You are on page 1of 8

Engineering Technical Note

Technical Note
ETN-D-1-13

Tension Development and Lap


Splice Lengths of Reinforcing
Bars Under ACI 318-11
Introduction • Compressive strength of the concrete
Section 1.2.1 in the ACI 318 Building Code • Lateral spacing of the bars
[2011] lists 14 informational items that must be • Concrete cover
shown in contract documents, which includes • Bar position – “other” bar or “top” bar
project drawings and project specifications. Two • Type of concrete – normal weight or light-
items, 1.2.1(i) and 1.2.1(j), are concerned with weight aggregate
anchorage and splicing of reinforcement: • Presence of transverse reinforcement
(stirrups or ties)
(i) Anchorage length of reinforcement and lo- • Uncoated or epoxy-coated bars
cation and length of lap splices;
Since the 1971 Code, major changes were
(j) Type and location of mechanical and weld- made to the provisions for calculating ℓd in ACI
ed splices of reinforcement; 318-89 and -95 [1989, 1995]. No major techni-
cal revisions were introduced in the 1999 edition
This Technical Note focuses on Item “(i)”, i.e., through the current 2011 edition, i.e., the provi-
on determining tension development lengths and sions for calculating ℓd in the 2011 Code are es-
tension lap splice lengths of reinforcing bars. “An- sentially the same as those in the 1995, 1999,
chorage length” can also be called “embedment 2002, 2005, and 2008 Codes. This Technical Note
length.” A reinforcing bar must be “embedded” or discusses the provisions in ACI 318-11. Several
“anchored” a sufficient distance or length in con- examples are presented to demonstrate applica-
crete so the bar is capable of developing its de- tion of the two procedures for calculating ℓd .
sign strength. The basic premise is the “anchor-
age length” or “embedment length” must be equal 2011 ACI Building Code
to or greater than the required tension develop-
Under ACI 318-11, as with the 1995, 1999,
ment length of the bar given by the Code.
2002, 2005, and 2008 Codes, the Architect / En-
Regarding Item “(j)”, provisions in other parts
gineer has a choice of two procedures for calcu-
of the Code include performance requirements
lating ℓd , which are presented in Code Sections
for mechanical and welded splices. Further infor-
12.2.2 and 12.2.3.
mation on mechanical splices is presented in the
CRSI publication, Reinforcing Bars: Anchorages Section 12.2.2. This section provides a short-
and Splices. Commentary Section R3.5.2 of the cut approach for calculating ℓd . The expressions
Code discusses welded splices. The ACI Code for calculating ℓd are reproduced in Table 1. Use
cites “Structural Welding Code – Reinforcing of Section 12.2.2 requires selection of the appli-
Steel (AWS D1.4/D1.4M:2011)” as the standard cable expression from the four expressions given
for welding reinforcing bars. in Table 1. The applicable expression is based on:
• Bar size; expressions are given for #3
Development Length. The concept of “de- through #6 bars, and for #7 bars and larger.
velopment length” of reinforcing bars was intro- • Concrete cover and clear spacing of the bars
duced in the 318-71 ACI Building Code [1971]. are compared with the limiting values under
Provisions in Chapter 12 of the Code attempt the “Conditions” heading of Table 1.
to account for the many variables affecting the • If the structural member is a beam or a col-
tension development length, ℓd , of a straight bar. umn, another consideration is the quantity of
These variables include: stirrups or ties being provided throughout the
• Bar size distance ℓd .
• Yield strength of the bar
Table 1 – Tension Development Length – Section 12.2.2 in ACI 318-11*
Conditions Bar Sizes #3 to #6 Bar Sizes #7 to #18
Clear spacing of bars or wires being developed or
lap spliced not less than db , concrete cover not less
than db , and stirrups or ties throughout ℓd not less
than the Code minimum; or
Clear spacing of bars or wires being developed or
( )
fy ψt ψe
⎯ db
25λ√fc´
(a) ( )
fy ψt ψe
⎯ db
20λ√fc´
(b)

lap spliced not less than 2db and concrete cover not
less than db

Other cases
­­ ( )
3fy ψt ψe
⎯ db
50λ√fc´
(c) ­­ ( )
3fy ψt ψe
⎯ db
40λ√fc´
(d)

* The notation is defined in the discussion of Code Section 12.2.3 and Eq. 12-1.

Section 12.2.3. This section presents a general ap- Based on experience in fielding inquiries from design-
proach in which particular values of concrete cover and ers and in presenting seminars, there seems to be
bar spacing, as well as the amount of transverse rein- a tendency among some Code users to categorize
forcement, is taken into account. Code Eq. 12-1 in Sec- Section 12.2.3 as being applicable only to structural
tion 12.2.3 includes the effects of several of the major members with transverse reinforcement. Or that Sec-
variables: tion 12.2.3 is most advantageous for use with struc-

( ))
tural members having stirrups or ties. Presumably,
3 fy ψ ψ ψ the presence of the K tr term in the denominator of
t e s
ℓd = db (Code Eq. 12-1)
40 λ√f⎯
(
´ cb+Ktr Eq. 12-1 has an influence for such actions.
c

db
The Code is clear as to the use or applicability of
The confinement term (cb + Ktr ) /db is limited to a maxi- the K tr term. At the end of Section 12.2.3, following the
mum value of 2.5. equation for K tr , the Code states:
At r = total area of all transverse reinforcement within
“It shall be permitted to use K tr = 0 as a design sim-
the spacing s that crosses the potential plane of
plification even if transverse reinforcement is present.”
splitting through the bars being developed, in.2
cb = see discussion in text, in. Thus, for those structural members without transverse
db = nominal diameter of the bar, in. reinforcement, or if the stirrups in beams or the ties in col-
f c´ = specified compressive strength of concrete, psi umns are ignored, the part of the denominator of Eq.12-1
with the K tr term reduces to determining the value of (cb /
fy = specified yield strength of reinforcing bars, psi
db) for the particular conditions. The value “cb” is the small-
/
K t r = 40 Atr sn, in. er of: (1) one-half of the center-to-center spacing of the
n = number of bars being developed or lap spliced bars; or (2) the distance from center of the bar to the near-
along the plane of splitting est concrete surface. The definition of “cb” presents new
s = maximum center-to-center spacing of transverse concepts. Center-to-center bar spacing (actually one-half
reinforcement within ℓd , in. of the c.–c. spacing) is used rather than the clear spacing,
which is used in Section 12.2.2. Instead of concrete cover
λ = 1.0 for normal weight concrete
to the bar as used in Section 12.2.2 and prescribed in Sec-
= 0.75 for lightweight concrete
tion 7.7, cover as used in Section 12.2.3 is the distance
ψ = 1.0 for uncoated and galvanized bars from the center of the bar to the nearest concrete surface.
e


=1  .5 for epoxy-coated or zinc and epoxy dual
coated bars with concrete cover < 3db, Examples
or clear spacing < 6db
The provisions in Section 12.2.3 can be used ad-
= 
1 .2 for epoxy-coated or zinc and epoxy dual
vantageously for certain structural members and condi-
coated bars with concrete cover ≥ 3db,
tions—those applications that may be ignored if K t r is
and clear spacing ≥ 6db
regarded as being relevant only to structural members
ψ = 0.8 for bar sizes #3 to #6 with transverse reinforcement. Generally, slabs, footings
s


= 1.0 for bar sizes #7 to #18 and walls, in which the reinforcing bars have relatively
ψ = 1.3 for “top” bars large concrete cover and spacing, will be the candidates
t


= 1.0 for “other” bars where the use of Eq. 12-1 and taking K tr = 0 will often
The product of ψt ψe need not be taken greater than 1.7. result in significantly shorter values of ℓd .

2 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-11 [ETN-D-1-13]
Example No. 1 If the #6 bars are epoxy-coated, the coating factor
Given: An 8-in. thick slab is reinforced with #6 Grade ψ = 1.5 as determined in the preceding section:
e
60 uncoated bars with a center-to-center spacing of ℓd = 1.5(17.1) = 25.6 or 26 in.

10 in. Concrete cover is 2 in.; normal-weight concrete
with fc´ = 4,000 psi. Comments: The results are summarized in Table 2. Note
that ℓd for the uncoated #6 bars under Section 12.2.2
Find: ℓd for the #6 bars using Code Sections 12.2.2 and is 71% longer than the ℓd required by Section 12.2.3.
12.2.3: For epoxy-coated #6 bars, Section 12.2.2 requires an
ℓd which is 65% longer than the ℓd required by Section
Solution: 12.2.3.
(A) ℓd by Section 12.2.2
Clear spacing of the bars = 10.0 – 0.75 Table 2 – Results of Example No.1
= 9.25 in. or 12.3db Tension Development Length,
2011 Code ℓd , for #6 Bars
Concrete cover = 2.0 in. or 2.7db
Section
Uncoated Epoxy-Coated
From Table 1; under the heading “Conditions” with
clear spacing > 2db , concrete cover > db , and bar size 12.2.2 29 in. 43 in.
#6, the applicable expression is: 12.2.3 17 in. 26 in.

ℓd = (
fy ψt ψe
25 λ√fc´
⎯ db ) A substantial reduction in reinforcement could be re-
alized by using Section 12.2.3 if the 8-in. thick slab had
large plan dimensions and the #6 bars at 10 in. were
For this example, the factors ψt , ψe and λ are equal typical reinforcement. Savings in reinforcement would
to 1.0. Thus, result from shorter lap splice lengths, because tension
(60,000)(1.0)(1.0)(0.75) lap lengths are multiples of tension development length:
ℓd = ⎯
25 (1.0)√ 4,000 Class A = 1.0 ℓd and Class B = 1.3 ℓd .


= 28.5 or 29 in.* The preceding calculated values of ℓd , using Sections
12.2.2 and 12.2.3, would not be affected if the bars are
If the bars are epoxy-coated, the coating factor, ψe , lap spliced. Lap splicing would reduce the clear spacing
has to be determined from Section 12.2.4. Because the by one bar diameter, i.e., the clear spacing = 10 – 0.75 –
concrete cover value of 2.7db is less than 3db , the coat- 0.75 = 8.5 in. or 11.3dd , which is still greater than the clear
ing factor ψe = 1.5. Thus, for the #6 epoxy-coated bars: spacing criterion of 2db in Table 1 (Section 12.2.2). And
ℓd = 1.5(28.5) = 42.7 or 43 in. with regard to Section 12.2.3, one-half of the c.– c. spac-

ing of the bars = (8.5 + 0.75) / 2 = 9.25/2 = 4.6 in., which is
(B) ℓd by Section 12.2.3 still greater than the governing value of cb= 2.4 in.

Determine the value of cb which is the smaller of: If the concrete cover to the #6 bars was 3/4 in. rather
2.0 + 0.75 / 2 = 2.4 in. 3 governs: cb = 2.4 in. than 2 in., i.e., cast-in-place concrete not exposed to
or 10 / 2 = 5.0 in. weather or earth (Code Section 7.7.1-c), the calculat-
ed ℓd by Section 12.2.2 or Section 12.2.3 would be the
Determine the value of (cb + K tr )/db where K tr = 0: same. Confirming this:
(cb + K tr )/db = (2.4 + 0)/0.75 = 3.2 > 2.5, use 2.5.
Using Section 12.2.2, the applicable expression for ℓd
Calculate ℓd using Code Eq. 12-1: from Table 1 is:

( )) ( )
fy ψt ψe
3 fy ψ ψ ψ
ℓd = t e s ℓd = ⎯ db
db 25 λ√fc´
40 λ√f⎯


c
´
(cb+Ktr
db As in the previous Section 12.2.2 solution, the factors
ψ , ψ and λ are equal to 1.0. Thus,
t e
For this solution, the factor ψs = 0.8 for the #6 bars, (60,000)(1.0)(1.0)(0.75)
and the factors ψt , ψe and λ are equal to 1.0. Thus, ℓd = ⎯
25 (1.0)√ 4,000
ℓd =
3
( 60,000

40 (1.0)√ 4,000
(1.0)1.0(0.8)
2.5
0.75 ) 
= 28.5 or 29 in.

= 17.1 or 17 in.
*It is CRSI practice in technical publcations to round the development and lap splice lengths
up to the next whole number if the decimal is 0.2 or higher.

CRSI Technical Note 3


Using Section 12.2.3 and Code Eq. 12-1: (A) ℓd by Section 12.2.2
Bar spacing and concrete cover:
cb is smaller of (0.75 + 0.75/2) = 1.1 in. 3 governs
c.–c. spacing #10 bars
or 10/2 = 5.0 in.
cb = 1.1 in. = [(13.5)(12) – (2)(3) – 1.27 ] /16 = 9.7 in.
(cb+ Kt r )/db = (1.1 + 0)/0.75 = 1.5 < 2.5, use 1.5 Clear spacing = 9.7 – 1.27 = 8.4 in. or 6.6db

ℓd = ( 3 fy

ψ ψ ψ
t

(
e

40 λ√fc´ cb+Ktr
s
))
db
Concrete cover = 3.0 / 1.27 = 2.4db

The applicable expression from Table 1 is:

( )
db fy ψt ψe

ℓd = ⎯ db
20 λ√fc´
Here again, as in the previous Section 12.2.3 solu-
tion, the factor ψs = 0.8 for the #6 bars, and the factors
ψ , ψ and λ are equal to 1.0. Thus, For this example, the factors ψt , ψe and λ are equal
t e
to 1.0. Thus,
ℓd = (
3 60,000

40 (1.0)√ 4,000
(1.0)1.0(0.8)
1.5
)
0.75 ℓd =
(60,000)(1.0)(1.0)(0.75)

20 (1.0)√ 3,000
= 28.5 or 29 in.

= 69.6 or 70 in.
For 3/4 in. concrete cover, ℓd = 29 in. using Section
12.2.2 or Section 12.2.3. Maximum factored moment occurs at the face(s) of
the column. Thus, the available embedment length for
the #10 bars = (13.5)(12)/2 – (15 + 3) = 63 in. Because
The rationale for ℓd being the same value, based
the available embedment length of 63 in. is less than the
on Section 12.2.2 or 12.2.3, is: the value of (cb + Kt r )/
calculated ℓd of 70 in., the #10 straight bars are unac-
db in Eq.12-1 is equal to 1.5; then dividing the 3/40 in
ceptable according to Code Section 12.2.2. (If the rein-
Eq.12-1 by (cb + Kt r )/db and multiplying by ψs results in
forcement were changed to 22 – #9 bars, ℓd , according
((3/40)/1.5)0.8=0.04=1/25, which is the constant in the
to the Table 1 expression would be 62 in. Because ℓd of
expression from Table 1.
62 in. is less than the available embedment, the #9 bars
would be acceptable.)
Example No. 2
Given: A spread footing has plan dimensions of
(B) ℓd by Section 12.2.3
13'-6" × 13'-6" and an overall depth of 56 in. The footing
is reinforced with 17 – #10 Grade 60 uncoated bars each cb is smaller of (3.0 + 1.27/2) = 3.6 in. 3 governs
way; normal-weight concrete with fc´ = 3,000 psi; the col- or 9.7/2 = 4.9 in.
umn dimension is 2'-6" square.
(cb + K tr )/db = (3.6 + 0)/1.27 = 2.8 > 2.5, use 2.5
Find: Check the required tension development length of
Calculate ℓd using Code Eq. 12-1:
the #10 bars versus the available embedment.

Solution: ℓd = ( 3 fy
40 λ√f⎯
c
´
ψ ψ ψ

(
t e

cb+Ktr ))
s
db

db

For this example, the factors ψt , ψe , ψs and λ are


equal to 1.0. Thus,

ℓd =
3
( 60,000

40 (1.0)√ 3,000
(1.0)1.0(0.8)
2.5
1.27 )
= 41.7 or 42 in.

Because the ℓd of 42 in. is less than the available em-


bedment length of 63 in., the #10 bars are satisfactory
according to Section 12.2.3. The results are summarized
in Table 3.
Figure 1 – Spread Footing—Side Elevation

4 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-11 [ETN-D-1-13]
Table 3 – Results of Example No. 2 (A) ℓd by Section 12.2.2
2011 Code Available Properly The applicable expression from Table 1 is:
ℓd
Section Embedment Anchored?
12.2.2 70 in. 63 in. No ℓd = (
fy ψt ψe
20 λ√fc´
⎯ db )
12.2.3 42 in. 63 in. Yes
For this example, the factors ψt , ψe and λ are equal to
1.0. Thus,
Example No. 3
(60,000)(1.0)(1.0)(1.27)
ℓd =
Given: This example demonstrates the use of Sections ⎯
20 (1.0)√ 4,000
12.2.2 and 12.2.3 for calculating ℓd for beam bars with
stirrups. Grade 60, uncoated bottom bars in the interior 
= 60.2 or 61 in.
span of a continuous beam. Other data are: bw = 24 in.;
h = 30 in.; concrete cover to the stirrups is 1.5 in.; normal- (B) ℓd by Section 12.2.3
weight concrete with fc´ = 4,000 psi; #4 U-stirrups are
cb is smaller of 4.5/2 = 2.25 in. 3 governs
spaced at 13 in. on center and provided throughout ℓd .
or (1.5 + 0.5 + 1.27/2) = 2.6 in.
cb = 2.25 in.
 40At r /sn
K tr =
= 40 (2) (0.20)/13(5) = 0.25 in.
(cb + K tr )/db = (2.25 + 0.25)/1.27
= 2.0 ≤ 2.5, use 2.0

Calculate ℓd using Code Eq. 12-1:

Figure 2 – Beam Cross-Section ℓd = ( 3 fy


40 λ√f⎯
c
´
ψ ψ ψ

(
t e

cb+Ktr ))
s
db

Find: Compute the tension development length for the db



5 – #10
For this example, the factors ψt , ψe , ψs and λ are
Solution: From Figure 3, dimension X is the larger of: equal to 1.0. Thus,
2dbt = 2(0.5) = 1.0 in. 3 governs
dbl /2 = 1.27/2 = 0.64 in.
ℓd =
3
( 60,000

40 (1.0)√ 4,000
(1.0)1.0(1.0)
2.0
1.27 )
= 45.2 or 46 in.

If K tr is taken as zero:
(cb + K tr )/db = (2.25 + 0)/1.27
= 1.8 < 2.5, use 1.8
Then ℓd = (45.2)(2.0)/1.8 = 50.2 or 51 in.

This example shows a reduction in ℓd using Section


Figure 3 – Assumed Location of #10 Bar at 12.2.3 instead of Section 12.2.2 of 25% when taking the
Corner of #4 Stirrup #4 stirrups into account, and 16% when the stirrups are
neglected. The results are summarized in Table 4.
Bar spacing and concrete cover:
From side face of beam to center of outermost #10 Table 4 – Results of Example No. 3
bar, the distance is: 1.5 (cover) + 0.5 (stirrup diameter) 2011 Code Section ℓd
+ 1.0 (X) = 3.0 in.
12.2.2 61 in.
c.–c. spacing of the 5 – #10 bars 12.2.3 (with K tr = 0.25) 46 in.
= (24 – (2)(3))/4
= 4.5 in. 12.2.3 (with K tr = 0) 51 in.

Clear spacing = 4.5 – 1.27 = 3.2 in. or 2.5db


Concrete cover = 1.5 + 0.5 = 2.0 in. or 1.6db

CRSI Technical Note 5


Example No. 4 Calculate ℓd using Code Eq. 12-1:

( ))
Given: Consider the base slab of a cantilever retaining ψ ψ ψ
3 fy
wall. The concrete is normal weight with fc´ = 3,000 psi. ℓd = t e s
db
40 λ√f⎯
Assume that the #11 bars, spaced at 8 in. c. to c., are
required to resist the factored moment at Point A, i.e., the

c
´
( cb+Ktr
db
tension ℓd cannot be reduced by the ratio of As (required)
to As (provided). For this example, the bar location factor ψt = 1.3, and
the factors ψe , ψs and λ are equal to 1.0. Thus,

ℓd =
3
( 60,000

40 (1.0)√ 3,000
(1.3)1.0(1.0)
1.9
1.41 )
= 79.3 or 80 in.

Because ℓd = 80 in. does not exceed the available


embedment length of 81 in., the #11 bars can be an-
chored as straight bars. This example clearly demon-
Figure 4 – Base Slab of Retaining Wall strates the significant reduction in ℓd that is possible, un-
der certain conditions, by using Section 12.2.3 instead
Find: Using Code Sections 12.2.2 and 12.2.3, cal- of Section 12.2.2. The computed ℓd of 80 in. by Section
culate the tension ℓd for the #11 Grade 60 un- 12.2.3 is 21% shorter than the 101 in. computed by Sec-
coated bars in the top of the slab. And determine tion 12.2.2. The results are summarized in Table 5.
whether the bars can be anchored in the available
embedment length. Table 5 – Results of Example No. 4
2011 Code Available Properly
ℓd
Solution: Section Embedment Anchored?
(A) ℓd by Section 12.2.2 12.2.2 101 in. 81 in. No
Clear spacing of the bars = 8.0 – 1.41 12.2.3 80 in. 81 in. Yes
= 6.59 in. or 4.7db
Concrete cover = 2 in. or 1.4db

The applicable expression from Table 1 is: Tabular Values Based on Section 12.2.3

(
ℓd =
fy ψt ψe
20 λ√fc´
)
⎯ db
Tables 6 and 7 give values of ℓd , based on Code Sec-
tion 12.2.3 and Eq. 12-1, for walls, slabs and footings.
The values for “Lap Class A” are also the values of ℓd ,
For this example, the bar location factor ψt = 1.3 for because the required lap length for a Class A tension lap
top bars, and the factors ψe and λ are equal to 1.0. Thus splice is 1.0 ℓd .
(60,000)(1.3)(1.0)(1.41)
ℓd = ⎯ An important restriction on the use of Tables 6 and
20 (1.0)√ 3,000 7 is described in Note 3, i.e., it is assumed that the val-
ue “cb“ in the quantity, (cb + K tr )/db, in Code Eq. 12-1
= 100.4 or 101 in.

is governed by concrete cover rather than by one-half
the center-to-center spacing of the bars.
The available embedment length to the left of Point
A is 6 ft.-9 in. or 81 in. Because the required ℓd = 101 in.
The preceding examples are re-considered using
is greater than the available embedment length, the #11
Tables 6 and 7, and identified with a "T".
bars cannot be anchored as straight bars according to
Section 12.2.2.
Example No. 1T For the slab with #6 bars spaced at
10 in. c.–c., concrete cover of 2 in., normal weight con-
(B) ℓd by Section 12.2.3
crete with fc´ = 4,000 psi...
cb is smaller of (2.0 + 1.41/2) = 2.7 in. 3 governs
or 8/2 = 4.0 in. Enter Table 7; for Lap Class A and “other” bars:
cb = 2.7 in.
ℓd = 17 in. for uncoated bars
(cb + K tr )/db = (2.7 + 0)/1.41 = 1.9 < 2.5, use 1.9 ℓd = 26 in. for epoxy-coated bars

By inspection, the tabulated values are valid for this


example because one-half of the c.–c. bar spacing

6 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-11 [ETN-D-1-13]
Table 6 – Tension Development and Lap Splice Lengths for Bars in Walls, Slabs and Footings (ACI 12.2.3)
f’c = 3,000 psi
Concrete Cover = 0.75 in. Concrete Cover = 1.50 in. Concrete Cover = 2.00 in. Concrete Cover = 3.00 in.
Bar Lap
Uncoated Epoxy-Coated Uncoated Epoxy-Coated Uncoated Epoxy-Coated Uncoated Epoxy-Coated
Size Class
Top Other Top Other Top Other Top Other Top Other Top Other Top Other Top Other
A 13 12 17 15 13 12 17 15 13 12 17 15 13 12 17 15
#3
B 17 13 22 20 17 13 22 20 17 13 22 20 17 13 22 20
A 22 17 28 25 17 13 23 20 17 13 23 20 17 13 23 20
#4
B 28 22 37 32 23 17 29 26 23 17 29 26 23 17 29 26
A 32 24 41 37 22 17 28 25 22 17 28 25 22 17 28 25
#5
B 41 32 54 47 28 22 37 32 28 22 37 32 28 22 37 32
A 43 33 56 50 26 20 34 30 26 20 34 30 26 20 34 30
#6
B 56 43 73 64 34 26 44 39 34 26 44 39 34 26 44 39
A 69 53 90 80 43 33 55 49 38 29 49 43 38 29 49 43
#7
B 90 69 117 104 55 43 72 64 49 38 64 56 49 38 64 56
A 86 66 112 99 54 41 70 62 43 33 56 50 43 33 56 50
#8
B 111 86 146 128 70 54 91 80 56 43 73 64 56 43 73 64
A 104 80 136 120 66 51 86 76 53 41 70 61 48 37 63 56
#9
B 135 104 176 155 86 66 112 99 69 53 90 80 63 48 82 73
A 125 96 163 144 81 62 106 93 66 51 86 76 55 42 71 63
#10
B 162 125 212 187 105 81 137 121 85 66 111 98 71 55 93 82
A 146 113 191 169 97 74 126 111 79 61 103 91 61 47 79 70
#11
B 190 146 248 219 125 97 164 145 102 79 134 118 79 61 103 91

Table 7 – Tension Development and Lap Splice Lengths for Bars in Walls, Slabs and Footings (ACI 12.2.3)
f’c = 4,000 psi
Concrete Cover = 0.75 in. Concrete Cover = 1.50 in. Concrete Cover = 2.00 in. Concrete Cover = 3.00 in.
Bar Lap
Uncoated Epoxy-Coated Uncoated Epoxy-Coated Uncoated Epoxy-Coated Uncoated Epoxy-Coated
Size Class
Top Other Top Other Top Other Top Other Top Other Top Other Top Other Top Other
A 12 12 15 13 12 12 15 13 12 12 15 13 12 12 15 13
#3
B 15 12 19 17 15 12 19 17 15 12 19 17 15 12 19 17
A 19 15 24 22 15 12 20 17 15 12 20 17 15 12 20 17
#4
B 24 19 32 28 20 15 25 22 20 15 25 22 20 15 25 22
A 28 21 36 32 19 15 24 22 19 15 24 22 19 15 24 22
#5
B 36 28 47 41 24 19 32 28 24 19 32 28 24 19 32 28
A 37 29 49 43 22 17 29 26 22 17 29 26 22 17 29 26
#6
B 48 37 63 56 29 22 38 34 29 22 38 34 29 22 38 34
A 60 46 78 69 37 28 48 42 33 25 43 38 33 25 43 38
#7
B 78 60 102 90 48 37 62 55 42 33 55 49 42 33 55 49
A 74 57 97 86 47 36 61 54 37 29 49 43 37 29 49 43
#8
B 96 74 126 111 60 47 79 70 48 37 63 56 48 37 63 56
A 90 69 117 104 57 44 75 66 46 36 60 53 42 32 55 48
#9
B 117 90 153 135 74 57 97 86 60 46 78 69 55 42 71 63
A 108 83 141 125 70 54 92 81 57 44 74 66 47 36 62 55
#10
B 140 108 183 162 91 70 119 105 74 57 97 85 61 47 80 71
A 127 98 166 146 84 64 109 97 68 53 89 79 52 40 69 60
#11
B 165 127 215 190 109 84 142 125 89 68 116 102 68 52 89 79

Notes:
1. Tabulated values are based on a minimum yield strength of 60,000 psi and normal-weight concrete. Lengths are in inches.
2. Tension development lengths and tension lap splice lengths are calculated per ACI 318-11, Sections 12.2.3 and 12.15, respectively, with bar
sizes limited to #3 through #11.
3. When the variable “cb” from ACI 12.2.3 was calculated, it was assumed that concrete cover controlled. That is, c.– c. spacing was assumed
to be greater than 1.0 db plus twice the concrete cover.
4. Lap splice lengths (minimum of 12 inches) are multiples of tension development lengths; Class A = 1.0 ℓd and Class B = 1.3 ℓd
(ACI 318 12.15.1). When determining the lap splice length, ℓd is calculated without the 12-inch minimum of ACI 12.2.1.
5. Top bars are horizontal bars with more than 12 inches of concrete cast below the bars.
6. For epoxy-coated bars, if the c.-c. spacing is at least 7.0 db and the concrete cover is at least 3.0 db, then lengths may be multiplied by 0.918
(for top bars) or 0.8 (for other bars).
7. For Grade 75 reinforcing bars, multiply the tabulated values by 1.25. For Grade 80 reinforcing bars, multiply the tabulated values by 1.33.
8. For lightweight concrete, divide the tabulated values by 0.75.

= 5 in., which is much greater than the concrete cover Example No. 2T For the spread footing with uncoat-
plus one-half of a bar diameter, i.e., 2.4 in. ed #10 bars and concrete cover of 3 in. to the layer of
bars nearest the bottom, normal-weight concrete with
For the second part of Example 1, the concrete cover fc´ = 3,000 psi...
is only 0.75 in. From Table 7 for Lap Class A and “other”
bars: Enter Table 6; for Lap Class A and “other” bars:
ℓd = 29 in. for uncoated bars ℓd = 42 in. for uncoated bars

CRSI Technical Note 7


Example No. 3T Tables 6 and 7 are not intended for American Concrete Institute – ACI Committee 318
and consequently are not applicable for closely-spaced [1989], Building Code Requirements for Reinforced
bars in beams. For the beam in Example 3, the value of Concrete (ACI 318-89) and Commentary (ACI 318R-89),
cb would be governed by one-half of the c.–c. spacing of American Concrete Institute, Detroit, Michigan, 353 pp.
the bars, i.e., 2.25 in., rather than by the concrete cover
plus one-half of a bar diameter, i.e., 2.6 in. American Concrete Institute – ACI Committee 318
[1995], Building Code Requirements for Structural Con-
Example No. 4T For the base slab of the cantilever crete (ACI 318-95) and Commentary (ACI 318R-95),
retaining wall with uncoated #11 bars spaced at 8 in. c.– American Concrete Institute, Detroit, Michigan, 369 pp.
c., concrete cover of 2 in., normal-weight concrete with
fc´ = 3,000 psi... American Concrete Institute – ACI Committee 318
[1999], Building Code Requirements for Structural Con-
Enter Table 6; for Lap Class A and “top” bars: crete (ACI 318-99) and Commentary (ACI 318R-99),
American Concrete Institute, Farmington Hills, Michigan,
ℓd = 79 in. for uncoated bars
391 pp.

Summary American Concrete Institute – ACI Committee 318


[2002], Building Code Requirements for Structural Con-
This Technical Note discusses the provisions in Sec- crete (ACI 318-02) and Commentary (ACI 318R-02),
tions 12.2.2 and 12.2.3 of the 2011 ACI Building Code for American Concrete Institute, Farmington Hills, Michigan,
determining the tension development lengths, ℓd , of re- 443 pp.
inforcing bars. Several examples are presented to com- American Concrete Institute – ACI Committee 318
plement the discussion. The examples serve to identify [2005], Building Code Requirements for Structural Con-
some of the conditions and the structural members for crete (ACI 318-05) and Commentary (ACI 318R-05),
which the more rigorous provisions in Section 12.2.3 can American Concrete Institute, Farmington Hills, Michigan,
be used advantageously. 430 pp.
References American Concrete Institute – ACI Committee 318
[2008], Building Code Requirements for Structural Con-
American Concrete Institute – ACI Committee 318 crete (ACI 318-08) and Commentary (ACI 318R-08),
[1971], Building Code Requirements for Reinforced American Concrete Institute, Farmington Hills, Michigan,
Concrete (ACI 318-71), American Concrete Institute, 465 pp.
Detroit, Michigan, 78 pp.
American Concrete Institute – ACI Committee 318
American Concrete Institute – ACI Committee 318 [2011], Building Code Requirements for Structural Con-
[1977], Building Code Requirements for Reinforced crete (ACI 318-11) and Commentary (ACI 318R-11),
Concrete (ACI 318-77), American Concrete Institute, American Concrete Institute, Farmington Hills, Michigan,
Detroit, Michigan, 103 pp. 473 pp.
American Concrete Institute – ACI Committee 318 American Welding Society [2011], Structural Welding
[1983], Building Code Requirements for Reinforced Code – Reinforcing Steel (AWS D1.4:2011), American
Concrete (ACI 318-83), American Concrete Institute, Welding Society, Miami, Florida, 72 pp.
Detroit, Michigan, 111 pp.
Concrete Reinforcing Steel Institute [2008], Reinforc-
ing Bars: Anchorages and Splices, 5th Edition, Concrete
Reinforcing Steel Institute, Schaumburg, Illinois, 64 pp.

Contributors: Dr. David P. Gustafson, P.E., S.E. and Anthony L. Felder, P.E., with subsequent
contributions from Neal S. Anderson, P.E., S.E..

Keywords: development, lap splices

Reference: Concrete Reinforcing Steel Institute-CRSI [2013], “Tension Development and Lap
Splice Lengths of Reinforcing Bars Under ACI 318-11,” CRSI Technical Note ETN-D-1-13, Con- 933 North Plum Grove Rd.
crete Reinforcing Steel Institute, Schaumburg, Illinois, 8 pp. Schaumburg, IL 60173-4758
p. 847-517-1200 • f. 847-517-1206
Note: This publication is intended for the use of professionals competent to evaluate the signifi- www.crsi.org
cance and limitations of its contents and who will accept responsibility for the application of the
material it contains. The Concrete Reinforcing Steel Institute reports the foregoing material as Regional Offices Nationwide
a matter of information and , therefore, disclaims any and all responsibility for application of the A Service of the Concrete Reinforcing Steel Institute
stated principles or for the accuracy of the sources other than material developed by the Institute. ©2013 This publication, or any part thereof, may not be
reproduced without the expressed written consent of CRSI.

Printed in the U.S.A.

You might also like