Catalogue
11/2005 edition
MT11250
MT11344
E@gle Contents
Presentation
Major advantages 2
Principle 3
Link to process control and electrical monitoring and control systems 4
Architecture and redundancy 5
Setup in the switchboard 6
Functional description
Relays 7
Motor protection, control and monitoring SCU 7
Incomer or distribution feeder control and monitoring FCU 8
Measurement sensors 9
Fixed interface board 10
Cable auxiliary 10
Relay and frame racks 11
Stand-alone module 11
E@gleNet network 12
Gateway 12
Network node number parameter setting cable 13
E@gle System Manager 13
E@gle Software Development Kit 14
Power supplies 15
Connections 16
Inter-column wiring 17
Characteristics
Motor protection : SCU 18
Measurement : SCU 18
Programmable logical equation AND 18
Measurement : FCU 19
Relays general characteristics 19
Power supply GPS and NPS 20
Measurement sensors 20
Environment 21
Connection diagrams MIU 22
Relay connection diagrams 23
input/output connection principle 24
Dimensions 25
Training
Sales engineering course 26
Application design office course 26
Schneider Electric 1
E@gle Presentation
Major advantages
productivity improvement :
b the communication of fault diagnosis and maintenance data allows the
maintenance staff to act faster and precisely reducing down time in case of default .
b the use of relevant information related to the motor-starter , motor and driven
machine operating data reduces the maintenance cost.aintenance time and costs.
Flexibility
E@gle provides with the expected flexibility :
MT11342
Availability
MT11343
2 Schneider Electric
E@gle Presentation
Principle
Schneider Electric 3
E@gle Presentation
Link to process control and electrical
monitoring and control systems
The interface control unit (ICU: Quantum P.L.C.(2)) is used to link E@gle to
a higher-level process control or electrical monitoring and control system.
A Software Development Kit is used for easy communication integration in the
higher level system.
DD405015
4 Schneider Electric
E@gle Presentation
Architecture and redundancy
Redundancy may be implemented for one, two or all three items (total redundancy).
DD405005
Schneider Electric 5
E@gle Presentation
Setup in the switchboard
The figure below shows the main components of the E@gle system and its
interconnection to the process control and electrical monitoring control systems.
DE50203
6 Schneider Electric
E@gle Functional description
Relays
Motor protection, control and
monitoring SCU
Relays
The relay board may be configured by moving a jumper on the board:
PD405020
Starter logic
b direct on line
b star delta
b forward-reverse
b dual-speed
b automatic restart after voltage failure.
Protection
b thermal
b unbalance
b earth leakage
b process underload
b process overload
DE50204
b stall
b external protection.
Metering
b voltage
b phase current
b residual current (Earth)
b power factor
b temperature rise (thermal image)
b active, reactive and apparent power
b active, reactive and apparent energy.
Inputs - Outputs
b 8 digital inputs
b 8 digital outputs
b 6 analog inputs (I and U measurement)
b 1 analog input 4-20 mA
b 1 analog output 0-20 mA or 4-20 mA.
Warning lights
b 3 bicolor (red/green) LED’s:
v network A status
v network B status
v relay status
Schneider Electric 7
E@gle Functional description
Incomer or distribution feeder control
and monitoring FCU
Configured for incomer or distribution feeder control and monitoring the relay allows
3 types of mains configuration :
DE50205
Inputs / Outputs
b 8 digital inputs
b 8 digital outputs
b 7 analog inputs (I and U measurement )
Communication network connections
b 2 separate network connections
b Relay RJ 45 front connection linked to a PC to address the relay .
Power supplies
b 4 connections for separate power supplies (2 for the network and 2 for the relay
functions) (voir §"Alimentations", page 15).
8 Schneider Electric
E@gle Functional description
Measurement sensors
in the drawers.
Identification: MIU xy - zz
Characteristics :
b 0.3 VA CT’s : CL5P10/CL1
b indoor installation
b ring CT’s
b 0.75/4kV – 50/60Hz
b compliance with IEC 60044-1
b M1BA technical data sheet.
Type Size (W x D x H)
100/5A 2M 66 x 31 x 80
125/5A 2P 66 x 26 x 80
150/5A 2P 66 x 26 x 80
200/5A 2P 66 x 26 x 80
250/5A 2P 66 x 26 x 80
300/5A 2P 66 x 26 x 80
400/5A 2P 66 x 26 x 80
500/5A 2P 66 x 26 x 80
600/5A 2P 66 x 26 x 80
See technical characteristics in E@gle User Manual to determine the right model type.
Schneider Electric 9
E@gle Functional description
Fixed interface board
Cable auxiliary
rack.
The interface is used for :
b non-volatile storage (EEPROM) of configuration parameters and relay protection
settings
b connection to the drawer
b connection to the E@gleNet communication networks
b connection of power supplies
b Auxiliary connexions.
The main board may be replaced when the system is functioning, no protection or
parameter setting is required.
The parameter and protection setting data contained in the EEPROM are
automatically transfered to the new main board.
The fixed interface board is connected to the drawer contact s with a 30-pin
connector.
30-pin connector
The 30-pin connector and the wires connect the drawer switchgear auxiliaries and to
PD405009
the relay.
It consist of a connector in which you can insert cable fitted with specific pins.
The sub assembly inclused :
b one connector 30 pins
b one set of 30 wires length 1000 mm
b one set of 400 wires length 530 mm.
This assembling is supplied in set of 20 units .
The drop line includes the communication and power supply networks for 11 or 12
relays mounted in a same vertical rack.
LSR Board
Connects the relays of a vertical rack to the communication and general power
PD405014
supply ( GPS ) network and links each rack to the next one.
In case of redundancy there are two LSR boards.
T-port tape
Allows the connection of three accessories of E@gleNet network :Cable or
terminations or other.
10 Schneider Electric
E@gle Functional description
Relay and frame racks
Stand-alone module
switchboard.
b 11 relays capacity
b 12 relays capacity.
2 vertical racks may be mounted side by side (case of 2 half- drawers at the same
level).
the vertical racks must be mounted in the "distribution cable" compartment on the
right of the drawers.
the fisrt vertical rack is mounted on runners to provide maximum access to the
connections.
empty slots are blocked off by blind fronts.
the vertical racks is delivered empty, relays and accessories supplied separately.
Rack frame
the vertical rack is fixed into the switchboard with a device allowing the easy and
quickly mounting or taking down.( see E@gle User Manual ).
Hinge Set
The secon rack is mounted side by side the first with a set of 3 hinges to allow
PD405006
pivoting of the second rack an acces to the wiring of the fisrt rack.
Stand-alone module
A relay in a box referred to as a "stand-alone" may be used to install individual relays
PD405019
The stand alone can be fixed on the right or on the left side of the switchboard.
Schneider Electric 11
E@gle Functional description
E@gleNet network
Gateway
E@gleNet network
The relays may be connected directly to two independent E@gleNet networks.
The protocol used is the E@gleNet protocol, the main characteristics of which are as
follows:
b transmission rate: 125, 250 or 500 kbauds (1)
b maximum connection distances: 70 meters.
DD405007
Gateway
The function of this gateway is to drive the communication between 40 to 60 relays
PD405011
Reference : AB7664
ABX - DEV - EIP firmware release 1.07.01
Document rev. 1.10
12 Schneider Electric
E@gle Functional description
Network node number parameter
setting cable
E@gle System Manager
Network node number parameter setting cable
MT11286
This cable is used to connect the PC to a connector on the front panel of the relay
and to assign the relay a "node" number in the E@gleNet network.
You have to connect it to serial port of a personal computer and use Windows
Hyperterminal. ( see E@gle user manual)
Schneider Electric 13
E@gle Functional description
E@gle Software Development Kit
The development kit includes a library of basic functional units for the Concept®
programming tool.
The library also contains :
b functional units for communication management on the E@gleNet network
b functional units for communication management on the higher level network based
on the protocol or derivative, ModBus /IP or ModBus Plus.
Use of the E@gle software development kit calls for an in-depth knowledge of
the QUANTUM PLC, the Concept® software workshop and the E@gle system.
DE50227
14 Schneider Electric
E@gle Functional description
Power supplies
Power supplies
As shown in the left figure, the power supplies for the relay and communication
PD405022
DE50208
one GPS power supply and one NPS power supply for 60 network nodes
(60 relays)
DE50210
2 redundant GPS power supplies for the relays and two NPS power supplies.
Note: For more information on power supplies use see user manual.
Schneider Electric 15
E@gle Functional description
Connections
relay vertical rack wiring
DD405009
Relays are connected by one ( or two if there is redundancy ) vertical flat cable.
Relays connections to drawer and auxiliaries are realized by the 30 pins connectors.
16 Schneider Electric
E@gle Functional description
DD405011
Inter-column wiring
E@gleNet network
The E@gleNet network consists of a group of pre-fabricated connections listed
in the catalogue :
b vertical drop line 16
b stan alone module drop line 16b
b link to the E@gleNet / Ethernet gateway 16b
15
b switch board inter-column trunk line connection cable 14
v comes in different lengths
b T-port tap 12
b male and female terminations 11
v necessary to adapt the connections at each end of the network.
Schneider Electric 17
E@gle Characteristics
Motor protection : SCU
Measurement : SCU
Programmable logical equation AND
Motor protection : SCU
Unbalance Range Default Unit
Tripping time 0-100.00 10.00 s
Tripping level 0-100 40 %
Warning level 0-100 20 %
Earth leakage Range Default Unit
Tripping time 0.05-100.00 0.50 s
Tripping level 0.3-6.0 1.0 A
Warning level 0.3-6.0 0.8 A
Process underload Range Default Unit
Inhibition time 0-100.00 60.00 s
Tripping time 0-100.00 60.00 s
Tripping level 0-2.00 0.20 P/Pn
Warning level 0-2.00 0.30 P/Pn
Process overload Range Default Unit
Inhibition time 0-100.00 60.00 s
Tripping time 0-100.00 60.00 s
Tripping level 0-2.00 1.50 P/Pn
Warning level 0-2.00 1.20 P/Pn
Motor overload (thermal protection)
Class Triping time
1.05 In 1,. 1,.5 In 7.2 In (locked)
10 A > 2 hours < 2 hours y 2 min. 2 < t y 10 s
10 > 2 hours < 2 hours y 4 min. 4 < t y 10 s
20 > 2 hours < 2 hours y 7 min. 6 < t y 20 s
30 > 2 hours < 2 hours y 7 min. 9 < t y 30 s
Measurement : SCU
Values measured Range Accuracy Unit
Phase voltage 0-863 ±2 % V
Phase and neutral current 0-1200 (1) ±2.5 % A
Earth leakage current 0.3-6.0 ±2.5 % A
Power factor -1 to 1 ±5 %
Frequency 48.0-62.0 (2) ±0.1 % Hz
Active power -18000 to +18000 (1) ±4 % kW
Active energy import/export 0 to 999 999 (1) ±4 % kWh
(1) Three significant figures after the decimal point.
(2) Two significant figures after the decimal point.
18 Schneider Electric
E@gle Characteristics
Measurement : FCU
Relays general characteristics
Measurement : FCU
Values measured Range Accuracy Unit
Phase-to-neutral voltage 0-1220 V ±2 % V
Phase-to-phase voltage 0-2110 V ±2 % V
Phase and neutral current 0 to 13000 A (1) ±2.5 % A
Earth leakege current 0.3-6.0 A ±2.5 % A
Power factor -1, +1 ±5 %
Average power factor -1, +1 ±5 %
Frequency 48.0 to 62.0 Hz ±0.1 % Hz
Active power -15000 to +15000 (1) ±4 % kW
Reactive power -15000 to +15000 (1) ±4 % kVAR
Apparent power : -15000 to +15000 (1) KVA
Apparent energy 0 à 999 999 (1) ±4 % kVAh
import active energy 0 à 999 999 (1) kWAh
Export active energy 0 à 999 999 (1) kWAh
Import reactive energy 0 à 999 999 (1) kVARh
Export reactive energy 0 à 999 999 (1) kVARh
(1) Three significant figures after the decimal point.
Schneider Electric 19
E@gle Characteristics
Power supply GPS and NPS
Measurement sensors
Measurement sensors
Measurement range Characteristics Unit
MIU 21-16 and MIU 22-16 0.25 < I nom. < 1 A
MIU 21-16 and MIU 22-16 1 < I nom. < 4 A
MIU 21-16 and MIU 22-16 4 < I nom. < 16 A
MIU 21-64 and MIU 22-64 16 < I nom. < 64 A
Measurement interface unit MIU Characteristics Unit
MIU 21-16 and MIU 22-16 0.25 < I nom. < 1 A
Operating temperature 0...70 °C
Storage temperature -5...80 °C
Relative humidity 0-95 %
Dimensions 120 mm x 96 mm x 48 mm
Mounting Fixed by two screws
Voltage transformer
Rated input voltage 0-690 V
Max. input voltage 863 V
Load 0-70 Ω
Frequency 50/60 Hz
Output current 0.0005 A
Accuracy 1
Isolation voltage 3 kV / 50/60 Hz / 60 s
Current transformer
Rated primary current 1, 4, 16 and 64 A
Output current 0,016 A
Accuracy class Class 1
Frequency 50/60 Hz
Accuracy limit factor 10
Measurement range 0-10 In
Isolation 3 V 50/60 Hz / 60 s
Load 0-2.75 Ω
See page 9 for authorized additional CT’s characteristics and consult User manual
20 Schneider Electric
E@gle Characteristics
Environment
Environment
Electromagnetic compatibility (generic standard: IEC 61000-6-2)
Test Standard Severity level Test report
Radiated disturbances NF EN 50081-2 As per standard DAES 0145
Radio frequency electromagnetic field IEC 61000-4-3 12 V/m DAES 0148
immunity
Radio frequency common mode immunity IEC 61000-4-6 12 V DAES 0150
Electrical fast transient immunity IEC 61000-4-4 12 kV DAES 0149
Electrostatic discharges immunity IEC 61000-4-2 8 kV (air) DAES 0151
4 kV (contact)
1.2/50 µs surge immunity IEC 61000-4-5 2 kV (common) DAES 0144
1 kV (differential)
Direct injection
Climatic withstand
Standard Severity level Test report
Cold (operating) IEC 60068-2-1 -5 °C/16 h (Ab test) CLIM 010078
Dry heat (operating) IEC 60068-2-2 +55 °C/16 h (Bb test) CLIM 010078
Damp heat - steady state (operating) IEC 60068-2-3 40 °C/93 % HR CLIM 010078
10 days (Ca test)
(1) XCU relays
Mechanical withstand
Class 1 Standard Test report
Endurance without power Vibrations 1g 10 Hz-150 Hz 2 h 40 IEC 255-21-1 G 0110101
Jolts 10 g 16 ms 1000+ and 1000- IEC 255-21-2 G 0110101
Shocks 15 g 11 ms 3+ and 3- IEC 255-21-2 G 0110101
Operating behavior Vibrations 0.5 g 10 Hz-150 Hz 8'' IEC 255-21-1 G 0110101
Horizontal seism 1 g 3 Hz-35 Hz 7'' IEC 255-21-3 G 0110101
Vertical seism 0.5 g 3 Hz-35 Hz 7'' IEC 255-21-3 G 0110101
Shocks 5 g 11 ms 3+ 3- IEC 255-21-2 G 0110101
Schneider Electric 21
E@gle Characteristics
Connection diagrams MIU
DE50213
22 Schneider Electric
E@gle Characteristics
Relay connection diagrams
Schneider Electric 23
E@gle Characteristics
input/output connection principle
DE50215
24 Schneider Electric
E@gle Characteristics
Dimensions
MT11300
(1) 11 slots.
(2) 12 slots.
Main 11 or 12-slot vertical rack Additional 11 or 12-slot vertical rack
MT11299
Schneider Electric 25
E@gle Training
Sales engineering course
Application design office course
26 Schneider Electric
E@gle Related equipment specifications
Interface control unit (ICU)
PC
PC
Microcomputer (minimum configuration):
b Pentium III 800Mhz microprocessor or over
b Microsoft Windows 95, 98, 2000, NT04, XP
b Keyboard, mouse, VDU
b 10 MB available on hard floppy disk
b 128 MB of RAM
b CD-ROM drive and disk drive
b RS 232 link and parallel interface
b HyperTerminal software (normally supplied with Windows).
Schneider Electric 27
28 Schneider Electric
I.M.C.C. E@gle order
de / from : fax : +33 (0) 4 76 39 83 72
Société / Compagny Notes-mail : FR-PCR-Relay-Order
Pays / Country : e-mail : FR-PCR-Relay-Order@mail.schneider.fr
Tel : Date :
Fax : Projet / Project :
N° de commande / order n° :
Code client / Client code :
Delai / Delivery time :
Delivery adress :
51 247 516 FA Support relais 11 emplacements vide Empty vertical rack 11 slots
51 247 518 FA Support relais 12 emplacements vide Empty vertical rack 12 slots
51 247 522 FA Module unitaire vide précablé Empty pre-wired stand alone unit
Schneider Electric 29
AMTED302013EN © 2005 Schneider Electric - All rights reserved
http://www.schneider-electric.com
http://www.schneider-electric.co Publication : Schneider Electric