Incremental Encoder Series TRD-G

· Intrinsically safe:
EEx ia IIC T6 and
EEx ib IIC T6
· NAMUR Interface acc. to
DIN 19234
· For addittional accesso-
ries refer to
Pepperl+Fuchs catalogue
"Ex-i-Interface"
· 1- or 2 channels

Pulses per revolution:


TRD-G ... N1/N2 Plastic disc: 1, 2, 5, 10, 20, 25
TRD-G ... FN2 Metal disc: 30, 50, 60, 100

Electrical Specifications:
TRD-G ...-N1/N2 TRD-G ...-FN2
Measuring principle Inductive Photoelectric
Maximum pulse count [I/U] 25 100
Supply voltage UN acc. to DIN 19234 [V] 8 8
Internal resistance [kΩ] ca. 1 ca. 1
Internal inductance Li [µH] 30 0
Internal capacitance Ci [nF] 20 177
Maximum output frequency f [kHz] 5 1

Signal Output Configuration (for clockwise rotation):

Channel A

90 ° ± 15 % 50 % ± 25 %
Channel B

Electrical Connections
ANAMUR+ ANAMUR- BNAMUR+ BNAMUR-
5-wire cable brown blue white black
Date of issue 15.09.1998

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

26 Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-11 11 · USA (3 30) 4 25 35 55 · Singapore 8 73 16 37 · Internet http://www.pepperl-fuchs.com
Incremental Encoder Series TRD-G
Mechanical Dimensions:
90° ± 0.1
33 60 25
5

15
10 -0.015

20
-0.010
56 -0.029

1
-0

66 ± 0.1
78
72

42




M4x0.7
12 deep

22 3 3

Mechanical Specifications:
Housing Stainless steel
Flange die-cast aluminum alloy
Pulse disc Plastic or metal
Shaft Stainless steel
Bearings 2 grooved ball bearings
Weight [g] 630
Maximum rotation [min-1] 3000
Inertia [gcm2] 100
Starting torque (20 °C) [Ncm] <5
Torque (20 °C) [Ncm] <5
Maximum shaft load, axial [N] 50
Maximum shaft load, radial [N] 100
Minimal mechanical life [revolutions] 1.2 x 10 10
Environmental Conditions:
Storage temperature [°C] -25 ... 85
Working temperature [°C] -10 ... 60
Shock resistance acc. to IEC 68-2-27 100 g, 1 ms
Protection class acc. to DIN 40050 IP 65
Approval:
TRD-G ...-N1/N2 EEx ia IIC T6 PTB (D) Ex-83/2022 X
TRD-G ...-FN2 EEx ib IIC T6 PTB (D) Ex-85/2040

Key to Model Number:

T R D- G -

Pulses Signal output



N1 = A
Date of issue 01.08.1998


N2 = A + B

FN2 = A + B

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-11 11 · USA (3 30) 4 25 35 55 · Singapore 8 73 16 37 · Internet http://www.pepperl-fuchs.com 27

You might also like