ABB FOX Switch (AFS) Family for utility applications For ABB internal use only!

AFS670 / AFS675 Overview

A F S 6 7 5 - E R G T T T S U D A E E E E E E N Z Z X 0 5 . 0 1
Basic Options Port Options Temperature Options Future Option
– 670: FE Version – T: 2 x Ports 10/100BaseT – N: Temperature range 0°C – 60°C – X: Default
– 675: GbE Version – D: 2 x Ports FE SC, MM (8 dB) – P: Temperature range -40°C – 85°C
– 677: 16 x Ports GbE Version – F: 2 x Ports FE SC, SM (16 dB) – Z: Temperature range -40°C – 85°C incl. Conformal coating
– I: 2 x Ports FE SC, SM, Long haul (7-29 dB)
Power over Ethernet Option (PoE) – K: 2 x Ports FE SC, SM, extra Long haul (14-47 dB)
– A: 2 x Ports FE ST, MM (8 dB) Power Supply Options Firmware Option
– P: PoE (Slot 1 & 2 need to be of „T“ Type; PS need to be of „H / Z“ type) – B: 2 x Ports FE ST, SM (16 dB) – L: Low voltage PS (9,6–60VDC), spring clamps – Firmware release
– E: No PoE – S: 2 x SFP cages – H: High Voltage PS (77–320VDC, 90–265VAC), spring clamps
– U: 2 x Ports FE MTRJ, MM (8 dB) – Y: Low Voltage PS (9,6–60VDC), connector
Mounting Option – V: 2 x Ports FL ST, MM (9.5 dB) – Z: High Voltage PS (77–320VDC, 90–265VAC), connector
– R: Ports on rear side – M: 2 x Ports FE M12 connector – E: No redundant PS
– E: Ports on front side – E: Slot empty

Gigabit Ethernet (GbE) Option


– CP: 2 x GbE Combo Ports
– GP: 4 x GbE SFP cages
– GT: 4 x 10/100/1000 BaseT Ports
– GS: 2 x GbE SFP cages & 2 10/100/1000 BaseT Ports
– EE: No GbE Ports (AFS670/677)

© ABB Switzerland Ltd, January 2010. The right to modifications or deviations due to technical progress is reserved.
Management Ports Electrical Port Options Optical Port Options
10/100 BaseT SC connector SFP cage

M12 connector ST connector MTRJ connector

Ports on front side Ports on rear side

– USB Port for CRA (Configuration Recovery Adapter)


– V.24 Port for Management
– 2 x Alarm Switchover Contacts (230VAC, 2A)

1KHA - 001 138 - SEN - 01.10 - Printed in Switzerland


Available SFPs Utility grade Switch Applicable Standards Protection Features
Normal Temperature Range 0°C – 60°C IEC61850 approved IEEE802.1d MAC Bridges IEEE802.1w Rapid Spanning Tree Protocol (RSTP)
FAST SFP-MM LC: FE, MM, 1310nm, 0-8dB IEEE1613 approved IEEE802.1D/p Port Priority IEC62439 Media Redundancy Protocol (MRP)
FAST SFP-SM LC: FE, SM, 1310nm, 0-13dB IEEE802.1D Switching, GARP, GMRP, Spanning Tree E-MRP Enhanced MRP
FAST SFP-LH LC: FE, SM, 1550nm, 10-29dB EMC/ EMI (Supported via 802.1S implementation)
FAST SFP-SM+ LC: FE, SM, 1310nm, 10-29dB EN61000-4-2 (ESD): 8kV contact discharge,15kV air discharge IEEE802.1Q-1998 Virtual Bridged Local Area Networks E-MRP Performance:
EN61000-4-3: 35Vpp/m (80–2700 MHz); 1kHz, 80% AM (VLAN Tagging, Port Based VLANs, GVRP) Ring with < 10 Devices: Switch over time < 10ms
SFP-SX LC: GbE, MM, 850nm, 0-7.5dB EN61000-4-4 (Burst): 4kV power line, 4kV signal- und data line IEEE802.1x Port Authentication Ring with < 100 Devices: Switch over time < 40ms
SFP-LX LC: GbE, MM, 1310nm, 0-11dB EN61000-4-5 (Surge): power line: 2kV (line/earth),1kV (line/ line) IEEE802.1AB Topology Discovery (LLDP)
SFP-LH LC: GbE, SM, 1550nm, 6-22dB EN61000-4-12: 2,5kV line/earth,1kV line/line (1MHz) IEEE802.3 – 2002 Ethernet Redundant coupling of several E-MRP rings is supported. Network topo-
SFP-LH+ LC: GbE, SM, 1550nm, 13-32dB EN61000-4-16: 30V; 50Hz continous; 300V, 50Hz 1s IEEE802.3ac VLAN Tagging logy consisting of a main ring and subrings is also supported (up to 4
IEEE C37.90 HV impulse ±5 kV line/earth IEEE802.3ad Link Aggregation subring ports per device). Each device supports multiple protection proto-
Extended Temperature Range -40°C – 85°C IEEE C37.90.1 Burst ±4 kV, damped vibr. ±2.5 kV line/earth, ±1 kV line/line IEEE802.3af Power over Ethernet (PoE) cols (e.g. E-MRP on port 1 & 2, MRP on port 3 & 4).
FAST SFP-LH LC EEC: FE, SM, 1550nm, 10-29dB IEEE C37.90.2 Electromagnetic field 80 - 1000 MHz 35 v/m (peak) IEEE1588 Precision Time Protocol (PTP)
FAST SFP-MM LC EEC: FE, MM, 1310nm, 0-8dB IEEE C37.90.3 ESD; contact discharge ±8 kV; air discharge ±15 kV Radius Centralized Password Management For more details please refer to the AFS user manual.
FAST SFP-SM LC EEC: FE, SM, 1310nm, 0-13dB RMON Remote Monitoring
FAST SFP-SM+ LC EEC: FE, SM, 1310nm, 10-29dB Mechanical Tests SNMP V1/V2/V3 Simple Network Management Protocol
IEC60068-2-27 Shock: 15g,11ms duration,18 Shocks SNTP Simple Network Time Protocol
SFP-LH LC-EEC: GbE, SM, 1550nm, 6-22dB IEC60068-2-6 Vibration: 1mm, (2–13,2Hz), 90min.; 0,7g, (13,2–100Hz),
SFP-LX LC EEC: GbE, MM, 1310nm, 0-11dB 90min.; 3,5 mm, (3–9Hz),10 cycles, 1 octave/
SFP-SX LC EEC: GbE, MM, 850nm, 0-7.5dB min.; 1g, (9–150Hz),10 cycles,1 octave/min.

www.abb.com/utilitycommunications
ABB FOX Switch (AFS) Family for utility applications For ABB internal use only!
AFS650 / AFS655 Overview

Customer Benefits
Utility Grade Products, specially designed for substation environment
−− High EMC EMI Immunity
Applications −− Extended temperature range
−− Redundant power supply available for DIN rail & 19”
Substation Automation −− AC/ DC power supply
Establish a Fast Ethernet or Gigabit Ethernet Backbone to provide com- −− Wide input range of power supply
munication for IEC61850 Substation Automation applications such as: −− PoE as an option
−− Enhanced protection schemes for traffic protection
– GOOSE messages
– Sampled Values (SV)
– Client Server communication Very high system availability because of:
−− High MTBF of the equipment itself
Distribution Communication −− Fan-less design
Establish a Wide Area Network based on Fast Ethernet or Gigabit −− Very fast switchover time in case of link disturbance
Ethernet to provide communication for Distribution SCADA System appli-
cations such as: Scalable port density from 8 to 28 Ports, including GbE functionality
– IEC60870-5-104 data communication
– Operational telephony system Overall ABB Communication Solution
– Metering −− Part of ABB Communication Solution Family
−− Part of ABB Substation Solution
In Plant Communication
Establish a Local Area Network based on Fast Ethernet or Gigabit System integration covering all aspects and applications such as SCADA
Ethernet to provide communication for In Plant applications such as: data traffic, IEC61850 or operational telephony. Specially for packet
switched solutions design and system integration plays a key role for
– CCTV system network performance and availability.
– Public Announcement System
– In Plant telephony system Based on more than 60 years if experience, a broad solution portfolio and
intensive application and system testing, ABB offers solutions designed
according to utility requirements providing highest system availability.

A F S 6 5 5 - 6 2 C E C T N H H X 0 5 . 0 1

© ABB Switzerland Ltd, February 2010. The right to modifications or deviations due to technical progress is reserved.
Basic Options Firmware Option Management Ports
– 650: FE Version – Firmware release
– 655: GbE Version
Future Option
Port Amount
– X: Default
– 6: 6 x 10/100 BaseT Ports (only AFS655)
– 7: 7 x 10/100 BaseT Ports (only AFS655)
– 8: 8 x 10/100 BaseT Ports Power Supply Options (only connector)
– 9: 9 x 10/100 BaseT Ports (only AFS650) – LL: Redundant Low Voltage PS (18VDC - 60VDC)
– HH: Redundant High Voltage PS (48VDC - 320VDC or 90VAC - 265VAC)
Uplink 1 Option – HE: Single High Voltage PS, spring clamps – USB Port for CRA (Configuration Recovery Adapter)
AFS650 – V.24 Port for Management
– 2 x Alarm Switchover Contacts (230VAC, 2A)
AFS650-8 AFS650-9
– ED: 1 x Port FE SC, Multimode – 2D: 2 x Ports FE SC, Multimode
– EF: 1 x Port FE SC, Singlemode – 2F: 2 x Ports FE SC, Singlemode Temperature Options
– EI: 1 x Port FE SC, Singlemode, Long Haul – 2I: 2 x Ports FE SC, Singlemode, Long Haul
– N: Temperature range 0°C – 60°C

1KHA - 001 138 - SEN - 02.10 - Printed in Switzerland


– EK: 1 x Port FE SC, Singlemode, extra Long Haull – 2K: 2 x Ports FE SC, Singlemode, extra Long Haul
– EA: 1 x Port FE ST, Multimode – 2A: 2 x Ports FE ST, Multimode – P: Temperature range -40°C – 85°C Glossary
– EB: 1 x Port FE ST, Singlemode – 2B: 2 x Ports FE ST, Singlemode – Z: Temperature range -40°C – 85°C incl. Conformal coating
Combo Port SFP cage & electrical port
–– EU: 1 x Port FE MTRJ, Multimode – 2U: 2 x Ports FE MTRJ, Multimode E-MRP Enhanced MRP
Additional Port Option GbE Gigabit Ethernet (1000Mbps)
AFS655 – T: 6 x 10/100BaseT MM Multimode
AFS655-6 – S: 6 x FE SFP cage (AFS655 only) MRP Media Redundancy Protocol
AFS655-7 PoE Power over Ethernet
AFS655-8 RSTP Raid Spanning Tree Protocol
– 2C: 2 x GbE Combo Ports SM Singlemode
– 2G: 2 x GbE SFP cage VLAN Virtual LAN

Uplink 2 Option
AFS650 AFS655
AFS650-8 AFS655-6
AFS650-9 AFS655-7
– ED: 1 x Port FE SC, Multimode AFS655-8
– EF: 1 x Port FE SC, Singlemode – 2S: 2 x FE SFP cage
– EI: 1 x Port FE SC, Singlemode, Long Haul – EC: 1 x GbE Combo Ports
– EK: 1 x Port FE SC, Singlemode, extra Long Haul – EG: 1 x GbE SFP cage
– EA: 1 x Port FE ST, Multimode
– EB: 1 x Port FE ST, Singlemode
– EU: 1 x Port FE MTRJ, Multimode

www.abb.com/utilitycommunications

You might also like