Professional Documents
Culture Documents
This report has been published with its distribution limited to employees and
advisors of IRC for the sole purpose of evaluating the progress and future course
of the project described in the report. This report is not available for general
distribution. Until the report has been reviewed and evaluated by IRC, it should
be neither disclosed to others nor reproduced, wholly or partially, without written
consent of IRC. This report is a copyrighted publication and its contents shall not
be reproduced or distributed without permission from the IRC.
List of Tables
Table 1 Summary of anhydrous ammonia exposure effects. ..........................................1-1
Table 2 Electrochemical sensor specifications................................................................2-2
Table 3 Solid-state sensor specifications. .......................................................................2-4
Table 4 Infrared sensor specification. .............................................................................2-5
Table 5 Charged carrier injection sensor specifications..................................................2-6
Table 6 Polymer thin-film capacitive sensor specifications............................................2-7
Table 7 Catalytic bead sensor specifications...................................................................2-8
Table 8: Generic specification for low concentration range detectors used in machinery
room applications. ....................................................................................................4-3
Table 9: Recommended control function setpoints for low concentration range refrigerant
detectors in machinery rooms. .................................................................................4-3
Table 10: Generic specification for high concentration range refrigerant detectors in
machinery room applications. ..................................................................................4-4
Table 11: Recommended control functions for high concentration range refrigerant
detectors in machinery rooms. .................................................................................4-4
Table 12: Recommended control functions for refrigerant detectors in production spaces.
..................................................................................................................................4-8
The authors would also like to especially thank those who reviewed and offered
comments on this report: Frank Wewers and Brian EuDaly, Manning Systems; Eleny
Fotis, Vaisala; and Rob Walden, GfG Instrumentation.
Thanks to Wendy Beckman for accumulating information and multiple runs to the
library. We would also like to acknowledge the other IRC staff that contributed to this
report including Dan Dettmers and Jim Elleson.
The authors would also like to gratefully acknowledge members of the Industrial
Refrigeration Consortium for their support to develop this report. At the time of this
printing, members of the IRC include: Alliant Energy, CF Industries, EPA, Kraft Foods,
Nor-Am Cold Storage, OSHA, Schoep’s Ice Cream, Tropicana Products, Wells’ Dairy,
and Xcel Energy.
1.1 Purpose
The purpose of ammonia detectors is simply to sense and communicate the presence of
ammonia for human or property protection and for equipment control. Uses for ammonia
sensors are rapidly evolving with the improving sensors and refrigeration controls.
1.2 Definitions
ppm: Parts Per Million, a measure of gas concentration by volume
sensor: The device that includes detector and the associated electronics
necessary to process and respond to the detector output.
Notice, the first instantaneous concentration spike approaches but does not exceed the
OSHA PEL; however, the 15-minute average exceeds the NIOSH STEL of 35 ppm a
short time later.
60
1
50 OSHA PEL (TWA)
Instantaneous Concentration
2
40
Concentration, ppm
20
TWA
10
0
0 1 2 3 4 5 6 7 8
Time, h
For ammonia machinery rooms to satisfy the National Electric Code (NEC, 2002) criteria
for an “unclassified” location, machinery room mechanical ventilation systems must run
continuously with an alarm that actuates upon failure or the room must be equipped with
an ammonia detector that alarms at 1,000 ppm. In addition, ventilation systems may be
designed for emergency mode operation where their operation attempts to keep the
accumulation of gas-phase ammonia from approaching the LFL in the machinery room
because of a leak. Generally, low concentration range detectors are used for initiating
purge ventilation under emergency situations.
A high concentration range detector (i.e. 1,000-30,000 ppm) can provide “hot zone”
guidance to incident commanders during emergency response. The detector can quantify
the ammonia concentration and any trends toward impending danger for extremely high
concentration environments as they approach the LFL (160,000 ppm). A limitation that
should be identified is that, currently, most commercially available ammonia detectors
have an upper limit of detection at 20,000-30,000 ppm. A commonly used metric for
responding to hazardous environments or initiating emergency ventilation system
operation is 25% of the LFL (for ammonia, this would be 40,000 ppm) – which is beyond
the span of currently available commercial ammonia detectors. This requires emergency
response plans and decisions to be based on the concentration ranges measurable with
existing detector technologies.
§8.12 Machinery Room, Special Requirements (h) requires that “(1) the mechanical
ventilation system in the machinery room is run continuously and failure of the
mechanical ventilation system actuates an alarm or (2) the machinery room is
equipped with a detector, conforming to 8.11.2.1, except the detector shall alarm at
1,000 ppm.” This requirement is only necessary if the machinery room using
ammonia does not conform to Class 1, Division 2, of the National Electrical Code.
§6.2.1.3 Ventilation, Safety states that “a supervised alarm system shall be activated
when the ammonia leak detector is activated or when the mechanical ventilation
system fails so that corrective action can be taken.”
§1107.5 Emergency Control of the Ventilation Systems, requires that the purge
capability of a ventilation system responds automatically to the detection of
refrigerant concentrations at levels no higher than 25% of the LFL or 50% of the
IDLH, whichever is lower. For ammonia systems, the level of actuation would be
set at 150 ppm (50% of the IDHL).
§2.4.6 states that ammonia detectors can be substituted for visits every 8 hours by
responsible personnel to refrigerated areas served by ammonia. The detectors must
alarm to a continuously supervised location and be applied according to
manufacturer’s recommended spacing and location guidelines, or within 10 ft of any
evaporator. The detector should alarm at levels less than 1,000 ppm.
§6.0 Operation and Maintenance, states that the proper operation of the ammonia
detectors and control circuitry (including initiation of ventilation system and alarms)
should be confirmed at least every three (3) months.
1.7 Conclusion
Ammonia detectors play an important role in the safe operation of facilities that utilize
ammonia refrigeration systems. Detectors are used for insuring occupant safety (limiting
personal exposure), system controls (emergency ventilation and alarms), supporting
operations and maintenance (pressure relief monitoring), support of emergency response,
and shutdown of electrical equipment during release scenarios. The use of ammonia
detectors is also a requirement in nearly every code, standard, and guideline related to
ammonia refrigeration systems. Care is required to specify the correct detector for the
target application.
2.1 Detector
A detector is a device that senses the presence of a target gas and produces a signal that
is, typically, proportional to the magnitude of the gas concentration.
2.1.1 Electrochemical
Electrochemical sensors use an electrolyte solution that reacts to ammonia and produces
an electrical signal proportional to the concentration. Figure 2 shows the key elements of
an electrochemical sensor.
Electrolyte
The capillary diffusion barrier, filter and permeable membrane (also called a hydrophobic
barrier, because it keeps the electrolyte solution from dehydrating) together control the
amount of gas that is allowed to react with the electrolyte and keeps the electrolyte from
leaking out of the sensor. The filter may be necessary to reduce cross-sensitivity in
certain situations and is typically activated charcoal.
The electrode is made of a material with which the target gas undergoes an oxidization or
reduction reaction. The reference electrode is used to maintain a constant voltage on the
sensing electrode to compensate for the degradation of the electrolyte due to the reaction
on the electrode surface; thereby, extending the life of the sensor.
The more sensitive electrochemical sensors require the passage of more gas molecules
through the membrane in order to obtain a measurable signal. This accelerates the
evaporation of water from the electrolyte solution and shortens the operating life of the
sensor.
Electrochemical sensors are sensitive to temperature and often have internal temperature
compensation. Higher temperatures typically shorten the life of the sensor. Humidity is
also important; a high humidity environment can pass water vapor through the membrane
and dilute the electrolyte solution, a low humidity environment accelerates water loss and
shortens the sensor life.
Electrochemical sensors are usually designed for low (<200 ppm) concentrations and are
primarily used as toxic gas monitors (Chou, 2000); however, commercially available
electrochemical sensors can be specified to 1,000 ppm.
The life of the sensor depends on the amount of ammonia that it is exposed to, and
environmental conditions; however, a one- to three-year life is common.
2.1.2 Solid-state
During the development of semiconductors, it was found that the presence of background
gases affected the characteristics of the device. For most applications of semiconductors,
1
One manufacturer claims humidity to 100% and condensing with appropriate enclosure.
2
Cross-sensitivity will depend on sensor manufacturer.
Typically, solid-state sensors are made from one or more metal oxides (e.g. tin or
aluminum oxides) and can be formed either in a spherical bead or in a thin film
configuration. The conductivity change in the presence of the target gas is temperature
dependent; therefore, an internal heater is used to regulate and maintain the temperature
of the device (typically >550°F). Figure 3 shows as schematic of a solid-state sensor. In
general, interference from other gases is a problem; however, the use of filters can
minimize the problem.
Sensor Element
Sensor Load
Voltage Resistor
Heater
Voltage
The biggest advantage of the solid-state sensor is that it is not “consumed” during the
sensing; when the gas is present, it is absorbed on the surface of the sensor. Once the
ambient ammonia concentration decreases, the ammonia desorbs from the sensor’s
surface and the sensor returns to its original condition. The expected life of a solid-state
sensor is very long. In addition, the sensors become more sensitive as they age.
The biggest disadvantage of the solid-state sensor is cross-sensitivity with other gases.
Therefore, to avoid nuisance alarms, solid-state sensors should not be set for toxic level
alarm setpoints (TLV/TWA or STEL). One manufacturer recommends alarm levels no
lower than 150 to 300 ppm.
2.1.3 Infrared
Historically, infrared sensors were developed for sensing of hydrocarbon gases near their
LFL. However, several companies have evolved infrared sensors for sensing gas-phase
ammonia concentration. The operating principle is that the absorption of infrared light
through an ammonia/air environment is different than for air only. Detectors can
measure either the reduction of electromagnetic radiation through the sample, or the
temperature rise of the sample due to the absorption of the radiation. The most common
infrared detector senses the temperature rise through the environmental sample.
Regardless of the detector principle (i.e. radiation reduction or temperature rise) the
wavelength of the light-source is chosen specifically for ammonia and results in no
appreciable cross-sensitivity.
The complexity of these instruments can range from simple to complex based on the
sensitivity, selectivity, and stability required. The isolation of the detector from the
sample insures that the output of the device is independent of the amount of reference gas
that is sensed. Figure 4 shows both an infrared sensor that measures temperature rise and
a sensor that uses a single radiation detector and a rotating “chopper” to alternately direct
the light source between the reference and sample cell.
The gas sampling method for infrared detectors can be either diffusion or extraction (see
Section 2.2).
Infrared detectors are used for high concentrations of ammonia (1-2%). One
manufacturer recommends that alarm setpoints should not be below 5,000 ppm.
The infrared detectors are more expensive than their solid-state counterparts.
(a)
Mirror
Sample Cell
Detector
Infrared Source
(radiation)
Mirror
Reference Cell
Rotating "Chopper"
(b)
The response time of the sensor is lower than all other sensors considered in this
document.
Despite the reduced cross-sensitivity compared to solid-state sensors, alarm setpoints for
personal exposure (15-35 ppm) are at the lower limit of detection. Therefore, care must
be taken in specification of this sensor for personal exposure alarms because of the
increased probability of nuisance alarms.
According to the manufacturer, the life of the sensor is still uncertain due to the newness
of the product; however, testing by the manufacturer indicates that the estimated sensor
life is conservative.
The ammonia concentration measurement is done as a cycle that includes both a heating
(desorption) and cooling (absorption) period to determine and separate the effect of
humidity from the response to ammonia concentration. The absorption/desorption cycle
requires time (currently 18 seconds). The sensor averages multiple readings (currently 5)
and gives a readout; therefore, the absorption/desorption cycle time limits the response
time. The sensor continuously calculates and averages the readings.
Calibration of the sensor is recommended yearly and can be done in one of two ways:
either by the owner with a known gas sample or by removal and mailing of the probe to
the manufacturer for calibration. Calibration by the manufacturer includes checking at
multiple points including both ammonia and humidity. Since calibration by the
manufacturer requires that the sensor be removed, it is recommended that a spare sensor
be purchased and available during calibration so that the sensing location does not go
unmonitored.
The principle of operation is that combustible gas mixtures will burn at lower
temperatures in the presence of a catalyst. This behavior is called catalytic combustion.
A platinum wire is embedded in a catalyst-coated metal oxide bead. When catalytic
combustion occurs, the temperature of the bead increases and changes the resistivity of
the wire.
Catalytic bead sensors are sensitive to poisoning by certain chemicals that will reduce the
sensitivity and, under prolonged exposure, completely ruin the sensor. Halogen
compounds (such as halogenated refrigerants and fire extinguisher compounds) will
temporarily inhibit the sensor.
2.2 Sampling
In order for the sensor to measure the concentration of ammonia in the surrounding air, a
sample must be introduced to the detector. There are two methods for sampling:
diffusion and extraction.
2.2.1 Diffusion
Diffusion sampling is by far the most common and simplest method. The sensor is open
(but possibly shielded) to the surrounding environment. A combination of convection
(by room air movement) and gas diffusion brings the ammonia “in contact” with the
sensor. This method has no moving parts.
2.2.2 Extraction
Another method is extraction sampling. The sensor is exposed to a sample of air that is
deliberately pumped from the desired point. A sampling pump and tubing are required; a
sampling system may have multiple sampled points per sensor and the points may be up
to 500 ft from the sensor.
Some drawbacks of the system are that the time lag from the sampled point to the sensor
may be long depending on the distance from the point to the sensor, and maintenance of
2.3 Electronics
In addition to the detector, a sensor contains electronics to correct or compensate the
detector output and a controller to initiate the proper response.
2.3.2 Controller
The output of the signal conditioner is used by the controller to determine and initiate the
required action. The level of electronics in the controller section is largely dependent on
the purpose. For example, a controller that is charged with the electric shutdown of an
engine room will be more complicated than one that merely initiates an audible and
visual alarm.
2.4 Summary
A broad range of detector types is commercially available. In general, electrochemical
sensors are best suited for low-concentration sensing only. Solid-state, infrared and
catalytic bead sensors are for sensing high-concentrations. There are also a couple of
new sensor types that are relatively recently available. The polymer thin-film capacitive
sensor is a completely different type of technology. The charged carrier injection sensor
operates on a principle similar to a typical solid-state sensor, but with reduced cross-
sensitivity.
For example, toxic gas monitoring applications necessitate ammonia sensors that are
capable of accurately measuring low concentrations of ammonia in air (i.e. 0-200 ppm or
lower). If the sensor is expected to react to higher concentrations (i.e. approaching
percentages of the LFL), it is unlikely that concentrations of ammonia at toxic gas levels
will be safely discerned.
Since the uncertainty of most detectors is based on a percentage of full scale, a detector
range should be selected such that any alarm or critical control settings ranges are
triggered at concentrations near the maximum reading for the detector. According to
Chou (2000), the sensor maximum concentration should be 3 to 5 times the expected
monitoring concentrations.
Both high and low temperatures effect the operation and life of sensors. The highest
temperatures encountered in industrial refrigeration applications rarely effect the
operation; however, they may shorten the sensor life. In freezer or cooler application,
sensors may require an enclosure and auxiliary heating and response times may be longer
at the lower temperatures. In some sensors, the output is compensated based on the
actual temperature.
Most sensors also require a “non-condensing” environment. This means that liquid water
must not infiltrate to the sensor. In normal environments, the risk of condensation is low
as long as there is some minimal air circulation in the area (Chou, 2000). In detectors
Air velocity is also important, both its magnitude and direction relative to the sensor.
With sensors that rely on diffusion to sample the surrounding environment, high
velocities affect the ability for diffusion forces to deliver ammonia to the detector.
Some examples of gases are methane, carbon monoxide, propane, butane, hydrogen,
chlorine, propanole, benzole, sulfur dioxide, ethylene, hydrogen sulfide, paint vapors,
solvents, etc. Solid-state sensors are the most susceptible to background gases.
However, electrochemical sensors may have cross-sensitivity with hydrogen sulfide and
sulfur dioxide. The charged carrier injection sensor still showed significant cross-
sensitivity with propanole and hydrogen sulfide.
Electrochemical sensors have the shortest life of all of the technologies surveyed. Sensor
life is typically 1-3 years, with higher temperature applications, low humidity
applications, and continuous ammonia exposure applications resulting in shorter sensors
life.
Solid-state, catalytic bead, polymer thin-film capacitive, charged carrier injection and
infrared all have life expectancies in the range of 5-10 years.
3.5.1 Accuracy
The accuracy of a sensor is typically given as a percentage of full-scale. For example, if
the sensor is for the range of 0-100 ppm with a 5% of full-scale, a reading of 30 ppm will
be ±5 ppm.
0.9
Fraction of Concentration Change
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0 50 100 150 200 250
Time, s
Most manufacturers give a 90% response time. It can range from 10 seconds up to 90
seconds. A typical value for electrochemical and solid-state is < 30 seconds to 90%. The
high concentration infrared sensor’s t90 is 90 seconds. The charged carrier injection
sensor’s response is less than 10 seconds. The polymer thin-film capacitive sensor’s
response time is effected by the length of the absorption/desorption cycle and currently is
90 seconds to 50% of the reading.
3.6 Calibration/maintenance
Calibration is important to the proper functioning of the ammonia sensing system. It is
imperative that calibration is done as per the manufacturer’s recommendations. Not all
maintenance of the sensor will be formal calibration, often a ‘bump’ test is performed at a
higher frequency and the formal calibration frequency is reduced. For example, it is
recommended by one manufacturer that electrochemical sensors be ‘bump’ tested every
30-90 days and formally calibrated annually.
When considering a sensor, determine costs for calibration equipment (if in-house
calibration is done) as well as the time to perform the calibration.
In all application cases, it is important to insure the refrigerant detector’s capabilities are
consistent with the application requirements. All detectors have operating,
environmental, and span-of-life limitations that can compromise the functionality of an
ammonia detection system.
The buoyancy effects of ammonia are easily overridden by forced air movement in
spaces. Forced air convection currents are created by ventilation systems, evaporator
fans, and exhaust fans. Designers should take into account the air movement within a
space in selecting a sensor location. Avoid placing sensors in locations where they may
be biased by dilution of ammonia vapor generated within the space by supply air (e.g.
placement of sensors between ventilation intakes). In addition, the performance of some
sensing technologies is adversely impacted by placement within higher velocity air
streams. While no definition was found for “higher velocity” in literature, the ISA
Ammonia sensors should be positioned such that they will be free from direct mechanical
damage (due to impact of moving equipment or personnel) as well as indirect damage
(from exposure to moisture or chemicals from wash down or clean-up).
Finally, some sensors (capacitive type) may be susceptible to bias from electromagnetic
interference. If possible, avoid locating sensors in regions where electromagnetic
interference may be high. Alternatively, sensors can be guarded from the effects of
electromagnetic interference by proper shielding. Sensor manufacturers can be contacted
for specific equipment to accomplish the necessary shielding.
Table 9 includes recommended minimum control functions setpoints for the low
concentration range refrigerant detectors.
Table 10: Generic specification for high concentration range refrigerant detectors in
machinery room applications.
Description Characteristic
Minimum span 1,000-20,000 ppm
Response time <30 s
Potentially interferent gases
Expected temperature range 50-95°F
Located in exhaust air-stream? If yes,
estimated air velocity.
Table 11 outlines recommended minimum control functions for the high concentration
range refrigerant detectors.
Table 11: Recommended control functions for high concentration range refrigerant
detectors in machinery rooms.
Function Setpoint
High concentration emergency alarm (supervisory, 10,000 ppm (1.0%)
audible, and visual)
Initiate machinery room electrical shutdown 15,000 ppm (1.5%)
1. near sources of potential leaks where vapors tend to accumulate, that is,
near the ceiling, or
2. near exhausts, but not directly in the air stream (Perez-Blanco and
Stoecker, 1994). Note that if there are multiple exhaust locations, a sensor
should be placed at each exhaust.
Do not locate sensors near ventilation intakes because the incoming air (free of ammonia
vapor) will dilute the concentration to which the sensor is exposed and reduce the sensors
ability to assess the concentration in the area for which it is responsible.
Low concentration range refrigerant detectors are typically used for production spaces. A
number of other factors play key roles in underwriting the success of a refrigerant
detection system in production spaces including: environmental conditions, sensor
placement, and controls.
Often sensing for personnel protection is often done with a hand-held sensor if occupants
consistently smell ammonia. While this is an invaluable diagnostic tool, if offers no
warning of a leak to area personnel. Therefore, a fixed ammonia sensor is recommended
for “first warning” and should be installed near potential leak sources. The following
sections focus on the application of fixed ammonia sensors.
Humidity may present a greater challenge. In particular, production spaces that undergo
wash-down or cleanup often create humidity conditions that exceed the allowable relative
humidity ranges of most sensors.
Some sensors can be biased or damaged by the presence of other gas-phase constituents
that may be present in production spaces.
In blast freezers, sensors should be in an area with relatively still air. Both Perez-Blanco
and Stoecker (1994) and Manning Systems (2001) recommend that the sensors be
mounted above the spray area.
Since production spaces typically have more occupied hours than machinery rooms,
sensor locations should also include areas where people are located. Sensors should be
placed in an area within the production space that is representative of the production
employee’s “breathing zone”. Locating sensors near people is important to insure that
fair warning is given; however, it is also important that concentrations are logged to
insure that OSHA and NIOSH values of allowable time-weighted exposures are not
exceeded. Logging concentration values protects both the employee and the employer.
4.3.2.1 Local
Local placement refers to the proper positioning of refrigerant sensor(s) in areas where
production personnel operate or near a leak source. Care should be exercised to avoid
situations that may bias the sensor’s reading, for example, locating sensors in close
proximity to ventilation system inlets providing fresh supply air to the production area.
4.3.2.2 Zoned
In addition to a sensor that is responsible for a small area or equipment (i.e. local).
Figure 6 also shows a “zoned” sensor near the exhaust fan that is more representative of
the entire space due to the fact that exhaust fan brings air from throughout the space in
closer contact with the sensor. While this effectively increases the area that the sensor
can monitor, it does increase the effective time response of the sensor.
The frequency of sensor spacing within a production area depends, in part, on the layout
of the spaces that comprise the production area. At least one sensor should be positioned
within each zone of the plant’s production areas – keeping in mind that a “zone” can be
either physical or virtual. Physical zones are defined by physical boundaries that include
Exhaust Fan
Z oned sensor
L ocal sensor
Surge Drum
L
HX
4.3.3 Controls
The placement of refrigerant detectors in production areas offers the potential for
integration into various plant systems to significantly enhance plant safety and mitigate
consequences of an incident. Of course, refrigerant detectors provide the capability for
notifying plant personnel of the presence and concentration of refrigerant; however, the
output of the detector can also be used as an input to refrigerant-side systems, ventilation
systems, and other systems within the plant. For example, the presence of refrigerant
above a threshold concentration in a zone (e.g. 35 ppm) can be configured to initiate the
shutdown of refrigerant supply to that zone by closing a main supply solenoid for the
zone or by individual supply solenoids for all equipment within the zone. This strategy
can mitigate the loss of refrigerant by stopping the supply of refrigerant to the effected
zone. Use of multiple sensors to initiate this control may be advisable to minimize the
possibility of “nuisance” trips.
It is not possible to specify all possible strategies for the integration of a refrigerant
detection system in this document since each plant’s production equipment, layouts, and
operation is unique. The table below lists an example of control responses for refrigerant
detectors in production spaces.
At a minimum, a safety relief system will comprise the following two components: a
calibrated pressure relief device and interconnecting piping. There are a number of
alternative pressure relief devices available to designers including direct-acting relief
valves, rupture disks, pilot-operated relief valves, and balanced-port relief valves. By far,
the most widely used pressure relief device used in industrial refrigeration systems is the
direct-acting pressure relief valve. The interconnecting piping includes all necessary
piping to connect the component being protected with the relief device and route the
discharged refrigerant to a safe location. Minimum requirements for safety relief system
design are established by various code authorities including:
Both of the above standards provide prescriptive approaches for complying with the
ASME boiler and pressure vessel code (ASME Section VIII Division 1).
Refrigerant detectors can play a role in monitoring and alerting operators that a relief
valve has lifted as well as facilitating operators in pin-pointing which relief device
actually lifted so it can be replaced.
Figure 7 below illustrates the application of an ammonia sensor in a safety relief vent
main. In this configuration, the refrigerant detector will be capable of alarming/notifying
operators that the relief device protecting one (or more) of the components connected on
the vent main has lifted. In large relief vent systems where a considerable number of
components are interconnected to a common header, the use of a vent line refrigerant
detector placed near the header outlet offers little information on which safety relief valve
lifted. Therefore, it is then the responsibility of the operations staff to conduct a closer
inspection to determine which component(s) and safety relief valve(s) actually lifted. If
combination3 relief devices are used, operators can quickly pinpoint the component that
relieved. In the absence of combination relief devices, other techniques have to be
pursued. These may include conducting visual inspections (external and internal) and
applying ultrasonic detectors (to test for a valve that may be weeping).
Typically, the refrigerant detector in this application is a high range type detector (for
example, 1,000 – 30,000 ppm). If the sensor is not specifically designed for application
to safety relief vent lines, an adaptor may be necessary and available from the sensor
manufacturer. If possible, locate the sensor(s) indoors for protection from the outdoor
elements (temperature, moisture, and solar radiation/ultraviolet radiation). Keep in mind
that a diffusion type sensor needs some air movement to properly monitor the line.
Application should not be done without contacting the manufacturer with details of the
installation.
3
The combination relief is a series assembly of a rupture disk followed by a pressure-actuated relief valve.
An overpressure condition will break the internal member of the rupture disk and the pressure relief valve
opens to vent refrigerant from the system. After the overpressure condition subsides, the pressure relief
valve will close; however, the rupture member does not re-seal. By connecting a pressure gauge or
pressure switch between the rupture disk and the pressure relief valve, an operator can quickly determine
which component experienced and over pressure condition.
Sensor
Relief Vent
Runouts
NH3
Sensor
000 ppm
In situation where the relief vent line terminates in a water diffusion tank, consider the
impact of high moisture concentrations inside the vent line/header. The migration of
moisture into the vent header can be held in check by either trapping the outlet portion of
the header with a fluid (such as oil) or by bleeding instrument air into the header for
dehumidification.
www.irc.wisc.edu
Supporting Organizations