
lineorawholeutilitysystem.
Theresidentialloadhasthehighestdiversityfactor.Industrialloadshavelowdiversityfactorsusuallyof1.4,streetlight
practicallyunityandotherloadsvarybetweentheselimits.

Diversity Factor in distribution Network

(StandardHandbookforElectricalEngineersbyFinkandBeaty)

ElementsofSystem Residential Commercial GeneralPower LargeIndustrial

Betweenindividual 2.00 1.46 1.45


users
1.30 1.30 1.35 1.05
Betweentransformers

1.15 1.15 1.15 1.05


Betweenfeeders

1.10 1.10 1.10 1.10


Betweensubstations

Fromusersto 2.00 1.46 1.44


transformers
2.60 1.90 1.95 1.15
Fromuserstofeeder

Fromusersto 3.00 2.18 2.24 1.32


substation
Fromusersto 3.29 2.40 2.46 1.45
generatingstation

Diversity Factor for Distribution


Switchboards

Numberofcircuits DiversityFactorin%(ks)

Assembliesentirelytested2and3 90%

4and5 80%

6to9 70%

10andmore 60%

Assembliespartiallytestedineverycase 100%
choose

Diversity Factor as per IEC 60439

CircuitsFunction DiversityFactorin%(ks)
Lighting 90%

4 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Heatingandairconditioning 80%

Socketoutlets 70%

Liftsandcateringhoist

Forthemostpowerfulmotor 100%

Forthesecondmostpowerfulmotor 75%

Forallmotors 80%

Diversity Factor for Apartment


block

Apartment DiversityFactorin%(ks)

2To4 1

5To19 0.78

10To14 0.63

15To19 0.53

20To24 0.49

25To29 0.46

30To34 0.44

35To39 0.42

40To40 0.41

50ToAbove 0.40

Diversity Factor

TextBookofPrincipalofPowerSystemV.K.Mehta

Area ResidenceLtg CommercialLtg Ind.Ltg

BetweenConsumer 3 1.5 1.5

Between 1.3 1.3 1.3


Transformer

BetweenFeeder 1.2 1.2 1.2

BetweenS.S 1.1 1.1 1.1

TheratiooftheActualLoadofequipmenttoFullloadofequipment.

Load Factor=Actual Load / Full Load

ItistheratioofactualkilowattHoursusedinagivenperiod,dividedbythetotalpossiblekilowatthoursthatcouldhavebeen
usedinthesameperiodatthepeakKWlevel.
LoadFactor=(energy(kWhpermonth))/(peakdemand(kW)xhours/month)
InothertermsLoadfactorisdefinedastheratioofAverageloadtomaximumdemandduringagivenperiod.
LoadFactor=AverageLoad/MaximumDemandduringgivenTimePeriod

The Load factor is always <=1.

LoadFactorisalwayslessthan1becausemaximumdemandisalwaysmorethanaveragedemand.
LoadFactorcanbecalculatedforasingleday,foramonthorforayear.
Loadfactorinothertermsofeciency.

5 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Itisusedfordeterminingtheoverallcostperunitgenerated.
HighertheloadfactorisGOODanditwillmoreOutputofPlan,lesserthecostperunitwhichmeansanelectricitygeneratorcan
sellmoreelectricityatahighersparkspread,FixedcostsarespreadovermorekWhofoutput.Apowerplantmaybehighly
ecientatHighloadfactors.
LowloadfactorisaBED.Alowloadfactorwilluseelectricityinecientlyrelativetowhatwecouldbeifwewerecontrolling
ourpeakdemand.Apowerplantmaybelessecientatlowloadfactors.
Foralmostconstantloads,theloadfactorisclosetounity.
ForVaryingLoadFactorisclosedZero.
LoadFactorisameasureoftheeectiveutilizationoftheloadanddistributionequipment,i.e.higherloadfactormeansbetter
utilizationofthetransformer,lineorcable.
Ahighloadfactormeanspowerusageisrelativelyconstant.Lowloadfactorshowsthatoccasionallyahighdemandisset.To
servicethatpeak,capacityissittingidleforlongperiods,therebyimposinghighercostsonthesystem.Electricalratesare
designedsothatcustomerswithhighloadfactorarechargedlessoverallperkWh.
Sometimesutilitycompanieswillencourageindustrialcustomerstoimprovetheirloadfactors.
Loadfactoristermthatdoesnotappearonyourutilitybill,butdoesaectelectricitycosts.Loadfactorindicateshow
ecientlythecustomerisusingpeakdemand.
Calculation:

Motorof20hpdrivesaconstant15hploadwheneveritison.
Themotorloadfactoristhen15/20=75%.

Demand Factor & Load Factor

IntroductiontoPowerRequirementforBuildingJ.PaulGuyer,

Utility DemandFactor(%) LoadFactor(%)

Communicationsbuildings 6065 7075

Telephoneexchangebuilding 5570 2025

Airpassengerterminalbuilding 6580 2832

Aircraftfireandrescuestation 2535 1317

Aircraftlineoperationsbuilding 6580 2428

Academicinstructionbuilding 4060 2226

Appliedinstructionbuilding 3565 2428

ChemistryandToxicology 7080 2228


Laboratory

MaterialsLaboratory 3035 2732

PhysicsLaboratory 7080 2228

Electricalandelectronicslaboratory 2030 37

Coldstoragewarehouse 7075 2025

Generalwarehouse 7580 2328

Controlledhumiditywarehouse 6065 3338

Hazardous/flammablestorehouse 7580 2025

Disposal,salvage,scrapbuilding 3540 2520

Hospital 3842 4550

Laboratory 3237 2025

K6schools 7580 1015

712schools 6570 1217

Churches 6570 525

PostOce 7580 2025

Retailstore 6570 2532

Bank 7580 2025

Supermarket 5560 2530

Restaurant 4575 1525

Autorepairshop 4060 1520

6 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Hobbyshop,art/crafts 3040 2530

Bowlingalley 7075 1015

Gymnasium 7075 2045

Skatingrink 7075 1015

Indoorswimmingpool 5560 2550

Theatres 4555 813

Library 7580 3035

Golfclubhouse 7580 1520

Museum 7580 3035

Thereciprocalofdiversityfactoriscoincidencefactor
Thecoincidencefactoristheratioofthemaximumdemandofasystem,orpartunderconsideration,tothesumoftheindividual
maximumdemandsofthesubdivisions

Coincidence factor = Maximum demand / Sum of individual maximum demands

Expressedasapercentage(%)oraratiolessthan1.

The Confidence Factor is always <=1.

UsuallyConfidenceFactorwilldecreaseasthenumberofconnectedcustomersincreases.
Thefactorksisappliedtoeachgroupofloads(e.g.distributionorsubdistributionboard).
Thedeterminationofthesefactorsistheresponsibilityofthedesigner,sinceitrequiresadetailedknowledgeoftheinstallation
andtheconditionsinwhichtheindividualcircuitsaretobeexploited.Forthisreason,itisnotpossibletogiveprecisevaluesfor
generalapplication.

Themaximumdemandofaninstallationisthemaximumrateofconsumptionexpressedinamperes,kWorkVA.Itisgenerally
takenastheaveragerateofconsumptionoveraperiodoftime.Examplethe15minutemaximumkWdemandfortheweekwas
150kW.Maximumdemanddoesnotincludemotorstartingcurrentsorothertransienteects.Faultcurrentsandoverload
currentsarealsoexcluded.MaximumdemandinKWisrelevantonlyformetering/taripurposes.
Maximumdemand(oftenreferredtoasMD)isthelargestcurrentnormallycarriedbycircuits,switchesandprotectivedevices.It
doesnotincludethelevelsofcurrentflowingunderoverloadorshortcircuitconditions.
MaximumDemandisagreatestofalldemandsthatoccurduringaspecifictime
Themajordisadvantageofallocatingloadusingthediversityfactorsisthatmostutilitieswillnothaveatableofdiversityfactors
andsometimeitisnotviabletodetermineaccurateDiversityFactor.InthissituationMaximumDemandisveryhelpfulto
calculatesizeofFeederorTC.
ThekVAratingofalldistributiontransformersisalwaysknownforafeeder.Themeteredreadingscanbetakentoeach
transformerbaseduponthetransformerrating.Anallocationfactor(AF)canbecalculate.
AllocationFactor=MeteredDemand(KVA)/TotalKVA.
EquipmentDemand=AFxTotalKVAofEquipments

Calculation:
ActualLoadingorSizeofTC1andTC2.

(https://electricalnotes.files.wordpress.com/2011/10/11.jpg)

TotalLoadonTC1=10+11+12+08=41KW.
MaximumDiversityDemandofTC1=41/1.1=37.3KW.
TotalLoadonTC2=4+3+12+02=21KW.
MaximumDiversityDemandofTC2=21/1.2=17.5KW.
TotalLoad=37.3+17.5=54.8KW.
AllocatingFactor(AF)=M.D/TotalLoad
AllocatingFactor(AF)=0.27.
ActualLoadonTC1=0.2737.3=1.20KW.
ActualLoadonTC2=0.2717.5=4.8KW.
AssessmentofmaximumdemandisveryeasyforResistiveLoad,Forexample,themaximumdemandofa240Vsinglephase8

7 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

kWshowerheatercanbecalculatedbydividingthepower(8kW)bythevoltage(240V)togiveacurrentof33.3A.This
calculationassumesapowerfactorofunity,whichisareasonableassumptionforsuchapurelyresistiveload.
LightingcircuitsposeaspecialproblemwhendeterminingMD.Dischargelampsareparticularlydiculttoassess,andcurrent
cannotbecalculatedsimplybydividinglamppowerbysupplyvoltage.ThereasonsforthisareControlgearlossesresultin
additionalcurrent,thepowerfactorisusuallylessthanunitysocurrentisgreater,andChokesandothercontrolgearusually
distortthewaveformofthecurrentsothatitcontainsharmonicswhichareadditionaltothefundamentalsupplycurrent.
Solongasthepowerfactorofadischargelightingcircuitisnotlessthan0.85,thecurrentdemandforthecircuitcanbecalculated
from:
current(A)=(lamppower x1.8)/supplyvoltage(V)
Forexample,thesteadystatecurrentdemandofa240Vcircuitsupplyingten65Wfluorescentlampswouldbe:I=10X65X1.8A/
240=4.88A
Switchesforcircuitsfeedingdischargelampsmustberatedattwicethecurrenttheyarerequiredtocarry,unlesstheyhavebeen
speciallyconstructedtowithstandtheseverearcingresultingfromtheswitchingofsuchinductiveandcapacitiveloads.

ThereisgenerallyconfusionbetweenDemandfactorandDiversityfactor.Demandfactorsshouldbeideallyappliedto
individualloadsanddiversityfactortoagroupofloads.
Whenyoutalkaboutdiversity,therearenaturallymorethanoneormanyloadsinvolved.
Demandfactorcanbeappliedtocalculatethesizeofthesubmain,whichisfeedingaSubpanelorafixedloadlikeamotoretc,
individualLoad.
DemandfactorsaremoreconservativeandareusedbyNECforserviceandfeedersizing.
IftheSubpanelhavetotalloadis250kVA,consideringaDemandfactorof0.8,wecansizethefeedercablefor250x0.8=200
kVA.
TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionorsubdistributionboard),sizethe
Transformer.
Demandfactorsanddiversityfactorsareusedindesign.Forexample,thesumoftheconnectedloadssuppliedbyafeederis
multipliedbythedemandfactortodeterminetheloadforwhichthefeedermustbesized.Thisloadistermedthemaximum
demandofthefeeder.Thesumofthemaximumdemandloadsforanumberofsubfeedersdividedbythediversityfactorforthe
subfeederswillgivethemaximumdemandloadtobesuppliedbythefeederfromwhichthesubfeedersarederived.

Theestimatedelectricaldemandforallfeedersserveddirectlyfromtheserviceentranceiscalculatedbymultiplyingthetotal
connectedloadsbytheirdemandfactorsandthenaddingallofthesetogether.Thissumisdividedbythediversityfactor
(frequentlyassumedtobeunity)tocalculatetheserviceentrancedemandwhichisusedtodetermineampacityrequirements
fortheserviceentranceconductors.
WhenusedDiversityandDemandFactorinanelectricaldesignitshouldbeappliedasfollows,thesumoftheconnectedloads
suppliedbyafeedercircuitcanbemultipliedbythedemandfactortodeterminetheloadusedtosizethecomponentsofthe
system.
Thesumofthemaximumdemandloadsfortwoormorefeedersisdividedbythediversityfactorforthefeederstoderivethe
maximumdemandload.
Example1:CalculateSizeofTransformerhavingfollowingdetails:

(https://electricalnotes.files.wordpress.com/2011/10/2.jpg)

FeederBreaker1DemandLoad=FeederBreaker1xDemandFactor.

FeederBreaker1DemandLoad=20000.7=1400KVA

FeederBreaker2DemandLoad=FeederBreaker2xDemandFactor.

FeederBreaker2DemandLoad=15000.6=900KVA

FeederBreaker3DemandLoad=FeederBreaker3xDemandFactor.

FeederBreaker2DemandLoad=10000.5=500KVA
TotalFeederBreakerDemand=1400+900+500=2800KVA
TransformerDemandLoad=TotalFeederBreakerDemand/DiversityFactor.
TransformerDemandLoad=2800/1.1=2545KVA
IfweCalculatedTotalLoadonTransformerwithoutanyDemand&Diversity=2000+1500+1000=4500KVA.
ButafterCalculatingDemand&DiversityFactorTotalLoadonTransformer=2545KVA

Example2:CalculateSizeofMainFeederofMainTransformerhavingfollowingDetails:

8 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

(https://electricalnotes.files.wordpress.com/2011/10/3.jpg)

SumofMaximumDemandofCustomeronTC1=10KWx0.65=6.5KW
SumofMaximumDemandofCustomeronTC2=20KWx0.75=15KW
SumofMaximumDemandofCustomeronTC3=30KWx0.65=19.5KW
AsDiversityofConsumerConnectedonTC1is1.5so,
MaximumDemandonTC1=6.5KW/1.5=4KW.
AsDiversityofConsumerConnectedonTC2is1.1so,
MaximumDemandonTC2=15KW/1.1=14KW
AsDiversityofConsumerConnectedonTC3is1.5so,
MaximumDemandonTC3=19.5KW/1.5=13KW.
IndividualMaximumDemandonMainTransformer=04+14+13=31KW.
MaximumDemandonMainFeeder=04+14+13/1.3=24KW

Loadfactoranddiversityfactorplayanimportantpartinthecostofthesupplyofelectricalenergy.Higherthevaluesofload
factoranddiversityfactors,lowerwillbetheoverallcostperunitgenerated.
Thecapitalcostofthepowerstationdependsuponthecapacityofthepowerstation.Lowerthemaximumdemandofthepower
station,theloweristhecapacityrequiredandthereforeloweristhecapitalcostoftheplant.Withagivennumberofconsumers
thehigherthediversityfactoroftheirloads,thesmallerwillbethecapacityoftheplantrequiredandconsequentlythefixed
chargesduetocapitalinvestmentwillbemuchreduced.
Similarlyhigherloadfactormeansmoreaverageloadormorenumberofunitsgeneratedforagivenmaximumdemandand
thereforeoverallcostperunitofelectricalenergygeneratedisreducedduetodistributionofstandingchargeswhichare
proportionaltomaximumdemandandindependentofnumberofunitsgenerated.
Thusthesuppliersshouldalwaystrytoimprovetheloadfactoraswellasdiversityfactorbyinducingtheconsumerstousethe
electricalenergyduringopeakhoursandtheymaybechargedatlowerratesforsuchschemes.

FILEDUNDERUNCATEGORIZED

AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan14years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

78 Responses to Demand Factor-Diversity Factor-Utilization Factor-Load Factor

Manish says:
October31,2011at4:14pm
Thankyouverymuchforsuchagoodanddetailedarticle.
Yourblogpostsarealwaysquitegood!

Reply
Dieter says:
November9,2011at10:55am
AsajuniorE&IEngineer,Iherewiththankyouforyourkindnessofsharingyourknowledge.

Ilookforewardtomoreofyourwork.

Reply
S.SAMBATH says:
November29,2011at1:36pm

9 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Sir,
TheinformationsareveryusefullikemeasElectricityBoardEngineer.ThankuandIexpectmore.
s.sambath

Reply
zaheerkhattak says:
May30,2012at7:15am
dearsir,thanksalotbothofuiamelectricalengineerandimworkinginconsultancyfirminpakistan
imostlydesignhighriseocialandresidentialbuilding.iwanttoshareandgainsomeimportantknowledgeabout
designingforAllofuandeveryonehowhelpme.
thanks
Zaheerkhattak
shazconsultantPeshawarPakistan

availableonFacebook

chemie says:
November30,2011at6:21am
mefrommalaysiauaregreatsir..thanksalot

Reply
Md.Samiuddin says:
December7,2011at8:58am
DearMr.JigneshParmar,

Thedetailsprovidedbyareveryuseful.Excellent!

Ineedasmallhelp.IamanIndian,nativeofAndhraPradesh.Iamamechanicalengineer,handlinganewprojectinJeddah,
SaudiArabia.
Thedetailsinthepowersummaryreportare:
ConnectedPowerUsage=1290KWH
Aftermultiplyingbypowerfactorsandmaximumutilizationfactorsindividuallytoeachequipmentthesumis=535KWH.
Example:Craneconnectedpower=95kwh;powerfactor=0.6;Max.Utlzn.Factor=0.75gives95kwhX0.6X0.75=42.75kwh

Now,IfIwantbuythegenerators(OR)toaskforelectricitydept.whatpowershouldIask?Willitbe1290KWHor535KWH?
PleaseclarifyandexplainmetoimprovemyawaenessinthisperticulartopicbecausealwaysIcomeacrosswithsuchincidents.

Pleasereplytometomyemail:(or)

Thanksforyoursupportinadvance.

BestRegard

Md.Samiuddin
Plantmanager
MIMCo.,
Jeddah
KSA

Reply
MansourA, says:
January15,2012at7:08pm
ThankuverymuchMr.Parmar,Ireallygetuseandunderstandthesefactorswhichwereconfusedtome.Ihavesetthissitein
favouritieslookingforewardtoreadyourgoodactivities.

Reply
francisazumah says:
February18,2012at2:49pm
amverygreatfulfortheexplanatorynotes,isaywelldonebutneedsmoreofthat.thankyou

Reply
Rahman says:
February27,2012at11:49am
veryusefullinkthankyou

Reply
opeyemi says:
March17,2012at6:32am
Greatanswer,itreallymeetmydemand

Reply
ranx says:
March23,2012at6:57pm
Thankforyourkindness,yourexplanationveryusefulandveryunderstadbletous.

Reply
ranx says:
March23,2012at6:58pm
Thanksforthesharingofyourknowledgethissveryusefultomydesign

Reply
anam says:
April25,2012at1:03pm
canihavethedefinitionofgrowthfactor?

Reply
goldwincs says:
June18,2012at2:42pm
greatpost!canyouexplainaboutpeakdiversityfactor?

Reply
ahmednazmi says:
July19,2012at9:05am
whatthedierencebetweendiversityfactoranddiversityfactor(ks)andwhereiwilluse:diversityfactor,diversityfactor(ks)
anddemandfactor

Reply
daniel says:

10 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

August8,2012at5:45pm
great,pleasedomorepostanddetailedexplanation

Reply
mynameisokekhianstanley. says:
August16,2012at2:34pm
Thankyouforyourknowledge.Thiswillbeofhelpinmyfieldwork.

Reply
kwame says:
August16,2012at2:57pm
Thanksverymuch,Iamreallyenlightenedalot.

Reply
JoseAntonioMartins says:
September28,2012at6:06pm
DearMr.JigneshParmar,

Thedetailsprovidedaboutthisissueareveryuseful.

Wouldyoumindinformingmeabouttheoriginofthetable:DiversityFactorforanapartmentblock?

Pleaseanswermebyemail.

Thanksforyoursupportinadvance.

Reply
JoseAntonioMartins says:
December19,2012at8:21pm
IhavealreadyfoundthereferredtableintheFrenchStandardNFC14100(2008):Lowvoltagemainsinstallations.
Pleaseconsiderthecorrections:
whereis40To40shouldbe40to49
whereis50ToAbove,ks=0.40shouldbe50toAbove,ks=0.38.

Reply
dhananjayPrasad says:
October12,2012at2:18am
Thankyousir

Reply
salmanp says:
November7,2012at8:16am
thankusir

Reply
tiger says:
November19,2012at11:05am
Verygoodarticle,butthesecalculationderivedfromwhichCodeorstandard???speciallytable(DemandFactor&LoadFactor
accordingtoTypeofIndustries),becausethesevaluesisvariedanddependonthepracticewise

Reply
Jignesh.Parmar says:
November19,2012at2:35pm
Yes.Agreewithyou.ThisisjustreferenceValue.ThisValuevaryaccordingtoitsusersProfile.
Wecannotpredicttheactualvaluebutthistablevaluehelpfulustocalculatemorerealisticassumption.
IgotthisTablefromoneBookorManual.IfitismorevaluableforYouthanIwilldefiantlyconveyitsReferenceSource.

Reply
tigerman says:
November20,2012at7:48am
Manythanksforyourreply,andihopetosendtomethisreferenceorbookitwillbeakindfromyou

Samer says:
January2,2013at9:10am
Canyoupleaseprovidemewiththereferencesource?Itisveryimportanttome.
Thankyouforthegreatarticle.
Regards.

RonChatterji says:
December5,2012at1:26pm
IamfromUS.MynameisRon.Iwanttotalkwithyouonsomething.Pleasetellmewhatphone#Icancallandtime.Iwillcall
youaftergettingyour3

Reply
Jignesh.Parmar says:
December5,2012at2:20pm
IamavailableonEmail.
MyEmailIdisjiguparmar@yahoo.com

Reply
Mohammed says:
February24,2013at4:16pm
DearJignesh,ineedthereferencesofyourdiversity,demandandcoincidencefactrostables.aretheyasperany
international/nationalcodes.Yourkindreplywillbnehelfulinstudyingaproject.

M.A.Bari

Shakil says:
July6,2013at2:49am
Jignesh.Parmar,Ineedyourhelp.IamfmBangladesh.Iamalsoaelectricalengineer.Isawthatyouhavemostexperiencein
powersector.In15thjuly,aBangladeshipowergenerationcompanycallainterview.Iamalsoacandidateforthat
interview.Sirpleasegivesomematerialsandtellmehowcanigotthatjob.Iliketoinformyouthat,Ihavenoexperienceto
workanypowerplant.Iamafresherelectricalengineer

RonChatterji says:
December5,2012at1:27pm
Ineedyourphone#andthetime/date

11 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Reply
minhaz says:
December23,2012at5:00am
exellent

Reply
saad says:
December23,2012at9:31am
thanksdear

Reply
MarkJasonAcopioObordo says:
January17,2013at2:08pm
thanks!!nowiknow.:)

Reply
colinchallinger says:
February5,2013at9:59am
HiIhaveanappartmentblockwith12flatstocostandtheyareallelectrilyheatedtoalpotdivesityequals22.4Kva
refto(ks)willthisfactorstillapplytotheincomingmain?

Reply
PercyMakhuvha says:
February28,2013at8:28am
ThankyouverymuchknowIamhappy

Reply
AllanSanjose says:
March18,2013at12:32am
Yourfirststatementregardingdemandfactorisalwayslessthanone.

ifyourdemandfactoris100%thatisequaltoone.

Philippines

Reply
Jignesh.Parmar says:
March18,2013at2:25pm
PleasecarefullyReadDefinitionFirst!!!
DemandFactor=Maximumdemandofasystem/Totalconnectedloadonthesystem.
YourmaxdemandnevergoesbeyondconnectedloadsoD.Fisalwayslessthan1.
Hopethisclarificationmayclearyourdough.

Reply
Rahul says:
March21,2013at5:22pm
Dearsir,

Icameacrossanotherformulalike

Maximumnormalrunningplantload=100%sumofallcontinuouslyoperatingloads+30%sumofallintermittentloads.

Where100%and30%areconsideredasthediversityfactorsofcontinuousandintermittentloadsrespectively

Sirdoyouknowwhichindustryisthisformulacommonlyused.canyouexplainthisformula..

Ihopeyouwillreplytomyquestion

Reply
KhwajaSalim says:
April3,2013at9:36am
ThankYouMr.JigneshParmar.Itisveryusefulindesigningofelectricalinstalltion.

Reply
John says:
May11,2013at2:52pm
DearSir,Iwouldliketolearnaboutthereferenceforthisinfo.Thankyouverymuchforyourkindhelp.

Reply
avtarsingh says:
May27,2013at10:44am
Dearsir,oneconfusionisthatifmyconectedloadis450kwandconsumptionis307kwhthenwhattheratingofincomming
transformerpleasetellmebrief.

Reply
Bala says:
September22,2013at5:56am
ThankYouMr.JigneshParmar.

Reply
pritchitroda says:
October3,2013at6:04pm
veryusefullthingsuhavegiven,thanks,

Reply
saad says:
November2,2013at8:04am
thankyouverymuch.

Reply
atest says:
November12,2013at7:52am
thisisatest

Reply
aki says:
November25,2013at8:17am
thankuuu

12 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

Reply
haseebullha says:
November25,2013at12:51pm
niceandsimpleinformationthanksforyoureort

Reply
irdanraybodiongan says:
January17,2014at8:44am
whatisthedemandfactorandloadfactorfordraftingroom?

Reply
AlbertoGasmen says:
February24,2014at8:21pm
Basically,thesedatafortheDEMANDandDIVERSITYfactorsareexcellentinfoforafastestimationofPOWERSUPPLY,CABLE
/WIRESIZES,manythanks

Reply
souvik says:
March22,2014at8:56am
thanksforthearticle..ithelpedme.thanks

Reply
SPSarathy says:
March23,2014at12:46pm
Youreortislaudable.Westandtogainwithyoursharinginasimpleway.

Reply
ashokchaudhary says:
September7,2014at6:00am
thanksforusefulAndapplicablekno
wlge

Reply
HarishKumarJohri says:
September8,2014at5:10am
ThankyouMr.Jignesh!NiceexplanationsoftheseElectricityfactorsinoneArticle.
HarishKumarJohri,L&TFaridabad.

Reply
Rafiq says:
September21,2014at5:55pm
Thanksforthisnote,hopefullycaniknowwhatisyourreferenceforthisImgladtoknowthanksinadvance

Reply
Godfrey says:
November15,2014at8:45am
Amappreciationforthisprovisionoftheinfomatiomaboutdiversityfactorbcauseitsalwaysdiculttofindreliablenotesfor
thistopic.

Reply
DaramolaDele says:
November23,2014at7:00am
yourarticleisalwaysedifyingmystudies.MayGodBlessyoumoreandmore

Reply
DaramolaDele says:
November24,2014at10:06am
howcangetthispaper

Reply
MahmoudElghazaly says:
December29,2014at11:14am
thankyouverymuchforsuchvaluableinformations

Reply
Rajesh says:
January19,2015at12:12pm
Verysimpleexplanationandreallyvaluable.
Thisisanantibioticformyknowledge

Reply
zak says:
March2,2015at12:57pm
dearJignesh

ihaveasmallquestionregardingthetransformers.
ineedtoknowaccordingtoNECwhatisthepercentagetobeloadedforthecapacityofatransformer.
Asapracticewealwaysconsider80%oftotalkvaofatransformer.
ex.ifwehave1600kvat/rthenwecanuse1600*80%=1280kva.
wecanuseonly1280kvainsteadof1600kva.supooseyourtotalloadis1400kvathenyouhavetogotohighersizethatis2000
kva.

Reply
usman says:
April2,2015at7:12am
niceeortformakingitunderstandabletonontechnicalalso..

Reply
RAJNISHKUMAR says:
April22,2015at9:30am
Sir,thanksforprovidingusefulinformationasithelpsinpreparationofamie

Reply
monacodelpasao says:
June16,2015at5:38am
greatnotesbutalotofspellingmistakes

Reply

13 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

avnishkumar says:
July6,2015at9:41am
iamplantengineer(electrcial).disconceptalwayswerusing,soundestandtheLF,DFetc..

Reply
thongraty says:
August4,2015at8:46am
Dearsir,

Actuallysir,CouldyoupleasemoredetailformeaboutwhatistheKuandWhatistheKscosistillconfusewithwhatyou
showedabove.

Bestregard,

Reply
8463838172 says:
August22,2015at2:55pm
siriamelectricalengg.studentiwanttowriteresearchpaperonruralelectricitysocouldyouhelpme

Reply
sourabhvishwakarma says:
November9,2015at7:37am
thankyouforthisinformationbutihaveanQuestion:ifihave2000kwconnectedloadthanhowmuchkvatransformerwe
shoulduseeitherhigherfrom2000kworbelow.accordingtoyourcalculationitgiveverylowcapacitycapacityoftransformer.
pleasereply.

Reply
kimdongmin says:
December15,2015at1:46am
Thankyouforsharingyourknowledge!!

Reply
Nandakumar.R says:
December30,2015at1:33pm
DearMr.Jignesh.Parmar
Thankyouforyourideaandimplementationofsharingyourexperience&knowledgeandhelptechnicalenthusiaststolearn
more.

GREATTHINKING;GREATJOB!

Reply
says:
February7,2016at9:34am
+32.thanksverygoodsite,thankforhelp

Reply
ChandrakantGhan says:
February12,2016at9:07am
ChandrakantGhan:
DearMr.Parmar,AveryusefularticleandclearsmanydoubtsaboutthefactorsinElectricalisntalltion.

Thanksforsucharticle.

Regards

Reply
sunny says:
May12,2016at5:52am
whatisthecapacityoftransformerfor33000sqfeetareaplssuggested

Reply
AboderinSulaiman says:
June1,2016at3:33pm
DearMrParmar

WearecurrentlyworkingonaprojectforLagosStateMinistryofHousingatotalof53blocks.Eachblockisafourfloors
comprisesof8Nos1bedroomflat(2nosperfloor)onawingand8Nos2bedroomflat(2Nosperfloor)ontheotherwing.The
totalloadforeachblockis478.4KWandforallthe53blocks,thetotalloadwas25,355.2KWi.e25.355MW.

SelectingTransformersfortheEstate:

Adiversityfactorof0.8(1.25)wasapplyforeachblockandaloadfactorof0.3wasusedfortheentireestate,enblock

ThetotalutilityfactorappliedfortheentireEstateis0.8multiplyby0.3=0.24

TotalestimatedloadforselectionofTransformeris25.355MWX0.24=6.085MW

Applyingpowerfactorof0.8,estimatedloadinKVA=7,606KVA

NumberofTransformerrequired(AssumedeachselectedTransformerisof(500KVA)=7,606/500No=15.2say16Noof500KVA
willberequiredfortheEstate.

IneedyouradviceandIwanttoknowifthereisaRegulationthatconfirmtheaboveapplicationfactorforfinalload(Estimated)
asdoneabove.

IwanttoknowifIamontherighttrackconsideringyourdefinitionofdiversityfactor,loadfactoretc.

Baseontheabovecalculationwhatisthesizeofthemaininjectionsubstationthatwillsupplytheentireestate.Thankyou.

ThankyouasIexpecttohearfromyousoonest.

Reply
DeepakM.R. says:
July28,2016at6:38am
ThanksalotSir.Theseinformationwereveryuseful.

Reply
venkat says:
August26,2016at11:51pm

14 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...

IliketoreadyouranswersiwouldliketoSizeofGeneratorformynewPlant.PladvicehowtoarrivecorrectsizeofDGset.
similarly,ifiwanttodosamefromrunningplant,plspecifythesamealso..thanks..venkat

Reply
gideonmbato says:
November28,2016at8:24am
Isdiversityfactorsameasutilisationfactor

Reply
Chaddy says:
December31,2016at5:08am
Thankyoualotsir

Reply

15 of 15 19/09/2017 11:52

You might also like