You are on page 1of 4

Instrument transformers

Types VOY-15 and VOY-15G


Outdoor voltage transformers

Product features
−− 2 5 kV outdoor
−− 1 50 kV BIL, 60 Hertz
−− Primary volts: 7200 - 24940
−− Electrical clearances:
VOY-15 strike: 15.25" (387 mm)
VOY-15 creep: 38.00" (965 mm)
VOY-15G strike: 11.25" (286 mm)
VOY-15G creep: 33.60" (853 mm)
−− Approximate weights:
VOY-15: 125 lbs (57 kg)
VOY-15G: 120 lbs (54 kg)

Application
The VOY-15 and VOY-15G outdoor voltage transformers are
designed for solid state relaying and electronic metering where
the burden of the device is negligible.

Construction features Junction box


The layer wound and shielded high voltage winding is designed The junction box has a 1" conduit hub on either end and a
to withstand continuous operation at ratings higher than the knock out for a 1" conduit fitting on the bottom. The box is
line-to-ground voltage level when applied on a 25 kV, 150 kV anchored to the body of the transformer with screws and can
BIL system. Refer to the Selection Guide for the rated voltage be easily detached, simplifying installation and change-out
factor (RVF). Two cores placed through and around the windings procedures.
are protectively cushioned and secured to a support frame.
Baseplate
For insulation and protection, the assembly is cast in The base is constructed of corrosion-resistant aluminum and is
hydrophobic cycloaliphatic epoxy (HCEP) using automatic secured to the encapsulated base support.
pressure gelation. The HCEP material offers superior arc track,
ozone, and ultraviolet-resistive properties while maintaining Mounting
physical strength. The hydrophobic properties of HCEP ensure The VOY-15 and VOY-15G can be mounted in upright, cantilever,
a high level of performance in wet or humid environments. or upside-down positions. Stress relief devices should be used to
support cable connections.
Terminals
Electro-tin plated copper primary line terminals accommodate Test reports
#10 to 250 MCM conductors. The H2 neutral terminal of the Test reports are stored electronically and can be e-mailed in
VOY-15G is insulated to withstand a 19 kV test level and can be various formats at the time of shipment.
disconnected from the external ground cable for power factor
measurement. Standards
These units can be tested to all applicable IEEE, CSA, or IEC
Clamp-type secondary terminals accommodate #14 through standards as requested.
#3 wire. A ground terminal is also provided for grounding the
secondary circuit at the transformer.
Dimensions

NAMEPLATE

12.88
10.00 [327]
[254]
5.00
[127]

.44
[11] 15.97
16.94 Ø.41 [10]
[430] [406]
11.75
13.50 [298]
[343] TERMINALS FOR
#10 TO #250 MCM WIRE 5.87
6.75 [149]
[172]
2.25
[57]

19.00
[483]

16.57
[421]

RATING DECALS
BOTH SIDES 1.31
[33] 1" STD PIPE TAP
BOTH SIDES
.25
GROUND LUG WITH [6]
Ø.44 [11] HOLE 1.00
[25]

Type VOY-15

NAMEPLATE

12.89
10.01 [327]
[254]
5.01
[127]

.44
[11]
16.93 Ø.41 [10]
[430]

13.51 TERMINALS FOR


[343] #10 TO #250 MCM WIRE 5.88
6.76 [149]
[172]

Ø.25-20 TAP IN
19.00 H2 TERMINAL
[483]
GROUND
16.74
[425]

RATING DECALS
BOTH SIDES 1.32
[33] 1" STD PIPE TAP
BOTH SIDES
.25
GROUND LUG WITH [6]
Ø.44 [11] HOLE 1.00
[25]

Type VOY-15G

12.00
[305]
1.25 1.25
[32] [32]
.44
[11]

NAMEPLATE
12.88
.44 X 1.69 [327]
[11 X 43]
SLOT WITH 10.00
.22 [6] RADIUS [254]
4-TOTAL

Ø.44 [11]
4-TOTAL

8.63 .44
[219] [11]

Baseplate dimensions

2 Types VOY-15 and VOY-15G voltage transformers | ABB product bulletin


Selection guide
Primary Secondary IEEE Rated voltage Thermal rating
voltage voltage Winding ratio metering accuracy factor @ 30° C Style number
Type VOY-15
12000/20780Y 120 100:1 0.3 W, X, M, & Y 1.9 1000 E-7526A62G01
14400/24940Y 120 120:1 0.3 W, X, M, & Y 1.9 1000 E-7526A62G02
18000/18000Y 120 150:1 0.3 W, X, M, & Y 1.9 1000 E-7526A62G03
20000/20000Y 120 166.7:1 0.3 W, X, M, & Y 1.9 1000 E-7526A62G04
24000/24000Y 120 200:1 0.3 W, X, M, & Y 1.9 1000 E-7526A62G05
Type VOY-15G
7620/13200GY 120 63.5:1 0.3 W, X, M, & Y 1.9 1000 E-7526A63G08
12000/20780GY 120 100:1 0.3 W, X, M, & Y 1.9 1000 E-7526A63G01
13200/22860GY 120 110:1 0.3 W, X, M, & Y 1.9 1000 E-7526A63G06
14400/24940GY 120 120:1 0.3 W, X, M, & Y 1.9 1000 E-7526A63G02
14400/24940GY 120 & 120 120 & 120:1 0.3 W, X, M, & Y 1.9 1000 E-7882A07G06
20125/34500GY 115 175:1 0.3 W, X, M, & Y 1.9 1000 E-7526A63G18

Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.
Note: 50 Hz designs available

ABB product bulletin | Types VOY-15 and VOY-15G voltage transformers 3


1VAP429701-DB June 2014 Rev. E
For more information please contact:

ABB Inc.
Medium Voltage Distribution Components
3022 NC 43 North
Pinetops, NC 27864
USA
Phone: +1 252 827 3212
Fax: +1 252 827 4286

www.abb.com/mediumvoltage

Note:
The information contained in this document is for general information purposes
only. While ABB strives to keep the information up to date and correct, it makes
no representations or warranties of any kind, express or implied, about the
completeness, accuracy, reliability, suitability, or availability with respect to the
information, products, services, or related graphics contained in the document for
any purpose. Any reliance placed on such information is therefore strictly at your
own risk. ABB reserves the right to discontinue any product or service at any time.

Copyright 2006 ABB.


All rights reserved.

You might also like