3710 ACM

3-Phase Power
Instrumentation
Package

■ Demand Management
■ Commercial/
Industrial Metering
■ SCADA

The 3710 ACM is an economical, panel- Cost Effective


■ Replaces dozens of separate meters
mounted, 3-phase digital power monitoring ■ Simple installation
instrument. Well established and successful, Measurements
the 3710 ACM offers high accuracy, ■ True RMS voltage, current & power

reliability and exceptional ruggedness. It is Data Logging


■ Waveform Capture
an affordable solution for power utilities and ■ Scheduled or event-driven logging
industrial or commercial power distribution ■ Min/Max logging
systems. The 3710 ACM can be used ■ Sequence of events logging

stand alone or as one element in a large Extensive I/O


■ 4 digital/counter inputs
energy management network. ■ 3 digital relay outputs
Powerful Setpoint Control System
■ Setpoint on any parameter or condition
Communications
■ Supports Modbus, DNP and PLC/AB
2
3710 ACM
Front Panel Display Extensive I/O Control
The front panel features an easy-to-read, Use the inputs to monitor utility KYZ initiators, The 3710 ACM setpoint system provides
20-character vacuum fluorescent display. device cycles, running hours, etc. Outputs intelligent logging and control functions.
Voltage, current and power functions can all can be used for equipment control, alarms,
be displayed together for the selected phase. etc. Programmable Setpoint Control
Voltage or current readings can be displayed Setpoints are defined by independent high
for all three phases concurrently. Status Inputs and low trigger limits (for operate/release
The 3710 ACM may also be ordered with ■ Four optically isolated, digital (status) hysteresis), and time delays on both operate/
no front panel display for use as a digital inputs can monitor status, count pulses, release for the resulting function. Multiple
power transducer. or any other external dry contact setpoints can be channelled to a single relay
■ Four sealed membrane switches for ("OR" function) for multi-level setpoint
parameter selection and programming Relays protection functions. All setpoint activity is
■ Select voltage and current readings ■ 3 on-board relays controlled recorded automatically in the on-aboard
using the PHASE key automatically by the internal setpoints or Event Log.
■ Common power functions are available manually via a communications port ■ 17 setpoints, one second (typ.) response
using the FUNCTION key ■ Programmable for kWh, kVARh or kVAh time
■ Display the maximum and minimum output pulsing ■ Any setpoint condition can be set to
values for each measured parameter ■ Form C mechanical relays rated at 10 A control relays
using the MAX/MIN keys (AC or DC); or single-pole, single-throw
■ Programming and control is password solid state relays rated at 1 A (AC only)
protected
Auxiliary Output
■ Auxiliary analog current output provides
0-20mA or 4-20 mA proportional to any
3710 ACM Power Meter
measured parameter

Inputs and Outputs

Vacuum Fluorescent Displays

Full Width Display

Multi-reading Display
3710 ACM 3

Metering Logging & Recording Sampled waveform data is stored in on-board


memory and read via the communications
The 3710 ACM provides high accuracy true The 3710 ACM provides three types of on- port. High resolution data can be used by
RMS measurements of voltage, current, board data logging: events, min/max levels, Power Measurement's software for detailed
power and energy readings, as well as and snapshot readings are all automatically power quality analysis.
minima, maxima, and status parameters. All time-stamped and recorded in non-volatile ■ Perform high-speed sampling of any
parameters are quickly accessible via the memory. There is also a waveform capture voltage or current input
front panel display or through the feature. All logging functions are continuous ■ One full cycle of any voltage or current
communications port. Voltage, current, and concurrent. input sampled at 128 samples per cycle
power and energy readings are sensitive to Using Power Measurement’s software you
beyond the 50th harmonic. Four-quadrant can display all logged data. The software will
readings measure bidirectional (import/ automatically archive to disk all logged data
export) energy flow, useful in any retrieved from each device. The data can be
cogeneration application. converted to file formats compatible with other
software.
Instantaneous Min/max values can also be viewed via
■ Voltage (l-l/l-n), per phase & average the front panel. Single-cycle waveform recording displayed in
■ Current, per phase & average Power Measurement’s PowerView software
Historical Logging
■ Neutral Current Produce daily/weekly/monthly load profile
■ Real, Reactive & Apparent Power, total graphs for important readings.
(per phase available via ■ Log up to 12 channels of time-stamped
communications) data: V avg, I avg, kW total, kVAR total,
kW total Demand, I avg Demand, PF,
■ Power Factor, total Vaux, Frequency, kWh import, kWh
■ Frequency export, and kVARh total
■ Auxiliary Voltage
■ Trigger at specified time intervals, 1
second to 400 days for preset &
■ Phase Reversal programmable logs

Energy Minimum/Maximum Logging Historical trend displayed in PowerView


Real & reactive, imported, exported, total Records extreme values for system
and net kWh & kVARh. Apparent energy, operations analysis, troubleshooting and
total kVAh. problem tracking.
■ Records extreme values for all
Demand measured parameters
Sliding Window Demand calculated for ■ Minima/maxima for each parameter are
average current and total real power, or for logged independently with a date and
total apparent power and total real power. time stamp @ 1 second resolution
Minimums and Maximums
Event Logging & Alarming
Recorded for all base measurements &
Records all setpoint/alarm conditions, relay
Sliding Window Demand values.
operations, setup changes, and self-
diagnostic events. Single-cycle waveform recording displayed in
■ The 3710 ACM stores up to 50 date & PEGASYS software
time stamped records
■ Time stamp resolution to 1 second
■ Sequence-of-event recording

Waveform Capture
4
3710 ACM
Communications Software Integration Connections
The 3710 ACM can be integrated within The 3710 ACM can be readily integrated into
energy monitoring networks and supports a an energy management or SCADA system. Installation
variety of protocols. Links between remote Systems are easily expandable using any of ■ 4-wire Wye, 3-wire Wye, 3-wire Delta,
sites can use RS-485 or modems with the 3000 or 7000 series devices. and Single Phase systems
telephone lines (dedicated or dial-up), fiber ■ 3 voltage and 3 current inputs
optic and/or radio links. PEGASYS® ■ 1 current input for neutral or ground
Power Measurement’s Windows NT-based current monitoring
Optional Communications Port power monitoring software. PEGASYS
■ Single optically isolated, transient displays both real-time and logged data and
protected port offers manual control and configuration
Voltage & Current Inputs
■ For systems up to 347 VAC line-to-
■ Data rates up to 19,200 bps. capabilities. Its robust client-server
neutral / 600 VAC line-to-line no PTs are
RS-232 or RS-485 architecture provides enterprise-wide data

required
sharing in a secure networked environment.
■ PML, A-B DF1, Modicon Modbus RTU ■ For higher voltage systems, PTs with
or Alarm Dialer protocols
SCADA Software 120 VAC secondaries must be used
The Alarm Dialer (AD) communication Power Measurement’s economical DOS- ■ 5 A nominal full scale current inputs,
protocol enables the 3710 ACM to based power monitoring software (or optional 1 A current inputs)
automatically contact a master display station (M-SCADA, L-SCADA, and PowerView for 300 A surge protection
on the occurrence of an alarm condition. DOS). Provides power quality analysis tools ■ The basic model provides 125% current
and advanced control capabilities within a overrange capability
secure access system.
Control Power
The 3710 ACM can be powered from a
dedicated fused feed, or from the voltage
source it is monitoring.

Example Connections

4-Wire Wye (Direct Connect) 3-Wire Delta (2 PTs and 3 CTs)


3710 ACM 5

Measurement Specifications Input & Output Ratings


Parameter Accuracy‡ ±(% full scale) Resolution Range Voltage Inputs
Voltage 0.2 % 0.1 % 0 - 999,999* ■ Basic: 120 line-to-neutral / 208 line-to-line nominal
Current (see options) 0.2 % 0.1 % 0 - 30,000 full scale input
Neut/Gnd Current 0.2 % 0.1 % 0 - 9,999 ■ 277 Option: 277 VAC nominal full scale input
kW (& demand) 0.4 % 0.1 % 0 - 999,999† ■ 347 Option: 347 VAC nominal full scale input
kVAR (& demand) 0.4 % 0.1 % 0 - 999,999† ■ All options: Overload withstand: 1500 VAC
kVA (& demand) 0.4 % 0.1 % 0 - 999,999† continuous, 2500 VAC for 1 second.
Input impedance for all options: 2 MW
Power Factor 1.0 % 1.0 % -0.6 to 1.0 to +0.6
Frequency 0.2 Hz 0.1 Hz 50, 60, 400Hz Current Inputs
kWh 0.4 % 1 kWh 0 - 999,999,999 ■ Basic: 5.0 Amps AC nominal full scale input
kVARh 0.4 % 1 kVARh 0 - 999,999,999 ■ 1AMP Option: 1.0 Amp AC nominal full scale
kVAh 0.4 % 1 kVAh 0 - 999,999,999 ■ All options: Overload withstand 15 Amps
continuous, 300 Amps for 1 second. Input
Vaux (1 VAC scale) 0.25 % 0.1 % 0 - 999,999
impedance: 0.002W
*
Reads in kV for voltages over 9,999. Reads in MW, MVAR, MVA for readings over 9.999k.


@50.0 Hz or @60.0 Hz @ 25°C/77°F. ■ Burden: 0.05 VA
Aux. Voltage Input
■ 1.0 VAC/VDC nominal full scale input (1.25 VAC
Waveform Capture & Recording /VDC max.) Overload withstand: 120 VAC/
Sampling Rate Accuracy Resolution VDC continuous, 1000 VAC/VDC for 1 second.
Input impedance: 10 kW
Waveform Capture 8 kHz† (128 times/cycle) 2% of full scale 10 bits (0.1 %)
Aux. Current Output

Approximate
■ 0 to 20 mA into max. 250W load. Accuracy: 2%
Control Relays
User Programmable Log Capacity ■ Basic: Form C dry contact electromechanical
relays, max. 277 VAC or 30 VDC @ 10 Amp
Example configurations resistive
Parameters per log Interval Capacity per Log ■ SSR Option: SPST solid state relays, 24 to 280
12 with 3710 ACM 15 minutes 25 hours VAC @ 1 Amp AC resistive (AC operation only)
Status Inputs
■ Basic: external-excited, S1, S2, S3, S4

Mounting Front View - >20 VAC/VDC = active, <6 VAC/VDC =


inactive
The 3710 ACM can be panel-mounted in a Input impedance: 49.2 kW Overload withstand:
switchgear cabinet or other location for 1500 V continuous, 2500 V for 1 sec.
easy access and viewing. ■ SES Option: self-excited +30 VDC differential
■ Mounted flush against any flat surface SCOM output to S1, S2, S3, or S4 input
■ Only a single cutout is required ■ All Options: Minimum Pulse Width: 40 msec.
Power Supply
■ Basic: 85 to 132 VAC / 47 to 440 Hz or 110 to
Side View 170 VDC @ 0.2 Amps
Cutout (display & Tran model) ■ P24/48 Option: 20 to 60 VDC @ 10W
■ P240 Option: 85 to 264 VAC / 47 to 440 Hz or
110 to 340 VDC / 0.2 A
Environmental Conditions
Operating Temp: 0oC to 50oC (32oF to 122oF)
ambient air
(XTEMP Option): -20oC to +70oC (-4oF to +158oF)
Storage Temp: -30oC to +70oC (-22oF to +158oF)
Humidity: 5 to 95 %, non-condensing
6
3710 ACM
Meet the Ordering Information Shipping
World Leader ■ 3.8 kg (8 lb, 6oz)
For over two decades, Model Options ■ 38 x 25 x 18 cm (15" x 9.8" x 7.1")
Power Measurement has 3710 ACM includes display, logs and I/O

been providing cost-effective


3710 ACM Display includes display only
3710 ACM TRAN includes logs, I/O and comm Standards
power monitoring, analysis,
Meter Options
card without display
Compliance
and control systems to
(specify when ordering) Voltage, Current, Status, Relay and Power inputs all
customers around the globe pass the ANSI/IEEE C37.90A-1989 surge withstand and
including power utilities, com- 277 To monitor 277/480 Volts or fast transient tests.
240/380 Volts (instead of 120/208
mercial and industrial Volts)
facilities, and major electrical 347 To monitor 347/600 Volts LR 57329 E95810
OEMs. Let our experience
(instead of 120/208 Volts)
1AMP 1 Amp nominal full scale
and proven track record give current inputs Warranty
you an end-to-end energy COMM Combination RS-232/RS-485 plug 3 years limited parts and labour, F.O.B.
in comm card Saanichton, B.C., CANADA
management solution that ex-
PLC/AB* Allen-Bradley communications
ceeds your expectations. protocol
PLC/MOD Modicon-Modbus communications
protocol
AD Alarm Dialer protocol
SES Self-excited status inputs
SSR SPST solid state relays
(instead of Form C electro-
Worldwide Headquarters mechanical)
Power Measurement Ltd. P24/48 20 to 60 VDC power supply
2195 Keating Cross Road, (instead of 120 VAC)
Saanichton, British Columbia, Canada V8M 2A5 P240 85 - 264 VAC or 110 - 340 VDC
Tel: 1-250-652-7100 Fax: 1-250-652-0411 kVD kVA Demand replaces Amps
Web: www.pml.com Email: sales@pml.com
Demand
Europe & Middle East XTEMP Extended operating temp. range:
Power Measurement Europe -20oC to +70oC (-4oF to +158oF)
Bayreuther Strasse 6, D-91301 Forchheim, TROP Tropicalization (conformal coating)
Germany treatment
Tel: 49-9191-7005-25 Fax: 49-9191-7005-20 RACK 19 inch rack mount panel
Email: pme@pml.com
* Not supported by Power Measurement software.
Asia & Pacific
Power Measurement Australia Ordering Example
7/16 Ledgar Road This example specifies a 3710 ACM with the -
Balcatta, Perth, Western Australia 6021 277 volts option, communications card with the
Tel: 61-89-345-3866 Fax: 61-89-345-3899 Modbus protocol option, and powered by P240:

3710ACM -277 -COMM -MOD -P240

Officially Registered

Revision Date: Sept 30 1999 © 1999 Power Measurement Limited


All Rights Reserved Printed in Canada 70100-0000

All trademarks are the property of their respective owners.


Any reproduction or re-transmission in whole or in part of
this work is expressly prohibited without the prior consent
of Power Measurement Ltd. Please contact head office for
copyright permission. Information contained herein is YOUR LOCAL
subject to change without notice.
R E P R E S E N TAT I V E

You might also like