You are on page 1of 6

1

Insulation Coordination of Overhead


Transmission Lines
Miguel Carlos Valentim do Rosário, nº 56766

 practice is particularly important in high voltage environments,


Abstract—Insulation coordination methodologies are analyzed where the consequently high electric fields may cause
and a program built by the author is presented, which executes modifications in the properties of the insulation material.
the insulation coordination algorithm proposed by the standards The electric system, mostly its transport and distribution
of the International Electrotechnical Comission (IEC). Also
resulting from this analysis, a methodology for compacting
components, are forced by their function to use high working
transmission lines is presented, where alternative tower voltages. Therefore, because of the expanse of their use, air is
configurations are proposed and the benefits of this action are the most used type of insulation, complemented in the towers
analyzed. by solid insulators. However, the dimensioning of the air
The general analysis of the insulation coordination clearances are crucial, since air may become conductive when
methodology is carried out by comparison of the methodologies exposed to extreme electric fields, causing line faults that
presented in the international standards (IEC and IEEE).
affect negatively their normal operation.
In what concerns the specific case of line insulation, a more
detailed analysis is made of the insulation coordination In this context, this dissertation proposes to establish the
methodology presented in the IEC standards and the Insulation insulation coordination methodologies used on overhead
Coordination Guide provided by REN (national electric grid transmission line design.
operator, former EDP). This analysis begins to focus on the
dielectric stresses that the line insulation must stand, then the
strength provided by the insulation as regards the previously II. METHODOLOGIES AND STANDARDS OF INSULATION
presented stresses, and finishes with the methods used in the
COORDINATION
conjugation of these two factors.
Since this dissertation is concerned about overhead This chapter’s main objective is to analyze the general
transmission lines, whose major insulation component is air, an methodology of insulation coordination, by comparing the two
analysis of the required distances between the variety of most widespread standards of this matter: the IEC 60071-1 [1]
components that constitute a transmission line tower is also made. and IEEE Standard 1313.1 [2].
For that purpose, beyond the attention given to the evolution of
the models that characterize the dielectric breakdown, the real In this analysis, it was concluded that despite of the
distances implemented in the transmission lines owned by REN disagreement in the nomenclature of several variables with
are also analyzed. similar or even equivalent definitions, we can identify a
common line of action between those two. In both standards,
Index Terms—Insulation coordination, Overhead transmission the first step consists in the analysis of the system and in the
lines, Line compaction, Dielectric breakdown of long air gaps, identification of the representative overvoltages that best
Overvoltages, Insulation Standards.
characterize it. Then, the second step evaluates the strength
that the dielectric material presents to the overvoltage stresses
and how the relation between those two contribute to the line
I. INTRODUCTION
performance. The last step takes the result from the previous
O NE of the most important requirements of any electrical
equipment or system refers to its capacity of insulating its
conductive parts against the exterior environment. Beyond the
one, and returns the withstand voltage of the equipment as the
standardized value that best fits it.
Next, a more detailed analysis of these three steps will be
risks that insulation failures may cause on humans and presented.
animals, a correct insulation of an electrical equipment is
essential for an acceptable performance.
However, the insulation of an electric system is a complex A. Determination of the representative overvoltages of the
task, which requires the interoperability of several types of system
insulator types - solid, liquid or gaseous. To this necessity of This step analyzes the more relevant dielectric stresses that
using several insulator types with the objective of containing occur in the system, as well as the limitation and protection
electric current, is called insulation coordination. devices necessary for the desired line performance.
Due to the non-ideality of all dielectric materials, this Therefore, the system’s voltage stresses are separated in
four main classes.
2

 Temporary overvoltages; in substations, which led to the development of the very fast
 Slow front overvoltages (switching overvoltages); front overvoltages class, and consequently to a reorganization
 Fast front overvoltages (lightning overvoltages); of the overvoltage classes.
 Longitudinal overvoltages. B. Standard dielectric strength
B. Comparison of overvoltages and insulation strength In what concerns the dielectric strength, the two guides
Considering the previous results from the voltage stresses, characterize the accumulated probabilistic distribution of the
this chapter takes in consideration several factors that dielectric breakdown with very different expressions. IEC uses
influence the choice of the insulation. These factors are a modified Weibull distribution, while REN uses a Gaussian.
similarly defined in both standards, and represent the several The differences are negligible, and never higher than 5%.
uncertainties that characterize the system: However, the standard deviation used by these standards is
 Performance (acceptable number of insulation different. IEC uses a range of 3%-6%, while REN uses 6%-
failures); 8%, for disruptions caused by atmospheric and switching
 Statistical nature of test results; overvoltages, respectively.
 Deviation of the characteristics of the insulators The expressions used to relate the U50 voltage with the air
production and installation; clearance are also different, but both produce similar results,
 Ageing; always with differences below 4%. In figures 1 and 2, a
comparison is presented between the expressions used for each
 Different shapes of overvoltages, different from the
standard.
standardized ones;
 Real atmospheric conditions, different from the
standardized ones;
 Analysis precision.
C. Standardized results
Both standards present the standard insulation level as the
main output of the insulation coordination process. This
standard insulation level is the combination of:
 The maximum system voltage;
 Set of standard rated values of withstand voltages
that best fit and characterize the insulation, for
each of the overvoltage class that stresses the
system.

III. INSULATION COORDINATION ON OVERHEAD TRANSMISSION Fig. 1 – Comparison between expressions of U50(d) for switching
LINES overvoltages
In this chapter, a more detailed analysis is made of the
insulation coordination methodology, when applied to
overhead transmission line design. With this objective in mind,
another two standards will be compared and analyzed: the IEC
60071-2 [3] and the Insulation Coordination Guide from REN
[4].
This analysis will firstly focus on the dielectric stresses, then
on the dielectric strength of the insulation, followed by the
application of insulation coordination methods that relate both
of these factors, concluding with the air clearances proposed in
both standards.
A. Standard dielectric stresses
Fig. 2 - Comparison between expressions of U50(d) for lightning
Both standards divide the main representative dielectric overvoltages
stresses in equivalent classes, already analyzed in chapter II.
However, the time lag between these two guides results in C. Insulation coordination method application
different designations of the classes, as well as different Both guides suggest the same insulation coordination
expected values for the statistical overvoltages. With the methods, although each one applies a different insulation
natural technological evolution, since the last version of coordination factor. The differences found in the deterministic
REN’s guide, there’s been an intensification in the use of SF6 method are exposed in table 1.
3

Table 1 – Comparison of deterministic insulation coordination factors IV. INSULATION DISTANCES ON OVERHEAD TRANSMISSION
IEC REN LINES
Switching 1 1,2: 72,5 kV – 220kV In this chapter, the minimum air clearances used for
1,15: 420 kV insulation in overhead transmission lines are presented, as well
Lightning 1 1,2: 72,5 kV – 220kV as the methodology and critical analysis to achieve them.
1,25: 420 kV
A. Characterization of air clearances
From table 1 it’s possible to verify that the values proposed
In this section, an extensive analysis is made of the
by IEC are clearly less conservative than the ones from REN.
expressions used to calculate the U50 voltage (voltage where
Although there are no differences in the probabilistic
the air gap has a 50% probability of breakdown) of an air gap
method in the two guides, the simplified probabilistic method
with length d. This analysis is extended to the breakdown
is suggested in each standard with different values for the
caused by both types of overvoltages, and the several
statistical insulation coordination factor. These differences are
expressions are compared, with their validity range evaluated.
presented in figure 3.
B. Phase-to-ground air clearances
The phase-to-ground air clearances are divided in two types
of clearances: the air clearances between protection rods, and
between live parts and structures.
The first one is given by insulation coordination, and the
standard values are given by IEC. However, some deeper
research [5] revealed that the standard rated air clearances
used by IEC do not use the most adequate gap factor for
overhead transmission lines. With the proper gap factor, we
could reach a reduction of 6% to 15%, as shown in figure 5.

Fig. 3 – Comparison between statistical insulation coordination factors

D. Standard air clearances


Both guides present mainly different types of air clearances,
as the IEC suggests only insulation coordination air clearances,
while REN presents mainly security related air clearances, due
to conductor movement. However, REN also presents a range
of distances used in protection rods, designed by insulation
coordination. The differences between these two are shown in
figure 4.
From figure 4 it’s possible do conclude that even the Fig. 5 – Comparison between minimum air clearances
maximum values are similar, the minimum ones are very
different. It can be also seen that from the range of 170kV to On the other hand, the air clearances between live parts and
420kV, the minimum values of IEC are consistently smaller. structures are given by security reasons, due to wind deviation
of the insulator set.
C. Phase-to-phase air clearances
The phase-to-phase air clearances have two types as well.
The values suggested by IEC are concerned with insulation
coordination. In addition, the values proposed by REN and
DGEG are related with security, due to mid-air cable
oscillations caused by wind and snow. These values are
compared in figure 6, where we can conclude that the security
air clearances dominate the dimensioning for the phase-to-
phase air clearances. In phase-to-earth distances on the other
hand, it’s the insulation coordination that defines this type of
air clearances.

Fig. 4 – Comparison between air clearances of protection rods


4

structure with a 2,49m air clearance and a 10% probability of


disruption for that specific switching withstand voltage, would
result in a decrease of breakdown probability to 2,8%, with the
REN air clearance.

Fig. 6 – Comparison between phase-to-phase minimum air clearances

D. REN’s transmission line analysis


This section verifies the air clearances and gap factors
effectively used by REN, in the overhead transmission lines of
the Portuguese national electric grid. Figure 8 - Comparison between real and IEC Conductor-Window gap
factors
It was concluded that for any class of voltage and air
clearance, the tower dimensions are always at least 23%
V. CI-LINE PROGRAM
greater than any air clearance proposed by standards.
With the use of [6], it was also possible to calculate in a Due to the complexity of the algorithm proposed by IEC
more accurate way, the gap factor of each of the tower 60071-2, a program was developed to execute the
configurations. Considering this, figure 7 presents the methodology presented by this standard.
comparison between the Conductor-Crossarm gap factor This program receives the values of the representative
suggested by IEC and the real gap factor calculated. overvoltages, and returns the air clearances determined by the
standards for a line with specified characteristics.
The general architecture is presented in figure 9.

Inicial data Urp Ucw

Range 1
Uw Voltage range Urw
Range 1

Range 2

Range 1 air Uw
clearances Range 2
Fig. 7 – Comparison between real and IEC Conductor-Crossarm gap
factors

From figure 7, we can assess that the mean value of the


Phase-to- Phase-to-
Conductor-Crossarm gap factor (1,447) is very similar to the earth air Voltage type phase air
one proposed by IEC (1,45). However, this is not true for the clearances Phase-to- Phase-to-
clearances
earth phase
Conductor-Window configuration, as can be seen in figure 8. Figure 9 – General architecture of the CI-LINE program
From figure 8 we can conclude that the mean value of the
This program can be downloaded from:
calculated gap factor is 1,2, against the 1,25 suggested by IEC.
https://fenix.ist.utl.pt/homepage/ist156766/dissertacao/progr
Once again, we conclude that the value proposed by REN for
ama-ci-line
this specific gap factor configuration is overestimated,
following the propensity already verified in the methodology
VI. OVERHEAD TRANSMISSION LINE COMPACTION
of this guide. For example, considering a switching withstand
voltage of 950kV (average for 400kV class), the air clearance In this chapter, a methodology that describes overhead
according to IEC would be 2,49m. However, with the real gap transmission line compaction is presented. Subsequently, some
factor of 1,2, we would obtain 2,64m. Consequently, an IEC alternative compact tower configurations will be offered, and
their benefits and impacts analyzed.
5

A. Base configuration
The base configuration for this compaction will be the
400kV YS tower from the Portuguese national electric grid, as
15,58
shown in figure 10 [7].

2,23
3,10

3,10
7,75

10,00
R 3,40
R 3,40 R 3,40

5,10

Figure 12 – Proposed configuration

Figure 10 – YS tower configuration


C. Live line works
The proposed configuration in figure 12 has been
The only objective of this compaction is to reduce the top dimensioned considering only insulation coordination.
width of 24m, considered the minimum for this class of However, due to the necessity of service continuity in the
voltage. The height of the tower will remain unchanged, as this transmission lines, many maintenance operations are made
compaction would imply the consideration of local installation with the line energized. In these operations, called live line
factors that are clearly out of scope. works, it is necessary to ensure the safety of the workers, with
a minimum air clearance determined by (1) [8].
B. Proposed configuration
From the data obtained previously in chapter IV, we can
collect the minimum air clearances that the standards propose U 50  k  Cd  Cw  Ca  U 50rp (1)
for the various types of air clearances. This data is shown in
figure 11, along with the actual distances measured in the base where
configuration. U50rp is the voltage where a rod-plane air gap configuration has
a 50% probability of breakdown;
Cd is a factor that compensates damaged cap&pin insulators;
Cw is a factor that compensates the existence of metallic
floating objects and other tools used by workers that weakens
the dielectric strength of the air gap;
Ca is a factor that compensates atmospheric variations.
However, since 70% of the Portuguese territory is under
400 m of altitude [9], there is no reason to design a tower
configuration for the worst case. Therefore, two configurations
will be proposed, one that can only be used till 400 m of
altitude, and another till 1500 m.
Applying this minimum security air clearance to the
proposed configuration, we obtain the configurations in figure
Figure 11 – Comparison between real and normative distances
13 and 14.
From figure 11, we can assess that both air clearance types Considering this, it is possible to reduce the width of the
used in the base configuration can be reduced. The Conductor tower in 24% for the 400m and 18,6% for the 1500m in
– Structure air clearance is limited by the IEC value of 3,4 m, relation to the base configuration.
calculated by insulation coordination. However, the minimum
distance between phases is limited by the REN guide, which
declares 6 m as the minimum safety distance.
Respecting these distances, an alternative compact
configuration is proposed in figure 12.
6

18,32
performance (0,55 to 0,4 faults/100km of line/year obtained
with the program IEEE Flash v1,9).
In conclusion, the use of these compact configurations

2,23
3,10

3,10
provides not only a reduction in costs of production and
installation, but also an increase in service continuity due to
9,21
the enhanced lightning performance.
10,00

R 4,20
R 3,83 R 3,83 VII. CONCLUSION
Pursuing the main objective of this dissertation, an analysis
5,10
was made of the general methodology of insulation
coordination presented in the international standards. It was
concluded that both provided a similar path to achieve it.
Figure 13 – Proposed configuration for altitudes under 400 m Then, a more detailed analysis was made, comparing the
insulation coordination methodologies when applied to
19,52 overhead transmission lines. Some conclusions were drawn
from the comparison of IEC and REN guides, more
specifically, the consequences of the temporal lag existing
2,23

between them and the differences in the application of the


3,10

3,10

insulation coordination factors.


9,79
Subsequently, an analysis was made to the air clearances
10,00

needed to specify the insulation of an overhead transmission


R 4,43
R 4,04
R 4,04 line. The phase-to-earth and phase-to-phase air clearances
were specified based on the several existing standards for this
5,10 matter. Also, an analysis was made of the real air clearances
and gap factors implemented in REN transmission lines, which
were compared with the values proposed by the standards.
Figure 14 – Proposed configuration for altitudes under 1500 m The architecture of a program built by the author was also
presented. The program executes the insulation coordination
D. Lightning performance algorithm suggested by IEC, and generates all types of air
To conclude the design of the proposed configurations, it is clearances for the specified overhead transmission line.
necessary to calculate the position of the shield wires, which Finally, a methodology for overhead line compaction is
will be based in two main conditions. First, the minimum presented, and applied to a specific REN line configuration.
clearance between the shield wires and the phase conductors Some alternative configurations were proposed, with a
will have to be the same as the phase-to-phase clearance. possible reduction of 24% in width. The impacts that this
Second, it will be used the shielding failure current of the base modifications had on the lightning performance were studied,
configuration, and therefore the same striking distance. leading to an enhancement of 27%. This chapter is then
The conjugation of these two conditions results in the concluded with a brief evaluation of the benefits that can be
configuration proposed in figure 15. drawn from compaction of overhead transmission lines.
18,32

3,44 3,44
REFERENCES
[1] IEC, “Standard 60071-1, Insulation coordination - Part 1: Definitions,
1,81
1,81

principles and rules", 2006.


[2] IEEE, “Standard 1313.1 for Insulation Coordination - Definitions,
2,23
3,10

3,10

Principles and Rules”, 1996.


[3] IEC, “Standard 60071-2, Insulation coordination - Part 2: Application
Guide", 1996
10,00

[4] REN (former EDP), “Guia de coordenação de isolamento para a rede


PTI - EDP”, 1985.
[5] L. Thione, “Evaluation of the switching impulse strength of external
R 6,00
insulation”, Electra nº 94, 1976.
R 6,00 R 6,00
[6] L. Paris et al., “Phase-to-ground and phase-to-phase air clearances in
5,10
substations”, Electra nº 29.
[7] Companhia Portuguesa de Electricidade, “Esquemas Sumários dos
Postes da C.P.E.”, 1975.
[8] CIGRÉ, “Dielectric Strength of External Insulation Systems Under Live
Figure 15 – Shield wire position for the proposed configuration till 400m Working”, Sessões CIGRÉ de 1994, 33-306.
[9] A. M. P. Jorge Ferreira, “Dados Geoquímicos de Base de Sedimentos
Fluviais de Amostragem de Baixa Densidade de Portugal Continental”,
With this shield wire configuration, both the proposed Banco de dados do LNEG - Tese de Doutoramento, 2000.
configurations allow an increase of 27% in lightning

You might also like