You are on page 1of 3

version 1.2.

3
--------------
- ModBus TCP server connection will now timeout rapidly if communication is broken
while transmitting data.
- Correctly detects the event of the loss of the current time on the Real Time
Clock (RTC).
- Fix an issue in ModBus TCP server where interrupted communication could result in
communication error.
- Includes Boot code update (1.0.5) to fix an issue where ethernet communication
would not work at power-on after the unit has been offline for several days.

version 1.2.2
--------------
- Signaling relays are always enabled.
- Fixed an issue where a disabled PTP-1588 port cannot be re-enabled until restart.
- Improved digital input publication latency.
- Time synchronization will now turn unsynchronized if the occurence of a leap
second possible and not known.
- In PTP-1588, if the configured class is master only, ports will stay in
initialize state until UTC information is comfirmed.
- Fixed a very rare issue where digital input chatter filter may trigger when it
should not.
- Added automatic logout when the web browser close an online session.
- Fixed an issue with quality field of digital point in the GOOSE publisher.
- WEB: Fixed user profile page update issue after re-login as a different user.
- Fixed some issues in PTP/1588 when acting as a boundary clock.
- PMU: Updated ICD file of PMU010000 to reflect added functionalities when the
IEC61850-9-2 option is present.
- PMU: Fixed an issue with C37.118 custom command not being correctly blocked if
disabled.
- Fixed display of digital IOs on RTS models.
- Changed GOOSE publisher to be active also when the device is offline.
- Reworked GOOSE publisher retransmission scheme to use only min and max value.
- Removed IEC61850-9-2 version parameter which is not used anymore.
- Fixed potential issue when a very high rate of multicast traffic is received on
multiple ports.
- PMU: Fixed a connection issue in C37.118 UDP transport mode when using wildcard
as peer address.
- Improved precision of timestamping in digital IOs, and added supports of leap
second identification.
- Fixed an issue regarding 3-phase value quality when voltage or current neutral
input are disabled.
- Reworked time jump handling to make it smoother and make sure that no invalid
readings are published.
- Fixed an issue when changes to IED name are not applied correctly after system
configuration update.
- Fixed NTP client handling of leap seconds.
- ***WARNING*** Updated ICD files to includes digital outputs and reflect changes
to GOOSE dataset.
- ***WARNING*** Reworked GOOSE reported dataset to include digital outputs and use
data attributes instead of data objects.
- Fixed issue with pulsed output when using long pulse delay.
- PMU: Fixed handling of leap seconds in C37.118 stream.
- Fixed reloading of custom security certificate after deploying a new one.
- Reworked NTP Client to allow the system to synchronize without using a PPS input.
- Added various events to audit log.

version 1.2.1
--------------
- Fixed an issue encountered when receiving incoming C37.118 connections while
stopping the unit.

version 1.2.0
--------------
- Fixed signalization relays assignment to match documentation.
- Support for optional AMU software option on PMU product.
- Local management console now use role based access control for sensitive
commands.
- Added NTP server support.
- Added digital values to web HMI.
- PMU: Added C37.118 support for custom control commands.
- PMU: Fixed issue with C37.118 TCP-UDP communication mode.
- Fixes internal GPS firmware issue when extracting current TAI to UTC offset.
- Added ModBus slave protocol support.
- Role Base Access Management tool added to Web application.

version 1.1.6
--------------
- Added support for real-time simulator version of the product (low voltage).

version 1.1.5
--------------
- Added GPS module version and serial number on the System Information web page.
- Fixed input values quality indication when the input is detecting an overflow or
a failure.
- PMU: Fixed input angle correction issue that may cause a millidegree offset on
the reported angle if operated off frequency for an extended period.
- Added support for latest GPS receiver module version.

version 1.1.4
--------------
- Fixed wrong GoCB reference sent in GOOSE publisher.
- Changed content of published GOOSE message to include signalization relay
indicators.
- PMU: Improved PMU algorithm performance, V15.3
- Added Alarm(s) signalization to assigned LED and relay.
- Invert relay polarity of the synchronization status relay (R2)
- Updated self-signed certificate to use SHA-256 signing.

version 1.1.3
--------------
- PMU: Improved PMU algorithm performance, V15.2

version 1.1.2
--------------
- Device will now refuse some configuration that are invalid.
- PMU: Improved PMU algorithm performance, V15.1

version 1.1.1
--------------
- PMU: C37.118 reporting #2 might not work correctly if it is the only one enabled.
- PMU: Improved PMU algorithm performance, V15
- Fixed issue when special character is used in identification fields.
- Enforce password minimum length to 8 characters.

version 1.1.0
--------------
- Changed the accepted firmware update filename.
- Fixed an issue where unit might not return online after restart.
- Added strong password enforcement.
- Added power metering and sequences readings to web interface.
- Added test mode support.
- PMU: Major improvements to web dashboard. It now includes Summary, Measurements,
Synchrophasor, Alarms and Time synchronization panels.
- PMU: Set Phasor vector color to default color on older configurations.
- Fixed an issue preventing the web interface to display on iOS devices.
- PMU: Added ROCOF value to the synchophasor page of the Web interface.
- PMU: In C37.118, added configurability of configuration change count.
- Fixed save to file issues for DebugLevel properties.
- Fixed timezone handling and localtime display in journals.
- PMU: Improved PMU algorithm performance, V14.6
- Added proper handling of IO cards not responding or in error.
- Fixed compatibility issue with IE 11 web browser.
- Added boundary clock support.
- Added PTP-1588 Profiles support (default, C37.238 and IEC61850-9-3).
- Added PRP (Parallel Redundancy Protocol) functionality.
- Fixed an ethernet communication issue where the traffic can stop or experience
latencies.
- Added GPS status information in the web dashboard time synchronization page.
- Added leap second support.
- Added missing hardware information in the web System page.
- Added detailed view of current system alarms.
- Fixed typos in web site.

version 1.0.4
--------------
- Fixed calibration issue on voltage inputs of some units.
- Fixed issue in PTP/1588 synchronization when using P2P delay mechanism.
- Fixed IRIG-B parity check to work with inverted clock src polarity due to
ambiguous C37.118 definition.
- Fixed wrong offset for the GPS synchronization.

version 1.0.3
--------------
- Added support for PTP-1588 VLAN configuration.

version 1.0.2
--------------
- PMU: Updated phasor computation algorithm to v11.

version 1.0.1
--------------
- Fixed issue where device does not create the correct configuration templates when
reset to factory default.
- Fixed issue to display synchronization source as "None" if no clock source is
configured.
- Fixed issue where the WEB server page all the dynamic values are temporarily
displaying zero.

version 1.0.0
--------------
- Initial release