You are on page 1of 7

WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 39

DRILLING FLUIDS

Drilling fluid and cementing


improvements reduced per-ft
drilling costs by 10%
Coordinated well design improved drilling performance by lessening wellbore
washout, improving cementing practices and increasing bit performance
Doug Walton, Tom Brown, Inc., Estes Ward, Newpark Drilling Fluids, Taryn Frenzel, Schlumberger, Inc.,
and Harry Dearing, OGS Laboratory, Inc.

Comparing the drilling program in Evaluation of higher concentrations of depths of 5,500 to 6,500 ft.1 Since the
White River Dome field, Colorado, of the potassium silicate additive is expected field is on land under Bureau of Land
2001, in which 26 wells were drilled, to further reduce wellbore diameter. Management (BLM) jurisdiction, a num-
with the 2002 program, in which 14 wells Reduction of the cement density with ber of restrictions apply to drilling oper-
were drilled, shows that coordinated well other design changes will lower the equiv- ations. One important restriction is that
design significantly improves drilling per- alent circulating density. Bit performance year-round drilling is not permitted. The
formance. Lessened wellbore washout, and hydraulics improvements will result drilling season usually starts in the spring
improved cementing practices and in eliminating another bit per well. and goes through the end of the year.
increased bit performance reduced costs This break allows time to evaluate results
from $77.54 per ft in 2001 to $69.56 FIELD BACKGROUND of the previous year and plan on improve-
per ft in 2002, resulting in a savings of White River Dome gas field in the ments for the upcoming drilling season.
$810,000 for the 2002 drilling program. Piceance basin of western Colorado is With estimated reserves of 1.35 Bcf of
Use of a wellbore stabilization additive, operated by Tom Brown, Inc., Fig. 1. It natural gas per well and a large supply of
in conjunction with a 30% reduction in contains 67 active producing wells. The undrilled prospects, focusing on reducing
circulation rate, reduced hole enlarge- Cameo sandstones and coals are the main costs and improving performance pays
ment by an average of 14% for the inter- producing horizons and are found at dividends every year. Current plans are to
val drilled. Consisting of a reactive potas- drill 14 wells for 2003.
sium silicate solution, the additive reduces Establishing a good working relation-
wellbore enlargement by precipitating ship between management, geology, pro-
out of solution onto the wellbore walls. duction and drilling personnel is the
This reduced average wellbore diameter beginning point for a successful drilling
for the interval from 10.3 in. to 9.3 in. season. Working with vendors of drilling
Cement volumes were reduced by 899 services that are willing to propose
cu ft per well. new ideas and participate in their imple-
Improving cementing practices using mentation is also required to achieve
a lightweight cementing system along improvement in drilling performance.
with a more effective lost circulation addi- Successful coordinated well design results
tive increased cementing success from from selecting ideas and techniques for
40% to 75%. The cementing improve- improvements in several drilling areas
ments complemented the improvement in that will perform well together.
hole caliper and eliminated additional
costs from two-stage cementing. COORDINATED WELL DESIGN
Bit performance was improved from an For White River Dome field, a num-
average of 4.2 bits per well to 3.1 bits ber of opportunities for improving per-
per well by use of a rate-of-penetration formance were identified during the 2001
(ROP) additive in the drilling fluid. The drilling season:
ROP additive (a proprietary complex • Two-stage cementing increased
ester) provided enhanced performance FIG. 1. White River Dome Field lies cementing, rig and completion costs of a
when drilling bentonite stringers that had in the northern Piceance basin of well by $50,000 to $75,000.
previously caused bit balling and loss of northwestern Colorado. Produc- • Hole washout in the upper section
drilling rate with PDC bits. tion is from coals and sandstones below surface casing required large cement
in the Cretaceous Williams Fork
Continued design improvements are formation. volumes and increased the likelihood of
scheduled for implementation in 2003. lost circulation during cementing.
World Oil APRIL 2003 39
WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 40

DRILLING FLUIDS

• Due to the extensive fracture treat- (cement to surface) bit balling problems after drilling through
ments anticipated for the wells, primary • Drilling 77⁄8-in. hole to TD (water and a bentonite stringer in the Mesa
cementing success (as measured by cement LSND mud) Verde/Williams Fork formation. Mud-
bond logs) was a requirement for drilling • Running 51⁄2-in. casing (cement to up with an LSND mud occurs prior to
success. surface). pulling the PDC and the well is then
• PDC bits performed very effectively, Top of cement behind the 5 1⁄2-in. pro- drilled to TD (6,200 to 7,200 ft) in the
with average ROPs of more than 100 duction casing must be above the surface Rollins formation with as many as three
ft/hr in most wells. Increasing footage casing shoe to cover shallow water and gas three-cone bits.
drilled by PDC bits would result in fewer flows in the Wasatch formation. Lost cir- To improve bit life, increase ROP and
bits, higher ROPs and lower drilling costs. culation and hole washouts cause prob- reduce hole washouts, several changes
lems toward achieving an acceptable top were made over the past two years to the
RIG SELECTION of cement. Sloughing shales in the mud program, bit selection and drilling
For this project, a Tom Brown sub- Wasatch cause hole washouts, and con- hydraulics. To reduce hole washouts dur-
sidiary, Sauer Drilling, provided the rigs. sequently, large cement volumes. Lost ing the 2001 drilling program, circulating
The rigs were moderate-depth, conven- circulation problems exist during cement- rate during drilling of the 7 7⁄8-in. hole was
tional rotary rigs rated to 10,000 ft with ing due to breakdown of deeper sand and reduced by 28% from 460 gpm to 330
41⁄2-in. drill pipe fitted with at least one coal seams through the Cameo forma- gpm. This reduced annular velocity from
triplex mud pump. tion. Due to problems with lost circula- 270 fpm to 193 fpm. Hole washouts were
tion during cementing, lightweight reduced slightly (by ± 1⁄2-in.) due to
BIT SELECTION AND cement with a compressive strength above reduced circulating rate without any loss
HYDRAULICS 2,000 psi was used to achieve a top of of ROP, despite a drop in hydraulic horse-
During the past three years, wellbore cement above the surface casing shoe. power per square inch (HSI) at the bit.
design for drilling wells at White River With the higher-cost slurry, a reduction During 2003, jet sizes will be reduced
Dome field involved: in the cementing volume was necessary to during drilling with PDC and three-cone
• Drilling 11-in. hole to 1,100 ft reduce well cost. bits to increase HSI to between 2.5 to 5
(gel/lime spud mud) The Wasatch is drilled with water and in an attempt to improve ROP and reduce
• Running 8 5⁄8-in. surface casing a PDC bit, which is typically pulled for bit balling.
WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 41

DRILLING FLUIDS

reduced average time on location by one various regions.3,4 These applications are
TABLE 1. Properties of day between 2001 and 2002. usually with fully formulated drilling flu-
potassium silicate During 2000 and 2001, a potassium ids containing high concentrations of sil-
Density 10.5 ppb chloride (KCl) substitute was added to icates in combination with other inhibitive
K2O 8.3 wt% improve shale stability while drilling salts.
SiO2 20.75 wt%
Ratio, %SiO2 /% K2O 2.5
through the Wasatch. While the KCl sub- Analysis of well calipers obtained from
Viscosity 40 cPs stitute did help reduce washouts in the wells drilled during 2001 showed that
Solids 29.05 wt% shale, average hole size through the most hole enlargement occurred in the
Wasatch was still over 10 in., which meant portion below surface casing to about
that the KCL substitute did not effec- 4,000 ft TVD. This was also the section
During 2002, several changes were tively reduce cementing costs. A different that was drilled with water while circu-
made concerning bit selection and mud approach to stabilize shales involving lating the reserve pit. This resulted in
design. The typical PDC design used potassium silicate during the water section high ROPs with a PDC bit and low cost
during 2000 and 2001 was a 6-blade, 3⁄4- of drilling was implemented during the per foot.
in.-cutter bit., whereas during 2002, a 2002 drilling program. The addition of Experience in the area suggested that
switch was made to a 5-blade, 5⁄8-in.-cut- potassium silicate successfully reduced the hole washout could be reduced by
ter design in an attempt to improve on hole size, resulting in an average 28% mudding up in this interval with a partially
PDC durability for a longer run time. In reduction in cement volume as compared hydrolyzed polyacrylamide (PHPA) mud.
addition to the PDC change, an ROP to prior years. Experience also showed that this would
additive (a polyglycerol ester) was added result in increased mud costs and lower
to the mud system to reduce problems DRILLING FLUID ROPs. For these reasons, an alternate
with bit balling while drilling bentonite Interest in silicate-based drilling fluids, strategy was required.
stringers. The change in PDC design and which have been used in a number of The continuous injection of potas-
ROP additive resulted in longer PDC bit areas over the past 50 years, waned from sium silicate solution into the mud pump
runs and elimination of just over one the 1950s until the mid 1990s.2 However, suction at 0.1% of the drilling pumping
three-cone bit run per well. Elimination renewed interest has led to their use in a rate was proposed. This would result in a
of one bit trip and the enhanced ROP number of drilling fluid applications in low-cost treatment of the wellbore as
WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 42

DRILLING FLUIDS

12.0 0
11.6 Flowline
Depth = 6,424 ft Suction
11.2
Annular pressure, ppg

1,000
10.8

Depth, ft
10.4 2,000
10.0
9.6 Frac 3,000
9.2 Pore
Hydrostatic
8.8 Dynamic 4,000
8.4 0.00 0.05 0.10 0.15 0.20 0.25
0 30 60 90 120 150 Silicate content, wt%
Time, min.

FIG. 2. ECD data for LiteCRETE system. FIG. 3. Silicate concentration in drill water.

drilling progressed and not compromise cementing system is especially critical to Foamed cement design. A nitro-
drilling rate. Prior to mudding up at the success of these wells. Since coal sec- gen foamed cement system was pumped
4,000 ft, the addition of silicate would be tions are to be stimulated separately from on one well with a design based on 10%
discontinued and the silicate allowed to the sandstone sections, zonal isolation is excess over the caliper log as follows:
deplete from the fluid. The silicate selected very important. Thus, the entire cement- • 155 bbl of 10-ppg foamed lead
for this application has the properties ing process was examined critically and sev- cement
shown in Table 1.5 eral possible cement designs examined: • 75 bbl of 13-ppg foamed tail cement
The reaction between the exposed well- • Conventional cement using industry • 15 bbl of 14.3-ppg non-foamed tail
bore and potassium silicate occurs because standard additives for density control • Treated water displacement to bump
the lower pH of the wellbore surface and • Nitrogen foamed cement the plug.
presence of divalent cations, calcium and • Lightweight cement using propri- Job planning included the logistics for
magnesium cause precipitation of a etary density reduction solids. nitrogen handling equipment.
hydrous silicate gel. These gels act to seal The previous field operator’s experience
the wellbore surface, increasing its sta- using conventional cements indicated Lightweight slurry cement design.
bility. Potassium silicate was chosen over The first challenge was to overcome the
that a lower density slurry was required.
sodium silicate for two reasons. Potas- hydrostatic restrictions with a lightweight
This left the other two options. Both sys-
sium silicate is soluble at a lower pH than tems were designed and evaluated. slurry that still developed sufficient com-
sodium silicate. Also, the potassium ion pressive strengths to provide zonal iso-
has proven to inhibit clay lation for future fracture treat-
swelling. The presence of quartz ments. This was accomplished
(crystalline SiO2) in the sands using Schlumberger’s Lite-
and shales on the exposed well- CRETE technology consisting
bore provides preferential sites of an optimized particle-size-
for bonding of the silicate. distribution slurry.6 An 11.27-
In addition to potassium sil- ppg system that achieved 2,300-
icate, control of pH with caustic psi compressive strengths was
potash (KOH) at 10.5 was rec- designed for the project. This
ommended. It was also antici- production-quality cement was
pated that high viscosity sweeps used for the tail system follow-
would be pumped as needed to ing an 11-ppg conventional filler
facilitate hole cleaning. cement, which was used to cover
The fluid design was devel- the sands up to surface pipe.
oped to address the problem of This lead and tail system,
wellbore enlargement without achieved an ECD less than the
affecting ROP and minimally frac gradient of 0.61 psi/ft
increasing mud cost. After dis- (equivalent density = 11.7 ppg),
cussion and review, use of the sil- as seen in Fig. 2.
icate was approved for the 2002 With hydrostatic goals
drilling season. Sufficient product achieved, a more effective LCM
for several wells was ordered and was needed. A fiber-type LCM
maintained in stock. was chosen (CemNET) because
of its success in cementing across
FIG. 4. Caliper comparison between typical wells for
CEMENT DESIGN 2001 and 2002. fractured coals in other areas,
The design of an effective which not only helped maintain
42 APRIL 2003 World Oil
WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 44

DRILLING FLUIDS

returns, but also reduced the amount of the suction pit was 0.14 wt% for the ing off the fractures than the previous
excess cement needed on the jobs and interval. Average flow line concentration coarse particle.
minimized cement fallback when pumps was 0.10 wt%. This indicates that the In 2002, a single-stage foam treatment
were shutdown. In addition to running reaction of the silicate with the wellbore was attempted, which proved unsuccess-
the fiber-type LCM, it was also decided and cuttings was proceeding rapidly, even ful due to a permanent loss in returns
to drop the top plug on the fly. The at the low concentrations used. Also note during flush. The foamed cement job
thought was to minimize surging on the the rapid depletion of the silicate when was pumped at an average of 6 bpm with
formation caused from the annular veloc- additions were discontinued at about 1,000 psi surface pump pressure. Returns
ity slowing down then abruptly acceler- 3,200 ft. diminished during flush down to a 1⁄4 bpm
ating back to surface pump rates. Typical calipers for two wells, one from pump rate with no cement returns to sur-
2001 and one from 2002, are shown in face. A cement bond log prior to com-
DRILLING FLUID RESULTS Fig. 4. The main reduction of enlargement pletion showed top of cement at
The Ant Hill Unit 25–22 was the first came from under surface casing to about ± 3,100 ft. Thixotropic cement at 14.6
well drilled using the silicate additive to 4,000 ft—the interval drilled with water ppg was pumped down the 85⁄8-in. by 51⁄2-
supplement water. After drilling and set- and silicate additive. in. annulus as a cap. The foamed cement
ting surface casing, a Smith M75VPX For the 14 wells drilled in 2002, the job was comparable in cost to prior two-
bit was used to drill out. As soon as caliper averaged 9.4 in. In 2001, it aver- stage cement jobs, and did not achieve an
cement had been drilled, the silicate solu- aged 10.5 in. Most of this improvement acceptable top of cement without addi-
tion was added to the water in the suc- occurred in the sections drilled with water tional work and expense.
tion pit at a rate of 0.5 gpm (0.15 % of and the silicate additive. For these reasons, it was decided to
the circulation rate). stay with the LiteCRETE/CemNET sys-
As drilling proceeded, silicate solu- CEMENTING RESULTS tem and focus on increasing success from
tion7 concentration in the water at the At the end of 2001, this lightweight the test wells. In 2002, eight wells were
pump suction and flowline was moni- design was implemented and had early cemented using this combination, and six
tored with the pH and potassium level. success (60%) and effectively eliminated of the wells (75%) maintained returns,
Fig. 3 shows the silicate solution con- two-stage cementing. In one of the trial which led to successful treatments. Not
centration in the water at the flowline wells, annular returns stopped, but were only was the success ratio increased from
and suction. regained and a successful cement treat- the 2001 conventional treatments, but
As indicated, there was significant ment was achieved. The fact that returns the additional costs associated with 2-
depletion of the silicate solution in the were regained was proof that the new stage cementing had been eliminated.
well. Average silicate concentration for LCM chosen was more effective in pack- With the successful hole diameter reduc-

44
WO 0403 Walton-Drilling Fluid 6/18/03 8:56 AM Page 45

tion that occurred in 2002, the cement vol- was used in the active mud system. As
ume was reduced by an estimated 899 ft3 TABLE 2. Summary of stated earlier, application of the ROP
(160 bbls) per well. If this eight-well aver- well results enhancer with a more aggressive bit design
age was applied to all 14 wells in the 2002 2001 2002 eliminated one three-cone bit and reduced
project—this equates to a reduced cement Number of wells 26 14 time on location by one day.
volume of 2,232 bbl and a material cost Dry hole cost, $ 540,321 503,945
Well depth, ft 6,968 7,245
savings of over $150,000 for the project. Cost/foot, $ 77.54 69.56 SUMMARY OF WELLS
Days to depth 13.6 12.2 Table 2 gives a summary of the results
ROP ENHANCEMENT Mud cost, $ 31,177 26,977 obtained in 2002 compared with 2001.
As stated in the hydraulics section, the Hole diameter, in. 10.5 9.4 As can be seen, there was improve-
Tail cement volume, ft3 790 528
PDC bit runs in the 7 7⁄8-in. hole sections Lead cement volume, ft3 2.343 1,706 ment in every aspect of the drilling oper-
consistently ended with bit balling in ations from 2001 to 2002. Improved hole
the bentonite stringers of the Mesa conditions also resulted in improved
Verde/Williams Fork formation cementing performance. The goal
at around 4,000 ft. If bit balling of maintaining circulation
could be reduced, the PDC bit 12.0 throughout the cement job was
runs could probably be extended achieved on six of the eight com-
11.5 2002 design ECD (11 ppg lead;
by as much as 1,000 ft. parable wells in 2002 (a 75% suc-
11.3 ppg tail)
This situation was ideal for 11.0 2003 Design ECD (10.5 ppg slurry)
cess rate) compared to only six of
the application of an effective 15 comparable wells for 2001 (a
ECD, ppg

Frac Limit (11.73)


ROP enhancer. This product is 10.5 40% success rate).
based on a Newpark Drilling Application of the new
Fluids proprietary complex ester. 10.0 drilling technologies reduced
It was found that the additive 9.5
well costs across the board—
immediately cleaned the bit and including mud and cementing
increased ROP to the same level 9.0 costs. This suggests that, in this
as prior to bit balling. Typically, 0 15 30 45 60 75 90 105 120 135 case, the application of new tech-
Time, min.
the additive was used in slug- nology in a mature area can
ging treatments to aid in drilling improve performance and reduce
FIG. 5. Equivalent circulating density improvement
bentonite stringers. Over time, as for 2003 versus 2002 design. well costs.
much as 2 vol% of the additive Continued on pg. 47

45
Circle 76
WO 0403 Walton-Drilling Fluid 6/18/03 8:57 AM Page 47

CONCLUSIONS • Varying the silicate content of the


Coordinated well design has provided water drilling portion of the hole to fur-
substantial cost savings in the White River ther reduce wellbore enlargement
Dome field for Tom Brown, Inc. Work- • Improved bit designs to reduce the
ing in concert, several innovative new number of bits per well from the current
technologies have contributed to these average of about three to two
cost reductions: • Further refine the application of lost
• Reactive potassium silicate reduced circulation products and lightweight cement
wellbore enlargement without sacrific- to improve cementing success to 100%.
ing ROP or cost. The success in the 2003 cementing
• Improved bits and hydraulics elimi- program can be improved by studying
nated one bit and one day from the days the successful wells. Plotting the results
to TD. of hole diameter vs. success shows that
• Improved lightweight cement slurries when the lead section’s average diameter
provided excellent cementing performance was less than 9.25 in., then 100% suc-
with the application of new lost circula- cess was observed. If the lead section
tion products. was greater than 9.25 in., then 33% suc-
• ROP enhancing drilling fluid additives cess was observed. This correlation sug-
allowed longer and faster PDC bit runs. gested that the losses in returns might
have had something to do with the sec-
IMPROVEMENTS FOR 2003 tion at 2,500 ft that tended to be severely
A number of potential improvements washed out. Further evaluation of this
will be evaluated in 2003, including: trend will be studied to fully understand
the results. Improving the caliper in this
THE AUTHORS section should directly benefit cement-
ing success.
Doug Walton is an opera-
tions engineer for Tom
A second step to increase success in
Brown, Inc., in Denver, Col- 2003 will be to lower the cement slurry
orado. His areas of respon- densities. A new LiteCRETE system has
sibility include the Piceance been designed that has a 10.5 ppg density.
basin in Colorado and the
Green River basing in
With this lower density, the compressive
Wyoming. He holds a BS strengths will peak around 3,000 psi. A
degree in petroleum engi- 10.5-ppg conventional filler lead, which
neering from West Virginia has properties similar to the previous
University.
2002 lead system, also will be used. With
Estes Ward, operations these changes, the ECD in the well will
manager for Newpark be reduced by 0.7 ppg (from 0.6 psi/ft to
Drilling Fluids, Rocky Moun- 0.56 psi/ft). As seen in Fig. 5, this increases
tain Business Unit, provides
drilling fluid recommenda-
the fracture pressure safety margin, which
tions for wells drilled in the should lead to an increase in cementing
Rocky Mountains. He has success for 2003. WO
25 years of experience in
the Rocky Mountains as a
field mud engineer, senior
ACKNOWLEDGMENTS
fluids engineer and manager.
The authors thank Tom Brown, Inc., Newpark
Taryn Frenzel, a Schlum- Drilling Fluids and Schlumberger, Inc., for their sup-
berger well services engi- port. We also appreciate the field personnel who worked
neer of Denver, is working to implement the coordinated design for this project.
in the Tom Brown office as They include Curt Childers, Consulting Drilling Super-
a DESC engineer. He holds visor; Don Jackson, Newpark Drilling Fluids; Tony
a BS degree in engineer- Kenyon, Newpark Drilling Fluids; Garth McConkie,
ing science from Montana Schlumberger; and rig personnel, Sauer Drilling Co.
Tech of the University of
REFERENCES
Montana. 1 Olson, Terrilyn; Hobbs, Bill; Brooks, Robert; and Gale, Byron: “Paying
Off For Tom Brown In White River Dome Field’s Tight Sandstones, Deep
Harry Dearing manages Coals,” American Oil and Gas Reporter, December 2002, pp 67–75.
2
OGS Laboratory, Inc. (a Darley, H.C.H., Gray, George R.: Composition and Properties of
Drilling and Completion Fluids, 5th Edition, March 1998, pg 381.
Newpark Resources com- 3 D’Alessandro, Fulberto: “An inhibitor system for drilling active clays,”
pany). As laboratory man- World Oil, April 2001, pg E-39.
ager, he works in the areas 4 Rawlyk, Dave; McDonald, Michael: “Potassium Silicate Based Drilling
of fluid design, product eval- Fluids: An Environmentally Friendly Drilling Fluid Providing Higher
Rates of Penetration,” CADE/CAODC Drilling Conference, Calgary,
uation, and shale stability Alberta Canada, October 23 & 24, 2001.
testing. Prior to rejoining 5 Kasil® 1 Product Specification Sheet, PQ Corporation, November 1998.
6
OGS Laboratory in 1998, he Hun, Christian; El-Hassan, Hassan; Helou, Husam; Hasni, A. Latif;
Mohsen, A. Hammeed: “Innovative Solution for Cementing Across
worked for a major oil com- Very Low Fracture Gradient Formations,” IADC/SPE 72286, Mid-
pany in various positions, most relating to drilling dle East Drilling Technology Conference, Bahrain, October 2001.
fluids. He has a degree in engineering from The 7 “Field Test Method for Silica Content in a Potassium Silicate Drilling
University of Texas - Austin. Fluid,” National Silicates.

Circle 78
47 47

You might also like