You are on page 1of 6

| THE BUILDING ENVELOPE |

MEETING THE DEMAND


FOR HIGH-EFFICIENCY FAÇADES
At the top level of this energy-efficient By Russell M. Sanders, AIA, and
building, an adhered air barrier Craig A. Hargrove, AIA, LEED AP,
provides the primary Hoffmann Architects
weather protection for a metal panel
cladding system, to be installed.

LEARNING
OBJECTIVES
After reading this article, you
should be able to:

+ BALANCE energy use goals


with practical considerations,
such as constructability, perfor-
mance, and product availability.

+ APPLY principles of thermo-


dynamics and energy transfer

COURTESY HOFFMANN ARCHITECTS


to the appropriate design
of energy-efficient building
enclosures.

+ DETERMINE energy code


compliance by demonstrating
thermal efficiency through cal-
culations or energy modeling.

O
+ ACCOUNT for sites of
thermal bridging by incorporat-
n Russell M. Sanders, AIA, is EVP and Senior
n February 24, 2017, The New York Times
Director, Technical Services with Hoffmann ing high-efficiency detailing that
Architects, an architecture and engineering
published an article regarding the eventual
addresses sources of energy
firm specializing in the building envelope. In decommissioning of the Indian Point Nuclear
addition to building enclosure evaluation for Power Plant, just north of New York City, which loss and insulates against heat
existing structures, Sanders specializes in transfer.
design detail assessment and constructabil-
the governor intends to close by 2021. A report
ity review for new construction. on the implications of the plant shutdown found
that the need to find new sources of energy
n Craig A. Hargrove, AIA, LEED AP, SVP and

Director, Architecture, oversees demand-


could be mitigated if New York followed the lead
ing high-performance building envelope of Massachusetts and Rhode Island in providing
projects. Manager of the firm’s Manhattan incentives to drive down energy consumption, particularly
office, he leads project teams in developing
design details that meet energy efficiency
through improved efficiency in building systems.
goals with practical, cost-effective solutions. Energy codes mandating more efficient use of build-
ings—and, by extension, of building enclosures—are
already being adopted by many states as a logical step in
the reduction of energy consumption. On a national scale,

BDCuniversity.com | BUILDING DESIGN+CONSTRUCTION | 61


| THE BUILDING ENVELOPE |

the impetus to improve building energy performance


is manifest in the latest and most far-reaching model
energy code from the International Code Council, the
2015 International Energy Conservation Code (IECC).
Compared with energy standards of just a few years
earlier, the 2015 IECC sets a high benchmark for
energy performance.
In 2010, the required insulative value for a new
roof on an existing commercial building was R-20, per
the IECC. Today, it’s R-30, a 50% increase. Replace-
ment fixed windows in 2010 needed to perform at
R-1.82. Now, that number is R-2.38, 30% greater.
This trend toward increasingly stringent energy
performance standards is likely to continue. Several
states and municipalities, including New York, New
Jersey, and Maryland, were early adopters of the
2015 IECC. Others have already passed legislation to
roll out the new, more demanding energy standards
over the coming months.
For design professionals, designing and detailing

HOFFMANN ARCHITECTS
building enclosures to meet these strict performance
benchmarks demands knowledge not only of build-
ing envelope systems, but also of the requirements
and objectives of the energy code, the fundamentals
of thermodynamics and energy transfer, and high-
efficiency enclosure detailing. or with location-specific modifications.
For property owners and facility managers, under- Every three years, a new version is Eventually, high-
standing the code requirements for energy-efficient released, with guidelines that up the efficiency detailing
that cuts energy
design, the science behind those standards, and the ante on energy performance. The
use will likely be
process involved in achieving energy performance current edition, published in 2015, mandated by code.
goals is critical to an informed and judicious ap- incorporates ANSI/ASHRAE/IES Stan-
proach to planning construction that meets stringent dard 90.1-2013 – Energy Standard
energy mandates. for Buildings Except Low-Rise Residential Buildings
When and why to exceed the requirements of the (ASHRAE 90.1). A reference standard, ASHRAE 90.1
code, and how to balance energy-use goals with prac- provides minimum requirements for energy-efficient
tical considerations such as constructability, perfor- building design and establishes criteria by which to
mance limitations, product availability, logistics, and determine compliance.
cost, are further considerations. In some cases, it There are three basic steps to meeting energy
makes sense to go beyond the published standards code requirements. First, identify which version of
and achieve forward-thinking energy performance that the IECC applies to the project. Second, to establish
looks ahead to energy-efficiency trends. In other situ- performance criteria, determine the correct building
ations, the net energy reduction for a given upgrade climate zone. Finally, choose the correct path to en-
may not be sufficient to justify the costs. Primarily, ergy code compliance dictated by the characteristics
these considerations pertain to new construction, but and composition of the building dictate.
some of the cost-benefit analysis could just as well
apply to retrofit decisions for existing buildings. STEP 1: Know Your Code
The 2015 IECC is the newest version of the code and
UNDERSTANDING THE CURRENT therefore a logical reference point for this discussion.
ENERGY CONSERVATION CODE However, it is important to know which version of the
First issued in 2000, the IECC is a model code, code is in effect for the jurisdiction in which a build-
which means that it is not, in itself, a regulation ing is located. If there is no legal reason to comply
or law, but rather a set of directives that may be with a newer, more stringent version of the IECC, then
adopted by state or local jurisdictions, either as is decisions about the energy performance of a building

62 | BUILDING DESIGN+CONSTRUCTION | December 2017


assembly become about balancing practical concerns above-grade wall area. That figure
with performance goals, rather than about meeting includes windows, window walls,
immutable efficiency requirements. and glass doors, but not opaque
doors and spandrel panels. For
STEP 2: Know Your Climate Zone most climate zones, the propor-
To design an energy-efficient building enclosure, it is tion of glazing may be increased
essential to identify the type of climate in which the to 40% if code-compliant, day-
building is located. The basic distinction is between light-responsive shade controls
heating climates and cooling climates. are incorporated into the design.
ASHRAE 90.1 uses the concept of heating degree When considering the curtain
days (HDD) and cooling degree days (CDD) to wall buildings that dominated new
characterize these two climate types. Degree days construction in the second half
are calculated as the difference between the mean of the 20th century, it may seem
temperature and a given base temperature, in this excessively restrictive to limit
case 65°F for HDD and 50°F for CDD. Heating days window area so severely. However,
have an average temperature below 65°F, while cool- most of the energy loss across a

HOFFMANN ARCHITECTS
ing days are warmer than 50°F. building enclosure is through the
HDD and CDD are aggregated over the course of a fenestration. The code recognizes
year, to specify the nominal heating or cooling load that glazed assemblies are inef-
and to estimate energy consumption. If annual HDD ficient when compared with the
exceeds CDD, the building is in a heating climate, or opaque portions of the building
one that requires the use of heat more often than envelope. Furthermore, additional glazing is often un-
air conditioning. If the opposite is true, then the necessary to achieve the desired indoor environment. High-efficiency
building is in a cooling climate. As a result, the IECC and ASHRAE 90.1 (and, by details, such as warm
extension, the jurisdictions that adopt them) are spacers at window
While heating and cooling are the chief climate
assemblies, prevent
identifiers, there are many distinctions beyond stipulating a reduction in the proportion of fenestra- heat loss/gain by
these two broad categories. For the continental tion in building façades as a reliable way to improve providing a thermal
United States, ASHRAE 90.1 identifies no fewer energy efficiency. break at conductive
materials, like
than seven climate zones. From a practical design metal-to-metal
standpoint, though, there are four main climate Quantifying Glazing Performance connections.
types to consider: Let’s look briefly at the science behind these claims.
n Moist heating climate The energy efficiency of building materials is broadly
n Dry heating climate defined by their ability to conduct or resist energy
n Moist cooling climate transfer. For fenestration, energy performance is
n Dry cooling climate defined in two ways:
For each of these climate types, the IECC and n Solar heat gain coefficient (SHGC), a measure of

ASHRAE 90.1 provide prescriptive requirements for how much of the sun’s heat transmits through the
energy efficiency of the building envelope. Before windows and into the building interior.
applying these values, however, you must first n Thermal transmittance (U-factor), a material or

quantify certain key characteristics of the enclosure assembly’s propensity to conduct energy. U-factor
design to establish whether the prescriptive path is is the inverse of R-value, a measure of resistance
appropriate for the building. to energy transfer.
Within a building, most heat accumulation at-
STEP 3: Know Your Building tributable to radiation is the result of solar heat gain
Whether the prescriptive values set by ASHRAE and through the glazing. However, reducing the SHGC of
the IECC can be used to design an energy-efficient, windows is a tradeoff, for as SHGC diminishes so
code-compliant building envelope depends primarily too does visible light transmission (VLT), a measure
on the percentage of glass in the façade. of glass transparency.
As with heat gain, most energy loss at the build-
Prescriptive Path ing enclosure also takes place through glazed as-
The 2015 IECC states that, to follow the simpler, semblies. This tendency is reflected in the maximum
prescriptive path to energy code compliance, verti- allowable U-factor established by the IECC, which is
cal fenestration area must not exceed 30% of the higher for fixed fenestration than for mass walls by a

BDCuniversity.com | BUILDING DESIGN+CONSTRUCTION | 63


| THE BUILDING ENVELOPE |

factor of three. understand what an “energy-efficient” building enve-


In the design and lope really entails, it’s useful to consider what these
construction industry, values represent in terms of performance.
it is now generally The most straightforward path to energy code
accepted that fully compliance is the R-value method, whereby an
glazed walls are not exterior wall achieves conformance if insulation
necessary to achieve of a certain R-value is provided (as per IECC Table
optimal daylighting or C402.1.3). Although adding a thick layer of insula-
visibility. tion may seem the simplest way to meet energy-effi-
According to the ciency standards, the complexity of modern building
U.S. Green Building envelope systems may render this method impracti-
Council’s Leader- cal, or even impossible.
ship in Energy and A second path to compliance is the whole-assem-
Environmental Design bly U-factor method. In this approach, the thermal
Reference Guide for efficiency of the entire wall assembly is calculated
Building Design and to determine the overall U-factor, which is then
Construction, only win- compared to the maximum values set by the code
dow areas from two (per IECC Table C402.1.4). In practice, the whole-
feet, six inches to seven feet, six inches above the assembly method is likely the more complicated
Window performance floor are considered “vision glazing.” Windows below path to compliance, as the thermal values used for
testing establishes
thermal efficiency and
this “do not contribute to the daylighting of interior the various wall components are strictly dictated
moisture protection. spaces,” according to the USGBC. by ASHRAE 90.1. When modeling an enclosure to
Despite the established advantages of limiting demonstrate conformance, other material charac-
glazing area, there are reasons designers or build- teristics, such as heat capacity, must be taken into
ing owners might incorporate a greater proportion of consideration.
glass than the 30% cutoff. What then?
COMBATING AIR AND VAPOR MIGRATION
Building Envelope Tradeoff Option A code-compliant, properly designed, energy-efficient
Rather than plug in the energy-efficiency values set building enclosure relies not only on adequate insula-
by the IECC in the prescriptive path to compliance, tive performance, but also on comprehensive control
the project team would need to model the building to of the flow of air and moisture. The American Society
demonstrate that it will perform as efficiently as one of Heating, Refrigerating and Air-Conditioning Engi-
with the requisite percentage of glass. neers’ ASHRAE Handbook – Fundamentals warns that
Typically, such modeling follows the IECC methodol- “improving a building envelope’s energy performance
ogy for the Building Envelope Tradeoff Option, which may cause moisture-related problems,” and advises
enables designers to make up for inefficiencies in that “only a sophisticated moisture control strategy
certain elements of the building enclosure (in this can ensure hygienic conditions and adequate durabil-
case, a preponderance of glass) through superior ity for modern, energy-efficient building assemblies.”
performance of other assemblies, such as opaque Since heat, air, and moisture transfer are interrelat-
walls, roofing, or lighting. However, depending on how ed, the building envelope design must not treat each
far the proportion of vertical fenestration exceeds the separately, but, rather, should effectively integrate
prescribed maximum, compensatory efficiencies in comprehensive management of hygrothermal forces
other building systems may become cost-prohibitive (i.e., heat and humidity). Evaporation and removal of
or not in keeping with design requirements. water are of paramount concern.

UNDERSTANDING THERMAL EFFICIENCY Designing Comprehensive Air Barrier Systems


To quantify a material’s ability to resist the trans- The primary purpose of an air barrier system is to
fer of energy—to act as an insulator, rather than a reduce the flow of air between the building interior and
conductor—the design and construction industry exterior. However, air barriers may also restrict the mi-
uses R-value, the reciprocal of U-factor (the tendency gration of water vapor. Since excess moisture can lead
to transfer energy). In most cases, the IECC and to premature deterioration of building components,
ASHRAE 90.1 provide standard R-value and U-factor the design should consider the impact of air barrier
numbers of materials and assemblies, but to assemblies on water retention.

64 | BUILDING DESIGN+CONSTRUCTION | December 2017


ENERGY-EFFICIENCY CONSIDERATIONS
Design and installation of appropriate and com- FOR EXISTING BUILDINGS
prehensive air barriers is mandated by the IECC
(Section C402.5), which stipulates that air barri- Applying new energy require- tive, mandating that entire
ers must be continuous “throughout the building ments to existing buildings building systems or assemblies
thermal envelope.” To achieve compliance, care can be a difficult undertaking. be brought up to current code
should be taken to provide continuity of the air How do we assess the current standards, when only a portion
barrier across changes in the building envelope. thermal performance of the of that system is affected by
Large-format detail drawings are especially critical exterior enclosure of a build- a scope of work, could cause
to illustrate air barrier installation at transitions in ing constructed in the 1940s? financial hardship and a huge
materials and assemblies, changes in plane, and If we’re replacing 10 sf of a disruption to the building’s
intersections with fenestration and roof areas. façade, should we install an air activities.
Particularly at seams and transitions, the air barrier barrier as part of the replace- There is also a case to be
must be designed and installed to resist forces that ment system, even if the rest made for the impact such far-
tend to deteriorate the assembly, such as expan- of the building was constructed reaching alterations would have
sion/contraction and differential movement. without one? on the environment. Existing
Chapter 5 of the 2015 buildings have embodied ener-
Implementing Vapor Control International Energy Conserva- gy, a measure of the resources
IECC requirements for vapor control are less tion Code addresses the issue consumed to originally manu-
stringent than for air barriers. Without a compre- of energy performance when facture or extract materials
hensive air barrier system to restrict air working on existing build- and construct, say, a building
flow, vapor control strategies are ings. The IECC tries to façade. That energy can then
largely ineffective. The extent to strike a balance be- be compared to the additional
which vapor management is tween the need energy required to remove that
needed, and the appropriate to achieve a façade and replace it with a
design of such a system, is high level new one. Often, preserving the
dictated by: of perfor- embodied energy of the built
n Climate mance and environment by only addressing
n Building use and con- the financial the portion of an assembly that
struction and practical requires repair has a greater
n Potential sources of mois- limitations benefit to the environment than
ture beyond interior inherent to up- the increased energy efficiency
water vapor grading existing realized by complete replace-
Design consideration should assemblies. Section ment.
be given not only to keeping C501.2 establishes the The IECC discusses in some
water vapor out, but also to al- intent, stating, “…this code detail whether alterations re-
For some buildings,
lowing moisture to escape when shall not be used to require the quire compliance with the code
it may be less envi-
the building enclosure gets wet. ronmentally costly removal, alteration, or aban- when portions of existing sys-
To permit the exterior envelope to leave windows as donment of, nor prevent the tems or assemblies are modi-
is than it would be
to dry, a semipermeable vapor re- continued use and maintenance fied or replaced. New windows,
to replace them.
tarder may be specified. In other of, an existing building or build- for instance, need to comply
cases, a system with very low ing system lawfully in existence with the energy code, while
permeance may be appropriate, so the architect or at the time of adoption of this storm windows installed over
engineer should evaluate the building, climate, and code.” The IECC expands on existing fenestration do not.
situation and design accordingly. this concept by exempting The code also makes a dis-
When vapor retarders are required, their historic buildings from confor- tinction between “alterations”
placement relative to the insulation layer of the mance with the energy code and “repairs,” exempting the
wall assembly is extremely important. Typically when “compliance … would latter from compliance. Addi-
installed on the warm side of the insulation, “the threaten, degrade, or destroy tions to existing buildings are
retarder should be at or near the surface ex- the historic form, fabric, or afforded no such latitude and
posed to higher water vapor pressure and higher function of the building.” are regarded as new construc-
temperature,” according to the ASHRAE Hand- There are good reasons for tion by the IECC, requiring full
book – Fundamentals. ASHRAE 160 – Criteria for this. From a practical perspec- compliance with the code.
Moisture Control Design Analysis in Buildings is a

BDCuniversity.com | BUILDING DESIGN+CONSTRUCTION | 65


| THE BUILDING ENVELOPE |

recognized standard for evaluating the need for and of energy loss and incorporates thermal breaks that
placement of vapor retarders. insulate against heat transfer at windows, doors, floor
slabs, roof edges, and the bases of walls.
Dealing with Condensation The latest version of ASHRAE 90.1 now requires
When humid air contacts a cool surface, water vapor that linear transmittances must be accounted for in
changes from gas to liquid, collecting in droplets energy-performance calculations. Updated require-
through the process of condensation. To prevent ments for the Building Envelope Tradeoff Option
water damage, insulation should be thick enough to (ASHRAE 90.1, Normative Appendix C) stipulate that
maintain the surface above the dew point, the tem- uninsulated assemblies, such as projecting balconies,
perature at which condensation can occur. roof parapets, and floor slab edges, must be sepa-
Even without reaching the dew point, persistently rately modeled to achieve compliance.
high relative humidity can still create problems,
notably mold growth. Under the right conditions, WHEN HIGH-EFFICIENCY ENCLOSURES
though, a limited amount of interstitial condensa- GO WRONG (AND WHAT TO DO NEXT)
tion can be tolerated, provided there is ample If high-efficiency enclosures are designed incorrectly,
opportunity for the assembly to dry. Analysis of they can actually have an adverse impact on perfor-
moisture migration is complicated, and an accurate mance. Common problems include:
evaluation requires consideration of numerous vari- n Condensation

ables within the building system. n Drafts and cold spots

n Mold growth

PROVIDING HIGH-EFFICIENCY DETAILING n Premature deterioration of building materials and

Unfortunately, the danger of overreliance on simpli- assemblies


fied models is not limited to condensation analysis. n Scant energy savings and increased costs

Thermal efficiency calculations, too, tend to oversim- Ironically, even when they are designed correctly,
plify the behavior of the system. Analyses used to high-efficiency building enclosures can still succumb
determine energy code compliance for opaque wall to problems. Notably, the comprehensive insulating of
assemblies, including the R-value method and whole- the building envelope has led to increased problems
assembly U-factor method, may overrate insulating with snow and ice build-up on the exterior of buildings.
value by as much as 80%. To compensate for the thermally insulated enclosure’s
What these models fail to consider, primarily, is ther- tendency toward moisture accumulation in the colder
mal bridging, whereby highly conductive materials pass months, the design professional can include provi-
through insulation layers and transmit heat across sions to optimize weather integrity while maintaining
the wall assembly. Generally, thermal bridges can be peak energy performance.
grouped into two categories, based on their geometry:
n Linear transmittances, where heat flows across the THE FUTURE OF ENERGY-EFFICIENT
exterior wall along a two-dimensional length, such BUILDING ENVELOPES
as at floor slab edges, parapets, window and door As states continue to seek opportunities to reduce
heads/sills/jambs, and the base of walls energy consumption, more attention will be paid to
n Point transmittances, which transfer heat at a building envelope details that reduce inefficiencies. In-
single point of intersection between the wall and corporation of design details that minimize energy loss
another object, such as at beam penetrations. can result in improved indoor comfort, as well as cost
How significant is the impact of thermal bridging savings through smaller heating, ventilation, and air-
+EDITOR’S NOTE on energy performance? For a simple opaque exterior conditioning (HVAC) packages and reduced utility bills.
wall, the clear field, or basic wall assembly without To balance performance and practical consider-
This completes the
penetrations, might have an R-value that falls well ations, an energy-efficient enclosure should apply
reading for this
within the prescriptive requirements for the climate principles of energy transfer, heat loss, and moisture
course. To earn
zone and type of construction. However, factoring in migration. By considering how energy code require-
1.0 AIA CES HSW
learning units, study linear transmittances could reduce the total R-value ments are derived and why certain design factors
the article carefully by more than 50%. impact performance, building owners, managers, and
and take the exam This reduction in performance illustrates the impor- design professionals are better positioned to develop
posted at tance of eliminating linear and point transmittances in building envelope solutions that achieve real-world
www.BDCnetwork. building enclosure design as much as possible. High- efficiency demands without compromising aesthetics,
com/HEfacades efficiency detailing considers these potential sources comfort, or longevity. +

66 | BUILDING DESIGN+CONSTRUCTION | December 2017

You might also like