OCTOBER31,2011 78COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/10/31/DEMANDFACTOR
DIVERSITYFACTORUTILIZATIONFACTORLOADFACTOR/#COMMENTS)
TheworddemanditselfsaysthemeaningofDemandFactor.Theratioofthemaximumcoincidentdemandofasystem,orpart
ofasystem,tothetotalconnectedloadofthesystem.
Forexample,anoversizedmotor20Kwdrivesaconstant15KwloadwheneveritisON.Themotordemandfactoristhen15/20
=0.75=75%.
DemandFactorisexpressasapercentage(%)orinaratio(lessthan1).
DemandFactorisalwayschangewiththetimetotimeorhourstohoursofuseanditwillnotconstant.
Theconnectedloadisalwaysknownsoitwillbeeasytocalculatethemaximumdemandifthedemandfactorforacertainsupply
isknownatdierenttimeintervalsandseasons.
Thelowerthedemandfactor,thelesssystemcapacityrequiredtoservetheconnectedload.
Calculation:
(1)AResidenceConsumerhas10NosLampof400WbutatthesametimeItispossiblethatonly9NosofBulbsareusedatthe
sametime.HereTotalConnectedloadis1040=400W.Consumermaximumdemandis940=360W.DemandFactoofthisLoad
=360/400=0.9or90%.
(2)OneConsumerhave10lightsat60KweachinKitchen,theloadis60Kwx10=600KW.ThiswillbetrueonlyifAlllightsare
TurnsONthesametime(Demandfactor=100%or1)
ForthisConsumeritisobservedthatonlyhalfofthelightsbeingturnedONatatimesowecansaythatthedemandfactoris0.5
(50%).Theestimatedload=600KwX0.5=300Kw.
FeederconductorsshouldhavesucientAmpereCapacitytocarrytheload. TheAmpereCapacitydoesnotalwaysbeequalto
thetotalofallloadsonconnectedbranchcircuits.
Thisfactormustbeappliedtoeachindividualload,withparticularattentiontoelectricmotors,whichareveryrarelyoperatedat
fullload.
AsperNationalElectricalCode(NEC)demandfactormaybeappliedtothetotalload.Thedemandfactorpermitsafeeder
ampearcitytobelessthan100percentofallthebranchcircuitloadsconnectedtoit.
DemandfactorcanbeappliedtocalculatethesizeofthesubmainwhichisfeedingaSubpanelorafixedloadlikeamotoretc.If
thepanelhavetotalloadof250kVA,consideringaDemandfactorof0.8,wecansizethefeedercablefor250x0.8=200kVA.
Demandfactorsforbuildingstypicallyrangebetween50and80%oftheconnectedload.
Inanindustrialinstallationthisfactormaybeestimatedonanaverageat0.75formotors.
Forincandescentlightingloads,thefactoralwaysequals1.
TextBookofDesignofElect.InstallationJain
ElectricalLoad DemandFactor
1NoofMotor 1
Upto10NosofMotor 0.75
Upto20NosofMotor 0.65
Upto30NosofMotor 0.6
1 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Upto40NosofMotor 0.5
Upto50NosofMotor 0.4
Demand Factor
TextBookofDesignofElect.InstallationJain
Utility DemandFactor
Oce,School 0.4
Hospital 0.5
AirPort,Bank,Shops, 0.6
Restaurant,Factory, 0.7
WorkShop,Factory(24Hr 0.8
Shift)
ArcFurnace 0.9
Compressor 0.5
Handtools 0.4
InductanceFurnace 0.8
Demand Factor
SaudiElectricityCompanyDistributionStandard
Utility DemandFactor
Residential 0.6
Commercial 0.7
Flats 0.7
Hotel 0.75
Mall 0.7
Restaurant 0.7
Oce 0.7
School 0.8
CommonAreainbuilding 0.8
PublicFacility 0.75
StreetLight 0.9
IndoorParking 0.8
OutdoorParking 0.9
Park/Garden 0.8
Hospital 0.8
Workshops 0.6
WareHouse 0.7
Farms 0.9
FuelStation 0.7
Factories 0.9
2 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Demand Factor
TextBookofPrincipalofPowerSystemV.K.Mehta
Utility DemandFactor
ResidenceLoad(<0.25KW) 1
ResidenceLoad(<0.5KW) 0.6
ResidenceLoad(>0.1KW) 0.5
Restaurant 0.7
Theatre 0.6
Hotel 0.5
School 0.55
SmallIndustry 0.6
Store 0.7
MotorLoad(upto10HP) 0.75
MotorLoad(10HPto20HP) 0.65
MotorLoad(20HPto100HP) 0.55
MotorLoad(Above100HP) 0.50
DiversityFactorisratioofthesumoftheindividualmaximumdemandsofthevarioussubcircuitofasystemtothemaximum
demandofthewholesystem.
DiversityFactor=Installedload/Runningload.
DiversityFactorisalways>1becausesumofindividualmax.Demands>Max.Demand.
Inotherterms,DiversityFactor(0to100%)isafractionofTotalLoadthatisparticularitemcontributedtopeakdemand.70%
diversitymeansthatthedeviceoperatesatitsnominalormaximumloadlevel70%ofthetimethatitisconnectedandturned
ON.
Itisexpressedasapercentage(%)oraratiomorethan1.
Ifweusediversityvaluein%thanitshouldbemultiplywithLoadandifweuseinnumericalvalue(>1)thanitshouldbe
dividedwithLoad.
DiversityoccursinanoperatingsystembecauseallloadsconnectedtotheSystemarenotoperatingsimultaneouslyorarenot
simultaneouslyoperatingattheirmaximumrating.Thediversityfactorshowsthatthewholeelectricalloaddoesnotequalthe
sumofitspartsduetothistimeInterdependence(i.e.diverseness).
Ingeneraltermswecansaythatdiversityfactorreferstothepercentoftimeavailablethatamachine.70%diversitymeansthat
thedeviceoperatesatitsnominalormaximumloadlevel70%ofthetimethatitisconnectedandturnedON.
ConsidertwoFeederswiththesamemaximumdemandbutthatoccuratdierentintervalsoftime.Whensuppliedbythesame
feeder,thedemandonsuchislessthesumofthetwodemands.Inelectricaldesign,thisconditionisknownasdiversity.
Diversityfactorisanextendedversionofdemandfactor.Itdealswithmaximumdemandofdierentunitsatatime/Maximum
demandoftheentiresystem.
Greaterthediversityfactor,lesseristhecostofgenerationofpower.
Manydesignersprefertouseunityasthediversityfactorincalculationsforplanningconservatismbecauseofplantloadgrowth
uncertainties.Localexperiencecanjustifyusingadiversityfactorlargerthanunity,andsmallerserviceentranceconductorsand
transformerrequirementschosenaccordingly.
Thediversityfactorforallotherinstallationswillbedierent,andwouldbebaseduponalocalevaluationoftheloadstobe
appliedatdierentmomentsintime.Assumingittobe1.0may,onsomeoccasions,resultinasupplyfeederandequipment
ratingthatisratherlargerthanthelocalinstallationwarrants,andanoverinvestmentincableandequipmenttohandletherated
loadcurrent.Itisbettertoevaluatethepatternofusageoftheloadsandcalculateanacceptablediversityfactorforeach
particularcase.
Calculation:
OneMainFeederhavetwoSubfeeder(SubFeederAandSubFeederB),SubFeederAhavedemandatatimeis35KWandSub
3 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
FeederBhavedemandsatatimeis42KW,butthemaximumdemandofMainFeederis70KW.
TotalindividualMaximumDemand=35+42=77KW.
MaximumDemandofwholeSystem=70KW
SoDiversityfactorofTheSystem=77/70=1.1
Diversityfactorcanshootupabove1.
TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionorsubdistributionboard).
Diversityfactoriscommonlyusedforacompleteacoordinationstudyforasystem.Thisdiversityfactorisusedtoestimatethe
loadofaparticularnodeinthesystem.
DiversityfactorcanbeusedtoestimatethetotalloadrequiredforafacilityortosizetheTransformer
Diversityfactorshavebeendevelopedformainfeederssupplyinganumberoffeeders,andtypically1.2to1.3forResidence
Consumerand1.1to1.2forCommercialLoad.1.50to2.00forpowerandlightingloads.
Note:Reciprocaloftheaboveratio(willbemorethan1)alsoisusedinsomeothercountries.
Diversityfactorismostlyusedfordistributionfeedersizeandtransformeraswellastodeterminethemaximumpeakloadand
diversityfactorisalwaysbasedonknowingtheprocess.Youhavetounderstandwhatwillbeonoroatagiventimefor
dierentbuildingsandthiswillsizethefeeder.Notefortypicalbuildingsdiversityfactorisalwaysone.Youhavetoestimateor
haveadatarecordstocreate24hoursloadgraphandyoucandeterminethemaximumdemandloadfornodethenyoucan
easilydeterminethefeederandtransformersize.
Thediversityfactorofafeederwouldbethesumofthemaximumdemandsoftheindividualconsumersdividedbythe
maximumdemandofthefeeder.Inthesamemanner,itispossibletocomputethediversityfactoronasubstation,atransmission
lineorawholeutilitysystem.
Theresidentialloadhasthehighestdiversityfactor.Industrialloadshavelowdiversityfactorsusuallyof1.4,streetlight
practicallyunityandotherloadsvarybetweentheselimits.
(StandardHandbookforElectricalEngineersbyFinkandBeaty)
Numberofcircuits DiversityFactorin%(ks)
Assembliesentirelytested2and3 90%
4and5 80%
6to9 70%
10andmore 60%
Assembliespartiallytestedineverycase 100%
choose
CircuitsFunction DiversityFactorin%(ks)
Lighting 90%
4 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Heatingandairconditioning 80%
Socketoutlets 70%
Liftsandcateringhoist
Forthemostpowerfulmotor 100%
Forthesecondmostpowerfulmotor 75%
Forallmotors 80%
Apartment DiversityFactorin%(ks)
2To4 1
5To19 0.78
10To14 0.63
15To19 0.53
20To24 0.49
25To29 0.46
30To34 0.44
35To39 0.42
40To40 0.41
50ToAbove 0.40
Diversity Factor
TextBookofPrincipalofPowerSystemV.K.Mehta
TheratiooftheActualLoadofequipmenttoFullloadofequipment.
ItistheratioofactualkilowattHoursusedinagivenperiod,dividedbythetotalpossiblekilowatthoursthatcouldhavebeen
usedinthesameperiodatthepeakKWlevel.
LoadFactor=(energy(kWhpermonth))/(peakdemand(kW)xhours/month)
InothertermsLoadfactorisdefinedastheratioofAverageloadtomaximumdemandduringagivenperiod.
LoadFactor=AverageLoad/MaximumDemandduringgivenTimePeriod
LoadFactorisalwayslessthan1becausemaximumdemandisalwaysmorethanaveragedemand.
LoadFactorcanbecalculatedforasingleday,foramonthorforayear.
Loadfactorinothertermsofeciency.
5 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Itisusedfordeterminingtheoverallcostperunitgenerated.
HighertheloadfactorisGOODanditwillmoreOutputofPlan,lesserthecostperunitwhichmeansanelectricitygeneratorcan
sellmoreelectricityatahighersparkspread,FixedcostsarespreadovermorekWhofoutput.Apowerplantmaybehighly
ecientatHighloadfactors.
LowloadfactorisaBED.Alowloadfactorwilluseelectricityinecientlyrelativetowhatwecouldbeifwewerecontrolling
ourpeakdemand.Apowerplantmaybelessecientatlowloadfactors.
Foralmostconstantloads,theloadfactorisclosetounity.
ForVaryingLoadFactorisclosedZero.
LoadFactorisameasureoftheeectiveutilizationoftheloadanddistributionequipment,i.e.higherloadfactormeansbetter
utilizationofthetransformer,lineorcable.
Ahighloadfactormeanspowerusageisrelativelyconstant.Lowloadfactorshowsthatoccasionallyahighdemandisset.To
servicethatpeak,capacityissittingidleforlongperiods,therebyimposinghighercostsonthesystem.Electricalratesare
designedsothatcustomerswithhighloadfactorarechargedlessoverallperkWh.
Sometimesutilitycompanieswillencourageindustrialcustomerstoimprovetheirloadfactors.
Loadfactoristermthatdoesnotappearonyourutilitybill,butdoesaectelectricitycosts.Loadfactorindicateshow
ecientlythecustomerisusingpeakdemand.
Calculation:
Motorof20hpdrivesaconstant15hploadwheneveritison.
Themotorloadfactoristhen15/20=75%.
IntroductiontoPowerRequirementforBuildingJ.PaulGuyer,
Electricalandelectronicslaboratory 2030 37
6 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Thereciprocalofdiversityfactoriscoincidencefactor
Thecoincidencefactoristheratioofthemaximumdemandofasystem,orpartunderconsideration,tothesumoftheindividual
maximumdemandsofthesubdivisions
Expressedasapercentage(%)oraratiolessthan1.
UsuallyConfidenceFactorwilldecreaseasthenumberofconnectedcustomersincreases.
Thefactorksisappliedtoeachgroupofloads(e.g.distributionorsubdistributionboard).
Thedeterminationofthesefactorsistheresponsibilityofthedesigner,sinceitrequiresadetailedknowledgeoftheinstallation
andtheconditionsinwhichtheindividualcircuitsaretobeexploited.Forthisreason,itisnotpossibletogiveprecisevaluesfor
generalapplication.
Themaximumdemandofaninstallationisthemaximumrateofconsumptionexpressedinamperes,kWorkVA.Itisgenerally
takenastheaveragerateofconsumptionoveraperiodoftime.Examplethe15minutemaximumkWdemandfortheweekwas
150kW.Maximumdemanddoesnotincludemotorstartingcurrentsorothertransienteects.Faultcurrentsandoverload
currentsarealsoexcluded.MaximumdemandinKWisrelevantonlyformetering/taripurposes.
Maximumdemand(oftenreferredtoasMD)isthelargestcurrentnormallycarriedbycircuits,switchesandprotectivedevices.It
doesnotincludethelevelsofcurrentflowingunderoverloadorshortcircuitconditions.
MaximumDemandisagreatestofalldemandsthatoccurduringaspecifictime
Themajordisadvantageofallocatingloadusingthediversityfactorsisthatmostutilitieswillnothaveatableofdiversityfactors
andsometimeitisnotviabletodetermineaccurateDiversityFactor.InthissituationMaximumDemandisveryhelpfulto
calculatesizeofFeederorTC.
ThekVAratingofalldistributiontransformersisalwaysknownforafeeder.Themeteredreadingscanbetakentoeach
transformerbaseduponthetransformerrating.Anallocationfactor(AF)canbecalculate.
AllocationFactor=MeteredDemand(KVA)/TotalKVA.
EquipmentDemand=AFxTotalKVAofEquipments
Calculation:
ActualLoadingorSizeofTC1andTC2.
(https://electricalnotes.files.wordpress.com/2011/10/11.jpg)
TotalLoadonTC1=10+11+12+08=41KW.
MaximumDiversityDemandofTC1=41/1.1=37.3KW.
TotalLoadonTC2=4+3+12+02=21KW.
MaximumDiversityDemandofTC2=21/1.2=17.5KW.
TotalLoad=37.3+17.5=54.8KW.
AllocatingFactor(AF)=M.D/TotalLoad
AllocatingFactor(AF)=0.27.
ActualLoadonTC1=0.2737.3=1.20KW.
ActualLoadonTC2=0.2717.5=4.8KW.
AssessmentofmaximumdemandisveryeasyforResistiveLoad,Forexample,themaximumdemandofa240Vsinglephase8
7 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
kWshowerheatercanbecalculatedbydividingthepower(8kW)bythevoltage(240V)togiveacurrentof33.3A.This
calculationassumesapowerfactorofunity,whichisareasonableassumptionforsuchapurelyresistiveload.
LightingcircuitsposeaspecialproblemwhendeterminingMD.Dischargelampsareparticularlydiculttoassess,andcurrent
cannotbecalculatedsimplybydividinglamppowerbysupplyvoltage.ThereasonsforthisareControlgearlossesresultin
additionalcurrent,thepowerfactorisusuallylessthanunitysocurrentisgreater,andChokesandothercontrolgearusually
distortthewaveformofthecurrentsothatitcontainsharmonicswhichareadditionaltothefundamentalsupplycurrent.
Solongasthepowerfactorofadischargelightingcircuitisnotlessthan0.85,thecurrentdemandforthecircuitcanbecalculated
from:
current(A)=(lamppower x1.8)/supplyvoltage(V)
Forexample,thesteadystatecurrentdemandofa240Vcircuitsupplyingten65Wfluorescentlampswouldbe:I=10X65X1.8A/
240=4.88A
Switchesforcircuitsfeedingdischargelampsmustberatedattwicethecurrenttheyarerequiredtocarry,unlesstheyhavebeen
speciallyconstructedtowithstandtheseverearcingresultingfromtheswitchingofsuchinductiveandcapacitiveloads.
ThereisgenerallyconfusionbetweenDemandfactorandDiversityfactor.Demandfactorsshouldbeideallyappliedto
individualloadsanddiversityfactortoagroupofloads.
Whenyoutalkaboutdiversity,therearenaturallymorethanoneormanyloadsinvolved.
Demandfactorcanbeappliedtocalculatethesizeofthesubmain,whichisfeedingaSubpanelorafixedloadlikeamotoretc,
individualLoad.
DemandfactorsaremoreconservativeandareusedbyNECforserviceandfeedersizing.
IftheSubpanelhavetotalloadis250kVA,consideringaDemandfactorof0.8,wecansizethefeedercablefor250x0.8=200
kVA.
TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionorsubdistributionboard),sizethe
Transformer.
Demandfactorsanddiversityfactorsareusedindesign.Forexample,thesumoftheconnectedloadssuppliedbyafeederis
multipliedbythedemandfactortodeterminetheloadforwhichthefeedermustbesized.Thisloadistermedthemaximum
demandofthefeeder.Thesumofthemaximumdemandloadsforanumberofsubfeedersdividedbythediversityfactorforthe
subfeederswillgivethemaximumdemandloadtobesuppliedbythefeederfromwhichthesubfeedersarederived.
Theestimatedelectricaldemandforallfeedersserveddirectlyfromtheserviceentranceiscalculatedbymultiplyingthetotal
connectedloadsbytheirdemandfactorsandthenaddingallofthesetogether.Thissumisdividedbythediversityfactor
(frequentlyassumedtobeunity)tocalculatetheserviceentrancedemandwhichisusedtodetermineampacityrequirements
fortheserviceentranceconductors.
WhenusedDiversityandDemandFactorinanelectricaldesignitshouldbeappliedasfollows,thesumoftheconnectedloads
suppliedbyafeedercircuitcanbemultipliedbythedemandfactortodeterminetheloadusedtosizethecomponentsofthe
system.
Thesumofthemaximumdemandloadsfortwoormorefeedersisdividedbythediversityfactorforthefeederstoderivethe
maximumdemandload.
Example1:CalculateSizeofTransformerhavingfollowingdetails:
(https://electricalnotes.files.wordpress.com/2011/10/2.jpg)
FeederBreaker1DemandLoad=FeederBreaker1xDemandFactor.
FeederBreaker1DemandLoad=20000.7=1400KVA
FeederBreaker2DemandLoad=FeederBreaker2xDemandFactor.
FeederBreaker2DemandLoad=15000.6=900KVA
FeederBreaker3DemandLoad=FeederBreaker3xDemandFactor.
FeederBreaker2DemandLoad=10000.5=500KVA
TotalFeederBreakerDemand=1400+900+500=2800KVA
TransformerDemandLoad=TotalFeederBreakerDemand/DiversityFactor.
TransformerDemandLoad=2800/1.1=2545KVA
IfweCalculatedTotalLoadonTransformerwithoutanyDemand&Diversity=2000+1500+1000=4500KVA.
ButafterCalculatingDemand&DiversityFactorTotalLoadonTransformer=2545KVA
Example2:CalculateSizeofMainFeederofMainTransformerhavingfollowingDetails:
8 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
(https://electricalnotes.files.wordpress.com/2011/10/3.jpg)
SumofMaximumDemandofCustomeronTC1=10KWx0.65=6.5KW
SumofMaximumDemandofCustomeronTC2=20KWx0.75=15KW
SumofMaximumDemandofCustomeronTC3=30KWx0.65=19.5KW
AsDiversityofConsumerConnectedonTC1is1.5so,
MaximumDemandonTC1=6.5KW/1.5=4KW.
AsDiversityofConsumerConnectedonTC2is1.1so,
MaximumDemandonTC2=15KW/1.1=14KW
AsDiversityofConsumerConnectedonTC3is1.5so,
MaximumDemandonTC3=19.5KW/1.5=13KW.
IndividualMaximumDemandonMainTransformer=04+14+13=31KW.
MaximumDemandonMainFeeder=04+14+13/1.3=24KW
Loadfactoranddiversityfactorplayanimportantpartinthecostofthesupplyofelectricalenergy.Higherthevaluesofload
factoranddiversityfactors,lowerwillbetheoverallcostperunitgenerated.
Thecapitalcostofthepowerstationdependsuponthecapacityofthepowerstation.Lowerthemaximumdemandofthepower
station,theloweristhecapacityrequiredandthereforeloweristhecapitalcostoftheplant.Withagivennumberofconsumers
thehigherthediversityfactoroftheirloads,thesmallerwillbethecapacityoftheplantrequiredandconsequentlythefixed
chargesduetocapitalinvestmentwillbemuchreduced.
Similarlyhigherloadfactormeansmoreaverageloadormorenumberofunitsgeneratedforagivenmaximumdemandand
thereforeoverallcostperunitofelectricalenergygeneratedisreducedduetodistributionofstandingchargeswhichare
proportionaltomaximumdemandandindependentofnumberofunitsgenerated.
Thusthesuppliersshouldalwaystrytoimprovetheloadfactoraswellasdiversityfactorbyinducingtheconsumerstousethe
electricalenergyduringopeakhoursandtheymaybechargedatlowerratesforsuchschemes.
FILEDUNDERUNCATEGORIZED
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan14years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
Manish says:
October31,2011at4:14pm
Thankyouverymuchforsuchagoodanddetailedarticle.
Yourblogpostsarealwaysquitegood!
Reply
Dieter says:
November9,2011at10:55am
AsajuniorE&IEngineer,Iherewiththankyouforyourkindnessofsharingyourknowledge.
Ilookforewardtomoreofyourwork.
Reply
S.SAMBATH says:
November29,2011at1:36pm
9 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Sir,
TheinformationsareveryusefullikemeasElectricityBoardEngineer.ThankuandIexpectmore.
s.sambath
Reply
zaheerkhattak says:
May30,2012at7:15am
dearsir,thanksalotbothofuiamelectricalengineerandimworkinginconsultancyfirminpakistan
imostlydesignhighriseocialandresidentialbuilding.iwanttoshareandgainsomeimportantknowledgeabout
designingforAllofuandeveryonehowhelpme.
thanks
Zaheerkhattak
shazconsultantPeshawarPakistan
availableonFacebook
chemie says:
November30,2011at6:21am
mefrommalaysiauaregreatsir..thanksalot
Reply
Md.Samiuddin says:
December7,2011at8:58am
DearMr.JigneshParmar,
Thedetailsprovidedbyareveryuseful.Excellent!
Ineedasmallhelp.IamanIndian,nativeofAndhraPradesh.Iamamechanicalengineer,handlinganewprojectinJeddah,
SaudiArabia.
Thedetailsinthepowersummaryreportare:
ConnectedPowerUsage=1290KWH
Aftermultiplyingbypowerfactorsandmaximumutilizationfactorsindividuallytoeachequipmentthesumis=535KWH.
Example:Craneconnectedpower=95kwh;powerfactor=0.6;Max.Utlzn.Factor=0.75gives95kwhX0.6X0.75=42.75kwh
Now,IfIwantbuythegenerators(OR)toaskforelectricitydept.whatpowershouldIask?Willitbe1290KWHor535KWH?
PleaseclarifyandexplainmetoimprovemyawaenessinthisperticulartopicbecausealwaysIcomeacrosswithsuchincidents.
Pleasereplytometomyemail:(or)
Thanksforyoursupportinadvance.
BestRegard
Md.Samiuddin
Plantmanager
MIMCo.,
Jeddah
KSA
Reply
MansourA, says:
January15,2012at7:08pm
ThankuverymuchMr.Parmar,Ireallygetuseandunderstandthesefactorswhichwereconfusedtome.Ihavesetthissitein
favouritieslookingforewardtoreadyourgoodactivities.
Reply
francisazumah says:
February18,2012at2:49pm
amverygreatfulfortheexplanatorynotes,isaywelldonebutneedsmoreofthat.thankyou
Reply
Rahman says:
February27,2012at11:49am
veryusefullinkthankyou
Reply
opeyemi says:
March17,2012at6:32am
Greatanswer,itreallymeetmydemand
Reply
ranx says:
March23,2012at6:57pm
Thankforyourkindness,yourexplanationveryusefulandveryunderstadbletous.
Reply
ranx says:
March23,2012at6:58pm
Thanksforthesharingofyourknowledgethissveryusefultomydesign
Reply
anam says:
April25,2012at1:03pm
canihavethedefinitionofgrowthfactor?
Reply
goldwincs says:
June18,2012at2:42pm
greatpost!canyouexplainaboutpeakdiversityfactor?
Reply
ahmednazmi says:
July19,2012at9:05am
whatthedierencebetweendiversityfactoranddiversityfactor(ks)andwhereiwilluse:diversityfactor,diversityfactor(ks)
anddemandfactor
Reply
daniel says:
10 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
August8,2012at5:45pm
great,pleasedomorepostanddetailedexplanation
Reply
mynameisokekhianstanley. says:
August16,2012at2:34pm
Thankyouforyourknowledge.Thiswillbeofhelpinmyfieldwork.
Reply
kwame says:
August16,2012at2:57pm
Thanksverymuch,Iamreallyenlightenedalot.
Reply
JoseAntonioMartins says:
September28,2012at6:06pm
DearMr.JigneshParmar,
Thedetailsprovidedaboutthisissueareveryuseful.
Wouldyoumindinformingmeabouttheoriginofthetable:DiversityFactorforanapartmentblock?
Pleaseanswermebyemail.
Thanksforyoursupportinadvance.
Reply
JoseAntonioMartins says:
December19,2012at8:21pm
IhavealreadyfoundthereferredtableintheFrenchStandardNFC14100(2008):Lowvoltagemainsinstallations.
Pleaseconsiderthecorrections:
whereis40To40shouldbe40to49
whereis50ToAbove,ks=0.40shouldbe50toAbove,ks=0.38.
Reply
dhananjayPrasad says:
October12,2012at2:18am
Thankyousir
Reply
salmanp says:
November7,2012at8:16am
thankusir
Reply
tiger says:
November19,2012at11:05am
Verygoodarticle,butthesecalculationderivedfromwhichCodeorstandard???speciallytable(DemandFactor&LoadFactor
accordingtoTypeofIndustries),becausethesevaluesisvariedanddependonthepracticewise
Reply
Jignesh.Parmar says:
November19,2012at2:35pm
Yes.Agreewithyou.ThisisjustreferenceValue.ThisValuevaryaccordingtoitsusersProfile.
Wecannotpredicttheactualvaluebutthistablevaluehelpfulustocalculatemorerealisticassumption.
IgotthisTablefromoneBookorManual.IfitismorevaluableforYouthanIwilldefiantlyconveyitsReferenceSource.
Reply
tigerman says:
November20,2012at7:48am
Manythanksforyourreply,andihopetosendtomethisreferenceorbookitwillbeakindfromyou
Samer says:
January2,2013at9:10am
Canyoupleaseprovidemewiththereferencesource?Itisveryimportanttome.
Thankyouforthegreatarticle.
Regards.
RonChatterji says:
December5,2012at1:26pm
IamfromUS.MynameisRon.Iwanttotalkwithyouonsomething.Pleasetellmewhatphone#Icancallandtime.Iwillcall
youaftergettingyour3
Reply
Jignesh.Parmar says:
December5,2012at2:20pm
IamavailableonEmail.
MyEmailIdisjiguparmar@yahoo.com
Reply
Mohammed says:
February24,2013at4:16pm
DearJignesh,ineedthereferencesofyourdiversity,demandandcoincidencefactrostables.aretheyasperany
international/nationalcodes.Yourkindreplywillbnehelfulinstudyingaproject.
M.A.Bari
Shakil says:
July6,2013at2:49am
Jignesh.Parmar,Ineedyourhelp.IamfmBangladesh.Iamalsoaelectricalengineer.Isawthatyouhavemostexperiencein
powersector.In15thjuly,aBangladeshipowergenerationcompanycallainterview.Iamalsoacandidateforthat
interview.Sirpleasegivesomematerialsandtellmehowcanigotthatjob.Iliketoinformyouthat,Ihavenoexperienceto
workanypowerplant.Iamafresherelectricalengineer
RonChatterji says:
December5,2012at1:27pm
Ineedyourphone#andthetime/date
11 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Reply
minhaz says:
December23,2012at5:00am
exellent
Reply
saad says:
December23,2012at9:31am
thanksdear
Reply
MarkJasonAcopioObordo says:
January17,2013at2:08pm
thanks!!nowiknow.:)
Reply
colinchallinger says:
February5,2013at9:59am
HiIhaveanappartmentblockwith12flatstocostandtheyareallelectrilyheatedtoalpotdivesityequals22.4Kva
refto(ks)willthisfactorstillapplytotheincomingmain?
Reply
PercyMakhuvha says:
February28,2013at8:28am
ThankyouverymuchknowIamhappy
Reply
AllanSanjose says:
March18,2013at12:32am
Yourfirststatementregardingdemandfactorisalwayslessthanone.
ifyourdemandfactoris100%thatisequaltoone.
Philippines
Reply
Jignesh.Parmar says:
March18,2013at2:25pm
PleasecarefullyReadDefinitionFirst!!!
DemandFactor=Maximumdemandofasystem/Totalconnectedloadonthesystem.
YourmaxdemandnevergoesbeyondconnectedloadsoD.Fisalwayslessthan1.
Hopethisclarificationmayclearyourdough.
Reply
Rahul says:
March21,2013at5:22pm
Dearsir,
Icameacrossanotherformulalike
Maximumnormalrunningplantload=100%sumofallcontinuouslyoperatingloads+30%sumofallintermittentloads.
Where100%and30%areconsideredasthediversityfactorsofcontinuousandintermittentloadsrespectively
Sirdoyouknowwhichindustryisthisformulacommonlyused.canyouexplainthisformula..
Ihopeyouwillreplytomyquestion
Reply
KhwajaSalim says:
April3,2013at9:36am
ThankYouMr.JigneshParmar.Itisveryusefulindesigningofelectricalinstalltion.
Reply
John says:
May11,2013at2:52pm
DearSir,Iwouldliketolearnaboutthereferenceforthisinfo.Thankyouverymuchforyourkindhelp.
Reply
avtarsingh says:
May27,2013at10:44am
Dearsir,oneconfusionisthatifmyconectedloadis450kwandconsumptionis307kwhthenwhattheratingofincomming
transformerpleasetellmebrief.
Reply
Bala says:
September22,2013at5:56am
ThankYouMr.JigneshParmar.
Reply
pritchitroda says:
October3,2013at6:04pm
veryusefullthingsuhavegiven,thanks,
Reply
saad says:
November2,2013at8:04am
thankyouverymuch.
Reply
atest says:
November12,2013at7:52am
thisisatest
Reply
aki says:
November25,2013at8:17am
thankuuu
12 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
Reply
haseebullha says:
November25,2013at12:51pm
niceandsimpleinformationthanksforyoureort
Reply
irdanraybodiongan says:
January17,2014at8:44am
whatisthedemandfactorandloadfactorfordraftingroom?
Reply
AlbertoGasmen says:
February24,2014at8:21pm
Basically,thesedatafortheDEMANDandDIVERSITYfactorsareexcellentinfoforafastestimationofPOWERSUPPLY,CABLE
/WIRESIZES,manythanks
Reply
souvik says:
March22,2014at8:56am
thanksforthearticle..ithelpedme.thanks
Reply
SPSarathy says:
March23,2014at12:46pm
Youreortislaudable.Westandtogainwithyoursharinginasimpleway.
Reply
ashokchaudhary says:
September7,2014at6:00am
thanksforusefulAndapplicablekno
wlge
Reply
HarishKumarJohri says:
September8,2014at5:10am
ThankyouMr.Jignesh!NiceexplanationsoftheseElectricityfactorsinoneArticle.
HarishKumarJohri,L&TFaridabad.
Reply
Rafiq says:
September21,2014at5:55pm
Thanksforthisnote,hopefullycaniknowwhatisyourreferenceforthisImgladtoknowthanksinadvance
Reply
Godfrey says:
November15,2014at8:45am
Amappreciationforthisprovisionoftheinfomatiomaboutdiversityfactorbcauseitsalwaysdiculttofindreliablenotesfor
thistopic.
Reply
DaramolaDele says:
November23,2014at7:00am
yourarticleisalwaysedifyingmystudies.MayGodBlessyoumoreandmore
Reply
DaramolaDele says:
November24,2014at10:06am
howcangetthispaper
Reply
MahmoudElghazaly says:
December29,2014at11:14am
thankyouverymuchforsuchvaluableinformations
Reply
Rajesh says:
January19,2015at12:12pm
Verysimpleexplanationandreallyvaluable.
Thisisanantibioticformyknowledge
Reply
zak says:
March2,2015at12:57pm
dearJignesh
ihaveasmallquestionregardingthetransformers.
ineedtoknowaccordingtoNECwhatisthepercentagetobeloadedforthecapacityofatransformer.
Asapracticewealwaysconsider80%oftotalkvaofatransformer.
ex.ifwehave1600kvat/rthenwecanuse1600*80%=1280kva.
wecanuseonly1280kvainsteadof1600kva.supooseyourtotalloadis1400kvathenyouhavetogotohighersizethatis2000
kva.
Reply
usman says:
April2,2015at7:12am
niceeortformakingitunderstandabletonontechnicalalso..
Reply
RAJNISHKUMAR says:
April22,2015at9:30am
Sir,thanksforprovidingusefulinformationasithelpsinpreparationofamie
Reply
monacodelpasao says:
June16,2015at5:38am
greatnotesbutalotofspellingmistakes
Reply
13 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
avnishkumar says:
July6,2015at9:41am
iamplantengineer(electrcial).disconceptalwayswerusing,soundestandtheLF,DFetc..
Reply
thongraty says:
August4,2015at8:46am
Dearsir,
Actuallysir,CouldyoupleasemoredetailformeaboutwhatistheKuandWhatistheKscosistillconfusewithwhatyou
showedabove.
Bestregard,
Reply
8463838172 says:
August22,2015at2:55pm
siriamelectricalengg.studentiwanttowriteresearchpaperonruralelectricitysocouldyouhelpme
Reply
sourabhvishwakarma says:
November9,2015at7:37am
thankyouforthisinformationbutihaveanQuestion:ifihave2000kwconnectedloadthanhowmuchkvatransformerwe
shoulduseeitherhigherfrom2000kworbelow.accordingtoyourcalculationitgiveverylowcapacitycapacityoftransformer.
pleasereply.
Reply
kimdongmin says:
December15,2015at1:46am
Thankyouforsharingyourknowledge!!
Reply
Nandakumar.R says:
December30,2015at1:33pm
DearMr.Jignesh.Parmar
Thankyouforyourideaandimplementationofsharingyourexperience&knowledgeandhelptechnicalenthusiaststolearn
more.
GREATTHINKING;GREATJOB!
Reply
says:
February7,2016at9:34am
+32.thanksverygoodsite,thankforhelp
Reply
ChandrakantGhan says:
February12,2016at9:07am
ChandrakantGhan:
DearMr.Parmar,AveryusefularticleandclearsmanydoubtsaboutthefactorsinElectricalisntalltion.
Thanksforsucharticle.
Regards
Reply
sunny says:
May12,2016at5:52am
whatisthecapacityoftransformerfor33000sqfeetareaplssuggested
Reply
AboderinSulaiman says:
June1,2016at3:33pm
DearMrParmar
WearecurrentlyworkingonaprojectforLagosStateMinistryofHousingatotalof53blocks.Eachblockisafourfloors
comprisesof8Nos1bedroomflat(2nosperfloor)onawingand8Nos2bedroomflat(2Nosperfloor)ontheotherwing.The
totalloadforeachblockis478.4KWandforallthe53blocks,thetotalloadwas25,355.2KWi.e25.355MW.
SelectingTransformersfortheEstate:
Adiversityfactorof0.8(1.25)wasapplyforeachblockandaloadfactorof0.3wasusedfortheentireestate,enblock
ThetotalutilityfactorappliedfortheentireEstateis0.8multiplyby0.3=0.24
TotalestimatedloadforselectionofTransformeris25.355MWX0.24=6.085MW
Applyingpowerfactorof0.8,estimatedloadinKVA=7,606KVA
NumberofTransformerrequired(AssumedeachselectedTransformerisof(500KVA)=7,606/500No=15.2say16Noof500KVA
willberequiredfortheEstate.
IneedyouradviceandIwanttoknowifthereisaRegulationthatconfirmtheaboveapplicationfactorforfinalload(Estimated)
asdoneabove.
IwanttoknowifIamontherighttrackconsideringyourdefinitionofdiversityfactor,loadfactoretc.
Baseontheabovecalculationwhatisthesizeofthemaininjectionsubstationthatwillsupplytheentireestate.Thankyou.
ThankyouasIexpecttohearfromyousoonest.
Reply
DeepakM.R. says:
July28,2016at6:38am
ThanksalotSir.Theseinformationwereveryuseful.
Reply
venkat says:
August26,2016at11:51pm
14 of 15 19/09/2017 11:52
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electrical Notes & Articles https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversity-factor-utilization-factor-loa...
IliketoreadyouranswersiwouldliketoSizeofGeneratorformynewPlant.PladvicehowtoarrivecorrectsizeofDGset.
similarly,ifiwanttodosamefromrunningplant,plspecifythesamealso..thanks..venkat
Reply
gideonmbato says:
November28,2016at8:24am
Isdiversityfactorsameasutilisationfactor
Reply
Chaddy says:
December31,2016at5:08am
Thankyoualotsir
Reply