Product Specification

03247E

MFR 15
Multi Function Relay
Protection & Control

APPLICATIONS DESCRIPTION

The MFR 1 Series is a family of industrial grade protective Protection (all) ANSI # Complete generator
relays that offer multiple protective features in a single Over-/undervoltage (59/27)
Over-/underfrequency (81O/U)
protection and con-
package.
Voltage asymmetry (47) troller in one unit
Using a digital processor to measure true RMS values Overload (32) True RMS sensing
enables the control to have a high measuring accuracy, Reverse power (32R)
regardless of harmonics, transients or disturbing pulses. Reduced power (32F) Synchronization for
Unbalanced load (46) one breaker
The MFR 15 model includes a synchronizer and a load Loss of excitation (40Q)
(kW) and power factor (cosphi) controller via discrete Independent time-overcurrent (50/51) Load sharing
outputs to combine protection and control into one unit.
The SNY-I package offers additional functionality. It has Package SYN-I Discrete inputs for
kW load sharing capability for multiple unit applications. Synchronizer for 1 CB remote control
o Isolated operation
The compact size and multiple functions of the MFR 15 o Mains parallel operation Programmable relay
help to simplify switchgear design. The digital display Speed/frequency/real power outputs
offers a user-friendly interface to setup the unit as well as Voltage/power factor (cosphi)
monitor the operation and display any alarms. Remote real power set-point (0/4 to 20 mA)
PC and front panel
Load sharing via 0 to 4 Vdc analog line configurable
Interface RS-485/Modbus RTU Slave Microprocessor
Features (all)
True RMS voltage (generator/busbar) technology for
True RMS current (generator) accurate, repeatable
Configurable trip/control set points and reliable
Configurable delays for each alarm operation
3 configurable relays
3 dedicated control relay outputs Programmable
Two-line LC display threshold set-points
with individual time
delays
CE marked
UL/cUL Listed
GL Approval
SPECIFICATIONS

Accuracy .......................................................................................... Class 1 Relay outputs ................................................................................ isolated


Power supply ............................................................. 24 Vdc (18 to 30 Vdc) Contact material ............................................................................... AgCdO
Intrinsic consumption ..................................................................max. 12 W Load (GP) .................................................24 Vdc@2 Adc, 250 Vac@2 Aac
Ambient temperature ................................................................ -20 to 70 C Pilot duty (PD) ......................................................................24 Vdc@1 Adc
Ambient humidity...................................................... 95 %, non-condensing Housing ...................................................... Type APRANORM DIN 43 700
Voltage .......... Rated value /D: [1] 66/115 Vac or [4] 230/400 Vac Dimensions .........................................................................9672130 mm
Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac Front cutout ...............................................................91[+0.8]67[+0.7] mm
Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac Connection ................................................ screw/plug terminals depending
Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV on connector 1.5 mm, 2.5 mm or 4mm
Linear measuring range up to ....................................................... 1.3Vrated Front .................................................................................insulating surface
Measuring frequency ................................................50/60 Hz (40 to 70 Hz) Protection system................................................................................ IP 21
Input resistance ..................................................... [1] 0.21 MW, [4] 0.7 MW Weight ............................................... depending on version, approx. 800 g
Max. power consumption per path ................................................ < 0.15 W Disturbance test (CE) .......... tested according to applicable EN guidelines
Current (Irated) .............................................................. [1] ../1 A or [5] ../5 A Listings ............................................... UL/cUL listed for ordinary locations
Linear measuring range up to ........................................................ 3.0Irated Approvals........................................................... GL (Germanischer Lloyd)
Load ............................................................................................. < 0.15 VA
Rated short-time cur. (1 s)...............................[1] 100.0Irated, [5] 20.0Irated
Discrete inputs .............................................................................. isolated
Input range ........................................................................ 18 to 250 Vac/dc
Input resistance .....................................................................approx. 68 kW

DIMENSIONS
Front view

Configuration port
35
65
72

27

Back plate mounting


optional (please order
brackets P/N 8923-1023)
Bottom view
130 50
Back view with
connecting terminals
8

Configuration port
1 16

X1 X5 40 45
96

90

130

50 61 70 75

32 17

Configuration port 2005-07-11 | MFR 1 Dimensions r1ww-2805-ab.skf


WIRING DIAGRAM

X1 X2 X3 X4 X5
40 41 42 43 44 45 1 2 3 4 23 24 25 26 19 20 21 22 27 28 29

SYN-I

SYN-I
A (not inverted)
SYNCHRONIZATION B (inverted)
Impulse or holding relay
Interface
Bi-directional GND
[RS-485/Modbus RTU Slave]
A (not inverted)

lower

ACTIVE POWER
Three-position
Engine

controller
B (inverted)

SPEED
raise

REACTIVE POWER
lower
Three-position

EXCITATION
VOLTAGE
G

controller
raise
3/4

The socket for the PC configuration


(Generator voltage N) is situated on the side of the unit.
This is where the DPC has to be
3/4

Generator voltage L3 plugged in.


Measuring voltage
three-wire or
four-wire system Generator voltage L2
Generator voltage L1

s2 (l)

s1 (k)
Generator currrent L3 * Important note on
synch voltage measurement:
The synchronizing voltage must be connected three-
phase if the measuring voltage is connected three-
s2 (l) phase (N not connected). If the measuring voltage is
connected four-phase (L1-L2-L3-N), the synchronizing
Generator currrent L2 voltage may be connected two-phase (L1-L2). L3 is
s1 (k) connected only for compensation and is not measured.

9 10 11 12 13 14 15 16
s2 (l)
SYN-I

Generator currrent L1
s1 (k) Relay 3
5 6 7 8 70 71 72 30 31 32 73 74 75

Remote acknowledgement

Isolated operation Relay 2


MFR 15 (Multi Function Relay)

Common

Reply: CB is open
Relay 1
(Ready for operation)
Enable CB

Common
CB

not measured Synchronization voltage L3


2/3

SYN-I SYN-I

56 57 58 59

*
Synchronization voltage L2
Analog input (20 mA)
Synchronization voltage L1 20 mA
3/4

24 Vdc Input/output Psum (0 to 4 Vdc)


Reference point
terminal 4
0 Vdc NC

Blocking of protective functions /


remote acknowledgment
Subject to technical modifications. 2012-06-18 | MFR-15-SYN-I_Wiring_Diagram_EN_001.skf
TYPICAL APPLICATIONS / FEATURE OVERVIEW
International
Woodward
PO Box 1519 MFR 15
Fort Collins CO, USA
80522-1519 MFR 15
1000 East Drake Road SYN-I
Fort Collins CO 80525
Ph: +1 (970) 498-3634
Fax: +1 (970) 498-3058 ANSI
email: Control
SalesPGD_NAandCA@woodward.com Breaker control logic 1
Europe
Synchronization
Load
Woodward GmbH Isolated single-unit operation
Handwerkstrasse 29 Mains parallel operation
70565 Stuttgart, Germany Accessories
Ph: +49 (0) 711 789 54-510
Fax: +49 (0) 711 789 54-101
kWh counter
email: Configuration via PC #1
52 on/off 25
SalesPGD_EMEA@woodward.com Protection
Overvoltage 59
Distributors & Service
Woodward has an international 27 Undervoltage 27
network of distributors and Overfrequency 81O
service facilities. For your 47 Underfrequency 81U
nearest representative, call the Voltage asymmetry 47
Fort Collins plant or see the 59 Overload 32
Worldwide Directory on our Reverse power 32R
website. 50 81O Reduced power 32F/37
Corporate Headquarters Unbalanced load 46
32 81U Loss of excitation 40Q
Rockford IL, USA
Ph: +1 (815) 877-7441
32R Independent time-overcurrent 50/51*
Controller
www.woodward.com
32F Discrete raise/lower: n/f & P

(speed/frequency/real power)
40Q Discrete raise/lower: V & Q

(voltage/power factor cosphi)
G 46
I/O Remote real power set-point
(0 to 20 mA)

For more information contact:

90
0/4 to 20mA Load sharing (0 to 4 Vdc)
I/Os
Analog output -20/0/4 to 20 mA
(configurable, scaleable)
Pulse output for kWh
Relay outputs (configurable) 74 3
RS-485/Modbus RTU Slave
Listings/Approvals
CE marked
UL/cUL listed
GL (Marine)
Subject to technical Part numbers P/N
modifications. Measuring inputs 120 Vac, ../5 A 8440-1016
This document is distributed for Measuring inputs 400 Vac, ../5 A 8440-1448
informational purposes only. It is not
to be construed as creating or
becoming part of any Woodward * not according to ANSI guidelines (three-step protection instead of inverse time characteristic)
Governor Company contractual or #1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)
warranty obligation unless expressly
stated in a written sales contract.

We appreciate your comments about


the content of our publications.
Please send comments including the
document number below to
stgt-doc@woodward.com

Woodward Governor
Company

All Rights Reserved

03247E - 12/6/S