You are on page 1of 17

ACI 307-98

Design and Construction of Reinforced Concrete


Chimneys (ACI 307-98)
Reported by ACI Committee 307

Victor A. Bochicchio David J. Bird


Chairman Secretary

John J. Carty Jagadish R. Joshi Randolph W. Snook


Brian Cooley Erick N. Larson John C. Sowizal
Phillip B. Davidson Robert A. Porthouse Barry J. Vickery
Shu-Jin Fang Ronald E. Purkey Chung-Yee John Wei
Milton Hartstein Scott D. Richart Edward L. Yordy
Thomas Joseph Wadi S. Rumman

This standard gives material, construction, and design requirements for CONTENTS
cast-in-place and precast reinforced concrete chimneys. It sets forth mini- Chapter 1—General, p. 307-2
mum loadings for design and contains methods for determining the con- 1.1—Scope
crete and reinforcement required as a result of these loadings. The method
of analysis applies primarily to circular chimney shells; however, a general
1.2—Drawings
procedure for analysis of noncircular shapes is included. 1.3—Regulations
This standard is written in explicit, mandatory language, and as such, is 1.4—Reference standards
intended for reference in project specifications.
Equations are provided for determining the temperature gradient through Chapter 2—Materials, p. 307-2
the concrete resulting from the difference in temperature of the gases inside 2.1—General
the chimney and the surrounding atmosphere. Methods for combining the
effects of dead and wind (or earthquake) loads with temperature both verti- 2.2—Cement
cally and circumferentially are included in the standard. These methods 2.3—Aggregates
permit the designer to establish minimum concrete and reinforcement 2.4—Reinforcement
requirements.
This standard refers extensively to “Building Code Requirements for
Structural Concrete” (ACI 318); construction requirements are generally
Chapter 3—Construction requirements, p. 307-3
in accordance with ACI 318; and notation is in accordance with ACI 104. 3.1—General
3.2—Concrete quality
3.3—Strength tests
Keywords: chimneys; compressive strength; concrete construction; 3.4—Forms
earthquake-resistant structures; formwork (construction); foundations; high
temperature; linings; loads (forces); moments; openings; precast concrete;
3.5—Reinforcement placement
quality control; reinforced concrete; reinforcing steels; specifications; 3.6—Concrete placement
static loads; strength; structural analysis; structural design; temperature; 3.7—Concrete curing
thermal gradient; wind pressure. 3.8—Construction tolerances
ACI Committee Reports, Guides, Standard Practices, and 3.9—Precast erection
Commentaries are intended for guidance in planning, de-
signing, executing, and inspecting construction. This doc- Chapter 4—Service loads and general design
criteria, p. 307-4
ument is intended for the use of individuals who are 4.1—General
competent to evaluate the significance and limitations
4.2—Wind loads
of its content and recommendations and who will ac-
4.3—Earthquake loads
cept responsibility for the application of the material it
contains. The American Concrete Institute disclaims any 4.4—Special design considerations and requirements
and all responsibility for the stated principles. The Institute 4.5—Deflection criteria
shall not be liable for any loss or damage arising there-
from.
Reference to this document shall not be made in con-
ACI 307-98 became effective November 1, 1998, and supersedes ACI 307-95.
tract documents. If items found in this document are de- Copyright ©  1998, American
American Concrete
Concrete Institute.
Institute.
sired by the Architect/Engineer to be a part of the contract All rights reserved including rights of reproduction and use in any form or by any
means, including
including the
themaking
makingofofcopies
copiesbyby
anyany
photo
photo
process,
process,
or by
or any
by electronic
electronic or
documents, they shall be restated in mandatory language mechanical device, printed, written, or oral, or recording for sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device, unless permission in
for incorporation by the Architect/Engineer. writing is obtained from the copyright proprietors.

307-1
307-2 MANUAL OF CONCRETE PRACTICE

Chapter 5—Design of chimney shell: Testing and Materials referred to in this standard are listed in
Strength method, p. 307-9 the following with their serial designations, including the
5.1—General year of adoption or revision, and are declared to be a part of
5.2—Design Loads
this standard as if fully set forth here.
5.3—Required strength
5.4—Design strength ACI 104-71 Preparation of Notation for Concrete
5.5—Nominal moment strength: Circular shells (Revised 1982)
5.6—Noncircular shapes (Reapproved 1987)
5.7—Design for circumferential bending
ACI 318-95 Building Code Requirements for Re-
inforced Concrete
Chapter 6—Thermal stresses, p. 307-12
6.1—General ASCE 7-95 Minimum Design Loads for Buildings
6.2—Vertical temperature stresses and Other Structures
6.3—Circumferential temperature stresses ASTM A 615-95c Standard Specification for Deformed
and Plain Billet Steel Bars for Concrete
Appendix A—Notation, p. 307-15 Reinforcement
ASTM A 617-96 Standard Specification for Axle-Steel
Deformed and Plain Bars for Concrete
Reinforcement
CHAPTER 1—GENERAL ASTM A 706-96 Standard Specification for Low-Alloy
1.1—Scope
This standard covers the design and construction of Steel Deformed Bars for Concrete
circular cast-in-place or precast reinforced concrete chimney Reinforcement
shells. If other shapes are used, their design shall be substan- ASTM C 33-93 Standard Specification for Concrete
tiated in accordance with the principles used here. The standard Aggregates
does not include the design of linings, but includes the ASTM C 150-95 Standard Specification for Portland
effects of linings on the concrete shell. Cement
A precast chimney shell is defined as a shell constructed ASTM C 309-95 Standard Specification for Liquid
wholly from precast reinforced concrete sections, assembled Membrane-Forming Compounds for
one atop another, to form a freestanding, self-supporting Curing Concrete
cantilever. Vertical reinforcement and grout are placed in ASTM C 595-95 Standard Specification for Blended
cores as the precast sections are erected to provide structural Hydraulic Cement
continuity and stability. The use of precast panels as stay-in-
place forms is considered cast-in-place construction. CHAPTER 2—MATERIALS
2.1—General
1.2—Drawings All materials and material tests shall conform to ACI 318,
Drawings of the chimney shall be prepared showing all except as otherwise specified here.
features of the work, including the design strength of the
concrete, the thickness of the concrete chimney shell, the 2.2—Cement
size and position of reinforcing steel, details and dimen- The same brand and type of cement shall be used through-
sions of the chimney lining, and information on chimney out the construction of the chimney. The cement used shall
accessories. conform to the requirements for Type I, Type II, Type III,
or Type V of ASTM C 150, or Type IS or Type IP of
1.3—Regulations ASTM C 595.
1.3.1 The design and construction of the chimney shall
meet the requirements of all ordinances and regulations
2.3—Aggregates
of authorities having jurisdiction, except that where such
2.3.1 Concrete aggregates shall conform to ASTM C 33.
requirements are less conservative than the comparable
requirements of this standard, this standard shall govern. 2.3.2 The maximum size of coarse aggregate shall be not
1.3.2 Consideration shall be given to the recommendations larger than 1/8 of the narrowest dimension between forms
of the Federal Aviation Administration with respect to chim- nor larger than 1/2 the minimum clear distance between
ney heights and aviation obstruction lighting and marking, reinforcing bars.
and the standards of the Underwriters Laboratories regarding
lightning protection and grounding. 2.4—Reinforcement
Reinforcement shall conform to ASTM A 615, A 617, or
1.4—Reference standards A 706. Deformed reinforcement with a specified yield stress
Standards of the American Concrete Institute, the Ameri- fy exceeding 60,000 psi shall be permitted provided the ul-
can Society of Civil Engineers, and the American Society for timate tensile strain shall equal or exceed 0.07.
REINFORCED CONCRETE CHIMNEYS 307-3

CHAPTER 3—CONSTRUCTION 3.5.2 Vertical reinforcement projecting above the forms


REQUIREMENTS for the chimney shell or cores of precast sections shall be so
3.1—General supported as to prevent the breaking of the bond with the
Concrete quality, methods of determining strength of con- freshly placed concrete.
crete, field tests, concrete proportions and consistency, mix- 3.5.3 Not more than 50 percent of bars shall be spliced
ing and placing, and formwork and details of reinforcement along any plane unless specifically permitted and approved
shall be in accordance with ACI 318, except as stated by the responsible engineer.
otherwise here.
3.5.4 The concrete cover over the circumferential rein-
forcement shall be a minimum of 2 in. for cast-in-place
3.2—Concrete quality chimneys and 11/2 in. for precast units manufactured under
The specified concrete compressive strength shall not be plant control conditions.
less than 3000 psi at 28 days.
3.6—Concrete placement
3.3—Strength tests No vertical construction joints shall be used for cast-in-
The 28-day compressive strength of the concrete shall place chimney shells. Horizontal construction joints for
be determined from a minimum of two sets of cylinders jump-form and precast construction shall be maintained at
(consisting of three specimens each) per 8-hr shift (slipform) approximately uniform spacing throughout the height of the
or per lift (jump form). For precast sections, a minimum of chimney. Concrete shall be deposited in approximately level
two sets shall be taken from each class of concrete cast each layers no greater than 16-in. deep. Particular care shall be ex-
day and from each 100 yd3 of concrete placed each day. ercised when casting concrete in thin wall sections and when
casting cores of precast sections. Grout used to seat precast
3.4—Forms sections shall have a compressive strength at least equal to
3.4.1 Forms for the chimney shell shall be made of metal, the design strength of the shell.
wood, or other suitable materials. If unlined wooden forms
are used, they shall be of selected material with tongue-and- 3.7—Concrete curing
groove joints and shall be kept continuously wet to prevent 3.7.1 Immediately after the forms have been removed all
shrinking and warping due to exposure to the elements. A necessary finishing of concrete shall be done.
nonstaining form oil shall be permitted to be used. Form oil 3.7.2 As soon as finishing has been completed, both faces
shall not be used unless it is a nonstaining type and it has of concrete shall be cured by coating with a membrane cur-
been established that specified protective coatings or paint ing compound or other method approved by the engineer.
can be applied to concrete exposed to form oil. The curing compound shall comply with ASTM C 309 and
3.4.2 Forms shall be sufficiently tight to prevent leakage shall be applied in strict accordance with the manufacturer’s
of mortar. recommendations. If coatings are to be applied to the con-
3.4.3 No construction load shall be supported upon any crete, the curing compound shall be of a type compatible
part of the structure under construction until that portion of with these coatings.
the structure has attained sufficient strength to safely support
its weight and the loads placed thereon. 3.8—Construction tolerances
3.4.4 Forms shall be removed in such manner as to ensure 3.8.1 The chimney shell shall be constructed within the
the safety of the structure. Forms shall be permitted to be tolerance limits set forth here.
removed after concrete has hardened to sufficient strength to 3.8.1.1 Vertical alignment of centerpoint—The center-
maintain its shape without damage and to safely support all point of the shell shall not vary from its vertical axis by more
loads on it, including temporary construction loads. than 0.001 times the height of the shell at the time of mea-
3.4.5 Ties between inner and outer chimney shell forms surement, or 1 in., whichever is greater. Locally, the center-
shall not be permitted. point of the shell shall not be changed by more than 1 in. per
3.4.6 Construction joints shall be properly prepared to 10 ft.
facilitate bonding. As a minimum, all laitance and loose 3.8.1.2 Diameter—The measured outside shell diameter
material shall be removed. at any section shall not vary from the specified diameter by
more than 1 in. plus 0.01 times the specified or theoretical
3.5—Reinforcement placement diameter.
3.5.1 Circumferential reinforcement shall be placed 3.8.1.3 Wall thickness—The measured wall thickness
around the exterior of, and secured to, the vertical bars. All shall not vary from the specified wall thickness by more
reinforcing bars shall be tied at intervals of not more than than –1/4 in., +1/2 in. for walls 10-in.-thick or less, or by more
2 ft. Particular attention shall be paid to placing and securing than –1/2 in., +1 in. for walls greater than 10-in.-thick. A single
the circumferential reinforcement so that it cannot bulge or wall thickness measurement is defined as the average of at
be displaced during the placing and working of the concrete least four measurements taken over a 60-deg arc.
so as to result in less than the required concrete cover over 3.8.2 Openings and embedments—Tolerances on the size
this circumferential reinforcement. and location of openings and embedments in the shell cannot
307-4 MANUAL OF CONCRETE PRACTICE

be uniformly established due to the varying degrees of accuracy 4.1.7.4 Consideration shall be given to the effects of
required depending on the nature of their use. Appropriate radiant heat of gases on any part of the foundation, including
tolerances for opening and embedment sizes and locations the foundation floor area which is exposed within the liner
shall be established for each chimney. and also concrete floors supported from the concrete shell.

3.9—Precast erection 4.2—Wind loads


3.9.1 The precast sections shall be erected in a manner and 4.2.1 General—Reinforced concrete chimneys shall be
at a rate that ensures that sufficient strength has been attained designed to resist the wind forces in both the along-wind and
in grout, core concrete, and all connecting components to across-wind directions. In addition, the hollow circular cross
safely support construction and applicable design loads. section shall be designed to resist the loads caused by the
3.9.2 Precast sections shall be keyed if necessary to transfer circumferential pressure distribution.
shear and grouted to level and seal joints. The reference design wind speed in mph, which shall be
denoted as VR , shall be the “3-sec gust” wind speed at 33 ft
over open terrain where VR = ( I )0.5V. This speed V and im-
CHAPTER 4—SERVICE LOADS
AND GENERAL DESIGN CRITERIA portance factor I shall be as specified by ASCE 7. All
4.1—General chimneys shall be classified as Category IV structures as
4.1.1 The chimney shell shall be designed for the effects defined in ASCE 7-95. Terrain effects referenced in Sec-
of gravity, temperature, wind, and earthquake in accordance tion 6.5.5 of ASCE 7-95 are omitted.
with ACI 318, except as stated otherwise here. At a height z ft above ground, the mean hourly design
4.1.2 The chimney shell shall be designed for load combi- speed V(z) in ft/sec shall be computed from Eq. (4-1)
nations in accordance with the provisions of Chapter 5,
Design of chimney shell: Strength method. z 0.154
V(z) = ( 1.47 )V R  ------ ( 0.65 ) (4-1)
4.1.3  33
4.1.3.1 The chimney shell shall not be less than 8-in.
thick when cast in place, or less than 7-in. thick when com-
The provisions with respect to wind load take account of
posed of precast sections.
dynamic action but are simplified and lead to equivalent static
4.1.3.2 The chimney shell thickness, through openings,
loads. A properly substantiated dynamic analysis may be
shall not be less than 1/24 the height of the opening.
used in place of these provisions.
The thickened shell shall extend at least 1/2 the height of
4.2.2 Along-wind load: Circular shapes—The along-wind
the opening above and below the opening. Properly designed
load, w(z) per unit length at any height z ft, shall be the sum
buttresses or other means of lateral restraint may be used in
of the mean load w (z) and the fluctuating load w ′(z).
place of this requirement; however, the buttresses shall be
ignored when calculating vertical strength. The mean load w (z) in lb/ft shall be computed from
4.1.3.3 When the internal diameter of the shell exceeds Eq. (4-2)
28 ft, the minimum thickness shall be increased 1/8 in. for
each 1-ft increase in internal diameter. w ( z ) = C dr ( z ) • d ( z ) • p ( z ) (4-2)
4.1.4 A chimney shell that supports lining loads shall com-
ply with the requirements of this standard with the lining in
where
place. The interaction of the liner with the shell shall be
considered. Cdr(z) = 0.65 for z < h – 1.5d(h) (4-3a)
4.1.5 Consideration shall be given to loadings during the
construction phase. Cdr(z) = 1.0 for z ≥ h – 1.5d(h) (4-3b)
4.1.6 If required during construction, temporary access
openings may be provided in the concrete shell. For the design p(z) = 0.0013 [V(z)]2 (4-4)
of the shell, these openings shall be designed as permanent
openings. d(z) = outside diameter at height z, ft
4.1.7
h = chimney height above ground level, ft
4.1.7.1 The maximum foundation bearing pressure shall
be established using unfactored chimney loads. d(h) = top outside diameter, ft
4.1.7.2 The foundation shall be designed by the strength The fluctuating load w′(z) shall be taken equal to
method in accordance with the procedures of ACI 318. The
foundation design shall be based on a pseudo-bearing pressure
3.0z • G w′ • M w ( b )
distribution, or pile loads, using the loading combinations w′ ( z ) = ----------------------------------------------
- (4-5)
3
given in Section 5.3.1 and 5.3.2. h
4.1.7.3 The minimum factor of safety against overturning
shall be 1.50 using unfactored loads. where Mw(b) = base bending moment due to w(z) and
REINFORCED CONCRETE CHIMNEYS 307-5

0.47 g = acceleration due to gravity = 32.2 ft/sec2


11.0 [ T 1 • V ( 33 ) ]
G w′ = 0.30 + -------------------------------------------------
- (4-6) G = peak factor = 4.0
0.86
( h + 16 ) Ss = mode shape factor = 0.57 for first mode, 0.18 for
second mode
where V(33) is determined from Eq. (4-1) for z = 33 ft.
For preliminary design and evaluation of the critical wind C L = C Lo F 1 ( B ) (4-9)
speed Vcr , as described in Section 4.2.3.1, the natural period
of an unlined chimney T 1, in seconds per cycle, may be where
approximated using Eq. (4-7). However, for final design, the 2
period shall be computed by dynamic analysis C Lo = – 0.243 + 5.648i – 18.182i (4-10)

where
h
2 ρ ck t ( h ) 0.3
T 1 = 5 ----------- -------
- --------- (4-7)
d ( b ) E ck t ( b ) i = 1 -
------------------ (4-11)
⁄ 6h
 5------------
loge -
 Z 
where c

h = chimney height above base, ft


Zc = exposure length = 0.06 ft
t(h) = thickness at top, ft
t(b) = thickness at bottom, ft
h
d(b) = mean diameter at bottom, ft F 1 ( B ) = – 0.089 + 0.337log e ----------- (4-12)
d(u)
ρck = mass density of concrete, kip-sec2/ft4
Eck = modulus of elasticity of concrete, kip/ft2
but not > 1.0 or < 0.20.
If the lining is supported in any manner by the shell, the ρa = density of air = 0.075 lbs/ft3
effect of the lining on the period shall be investigated.
Vcr = critical speed at 5/6h, ft/sec
4.2.3 Across-wind load: Circular shapes
4.2.3.1 General—Across-wind loads due to vortex
(u)
shedding in the first and second modes shall be considered in V cr = fd
------------- (4-13)
St
the design of all chimney shells when the critical wind speed
Vcr is between 0.50 and 1.30 V(zcr) as defined here. Across-
wind loads need not be considered outside this range. f = first-mode frequency, Hz
4.2.3.2 Analysis—When the outside shell diameter at St = Strouhal number
1 h
/3 is less than 1.6 times the top outside diameter, across-
wind loads shall be calculated using Eq. (4-8) which defines S t = 0.25F 1 ( A ) (4-14)
the peak base moment Ma
where
G ρ 2 2
M a = ---- S s C L ----a-V cr d ( u )h • h
g 2 F 1 ( A ) = 0.333 + 0.206log e ----------- (4-15)
d(u)
1
1⁄2  --2-
π  -------------------------------
2L - 
but not > 1.0 or < 0.60.
------------------------- • Sp  (4-8)
4 ( βs + βa ) h
 ----------- + C E  d(u) = mean outside diameter of upper third of chimney,
 d(u)  ft
h = chimney height above ground level, ft
Eq. (4-8) defines the peak base moment Ma for values of
V, where V is evaluated between 0.5 and 1.30 V(zcr). When V
0.10 [ V – V ( Z ) ]
≥ V(zcr), Ma shall be multiplied by β s = 0.01 + --------------------------------------
cr
- (4-16)
V( Z )
cr
 V – V ( z cr ) 
 ------------------------
- 
 1.0 – 0.95  (4-8a) but not < 0.01 or > 0.04.
 V ( z cr ) 
  βa = aerodynamic damping

where 2
Ka ρa d ( u )
V(zcr) = the mean design wind speed at zcr , zcr = 5/6h, β a = -------------------------
- (4-17)
ft/sec wt ( u )
307-6 MANUAL OF CONCRETE PRACTICE

Ka = Kao F1(B) (4-18) Any method using the modal characteristics of the chim-
ney shall be used to estimate the across-wind response in the
where second mode.
4.2.3.4 Grouped chimneys—When two identical chim-
neys are in close proximity, the across-wind load shall be in-
– 1.0
K ao = ----------------------------------------------------
- (4-19) creased to account for the potential increase in vortex-

( 1 + 5i ) 1 + ------------------ k – 1  induced motions. In such cases, the lift coefficient CL in
 i + 0.10 Eq. (4-9) shall be modified as follows

where a) if s/d(zcr) > 12.75, CL is unaltered


b) if 3 < s/d(zcr) < 12.75, CL shall be multiplied by:
V
k = ------- [0.26 – 0.015 s/d(zcr)] + [2 – s/12d(zcr)]
(4-20)
V cr
where
s = center-to-center spacing of chimneys, ft
wt(u) = average weight in top third of chimney, lb/ft
d(zcr) = outside diameter of chimney at critical height
Sp = spectral parameter zcr, ft
For chimneys that are not identical and for identical chim-
3
--- neys where s/d(zcr) < 3, the value of CL shall be established
2 –1 2
k 11 – k 
S p = ------------exp – ---  ---------------- (4-21) by reference to model tests or observations or test reports of
1 1
--- --- 2 B
2 4 similar arrangements.
B π 4.2.3.5 Combination of across-wind and along-wind
loads—Across-wind loads shall be combined with the
where coexisting along-wind loads. The combined design moment
B = band-width parameter Mw(z) at any section shall be taken as
B = 0.10 + 2i (4-22)
0.5
L = correlation length coefficient  2 2
L = 1.20 Mw ( z ) =  [ Ma ( z ) ] + [ Ml ( z ) ]  (4-25)
 
CE = end effect factor = 3
After solving for Ma , across-wind moments at any height where
Ma(z) may be calculated based on the corresponding mode Ma (z) = moment induced by across-wind loads
shape of the chimney column. Ml (z) = moment induced by the mean
4.2.3.3 Second mode—Across-wind response in the sec- along-wind load wl (z)
ond mode shall be considered if the critical wind speed Vcr2 where
as computed by Eq. (4-23) is between 0.50 and 1.30 V(zcr),
where V(zcr) is the mean hourly wind speed at 5/6h
2
V
5d ( u ) w l ( z ) = w ( z ) --------------- (4-26)
V cr2 = -------------- (4-23) V ( z cr )
T2

except that wl (z) shall not exceed w(z).


The period T2 in seconds per cycle for an unlined shell 4.2.4 Circumferential bending—The maximum circum-
may be estimated by Eq. (4-24). For final design, T2 shall be ferential bending moments due to the radial wind pressure
calculated by dynamic analysis distribution shall be computed by Eq. (4-27) and (4-28)

0.09 – 0.22 Mi(z) = 0.31pr(z) [r(z)]2, ft-lb/ft (tension on inside) (4-27)


h
2 ρ ck t(h) d(h)
T 2 = 0.82 ----------- -------
- --------- ----------- (4-24)
d(b) E ck
t(b) d(b) Mo(z) = 0.27pr(z) [r(z)]2, ft-lb/ft (tension on outside) (4-28)

where t(h) and t(b) are the thicknesses at the top and bottom, where
respectively, and d(h) and d(b) are the mean diameters at the r(z) = mean radius at height z, ft
top and bottom, respectively.
pr(z) = 0.0013[V(z)]2 • Gr(z), lb/ft2 (4-29)
The effect of a shell-supported liner on the period of the
second mode shall also be investigated. Gr(z) = 4.0 – 0.8log10 z, except Gr(z) = 4 for z ≤ 1.0(4-30)
REINFORCED CONCRETE CHIMNEYS 307-7

The pressure pr(z) shall be increased by 50 percent for a 4.4—Special design considerations and
distance 1.5d(h) from the top. requirements
4.4.1 Two layers of vertical and circumferential reinforce-
4.2.5 Wind loads: Noncircular shapes—The provisions of
ment are required. The total vertical reinforcement shall be
ASCE 7 shall be followed including force coefficients and
not less than 0.25 percent of the concrete area. The outside
gust response factors. Unusual cross-sectional shapes not
vertical reinforcement shall be not less than 50 percent of the
covered in ASCE 7 shall require wind tunnel testing or other
total reinforcement. Outside-face vertical bars shall not be
similar documentation to verify along- or across-wind loads,
smaller than No. 4, nor shall they be spaced more than 12 in.
or both. Similarly, horizontal bending due to wind pressure
on centers. Inside-face vertical bars shall not be smaller than
distributions shall also require wind tunnel testing or other
No. 4, nor shall they be spaced more than 24 in. on centers.
documentation from reliable sources.
4.4.2 The total circumferential reinforcement shall not be
less than 0.20 percent of the concrete area. The circumferential
4.3—Earthquake loads reinforcement in each face shall be not less than 0.1 percent of
4.3.1 General—Reinforced concrete chimneys in earth- the concrete area at the section.
quake areas shall be designed and constructed to resist the
Spacing of outer face circumferential reinforcement shall
earthquake effects in accordance with the requirements of
not exceed the wall thickness or 12 in. Spacing of circumfer-
this section. Applicable effective peak velocity-related
ential reinforcement on the inner face shall not exceed 12 in.
accelerations Av shall be in accordance with the ASCE 7
maps for the site.
Table 4.3.2(a)— Special values for maximum
Chimneys shall be designed for earthquakes by means of ground acceleration of 1.0g*
the dynamic response spectrum analysis method given in
Section 4.3.2. In place of the dynamic spectrum analysis Velocity
Frequency, Displacement spectrum, Acceleration
method, time history analysis based on accelograms repre- Hz spectrum, in. in./sec spectrum, g
sentative of the locality may be used.
The effects due to the vertical component of earthquakes f ≤ 0.25 50.7 318.6f 5.186 f 2
are generally small and can be ignored in the earthquake de-
sign of chimneys. The horizontal earthquake force shall be as- 10.39 65.26
sumed to act alone in any lateral direction. 0.25 ≤ f ≤ 2.5 ----------------
1.1436
----------------
0.1436 1.062f
0.8564
f f
4.3.2 Dynamic response spectrum analysis method—The
shears, moments, and deflections of a chimney due to earth- 25.32 159.1 2.589
quake shall be determined by using a site-specific response 2.5 ≤ f ≤ 9 -----------------
2.1158
----------------
1.1158
-----------------
0.1158
f f f
spectrum and the elastic modal method. The site-specific
response spectrum shall be based on a 90 percent probability
63.87 401.3 6.533
of not being exceeded in 50 years with 5 percent damping. If 9 ≤ f ≤ 33 -----------------
2.5369
-----------------
1.5369
-----------------
0.5369
a site-specific response spectrum is unavailable, the design f f f
response spectrum for the site shall be obtained by scaling
down the normalized 1.0g peak ground acceleration 9.768
------------- 61.37
-------------
f > 33 2 1.00
spectrum for 5 percent damping shown in Fig. 4.3.2 or f f
Table 4.3.2(a) by the scaling ratios given in Table 4.3.2(b)
for the Av of the site. * Damping ratio = 0.05.
The normalized design response spectrum given in
Fig. 4.3.2 or Table 4.3.2(a) is suitable for firm soil condi- Table 4.3.2(b)—Response spectrum scaling ratio
versus Av
tions. The response spectrum shall be modified for soft and
shallow soil conditions by any method that is properly Av, effective peak
substantiated and complies with the basic principles herein. velocity-related
accelerations Scaling ratio
The analytical model of a chimney used in the dynamic
response spectrum analysis shall be sufficiently refined to 0.05 0.04
represent variations of chimney and liner masses, variations
0.08 0.06
of stiffness, and the foundation support condition. A mini-
mum of 10 elements shall be included. The total dy- 0.15 0.11
namic response of the chimneys in terms of shear and
0.20 0.15
moment shall be computed using the SRSS over a minimum
of five normal modal responses. SRSS means taking the 0.30 0.23
square root of the sum of the squares of modal maxima. The
0.40 0.30
use of the CQC method (complete quadratic combination)
is also permitted. Linear interpolation may be used in between Av coefficients not given.
307-8 MANUAL OF CONCRETE PRACTICE

Fig. 4.3.2—Normalized horizontal elastic seismic response spectra.

The minimum size of circumferential reinforcing bars shall steel ratio times one-half the area of the opening. The extra
be No. 3. reinforcement shall be placed within a distance not exceed-
4.4.3 The circumferential reinforcement for a distance of ing twice the wall thickness unless otherwise determined by
0.2d(h) from the top of the chimney or 7.5 ft, whichever is a detailed analysis.
greater, shall be at least twice the amount required by 4.4.7 At both the top and bottom of each opening, addi-
Section 5.7. tional reinforcement shall be placed having an area at least
4.4.4 Where a segment between openings is critical as equal to one-half the established design circumferential rein-
related to the height of the openings, this segment shall be forcement interrupted by the opening, but the area As of this
investigated as a beam-column. Where more than two open- additional steel at the top and also at the bottom shall be
ings occur at the same elevation, appropriate design methods not less than that given by Eq. (4-31), unless otherwise
consistent with the cases shown by Fig. 5.5.1(a), (b), and (c) determined by a detailed analysis
shall be used.
4.4.5 In addition to the reinforcement determined by design, 0.06f c ′tl
extra reinforcement shall be provided at the sides, top, bot- A s = -------------------
- (4-31)
fy
tom, and corners of these openings as hereinafter specified.
This extra reinforcement shall be placed near the outside
surface of the chimney shell as close to the opening as proper where
spacing of bars will permit. Unless otherwise specified, all f c′ = specified compressive strength of concrete, psi
extra reinforcement shall extend past the opening a minimum
of the development length. t = concrete thickness at opening, in.
4.4.6 At each side of the opening, the additional vertical l = width of opening, in.
reinforcement shall have an area at least equal to the design fy = specified yield strength of reinforcing steel, psi
REINFORCED CONCRETE CHIMNEYS 307-9

One-half of this extra reinforcement shall extend com- 5.3—Required strength


pletely around the circumference of the chimney, and the 5.3.1 Required vertical strength Uv to resist dead load D,
other half shall extend beyond the opening a sufficient or wind load W, and normal temperature T, shall be the largest
distance to develop the bars in bond. This steel shall be of the following
placed as close to the opening as practicable, but within a
height not to exceed three times the thickness t. Uv = 1.4D (5-1a)
4.4.8 For openings larger than 2-ft wide, diagonal rein-
forcing bars with a total cross-sectional area in square inches Uv = 1.1D + 1.4T + 1.3W* (5-1b)
of not less than 1/5 of the shell thickness in inches shall be
placed at each corner of the opening. For openings 2-ft wide and
or smaller, a minimum of two No. 5 reinforcing bars shall be
placed diagonally at each corner of the opening. Uv = 0.9D + 1.4T + 1.3W* (5-1c)

4.5—Deflection criteria
*The load factor 1.3 shall be used for the along-wind loads
The maximum lateral deflection of the top of a chimney
of Section 4.2.2. For the across-wind loading combined with
under all service conditions prior to the application of load
the along-wind loading (Section 4.2.3.5), a load factor of 1.2
factors shall not exceed the limits set forth by Eq. (4-33)
shall be used.
Ymax = 0.04 h (4-33) 5.3.2 For earthquake loads or forces E, the load combina-
tions of Section 5.3.1 shall apply except that 1.1E shall be
where substituted for W.
Ymax = maximum lateral deflection, in. 5.3.3 Required circumferential strength Uc to resist wind
h = chimney height, ft load W and normal temperature load T shall be

Uc = 1.05T + 1.3W (5-1d)


CHAPTER 5—DESIGN OF CHIMNEY SHELLS:
STRENGTH METHOD
5.1—General 5.4—Design strength
5.1.1 Except as modified herein, design assumptions shall 5.4.1 Design strength of a section in terms of moment shall
be in accordance with ACI 318, Chapter 10. The chimney be taken as the nominal moment strength calculated in accor-
shell shall be designed by the strength method. dance with the requirements of this standard multiplied by a
5.1.2 The equivalent rectangular concrete stress distribu- strength reduction factor φ equal to 0.70 for vertical strength
tion described in Section 10.2.7 of ACI 318 and as modified and 0.90 for circumferential strength.
herein shall be used. For vertical strength the maximum
strain on the concrete is assumed to be 0.003 and the maxi- 5.5—Nominal moment strength: Circular shells
mum strain in the steel is assumed to be 0.07. Whichever val- 5.5.1 The following equations apply [refer to Fig. 5.5.1(a),
ue is reached first shall be taken as the limiting value. and 5.5.1(b)]
In place of the equivalent rectangular concrete compres-
sive stress distribution used in this chapter, any other rela- P u ⁄ rtf c ′ = K 1 = 1.7Qλ + 2ε m K e ω t Q 1 + 2ω t λ 1 (5-2)
tionship between concrete compressive stress and strain may
be assumed that results in prediction of the strength of hol- where
low circular sections in substantial agreement with results of
comprehensive tests. Pu = factored vertical load
5.1.3 The design and detailing of precast chimney shells r = average radius of section
shall emulate the design of cast-in-place chimney shells un- t = thickness of section
less specifically stated otherwise herein. Particular attention
should be given to the spacing and reinforcement of cast-in- λ = τ – n 1 β (radians) (5-3)
place cores and closures joining precast units to ensure that
the reqirements of this and other applicable standards are
met. sin ψ – sin µ – ( ψ – µ ) cos α-
Q 1 = ------------------------------------------------------------------ (5-4)
5.1.4 Refer to Section 5.7 for design procedures of noncir- 1 – cos α
cular shells.
λ 1 = µ + ψ – π (radians) (5-5)
5.2—Design loads
5.2.1 Dead loads and wind or earthquake forces at service
µ, τ, ψ = angles shown in Fig. 5.5.1(a).
conditions prior to the application of load factors,shall be in
accordance with Chapter 4 of this standard. Thermal effects
at service conditions shall be in accordance with Chapter 6. cos τ = 1 – β 1 ( 1 – cos α ) (5-6)
307-10 MANUAL OF CONCRETE PRACTICE

Fig. 5.5.1(a)—Stress diagram.

Fig. 5.5.1(c)—Two symmetric openings partly in


Fig. 5.5.1(b)—Two openings in compression zone. compression zone.
REINFORCED CONCRETE CHIMNEYS 307-11

1 – cos α f For α > 35 deg


cos ψ = cos α –  ---------------------  ----y-  ≥ – 1.0 (5-7)
εm Es
Q = 0.89 (5-12f)

1 – cos α f
cos µ = cos α +  ---------------------  ----y-  ≤ 1.0 (5-8) where
εm Es
Mn = nominal moment strength of section

where
2
α = one-half the central angle subtended ( ψ – µ ) ( 1 + 2 cos α )
by neutral axis + ( 1 ⁄ 2 ) ( 4 sin 2α + sin 2ψ – sin 2µ )
ß = one-half opening angle – 4 cos α ( sin α + sin ψ – sin µ )
Q 2 = ------------------------------------------------------------------------------------------- (5-13)
ß1 = 0.85 for fc′ ≤ 4000 psi ( 1 – cos α )
= 0.85 – 0.05(fc′ – 4000)/1000 ≥ 0.65,
for fc′ > 4000 psi K = sinψ + sinµ + (π – ψ – µ) cosα (5-14)
Ke = Es /fy
R = sinτ – (τ – n1β) cosα –
ωt = ρt fy /fc′
(n1/2)[sin (γ + β) – sin(γ – ß)] (5-15a)
ρt = ratio of total vertical reinforcement
to total area of concrete
γ = 1/
2 angle between center lines of two openings
n1 = number of openings entirely in compression zone and for no openings, n1 = γ = β = 0; for one
(maximum 2) opening in compression zone, n1 = 1, γ = 0;
for two openings in compression zone, n1 = 2
εm = 0.07(1 – cosα)/(1 + cosα) ≤ 0.003 (5-9)
5.5.2 Two symmetric openings partly in compression zone—
Refer to Fig. 5.5.1(c). This condition exists when γ + β > τ
Mn /Pu r = K3 = cosα + K2 /K1, .⋅. Mn = Pu rK3 (5-10) and γ – β < τ. For this case, let δ = γ – β. Then in Eq. (5-2),
λ = δ.
K2 = 1.7QR + εm Ke ω t Q2 + 2ωt K (5-11) And in Eq. (5-11)

For α ≤ 5 deg R = sinδ – δcosα (5-15b)


2
Q = ( – 0.523 + 0.181α – 0.0154α ) 5.5.3 Openings in tension zone—Openings in the ten-
(5-12a) sion zone are ignored since the tensile strength of the con-
2
+ ( 41.3 – 13.2α + 1.32α ) ( t ⁄ r ) crete is neglected and the bars cut by the openings are
replaced at the sides of the openings.
For 5 deg < α ≤ 10 deg 5.5.4 Openings in compression zone—In calculations of
the forces in the compression reinforcement only, openings
Q = ( – 0.154 + 0.01773α + 0.00249α )
2 in the compression zone are ignored since the cut bars are re-
(5-12b) placed at the sides of the openings.
2
+ ( 16.42 – 1.980α + 0.0674α ) ( t ⁄ r ) 5.5.5 Limitation—The one-half opening angle β shall not
exceed 30 deg.
For 10 deg < α ≤ 17 deg 5.5.6 Calculation procedure—Given r, t, fc′, β, γ, Pu , Mu ,
and the number of openings (where Pu and Mu are the fac-
Q = (–0.488 + 0.076α) + (9.758 – 0.640α)(t / r) (5-12c) tored vertical load and the factored moment, respectively),
use the following procedure:
For 17 deg < α ≤ 25 deg
Step 1. Assume a value for the total vertical steel ratio ρt.
2 Step 2. By trial and error, find the value of α that
Q = ( – 1.345 + 0.2018α – 0.004434α )
(5-12d) satisfies Eq. (5-2).
2
+ ( 15.83 – 1.676α + 0.03994α ) ( t ⁄ r ) Step 3. Substitute this value of α in Eq. (5-10)
and calculate Mn.
For 25 deg < α ≤ 35 deg
Step 4. If φMn < Mu, increase ρt ; if φMn > Mu, decrease ρt.
Q = (0.993 – 0.00258α) + (–3.27 + 0.0862α)(t / r) (5-12e) Step 5. Repeat Step 2 through Step 4 until φMn = Mu.
307-12 MANUAL OF CONCRETE PRACTICE

5.5.7 For load combinations with temperature effects, fc


modify fy and fc′ using Eq. (5-16a) and (5-17a). b
a
0.85fc′
Replace fy with
1.4
fy′(v) = f y – -------------- ( fSTV – γ1 f ′′STV) (5-16a)
1 + γ1

Stress
Replace fc′ with
εc
Strain
fc″(v) = fc′ – 1.40f ″CTV (5-17a) 0.002 0.003
Strain
where γ1, fSTV, f ″STV , and f ″CTV are as defined in Chapter 6. 2ε c  ε c  2
a) fc = 0.85fc′ ------------
- – -------------
0.002  0.002
5.6—Noncircular shapes fc = 0.85fc′ (1000εc - 250,000 εc2)
5.6.1 General—All applicable sections of this Standard
shall be followed, including horizontal bending and temper- fc = 850fc′ εc (1 - 250 εc)
ature effects.
( ε c – 0.002 )
5.6.2 Design assumptions—Strain in reinforcement and b) fc = 0.85fc′ 1 – 0.15 ----------------------------
-
0.001
concrete shall be assumed directly proportional to the
fc = 0.85fc′ (1 - 150εc + 0.30)
distance from the neutral axis.
For vertical strength, the maximum strain in the concrete is fc = 0.85fc′ (1.30 - 150εc)
assumed to be 0.003 and the maximum strain in the steel is
assumed to be 0.07. Whichever value is reached first shall be
taken as the limiting value. Fig. 5.6—Stress-strain curve for concrete.
Stress in reinforcement below the specified yield strength
fy for grade of reinforcement used shall be taken as Es times Replace fy with fy′(c) = fy – 1.05fSTC (5-16b)
steel strain. For strains greater than that corresponding to fy ,
stress in reinforcement shall be assumed equal to fy . Replace fc′ with fc″(c) = fc′ – 1.05f ″CTC (5-17b)
Tensile strength of concrete shall be neglected.
Relationship of concrete compressive stress and concrete where fSTC and f ″CTC are as defined in Chapter 6.
strain shall be assumed in accordance with stress-strain curve
as shown in Fig. 5.6.
5.6.3 Calculation procedure—For a given geometry and CHAPTER 6—THERMAL STRESSES
given Pu and Mu (where Pu is the factored vertical load and 6.1—General
Mu is the factored moment), use the following procedure: 6.1.1 The equations for temperature stresses given in this
Step 1. Assume a value for the total vertical steel ratio ρt. chapter are based on working stress procedures and shall be
Step 2. By trial and error, find the location of the neutral considered in the calculation of the nominal moment
axis which makes the total vertical force in the sec- strength in Chapter 5.
tion equal and opposite to Pu.
6.2—Vertical temperature stresses
Step 3. With this location of the neutral axis, calculate Mn, 6.2.1 The maximum vertical stresses in the concrete and
the nominal moment strength of the section. steel, in psi, occurring at the inside of the chimney shell due
Step 4. If φMn < Mu, increase ρt. to temperature f ″CTV and f ″STV , respectively, shall be com-
puted by Eq. (6-1a) and (6-1b)
If φMn > Mu, decrease ρt.
Step 5. Repeat Step 2 through Step 5 until φMn = Mu. f ″CTV = α te ⋅ c ⋅ Tx ⋅ Ec (6-1a)

5.6.4 Horizontal bending—Design for horizontal bending f ″STV = αte (c – 1 + γ2) ⋅ Tx nEc (6-1b)
shall comply with the requirements of Section 5.7.
where
5.7—Design for circumferential bending α te = thermal coefficient of expansion of concrete and
5.7.1 Any horizontal strip of the concrete column shall be of reinforcing steel, to be taken as 0.0000065 per
designed as a horizontal beam resisting circumferential F
bending moments as given in Section 4.2.4 and thermal ef- Ec = modulus of elasticity of concrete, psi
fects described in Section 6.3. c = –ρn(γ1 + 1) +
5.7.2 For loads combined with temperature effects, modify 2
fy and fc′ using Eq. (5-16b) and (5-17b). [ ρn ( γ 1 + 1 ) ] + 2ρn [ γ 2 + γ 1 ( 1 – γ 2 ) ] (6-2)
REINFORCED CONCRETE CHIMNEYS 307-13

ρ = ratio of total area of vertical outside face Ti = maximum specified design temperature of gas
reinforcement to total area of concrete chimney inside chimney, F
shell at section under consideration To = minimum temperature of outside air surrounding
γ1 = ratio of inside face vertical reinforcement area chimney, F
to outside face vertical reinforcement area Cc = coefficient of thermal conductivity of the concrete
γ2 = ratio of distance between inner surface of of chimney shell, Btu/ft2/in. of thickness/hr/F
chimney shell and center line of outer face difference in temperature (12 for normal weight
vertical reinforcement to total shell thickness concrete)
n = Es/Ec Cb = coefficient of thermal conductivity of chimney
uninsulated lining or insulation around steel liner,
Tx, the temperature gradient across the concrete shell, shall Btu/ft2/in. of thickness/hr/F difference in
be computed by Eq. (6-3a), (6-3b), (6-3c), (6-3d), or by a temperature
complete heat balance study for all operating conditions. Cs = coefficient of thermal conductivity of insulation
filling in space between lining and shell, Btu/ft2/in.
a) For unlined chimneys
of thickness/hr/F difference in temperature
(3 for lightweight concrete)
td ci  Ti – To  Ki = coefficient of heat transmission from gas to inner
 --------------------------------------------
-
T x = -----------
Cc dc 1 td ci d ci  (6-3a) surface of chimney lining when chimney is lined,
 ----- + ----------- + ------------- - or to inner surface of chimney shell when chimney
 K i C c d c K o d co is unlined, Btu/ft2/hr/F difference in temperature
Ko = coefficient of heat transmission from outside
surface of chimney shell to surrounding air,
b) For lined chimneys with insulation completely filling
Btu/ft2/hr/F difference in temperature
the space between the lining and shell
Kr = coefficient of heat transfer by radiation
between outside surface of lining and inside
  surface of concrete chimney shell, Btu/ft2/hr/F
td bi  Ti – To  difference in temperature
T x = -----------  ---------------------------------------------------------------------------------- (6-3b)
C c d c  1 t b d bi t s d bi td bi d bi  Ks = coefficient of heat transfer between outside surface
K----- + ------------ + ----------- + ----------- + ------------- -
i C b d b C s d s C c d c K o d co
of lining, and inside surface of shell for chimneys
with ventilated air spaces, Btu/ft2/hr/F difference
in temperature
c) For lined chimneys with unventilated air space between
dbi = inside diameter of uninsulated lining or insulation
the lining and shell
around liner, ft
db = mean diameter of uninsulated lining or insulation
  around liner, ft
td bi  Ti – To 
T x = -----------  ---------------------------------------------------------------------------------- (6-3c) ds = mean diameter of space between lining and shell, ft
C c d c  1 t b d bi d bi td bi d bi 
K----- + ------------ + ----------- + ----------- + ------------- - dci = inside diameter of concrete chimney shell, ft
i C b bd K d
r b C d
c c K o d co dc = mean diameter of concrete chimney shell, ft
dco = outside diameter of concrete chimney shell, ft
d) For lined chimneys with a ventilated air space between
the lining and shell 6.2.2 Unless complete heat balance studies are made for
the particular chimney, it is permissible to use the approxi-
  mate values given below. These constants when entered into
td bi  Ti – To  equations for temperature differential through the chimney
T x = -----------  -------------------------------------------------------------------------------------------- (6-3d) shell Tx will give values of accuracy in keeping with the
Cc dc  1 t b d bi d bi td bi d bi 
 r---------
- + ---------------- - + ---------- - + ----------- + ------------- - basic design assumptions.
q K i r q C b d b K s d s C c d c K o d co
rq = 0.5
where Cc = 12
Cs = to be obtained from the manufacturer of the
rq = ratio of heat transmission through chimney shell
materials used
to heat transmission through lining for chimneys
with ventilated air spaces Cb = to be obtained from the manufacturer of the
materials used
t = thickness of concrete shell, in.
Ki = to be determined from curves in Fig. 6.2.2
ts = thickness of air space or insulation filling the space
between the lining and shell, in. Ko = 12
tb = thickness of uninsulated lining or insulation Kr = Ti /120
around steel liner, in. Ks = Ti /150
307-14 MANUAL OF CONCRETE PRACTICE

Fig. 6.2.2—Curves for determining Ki .

The value of rq = 0.5 shall apply only where the distance f ″CTC = αte • c′ • Tx • Ec (6-5)
between the lining and the chimney shell is not less than 4 in.
throughout the entire height of the lining and air inlet and where
outlet openings are provided at the bottom and top of the c′ =
chimney shell. The area of the inlet and outlet openings in
square feet shall numerically equal two-thirds the inside – ρ′n ( γ 1 ′ + 1 )
diameter in feet of the chimney shell at the top of the lining. (6-6)
2
Local obstructions in the air space between the lining and the + [ ρ′n ( γ 1 ′ + 1 ) ] + 2ρ′n [ γ 2 ′ + γ 1 ′ ( 1 – γ 2 ′ ) ]
chimney shell shall not restrict the area of the air space at any
horizontal section to less than that specified for air inlet or
and
outlet.
6.2.3 The maximum stress in the vertical steel fSTV in psi, Tx = value determined for vertical temperature stresses
occurring at the outside face of the chimney shell due to ρ′ = ratio of cross-sectional area of circumferential
temperature, shall be computed by Eq. (6-4) outside face reinforcing steel per unit of height to
cross-sectional area of chimney shell per unit of
f STV = α te • ( γ 2 – c ) • T x • E s (6-4) height
γ1′ = ratio of inside face circumferential reinforcing
steel area to outside circumferential reinforcing
where
steel area
Es = modulus of elasticity of the reinforcement, psi
γ2′ = ratio of distance between inner surface of chimney
shell and circumferential outside face reinforcing
6.3—Circumferential temperature stresses steel to total thickness t
6.3.1 The maximum circumferential stress in psi in the
concrete due to temperature f ″CTC occurring at the inside of All other notations are the same as for vertical temperature
the chimney shell shall be computed by Eq. (6-5) stresses.
REINFORCED CONCRETE CHIMNEYS 307-15

6.3.2 The maximum stress in psi in the outside circumfer- d(u) = mean outside diameter of upper third
ential reinforcement fSTC due to temperature shall be comput- of chimney, ft (Chapter 4)
ed by Eq. (6-7) d(z) = outside diameter of chimney at height z, ft
(Chapter 4 and Commentary Chapter 4)
fSTC = αte • (γ2′ – c′) • Tx • Es (6-7)
d(zcr) = outside diameter of chimney at critical height
zcr, ft (Chapter 4)
APPENDIX A—NOTATION
As = area of reinforcing steel at top and bottom of D = dead load (Chapter 5)
opening, in.2 (Chapter 4) E = earthquake loads or forces (Chapter 5)
B = band width parameter (Chapter 4)
Ec = modulus of elasticity of concrete, psi (Chapter
c = ratio of distance from extreme compression 6)
fiber to neutral axis for vertical stresses to total
Eck = modulus of elasticity of concrete, kip/ft2
thickness t (Chapter 6)
(Chapter 4)
c′ = c for circumferential stresses (Chapter 6)
Es = modulus of elasticity of reinforcement, psi
Cb = coefficient of thermal conductivity of chimney (Chapters 5 and 6)
uninsulated lining or insulation around steel
EPV = effective peak velocity (Commentary Chapter 4)
liner, Btu/ft2/in. of thickness/hr/F difference
in temperature (Chapter 6) f = frequency, Hz (Chapter 4)
Cc = coefficient of thermal conductivity of concrete fc′ = specified compressive strength of concrete, psi
of chimney shell, Btu/ft2/in. of thickness/hr/F (Chapter 4)
difference in temperature fc″(c) = fc′ modified for temperature effects,
(12 for normal weight concrete) (Chapter 6) circumferential, psi (Chapter 5)
Cdr = drag coefficient for along-wind load fc″(v) = fc′ modified for temperature effects, vertical, psi
(Chapter 4 and Commentary Chapter 4) (Chapter 5)
CE = end effect factor (Chapter 4) f ″CTC = maximum circumferential stress in concrete due
CL = rms lift coefficient (Chapter 4) to temperature at inside of chimney shell, psi
(Chapters 5 and 6)
CLo = rms lift coefficient modified for local turbulence
(Chapter 4) f ″CTV = maximum vertical stress in concrete at inside of
chimney shell due to temperature, psi
Cs = coefficient of thermal conductivity of insulation
(Chapters 5 and 6)
filling in space between lining and shell,
Btu/ft2/in. of thickness/hr/F difference fSTC = maximum stress in outside circumferential
in temperature (3 for lightweight concrete) reinforcement due to temperature, psi
(Chapter 6) (Chapters 5 and 6)
d = diameter of chimney (Commentary Chapter 4) fSTV = maximum stress in outside vertical
reinforcement due to temperature, psi (Chapters
db = mean diameter of uninsulated lining or
5 and 6)
insulation around liner, ft (Chapter 6)
f ″STV = maximum stress in inside vertical reinforcement
dbi = inside diameter of uninsulated lining or
due to temperature, psi (Chapters 5 and 6)
insulation around liner, ft (Chapter 6)
fy = specified yield strength of reinforcing steel, psi
dc = mean diameter of concrete chimney shell, ft
(Chapters 4 and 5)
(Chapter 6)
fy′(c) = fy modified for temperature effects,
dci = inside diameter of concrete chimney shell, ft
circumferential, psi (Chapter 5)
(Chapter 6)
fy′(v) = fy modified for temperature effects, vertical, psi
dco = outside diameter of concrete chimney shell, ft
(Chapter 5)
(Chapter 6)
F1A = strouhal number parameter (Chapter 4)
ds = mean diameter of space between lining
and shell, ft (Chapter 6) F1B = lift coefficient parameter (Chapter 4)
d(b) = bottom outside diameter of chimney, ft g = acceleration due to gravity, 32.2 ft/sec2
(Chapter 4) (Chapter 4 and Commentary Chapter 4)
d(b) = mean diameter at bottom of chimney, ft G = across-wind peaking factor (Chapter 4)
(Chapter 4) Gr(z) = gust factor for radial wind pressure at height z
d(h) = top outside diameter of chimney, ft (Chapter 4 and Commentary Chapter 4)
(Chapter 4 and Commentary Chapter 4) Gw′ = gust factor for along-wind fluctuating load
d(h) = mean diameter at top of chimney, ft (Chapter 4) (Chapter 4 and Commentary Chapter 4)
307-16 MANUAL OF CONCRETE PRACTICE

h = chimney height above ground level, ft Mw(z)= combined design moment at height z
(Chapter 4 and Commentary Chapter 4) for across-wind and along-wind loads (Chapter 4)
i = local turbulence parameter (Chapter 4) n = modular ratio of elasticity Es /Ec (Chapter 6)
I = importance factor for wind design in Chapter 4 n1 = number of openings entirely in compression zone
and ASCE 7 (Chapter 5)
k = ratio of wind speed (V) to critical wind speed (Vcr ) p(z) = pressure due to mean hourly design wind speed
at height z, lb/ft2 (Chapter 4)
ka = aerodynamic damping parameter (Chapter 4)
pr(z) = radial wind pressure at height z, lb/ft2
kao = mass damping parameter of small amplitudes (Chapter 4 and Commentary Chapter 4)
(Chapter 4)
Pcr = pressure due to wind at critical speed (Chapter 4)
ks = equivalent sand-grained surface roughness factor
(Commentary Chapter 4) Pu = factored vertical load (Chapter 5)
Q = stress level correction parameter
K = parameter for nominal moment strength
(Chapter 5 and Commentary Chapter 5)
in Chapter 5 or horizontal force factor
for earthquake design in Commentary Q′, Q1,
Introduction Q2, Q3= parameters for nominal moment strength
Ke = Es /fy (Chapter 5) (Chapter 5)
Ki = coefficient of heat transmission from gas to inner r = average radius of section (Chapter 5)
surface of chimney lining when chimney is lined, rq = ratio of heat transmission through chimney shell
or to inner surface of chimney shell when chimney to heat transmission through lining for chimneys
is unlined, Btu/ft2/hr/F difference with ventilated air spaces (Chapter 6)
in temperature (Chapter 6)
r(z) = mean radius at height z, ft (Chapter 4)
Ko = coefficient of heat transmission from outside R = parameter for nominal moment strength
surface of chimney shell to surrounding air, (Chapter 5)
Btu/ft2/hr/F difference in temperature (Chapter 6)
s = center-to-center spacing of chimneys, ft
Kr = coefficient of heat transfer by radiation between (Chapter 4 and Commentary Chapter 4)
outside surface of lining and inside surface of
concrete chimney shell, Btu/ft2/hr/F difference in Sp = spectral parameter (Chapter 4)
temperature (Chapter 6) Ss = mode shape factor (Chapter 4)
Ks = coefficient of heat transfer between outside St = strouhal number (Chapter 4)
surface of lining and inside surface of shell for t = thickness of concrete shell (Chapters 5 and 6)
chimneys with ventilated air spaces,
Btu/ft2/hr/F difference in temperature (Chapter 6) tb = thickness of uninsulated lining or insulation
around steel liner, in. (Chapter 6)
K1, K2,
ts = thickness of air space or insulation filling the
K3 = parameters for nominal moment strength (Chapter space between lining and shell, in. (Chapter 6)
5)
t(b) = thickness of concrete shell at bottom, ft
l = width of opening in concrete chimney shell, in. (Chapter 4)
(Chapter 4)
t(h) = thickness of concrete shell at top, ft (Chapter 4)
L = length coefficient (Chapter 4)
T = normal temperature effect (Chapter 6)
Ma(z)= moment induced at height z by across-wind loads, Ti = maximum specified design temperature
ft-lb (Chapter 4) of gas inside chimney, F (Chapter 6)
Mi(z)= maximum circumferential bending moment due to To = minimum temperature of outside air
radial wind pressure, at height z, tension on inside, surrounding chimney, F (Chapter 6)
ft-lb/ft (Chapter 4)
Tx = temperature drop across concrete shell
Ml (z)= moment induced at height z by mean along-wind (Chapter 6)
load, ft-lb (Chapter 4)
T1 = fundamental period of vibration for unlined shell,
Mn = nominal moment strength at section (Chapter 5) sec per cycle (Chapter 4 and Commentary Chapter
Mo(z)= maximum circumferential bending moment due to 4)
radial wind pressure, at height z, tension on T2 = second mode period of vibration for unlined shell,
outside, ft-lb/ft (Chapter 4) sec per cycle (Chapter 4 and
Mu = factored moment at section (Chapter 5) Commentary Chapter 4)
Mw (b)= bending moment at base due to mean along-wind Uc = required circumferential strength (Chapter 5)
load, ft-lb (Chapter 4) Uv = required vertical strength (Chapter 5)
REINFORCED CONCRETE CHIMNEYS 307-17

V = basic wind speed, mph (ASCE 7 and Chapter 4) βa = aerodynamic damping factor (Chapter 4)
Vcr = critical wind speed for across-wind loads, βs = fraction of critical damping for across-wind
corresponding to fundamental mode ft/sec load (Chapter 4)
(Chapter 4)
βl = factor defined in Section 10.2.7.3 of ACI 318
Vcr2 = critical wind speed for across-wind loads (Chapter 6)
corresponding to second mode
Vr = V(I 0.5 ), mph (Chapter 4) γ = on chimney cross section, one-half central angle
subtended by the center lines of two openings
V = mean hourly wind speed at 5/6h varying (Chapter 5)
over a range of 0.50 and 1.30 V(zcr), ft/sec
γd = d(h)/d(b) (Chapter 4)
V(h) = mean hourly wind speed at top of chimney, ft/
sec (Chapter 4) γ1 = ratio of inside face vertical reinforcement area
V(z) = mean hourly design wind speed at height z, ft/ (Chapter 6)
sec (Chapter 4) γ2 = ratio of distance between inner surface of
V(zcr) = mean hourly design wind speed at 5/6h, ft/sec chimney shell and outside face vertical
(Chapter 4) reinforcement to total shell thickness (Chapter
V(33) = mean hourly wind speed at a height 6)
of 33 ft, ft/sec (Chapter 4) γ1′ = ratio of inside face circumferential
w(z) = total along-wind load per unit length at height z, reinforcement area to outside face
lb/ft (Chapter 4) circumferential reinforcement area (Chapter 6)
w(z) = mean along-wind load per unit length at height γ2′ = ratio of distance between inner surface of
z, lb/ft (Chapter 4 and Commentary Chapter 4) chimney shell and outside face circumferential
w′(h) = fluctuating along-wind load per unit length reinforcement to total shell thickness (Chapter
at top of chimney, lb/ft (Commentary Chapter 6)
4) δ = γ – β for two symmetric openings partly
w′(z) = fluctuating along-wind load per unit length in compression zone (Chapter 5)
at height z, lb/ft (Chapter 4)
εm = maximum concrete compressive strain
wa(h) = across-wind load per unit length at top (Chapter 5 and Commentary Chapter 5)
of chimney, lb/ft (Chapter 4)
λ = τ – n1β (Chapter 5)
wa(z) = across-wind load per unit length at height z, lb/
ft (Chapter 4) λ1 = µ + ψ – π (radians) (Chapter 5)
wt(u) = average weight per unit length for top third of µ, τ,
chimney, lb/ft (Chapter 4)
ψ = angles shown on Fig. 5.5.1(a) (Chapter 5)
w1(z) = mean along-wind load per unit length as given
by Eq. (4-27), lb/ft (Chapter 4) π = 3.1416 (Chapter 5)
W = wind load (Chapter 5) ρ = ratio of area of vertical outside face
Ymax = maximum lateral deflection of top of chimney, reinforcement to total area of concrete shell
in. (Chapter 4) (Chapter 6)
z = height above ground, ft ρ′ = ratio of area of circumferential outside face
(Chapter 4 and Commentary Chapter 4) reinforcement per unit of height to total area
zcr = height corresponding to Vcr (Chapter 4) of concrete shell per unit of height (Chapter 6)
Zc = exposure length factor (Chapter 4) ρa = specific weight of air, 0.075 lb/ft3 (Chapter 4)
α = on chimney cross section, one-half ρck = mass density of concrete, kip-sec2/ft4 (Chapter
the central angle subtended by neutral axis 4)
(Chapter 5 and Commentary Chapter 5)
ρt = ratio of total area of vertical reinforcement
αte = thermal coefficient of expansion of concrete to total area of concrete shell cross section
and of reinforcing steel, 0.0000065 per F (Chapter 5)
(Chapter 6)
φ = strength reduction factor
β = on the chimney cross section, one-half
(Chapter 5 and Commentary Chapter 5)
central angle subtended by an opening
(Chapter 5 and Commentary Chapter 5) ωt = ρt fy / fc′ (Chapter 5)

You might also like