Important Notice
This document does not replace the IOM of the MYPRO TOUCH+.
Carefully read and understand the IOM prior to using this document.
NOTE: Base panel is built and distributed by Mayekawa USA.
Table of Contents
1. Introduction ................................................................................................................................. 2
2. Connect Power to the MYPRO TOUCH+ ................................................................................... 2
3. Configuring MYPRO TOUCH+ ................................................................................................... 3
Control option selections. ............................................................................................................ 4
Verify Analog Inputs.................................................................................................................... 4
4. DIO Test Operation, Motor Bump & Slide Valve Calibration ................................................... 5
DIO Test Operation ..................................................................................................................... 5
Motor Bump Test ......................................................................................................................... 5
Slide Valve Calibration ................................................................................................................ 6
5. Set Time and Date ....................................................................................................................... 7
6. User and Password Assignment ................................................................................................. 7
7. Back Up Settings & Setpoints .................................................................................................... 8
8. Operation Mode ........................................................................................................................... 9
Contact us: ..................................................................................................................................... 10
Digital Input/Output (DI/O) .......................................................................................................... 11
Analog Input/Output (AI/O) .......................................................................................................... 12
MTP-QSG-001
Revision: July 29, 2016
1 / 12
SECTION 1: INTRODUCTION
1. Introduction
Verify the proper MYPRO TOUCH+ factory-option is specified. The MYPRO TOUCH+ is available in
the following factory-option variations:
MTP- 0 - 1- 1-120
ANALOG IN 0 to 2 Boards
all safety instructions included in this manual and other safeguards by regulatory authorities.
Hot
X1 – 120 VAC
L1 – 220 VAC
Neutral
X2 – 120 VAC
L2 – 220VAC
Ground (GND)
MTP-QSG-001
Revision: July 29, 2016
2 / 12
CAUTION
- POWER SUPPLY TERMINAL BLOCK SHOULD BE TIGHTENED BY PROPER TORQUE OF 1.4 Nm.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN DEATH, SERIOUS INJURY OR PROPERTY DAMAGE.
security login.
MTP-QSG-001
Revision: July 29, 2016
3 / 12
SECTION 3: PANEL CONFIGURATION
CAUTION
THIS MAY CAUSE SEVERE ADVERSE EFFECT TO THE OPERATION OF THE UNIT.
MTP-QSG-001
Revision: July 29, 2016
4 / 12
SECTION 4: DIO TEST MODE
Touch T (TEMPORARILY) or P
(PERMANENT) to test the output
channels.
CAUTION
DO NOT PERFORM THIS OPERATION IF THE COMPRESSOR AND MOTOR ARE DIRECTLY COUPLED. IF MOTOR
PHASES ARE INCORRECT AND THE COMPRESSOR TURNS IN THE WRONG DIRECTION, SEVERE DAMAGE MAY OCCUR
TO THE EQUIPMENT AND/OR CAUSE SERIOUS HARM OR DEATH TO THE PERSONNEL WORKING AROUND THE UNIT.
MTP-QSG-001
Revision: July 29, 2016
5 / 12
Disconnect the MSRB signal from the starter to CH12 of the digital input channels by pulling
the green terminals from the Phoenix connector.
After bump test, turn off all outputs, DISABLE the DIO test mode and exit the screen by selecting
the HOME icon. Reconnect the MSRB terminals.
Touch the [START CALIBRATOR] button to initiate the slide valve calibrator.
MTP-QSG-001
Revision: July 29, 2016
6 / 12
The slide valve will load and the
raw analog value will increase. RAW value of potentiometer
With the slide valve fully loaded must be > 3850 at 100% load.
The compressor will fully unload. When the STATUS: FINISHED appears, DISABLE the slide valve
calibration mode and return to the home screen.
MTP-QSG-001
Revision: July 29, 2016
7 / 12
Create user name, password and select the user group Level-(1 or 2) to add new user.
Touch the [CONFIG] icon from MENU 2. When prompted, select YES to continue to the SYSTEM
CONFIGURATION mode. Touch the CONFIG & SETTINGS IMPORT/EXPORT button.
Option/Setpoint Group
SystemDetails: Configuration and options.
AlarmLimits: Alarm and failure limits.
Control_Cut_In_Setpoints: Capacity control
and other setpoints.
After prompted Upload Completed, touch the [DUMP MEMORY TO USB] button to save the data to
the USB thumb drive.
Touch [Eject USB] button to remove the USB memory from the panel.
MTP-QSG-001
Revision: July 29, 2016
8 / 12
SECTION 8: SET OPERATION MODE
8. Operation Mode
Select the [CONTROLS] icon from the MENU.
Four setpoints can be programed. Each setpoint is activated by touching the setpoint title. The
active setpoint is designated with orange text.
MTP-QSG-001
Revision: July 29, 2016
9 / 12
Verify Operation – Check Sheet
Panel No.
Customer
Location
Program Version
System configuration.
Alarm/failure limits.
Contact us:
MAYEKAWA USA, INC.
http://www.mayekawausa.com
http://www.mayekawa.ca
MTP-QSG-001
Revision: July 29, 2016
10 / 12