NetSure™ DC Power Systems with NetSure™ Control Unit (NCU)

Table of Set Values, 11PC3421MC (Revision B, November 28, 2016) CXC140201


NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

This page is intentionally blank.


NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Table of Contents
Tables of set values 1
Settings 1
Alarm Settings ............................................................................................................................................................... 1
Settings->Quick Settings .............................................................................................................................................. 11
Settings->System ......................................................................................................................................................... 12
Settings->Battery Charge ............................................................................................................................................. 14
Settings->ECO .............................................................................................................................................................. 15
Settings->LVD .............................................................................................................................................................. 16
Settings->Temperature ................................................................................................................................................ 17
Settings->Rectifiers ...................................................................................................................................................... 17
Settings->Battery Test ................................................................................................................................................. 18
Settings->Time Settings ............................................................................................................................................... 19
Settings->Output Relays .............................................................................................................................................. 19
Advanced Settings->Ethernet ...................................................................................................................................... 21
Advanced Settings->Users ........................................................................................................................................... 22
Advanced Settings->SNMP ........................................................................................................................................... 22
Advanced Settings->Language ..................................................................................................................................... 23
Advanced Settings->Alarm Report ............................................................................................................................... 23
Advanced Settings->Shunt ........................................................................................................................................... 24
Settings->System settings............................................................................................................................................ 24
NetPerform™ Optimization Services 25

[iii]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

This page is intentionally blank.

[iv]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Tables of set values


These tables are based on software revision 2.1.50 for the NetSure™ Control Unit (NCU) used in NetSure™ 5100 DC power systems.
All settings and choices affect the functions of the power supply system. The values shall therefore not be changed without a
consequence analysis. If a default value is adjusted, the new value shall be entered in the column “Plant-specific settings”. The
default settings listed are the factory default settings.

Settings
Alarm Settings
Severity
Power system

Level Output Relay


Remark Sign. Date
(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name
Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Supervision Unit
Observation None
Internal Fault
CAN Communication
Major None
Failure
Outgoing Alarms
Observation None
Blocked
Maintenance Alarm No Alarm None
Configuration Error
Observation None
from Backup
Configuration Error
Observation None
from Default
Abnormal Load Current Critical None
Overload Observation None
SPD Critical None
Emergency
No Alarm None
Stop/Shutdown
System Temperature 1
Critical None
not Used
System Temperature 2
Critical None
not Used
System Temperature 3
Critical None
Not Used
IB2 Temperature 1 Not
Critical None
Used
IB2 Temperature 2 Not
Critical None
Used
EIB Temperature 1 not
No Alarm None
Used
EIB Temperature 2 not
No Alarm None
Used
System Temperature 1
Critical None
Sensor Fault

[1]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Level Output Relay


Remark Sign. Date
(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name
Plant-
Plant-specific Default
Default setting specific
setting setting
setting

System Temperature 2
Critical None
Sensor Fault
System Temperature 3
Critical None
Sensor Fault
IB2 Temperature 1
Critical None
Sensor Fault
IB2 Temperature 2
Critical None
Sensor Fault
EIB Temperature 1
No Alarm None
Sensor Fault
EIB Temperature 2
No Alarm None
Sensor Fault
DHCP Failure Observation None
PLC Config Error Observation None
485 Communication
No Alarm None
Failure
OBSERVATION
No Alarm None
SUMMARY
MAJOR SUMMARY No Alarm None
CRITICAL SUMMARY No Alarm None
Secondary NCU Lost No Alarm None
Overvoltage 1 Critical None
Overvoltage 2 Critical None
Undervoltage 1 Major None
Undervoltage 2 Critical None
Overvoltage 1 (24V) No Alarm None
Overvoltage 2 (24V) No Alarm None
Undervoltage 1 (24V) No Alarm None
Undervoltage 2 (24V) No Alarm None
Diesel Run Over
No Alarm None
Temperature
DG1 is Running No Alarm None
DG2 is Running No Alarm None
Hybrid is High Load No Alarm None
DG1 Failure No Alarm None
DG2 Failure No Alarm None
Grid is on No Alarm None
High Ambient
Observation None
Temperature
Low Ambient
Observation None
Temperature

[2]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Level Output Relay


Remark Sign. Date
(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name
Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Very High Ambient


Observation None
Temperature
Ambient Temp Sensor
Observation None
Fault
IB2-DI1 Observation IB2-4 Door open
IB2-DI2 Critical None BBS Bat Fuse
IB2-DI3 Critical IB2-5 Fan Failure
IB2-DI4 No Alarm None
IB2-DI5 No Alarm None
IB2-DI6 No Alarm None
IB2-DI7 No Alarm None
IB2-DI8 No Alarm None
IB Communication
Critical None
Failure
High Load Level1 Observation None
High Load Level2 Observation None
Ext.l Cab Hi/LOW
IB0-DI1 Critical None
Temp Alarm
Climate input
IB0-DI2 Critical None
power failure
IB0-DI3 No Alarm None
IB0-DI4 No Alarm None
Testing Relay 14 No Alarm None
Testing Relay 15 No Alarm None
Testing Relay 16 No Alarm None
Testing Relay 17 No Alarm None
Over Maximum Power
Observation None
Alarm
SMS Modem Fail Critical None
Manual State Observation None
SNMP Config Error Observation None
Mains Failure Observation None
Internal
Major None
Communication Failure

[3]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Rectifier Group

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Multiple Rectifiers
Critical None
Failure
Rectifier Lost Major None
ECO Mode Active Observation None
All Rectifiers Comm Fail Major None
ECO Cycle Alarm Observation None

Rectifier

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

AC Input Failure Major None


Rectifier High
Major None
Temperature
Rectifier Fault Critical None
Overvoltage Major None
Rectifier Protected No alarm None
Fan Failure Major None
Current Limit No Alarm None
Communication Fail Major None
Derated Observation None
Current Sharing Alarm Observation None
AC Undervoltage
Major None
Protection
DC Output Shut Off No Alarm None

[4]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Battery Group

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Short Battery Test


No Alarm None
Running
Equalize Charge for Observation
None
Test
Manual Test No Alarm None
Planned Test No Alarm None
AC Failure Test No Alarm None
Manual Equalize Observation
None
Charge
Automatic Equalize Observation None
Cyclic Equalize Charge Observation None
Master Equalize Observation
None
charge in Progr
Master Battery Test in No Alarm
None
Progress
Discharge Current
No Alarm None
Imbalance
Abnormal Battery
Observation None
Current
Temperature
No Alarm None
Compensation Active
Battery Current Limit
Observation None
Active
Bad Battery Observation None
Battery Discharge Observation None
Battery Test Failure Observation None
Very High Critical
Compensation None
Temperature
High Compensation Major
IB2-6
Temperature
Low Compensation Major
IB2-6
Temperature
Compensation Sensor
Critical IB2-6
Fault
Very High BTRM
Critical None
Temperature
High BTRM
Major None
Temperature
BTRM Temperature
Critical None
Sensor Fault
Li-Ion Battery Lost No Alarm None

[5]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

1 Li-Ion Battery
No Alarm None
Disconnect
2+Li-Ion Battery
No Alarm None
Disconnect
1 Li-Ion Battery
No Alarm None
No Reply
2+Li-Ion Battery
No Alarm None
No Reply
Inventory Update
No Alarm None
In Process
ABCL is Active No Alarm None
Battery Charge
No Alarm None
Prohibited Alarm

Battery

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Current Limit
Observation None
Exceeded
Over Battery Current Observation None
Low Capacity Observation None

Battery Fuse

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Fuse 1 Alarm Critical None BFuse1 (Yellow)


Fuse 2 Alarm Critical None BFuse2 (Green)
Fuse 3 Alarm Critical None BFuse 3 (Red)
Fuse 4 Alarm No Alarm None
Fuse 5 Alarm No Alarm None
Fuse 6 Alarm No Alarm None

[6]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

DC

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Overvoltage 1 Critical None


Overvoltage 2 Critical None
Undervoltage 1 Major None
Undervoltage 2 Critical None
Overvoltage 1(24V) No Alarm None
Overvoltage 2(24V) No Alarm None
Undervoltage 1(24V) No Alarm None
UnderVoltage 2(24V) No Alarm None
Current High Current Major None
Current Very High
Major None
Current

DC Fuse Unit

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Fuse 1 Alarm Critical None Load Fuse Alarm


Fuse 2 Alarm No Alarm None
Fuse 3 Alarm No Alarm None
Fuse 4 Alarm No Alarm None
Fuse 5 Alarm No Alarm None
Fuse 6 Alarm No Alarm None
Fuse 7 Alarm No Alarm None
Fuse 8 Alarm No Alarm None
Fuse 9 Alarm No Alarm None
Fuse 10 Alarm No Alarm None
Fuse 11 Alarm No Alarm None
Fuse 12 Alarm No Alarm None

[7]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

LVD

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

LVD 1 Disconnect Critical IB2-7


LVD 2 Disconnect Critical None
LVD 1 Failure No Alarm None
LVD 2 Failure No Alarm None

LVD 3 Unit

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

LVD3 Disconnected No Alarm None


LVD3 Failure No Alarm None

AC

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

High Line Voltage L1-


No Alarm None
L2
Very High Line Voltage
No Alarm None
L1-L2
Low Line Voltage L1-L2 No Alarm None
Very Low Line Voltage
No Alarm None
L1-L2
High Line Voltage L2-
No Alarm None
L3
Very High Line Voltage
No Alarm None
L2-L3
Low Line Voltage L2-L3 No Alarm None
Very Low Line Voltage
No Alarm None
L2-L3
High Line Voltage L3-
No Alarm None
L1

[8]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Very High Line Voltage


No Alarm None
L3-L1
Low Line Voltage L3-L1 No Alarm None
Very Low Line Voltage
No Alarm None
L3-L1
High Phase Voltage L1 No Alarm None
Very High Phase
No Alarm None
Voltage L1
Low Phase Voltage L1 No Alarm None
Very Low Phase
No Alarm None
Voltage L1
High Phase Voltage L2 No Alarm None
Very High Phase
No Alarm None
Voltage L2
Low Phase Voltage L2 No Alarm None
Very Low Phase
No Alarm None
Voltage L2
High Phase Voltage L3 No Alarm None
Very High Phase
No Alarm None
Voltage L3
Low Phase Voltage L3 No Alarm None
Very Low Phase
No Alarm None
Voltage L3
Mains Failure Observation None

IB

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

Communication Fail Critical None

[9]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Rectifier Group 2 up to 4

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

All Rectifiers Comm


Major None
Fail
Secondary Rectifier
Critical None
Lost
Communication
Critical None
Failure
Mains Fail Observation None
Multiple Rectifiers Fail Critical None

Group 2 up to 4 Rectifier

Level Output Relay


(Critical/Major/Observation/No Alarm) (None, 1 to 8)

Alarm Name Remark Sign. date


Plant-
Plant-specific Default
Default setting specific
setting setting
setting

AC Input Fail Major None


Rectifier High
Major None
Temperature
Rectifier Fault Major None
Overvoltage Major None
Rectifier Protected Observation None
Fan Failure Major None
Current Limit No Alarm None
Communication Fail Major None
Derated Observation None
Current Share Alarm Observation None
AC Undervoltage
Major None
Protection
DC Output Shut Off Observation None

Alarm Relay
There are eight potential free relay outputs are provided on NCU. Three of the relays are default configured and mapped to alarms:
• Relay 1 — Critical alarm

• Relay 2 — Major alarm


• Relay 3 — Observation alarm

[10]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Alarm Settings (on Local Display)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

On/Off/ 3min/ 10min/


Audible Alarm Off Buzzer setting
1Hour/ 4Hours
Alarms Blocked Normal Normal/Blocked Blocking of outgoing alarms
Clear Comm Fail Y(Yes) Y/N
Reset Rect Lost Y(Yes) Y/N
Reset Bad Bat Y(Yes) Y/N
Clear Test Fail Y(Yes) Y/N
Reset Cycle Alm Y(Yes) Y/N
Reset AbCur Alm Y(Yes) Y/N
Reset Im Cur Alm Y(Yes) Y/N
ClrAllConvCommF Y(Yes) Y/N
ClrConvCommFail Y(Yes) Y/N
Clear Conv Lost Y(Yes) Y/N

Settings->Quick Settings

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

SITE SETTINGS
Site Name NCU
Site Location Europe
Site Description NCU
TIME SETTINGS
Date and Time -
SIGNAL SETTINGS
Float Charge
54.5 V 42 — 58 V
Voltage
Equalize Charge
56.4 V 42 - 58 V
Voltage
Automatic Equalize No No/Yes
Sensor for
None/ Max/ Average/
Temperature Max
Temp1/ Temp2
Compensation
Compensation
48mV/deg.C 0 — 500mV/deg.C
Coefficient
Temp
Compensation 20.0 deg.C 0 — 40 deg.C
Center
LVD1 Voltage 42.0 V 36 — 60 V

[11]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

LVD1 Time 300 min 1 — 1000 min


LVD1 Mode By Voltage By Voltage/By Time
ECO Mode Disabled Disabled/Enabled
Load Fluctuation
10 % 1 — 50 %
Range
Cycle Period 168 h 1 — 8760 h
All Rectifiers ON
120 min 0 — 255 min
Time
Outgoing Alarms
Normal Normal/Blocked
Blocked
Auto/Man State Auto Auto/Manual
Battery1 Rated
100 Ah 50 — 50000 Ah
Capacity

Settings->System

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

POWER SYSTEM
Reset Maintenance
Yes Yes
Run Time
Auto/Man State Auto Auto/Manual
To Auto Delay 0h 0 — 24 h
Maintenance
360 d 10 — 7200 d
Interval
Slave Current Limit 60 % 10 -90 %
Slave Delta Voltage 0.5 V 0.1 — 2 V
Outgoing Alarms
Normal Normal/Blocked
Blocked
Secondary System
201 201/202/203
Address
System Expansion Inactive Inactive/Primary/Secondary
Overvoltage 1 58.5 V 40 — 60 V
Overvoltage 2 58.5 V 40 — 60 V
Undervoltage 1 48.5 V 40 — 60 V
Undervoltage 2 43.5 V 40 — 60 V
PowerSplit Master
Master Controlled/Slave
Contactor Mode Controlled
High Load Level1 70 % 5 — 100 %
High Load Level2 85 % 5 — 100 %

[12]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Fuse Threshold
70 % 0 — 100 %
Value
Fuse Overload Value 80 % 0 — 100 %
AC Equipment
Nominal Phase
220 V 50 — 450 V
Voltage
Mains Failure Alarm
25 % 0 — 100 %
Threshold 1
Mains Failure Alarm
25 % 0 — 100 %
Threshold 2
LVD GROUP
HTD Point 40.0 deg.C 20 — 80 deg.C
HTD Reconnect
38.0 deg.C 20 — 80 deg.C
Point
Relay Output 1/Relay Output
2/Relay Output 3/Relay
Output 4/ Relay Output
5/Relay Output 6/Relay
Relay for LVD3 Relay Output 17
Output 7/Relay Output 8/
Relay Output 14/Relay
Output 15/Relay Output
16/Relay Output 17
EIB1
Not Used / General / Load /
Shunt 1 Set As Not Used
Battery
Not Used / General / Load /
Shunt 2 Set As Not Used
Battery
Not Used / General / Load /
Shunt 3 Set As Not Used
Battery
Shunt 1 Full Current 500.0 A 50 — 5000 A
Shunt 1 Full Voltage 75.0 mV 1 — 150 mV
Shunt 2 Full Current 500.0 A 50 — 5000 A
Shunt 2 Full Voltage 75.0 mV 1 — 150 mV
Shunt 3 Full Current 500.0 A 50 — 5000 A
Shunt 3 Full Voltage 75.0 mV 1 — 150 mV
48(Block4)/ Midpoint /
Voltage Type 48(Block4)
24(Block2)/ Disable
Number of Used
0 0—8
Blocks
Block Voltage Diff 1.00V 0—2V
LVD3 Equipment
LVD3 Control Connected Connected/Disconnected
LVD3 Enabled Disabled / Enabled

[13]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

LVD3 Mode By Voltage By Voltage / By Time


LVD3 Voltage 44.0 V 36 — 60 V
LVD3 Reconnect
50.0 V 40 — 60 V
Voltage
LVD3 Reconnect
2 min 1 — 30 min
Delay
LVD3 Time 300 min 1 — 1000 min
LVD3 Dependency None None / LVD1 / LVD2 / LVD3
High Temp
Disabled Disabled / Enabled
Disconnect 3

Settings->Battery Charge

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

CHARGE
Number of Battery
1 0 /1/2
Shunts
Very High Battery
Lower Voltage Disabled / Lower Voltage
Temp Action
Very High Temp
49.0 V 45 — 55 V
Voltage
Low Capacity Level 75 % 25 — 100 %
Float Charge
54.5 V 42 — 58 V
Voltage
Equalize Charge
56.4 V 42 — 58 V
Voltage
Battery Current
0.1 C10 0.1 — 1 C10
Limit
Over Current
0.30 C10 0.3 — 1 C10
Setpoint
Automatic Equalize No No/Yes
Equalize Start
0.060 C10 0.04 — 0.08 C10
Current
Equalize Start
80.0 % 0 — 99 %
Capacity
Equalize Stop
0.010 C10 0.002 — 0.02 C10
Current
Equalize Stop Delay
180 min 0 — 1440 min
Time
Maximum Equalize
2880 min 60 — 2880 min
Charge Time
Equalize Charge for Disabled Disabled / Enabled

[14]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Test
Cyclic Equalize No No/Yes
Cyclic Equalize
180 d 2 — 365 d
Charge Interval
Cyclic Equalize
300 min 30 — 2880 min
Duration
Temperature
Compensation 20.0 deg.C 0 — 40 deg.C
Center
Temperature
Compensation 48.0 mV/deg.C 0 — 500 mV/deg.C
Coefficient
Very High
55 deg.C 0 -100 deg.C
Compensation
High Compensation
40 deg.C 0 — 100 deg.C
Temperature
Low Compensation
0 deg.C -40 — 100 deg.C
Temperature
Disabled / Current /
Curr Limited Mode Voltage
Voltage
Battery1 Rated
100 Ah 50 — 50000 Ah
Capacity
Equalize/Float Float Charge / Equalize
Float Charge
Charge Control Charge
Reset Abnormal Batt
Yes Yes
Curr Alarm
Reset Battery
Yes Yes
Capacity
Battery Charge
Enabled Disabled / Enabled
Prohibit
DI 1 / DI 2 / DI 3 / DI 4 / DI
DI for Charge
DI3 5 / DI 6 / DI 7 / DI 8 / DI9 /
Prohibit
DI 10 / DI 11 / DI 12

Settings->ECO

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

ECO
ECO Mode Disabled Enabled/Disabled
Load Fluctuation
10 % 1 — 50 %
Range
ECO Mode Capacity
45 % 10 — 90 %
Limit

[15]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Cycle Period 168 h 1 — 8760 h


All Rectifiers ON
120 min 0 — 255 min
Time
Switch Off Delay 5 min 1 — 60 min
Reset ECO Cycle
Reset Reset
Alarm

Settings->LVD

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

LVD MAIN CABINET


LVD1 Enabled Disabled/Enabled
LVD1 Mode By Voltage By Voltage / By Time
LVD1 Voltage 43.0 V 36 — 60 V
LVD1 Reconnect
50.0 V 40 — 60 V
Voltage
LVD1 Reconnect
2 min 1 — 30 min
Delay
LVD1 Time 300 min 1 — 1000 min
LVD1 Dependency None None/LVD1/LVD2/LVD3
LVD2 Enabled Disabled/Enabled
LVD2 Mode By Voltage By Voltage / By Time
LVD2 Voltage 42.0 V 36 — 60 V
LVD2 Reconnect
50.0 V 40 — 60 V
Voltage
LVD2 Reconnect
2 min 1 — 30 min
Delay
LVD2 Time 600 min 1 — 1000 min
LVD2 Dependency None None/LVD1/LVD2/LVD3
High Temp
Disabled Disabled/Enabled
Disconnect 1
High Temp
Disabled Disabled/Enabled
Disconnect 2
Bistable / Monostable
Set to “Monostable” if EPO is
LVD Contactor Type Monostable /Monostable with
included in the system.
sampler

[16]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Settings->Temperature

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

TEMPERATURE
Ambient None/ Max/ Average/
None
Temperature Sensor Temp1/ Temp2
High Ambient
35 deg.C -40 — 100 deg.C
Temperature Level
Low Ambient
5 deg.C -40 — 100 deg.C
Temperature Level
Very High Ambient
55 deg.C -40 — 100 deg.C
Temperature
System Active from start
Battery None / Ambient / Battery
Temperature 1
System Active from start
Battery None / Ambient / Battery
Temperature 2
System Active from start
Battery None / Ambient / Battery
Temperature 3
IB2 Temperature 1 Battery None / Ambient / Battery Active from start
IB2 Temperature 2 Battery None / Ambient / Battery Active from start
EIB Temperature 1 None None / Ambient / Battery
EIB Temperature 2 None None / Ambient / Battery
Sensor for Temp None/ Max/ Average/
None
Compensation Temp1/ Temp2
Very High
Compensation 55 deg.C 0 — 100 deg.C
Temperature
High Compensation
40 deg.C 0 — 100 deg.C
Temperature
Low Compensation
0 deg.C -40 — 100 deg.C
Temperature
BTRM Temperature None/ Max/ Average/
None
Sensor Temp1/ Temp2

Settings->Rectifiers

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

RECTIFIERS
High Voltage Limit 59.0 V 56 — 59.5 V
Restart on
Overvoltage Enabled Disabled/Enabled
Enabled
Restart Time on 300 s 0 — 300 s

[17]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Overvoltage
Sequence Start
0s 0 — 10 s
Interval
WALK-In Disabled Disabled/Enabled
WALK-In Time 8s 8 — 128 s
Input Current Limit 30.0 A 1 — 50 A
Diesel Power
Disabled Disabled/Enabled
Limitation
None / DI 1 / DI 2 / DI 3 /
Diesel DI Input None DI 4 / DI 5 / DI 6 / DI 7 / DI
8
Diesel Power Limit
40.0 % 40 — 100 %
Point Set
Confirm Rect
Yes Yes
Position/Phase
Reset Rectifier IDs Yes Yes
Clear Rectifier
Yes Yes
Comm Fail Alarm
Reset Rectifier Lost
Yes Yes
Alarm

Settings->Battery Test

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

BATTERY TEST
AC Fail Test Disabled Disabled/Enabled
Constant Current
Disabled Disabled/Enabled
Test
Constant current
9999.0 A 1 — 9999 A
Test Current
Test Voltage Level 45.0 V 43 — 53.5 V
End Test Voltage 46.4 V 43.2 — 53.5 V
End Test Time 300 min 10 — 1440 min
End Test Capacity 30 % 0 — 100 %
Record Threshold 0.050 V 0.1 — 1 V
No. of Scheduled
0 0 — 12
Tests per Year
Planned Test 1 01-01 00 MM-DD HH
Planned Test 2 01-01 00 MM-DD HH
Planned Test 3 01-01 00 MM-DD HH
Planned Test 4 01-01 00 MM-DD HH

[18]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Planned Test 5 01-01 00 MM-DD HH


Planned Test 6 01-01 00 MM-DD HH
Planned Test 7 01-01 00 MM-DD HH
Planned Test 8 01-01 00 MM-DD HH
Planned Test 9 01-01 00 MM-DD HH
Planned Test 10 01-01 00 MM-DD HH
Planned Test 11 01-01 00 MM-DD HH
Planned Test 12 01-01 00 MM-DD HH
Lowest Capacity for
99 % 70 — 100 %
Battery Test
Battery Test Control Stop Stop/Start
Reset Bad Battery
Yes Yes
Alarm
Clear Battery Test
Yes Yes
Fail Alarm
Reset Discharge
Yes Yes
Curr Imbalance

Settings->Time Settings

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

TIME SYNCHRONIZATION
Specify Time / Get time
Type Specify Time automatically from the
following time servers
Date & Time
Local Zone GMT +00:00
Primary Server IP 0.0.0.0
Secondary Server IP 0.0.0.0
Interval to Adust Time 60 min

Settings->Output Relays

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

OUTOUT RELAYS
Relay IB1-DO1 Normal Non-Energized /
Non-Energized
State Energized

[19]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Relay IB1-DO2 Normal Non-Energized /


Non-Energized
State Energized
Relay IB1-DO3 Normal Non-Energized /
Non-Energized
State Energized
Relay IB1-DO4 Normal Non-Energized /
Non-Energized
State Energized
Relay IB1-DO5 Normal Non-Energized /
Non-Energized
State Energized
Relay IB1-DO6 Normal Non-Energized /
Non-Energized
State Energized
Relay IB1-DO7 Normal Non-Energized /
Non-Energized
State Energized
Relay IB1-DO8 Normal Non-Energized /
Non-Energized
State Energized
Relay IB0-DO1 Normal Non-Energized /
Non-Energized
State Energized
Relay IB0-DO2 Normal Non-Energized /
Non-Energized
State Energized
Relay IB0-DO3 Normal Non-Energized /
Non-Energized
State Energized
Relay IB0-DO4 Normal Non-Energized /
Non-Energized
State Energized
Relay EIB1-DO1 Non-Energized /
Non-Energized
Normal State Energized
Relay EIB1-DO2 Non-Energized /
Non-Energized
Normal State Energized
Relay EIB1-DO3 Non-Energized /
Non-Energized
Normal State Energized
Relay EIB1-DO4 Non-Energized /
Non-Energized
Normal State Energized
Relay EIB1-DO5 Non-Energized /
Non-Energized
Normal State Energized
Non-Energized /
Relay IB1-DO1 Non-Energized
Energized
Non-Energized /
Relay IB1-DO2 Non-Energized
Energized
Non-Energized /
Relay IB1-DO3 Non-Energized
Energized

Non-Energized /
Relay IB1-DO4 Non-Energized
Energized

Non-Energized /
Relay IB1-DO5 Non-Energized
Energized
Non-Energized /
Relay IB1-DO6 Non-Energized
Energized
Relay IB1-DO7 Non-Energized Non-Energized /

[20]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Energized
Non-Energized /
Relay IB1-DO8 Non-Energized
Energized
Non-Energized /
Relay IB0-DO1 Non-Energized
Energized
Non-Energized /
Relay IB0-DO2 Non-Energized
Energized
Non-Energized /
Relay IB0-DO3 Non-Energized
Energized
Non-Energized /
Relay IB0-DO4 Non-Energized
Energized
Non-Energized /
Relay EIB1-DO1 Non-Energized
Energized
Non-Energized /
Relay EIB1-DO2 Non-Energized
Energized
Non-Energized /
Relay EIB1-DO3 Non-Energized
Energized
Non-Energized /
Relay EIB1-DO4 Non-Energized
Energized
Non-Energized /
Relay EIB1-DO5 Non-Energized
Energized

Advanced Settings->Ethernet

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

IPV4
IP Address 192.168.0.1
Subnet Mask 255.255.255.0
Default Gateway 0.0.0.0
IPV4 DHCP
Server IP 192.168.100.100 Only possible to view
IPV6
Fe80::209:f5ff:fe
Link-Local Address
10:10b / 64
IPV6 Address
Subnet Prefix
Default Gateway
IPV6 DHCP
Server IP

[21]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Advanced Settings->Users

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

USER INFORMATION
admin Administrator
ADD OR MODIFY USER
User Name
Browser / Operator
Authority /Engineer / Administrator

E-Mail
Must be at least six
Password 640275
characters
Confirm Re-type password

Advanced Settings->SNMP

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Not Used / All Alarms /


Accepted Trap Level Not Used Major Alarms / Critical
Alarms
NMSV2 CONFIGURATION
NMS IP
Public Community
Private Community
Trap Enabled Disabled/Enabled
NMSV3 CONFIGURATION
User Name
Priv Password DES
Auth Password MD5
Trap Enabled Disabled/Enabled
Trap IP
NoAuthNoPriv /
Trap Security Level
AuthNoPriv / AuthPriv

[22]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Advanced Settings->Language

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

LOCAL LANGUAGE
Deutsch / Español /
Français / Italiano /
Pусский / Portuguese /
Türk

Advanced Settings->Alarm Report

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

SMTP
Email To
Server IP
Server Port
Email From
Authority Enabled Enabled/Disabled
SMTP Account
SMTP Password
None / All Alarms / Major and
Alarm Report Level None
Critical Alarm / Critical Alarm
SMS
Cell Phone Number 1
Cell Phone Number 2
Cell Phone Number 3
None / All Alarms / Major and
Alarm Report Level None
Critical Alarm / Critical Alarm

[23]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

Advanced Settings->Shunt

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Battery1 : Shunt Full


175 A 50 — 5000 A
Current
Battery1 : Shunt Full
25.0 mV 1 — 150 mV
Voltage
DC Distribution : No HW support
No No / Yes
Load Shunt Exists
DC Distribution:
200 A 50 — 5000 A
Shunt Full Current
DC Distribution:
25.0 mV 1 — 150 mV
Shunt Full Voltage

Settings->System settings

Plant-
Factory Setting
Selection Settings Range Remark specific Sign. Date
(Default)
Setting

Front panel
LCD Orientation 90 0/90
Key Pad Sound OFF ON/OFF

[24]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11PC3421MC (Revision B, November 28, 2016)

NetPerform™ Optimization Services


At Emerson Network Power, we understand the importance of reliable equipment — it’s critical to both your business and your
bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs.

Technical Support
Contact your sales representative. Provides quotes and bid responses, order placement and scheduling
Freedom for design, and deployment and optimization services. Download
EmersonNetworkPower.com service & maintenance reports online.
Care

EMEA Customer Support Center


ESEMEACustomerSupportCenter@ Dealing with customer problems related to:
Email
Emerson.com • Product field performance
• Product quality defects
• Product dead on arrival
Phone +421 32 7700 888 • Incomplete or incorrect deliveries
• Quality and product support

Order DC Power & OSP, Order Status


Email OPC.EES@EmersonNetworkPower.com Creates and processes orders, determines lead times and pricing,
Phone +421 32 7700 834 provides order shipping information and status.

Request DC Power Repair Service RMA


Email EMEA.HWServices@Emerson.com Creates and processes RMAs, determines lead times and pricing,
Phone +421 32 7700 733 provides repair shipping information and status.

Spare Parts

Email EMEA.HWServices@Emerson.com Pricing and PO processing of spare parts, including but not limited to
breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels,
Phone +421 32 7700 733 enclosure fans, doors & switches, etc.

DC Power Product Training

EMEA.Training@
Email Requests for quotes, order placement and scheduling.
EmersonNetworkPower.com

For More Information

To learn more about service offerings from Emerson Network Power, please contact your sales representative, or visit
EmersonNetworkPower.com/EnergySystems.

[25]
NetSure™ 5100 DC Power Systems with NetSure™ Control Unit (NCU)
Table of Set Values, 11 EN 9522 WL (Revision E, September 15, 2016)

The information contained in this document is subject to change without notice and may
not be suitable for all applications. While every precaution has been taken to ensure the
accuracy and completeness of this document, Emerson Network Power, Energy Systems,
North America, Inc. assumes no responsibility and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and materials to
be used in performing procedures not specifically described in this document.

The products covered by this instruction manual are manufactured and/or sold by Emerson
Network Power, Energy Systems, North America, Inc. This document is the property of
Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and
proprietary information owned by Emerson Network Power, Energy Systems, North
America, Inc. Any copying, use or disclosure of it without the written permission of Emerson
Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Names of companies and products are trademarks or registered trademarks of the


respective companies. Any questions regarding usage of trademark names should be
directed to the original manufacturer.

EmersonNetworkPower.com/EnergySystems (North America)


EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2016.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson™ and Consider it Solved are service marks and trademarks of Emerson Electric Co. EnergyMaster™, eSure™, NetPerform™, NetReach™,
NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.

While every precaution has been taken to ensure accuracy and completeness herein, Emerson Electric Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions.
Specifications subject to change without notice.