Professional Documents
Culture Documents
MATLAB software’s
Kourosh Mousavi Takami1, Hasan Gholnejad2 and Jafar Mahmoudi3
1,2:Ph.D. student in Mälardalen University, 3: professor in Mälardalen University
Box 883,721 23, IST Dep., Mälardalen University, Västerås, Sweden
1.kourosh.mousavi.takami@mdh.se, 2.hasan.gholinejad@mdh.se, 3.jafar.mahmoudi@mdh.se
1-4244-1106-8/07/$25.00
C 2007 IEEE —1—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007
of the fact that the estimation of temperature using the of the HST. This calls for a major revision of the thermal
formulations there in is not as accurate as are desired, new model considering the following changes.
and improved methods need to be developed to mitigate ¾ Oil is a Newtonian and incompressible fluid.
the situation. ¾ Properties of solid materials and fluids change
A perusal of current literature in this area indicates with the temperature.
that in the recent past, conventional heat run tests ¾ Fluid flow is laminar, unsteady and two-
performed after the transformer was manufactured were dimensional.
the only means of acquiring information on the magnitude ¾ There is internal heat generation.
of the possible HST, but the location of HST was not ¾ Effects of thermal radiation are included.
possible. The extrapolation of heat run test results to ¾ The transformer winding shall be treated as a
quantify the amount of insulation degradation was found thermally anisotropic structure, which is actually
to be highly inaccurate [2]–[5]. Recently, various methods true in practice.
have been suggested for direct measurements of HST in ¾ The heat source should be considered as a
transformer windings using fiber-optic sensors and function of the local temperature (distributed
fluoro-optic thermometers and the optimal location of heat source) in cylindrical or Cartesian
these sensors has also been demonstrated. It has been characterizing.
reported [6], [7] that optoelectronic modules have since ¾ The initial temperature distribution function
been introduced in the full-size transformers. should be rewritten as a new function of the
Certain empirical formulae have been proposed [4], curvature of the transformer winding.
[8], [11] whereby transformer designers could estimate
possible maximum winding temperature at the design
stage. These formulae, although not very accurate, serve
as broad guidelines for verifying the designs. It is
therefore important to note that a worthwhile treatment of
the thermal aspects of a transformer has been made only
very recently [9], [10] wherein a semi theoretical model
has been proposed to study certain aspects of heat transfer
in cylindrical geometries. A comprehensive report
generated by the CIGRE working group 12, examines,
critically, all aspects of diagnosis of power transformers
to show that the conventional factory heat run test and/or
gas analysis fail to provide information on the magnitude Fig.1. Simple model of transformer winding, HV = disc, LV =
of HST and overloading limits [2], [3]. In continuation to layer.
the IEEE Transformer loading guide [8], a recent
addendum [12] to it gives further information on thermal In most of work by another authorized, the thermal
modeling of a power transformer. An equivalent circuit time constant of the winding was assumed to be a
analogy of transformer model considered by Swift et al notional value of 5 min. In this paper, it has been found
[13]. Admittedly, these models are mathematically much with calculation.
simpler. The calculation of average bulk oil and winding 2. Experimental Data and Governing Equations
temperature can be made, knowing the thermal capacity
of the solid (winding) or liquid (oil) medium. Since the 2.1. Simplified Transformer Winding and
masses of winding and oil bulk are known from the experimental data
design, the heat capacity of bulk oil and winding can be Text The structure of a transformer winding is complex
easily calculated. These models present difficulties when and does not conform to any known geometry in the strict
used to estimate temperature of the hottest spot, or top-oil sense. Under fairly general conditions, the transformer
temperature. cores can be assumed rectangular in formation; hence, a
Earlier work in this area [1], [14] assumes a constant layer or a disc winding is considered to be a finite annular
heat source operating over the entire winding structure, cylinder. The thermal and physical properties of the
besides treating the winding to be thermally isotropic. system would be equivalent to a composite system of
Also, a single empirical heat-transfer formula suggested insulation and conductor. A simple geometry of a model
thus far for calculating the boundary layer temperature transformer winding is given in Fig. 1. In the current
drop has been applied to all surfaces of the winding [14]. paper, the heat generated in the body of the winding is
But this is found to be incorrect as the mechanism of taken to be a function of the local temperature [see (9)].
natural heat convection in the axial direction is markedly The heat is conducted away from here by the insulating
different from that along the radial direction. Such an oil in constant circulation in the vertical and horizontal
assumption holds true for layer-type winding only. The ducts by a process of convection. However, in an actual
authors have now embarked on a technique for improving transformer, the copper conductor is the heat source and
the accuracy of predicting the magnitude and the location is distributed over the volume of the cylinder defining the
—2—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007
winding geometry. The heat generated in insulation due to Rated hot spot rise 58.6 50.8
dielectric loss is normally ignored. Rated average winding rise 41.7 39.7
The process of heat transfer in transformers is due both Rated bottom oil rise 16
to conduction and to convection. The mixed boundary Initial top oil 38.3
value problem describing the process automatically takes Initial top duct oil 38.3
care of both the modes of heat transfer. Initial average winding 33.2
Figure 1 shows that: Initial bottom oil 28
– Oil only flows through ducts Initial hot spot 38.3
– 10 degree winding rises are typical; makes two stage Transformer component weights, kg
cooling almost impossible Mass of core and coil assembly 172200
– Number of ducts limited by short-circuit strength Mass of tank 39700
– Demand a heat-run if two stage cooling is expected Mass of oil 37887
62
low voltage w inding
Q GC is the heat generated by the core losses, W.
60
58
temp Q GSL is the heat generated by stray losses, W.
56
high voltage w inding
temp
Q AO is the heat absorbed by the tank core oil, W.
54 oil temp. Q LO is the heat lost by the oil, W.
52 Q GC=PCR are the rated core losses, W.
50
1 3 5 7 9 11 13 15 17 19 21 23
Hours
2.2. Governing Equations of Heat Flow
With the thermal conductivity, in rectangular
coordinate system is written as
Variations of ambient temprature
¾ Continuity equation
∂ρ ∂ ∂
40
+ ( ρu ) + ( ρv) = 0 (1)
35
30
∂t ∂x ∂y
¾ Linear momentum equation in the x
Temp. (oc)
25
20 direction
15
∂ ( ρu ) ∂ ∂
10 + u ( ρu ) + v ( ρu ) =
5 ∂t ∂x ∂y (2)
0
∂p ∂ ∂u ∂ ∂u
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33
− + (µ ) + (µ )
Hours ∂x ∂x ∂x ∂y ∂y
¾ Linear momentum equation in the y
Fig.2. Variation of temperature in transformer and ambient for
three winding 250MVA, 230/63/0.4KV transformer on July direction
2006 in Pounel 230/63/20KV substation – Iran ∂ ( ρv) ∂ ∂
+ u ( ρv ) + v ( ρv ) =
∂t ∂x ∂y (3)
Figure 2 shows the variations of temperature in oil, LV ∂p ∂ ∂v ∂ ∂v
winding, HV winding and third winding a 230/63/0.4 KV − + ( µ ) + ( µ ) − g ( ρ − ρ ref )
∂y ∂x ∂x ∂y ∂y
transformer and ambient temperature in July 2006.
According IEEE standard data’s for 250 MVA Power ¾ Energy equation
transformer in IEEE loading guide 1995:[6]
Transformer Losses, W. ∂ ( ρC p T ) ∂ ∂
( ρC pT ) + v ( ρC pT ) =
+u
No Load 78100 ∂t ∂x ∂y (4)
Pdc losses (I2 Rdc ) 411780 ∂ ∂T ∂ ∂T
Eddy losses 41200 (k ) + (k ) + A(t )q′′′
∂x ∂x ∂y ∂y
Stray losses 31660
Nominal voltage 118 KV 230KV 0 for fluids
Pdc at hot spot location 467 527 −4
Eddy current losses at hot spot location
A(t ) = − 1.37 ×10 −9 × t 2 + 0.805 ×10 × t + 0.1358
309 (0.65 pu) 157 (0.3 pu) for the compunents of the active unit
Per unit height to winding hot spot 1 1
Temperature Rise °C .
Rated top oil rise 38.3
Rated top duct oil rise 38.8
—3—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007
In the above equations, temperature T , is a function The cu-loss in the winding per disc/layer of the above
of space variables x, y and z and time variable t transformers has been tabulated in appendix1. The total
(i.e., T = T ( x, y, z , t ) ), that z(thickness) is constant in losses in transformer 250 MVA are 562,780 kW (0.23%).
this model . The term A (t) is coefficient of the heat power transformer heat propagation in quiver and contur form
source function, and has been modified here to take care 1 200
of variation of resistivity of copper with temperature at
time t. With this representation, the function A becomes 180
0.8
time dependent, distributed, heat source.
ra d iu s o f w in d in g %
160
0.6
2.2.1. Boundary condition 140
x = 0, y = y, t = t , u = v = 0
0.4 120
∂T T (5)
− k w w = hyl ( − Tf ) 100
∂x x=0 0.2
T 80
+ εσ .(( + 273) 4 − (T f + 273) 4 )
x=0 0 60
0.2 0.4 0.60 0.8 1
ε = 0.2, σ = 5.67 × 10 −8 k 2 4 Height of core and winding %
m k
x = l x , y = y, t = t , u = v = 0 Fig. 3. Temperature distribution in the high voltage disc.
y = 0, x = x, t = t , u = v = 0 0.6
140
∂T T (7)
− k w w = hyb ( − Tf ) 0.4 120
∂y y=0
100
T 0.2
+ εσ .(( + 273) 4 − (T f + 273) 4 ) 80
y=0
0
y = l y , x = x, t = t , u = v = 0 0 0.2 0.4 0.6 0.8 1
60
Height of core and winding %
∂Tw T (8)
− kw = hyt ( − Tf ) Fig. 4. Temperature distribution of low voltage (LV) winding
∂y y = ly layer.
T
+ εσ .(( + 273) 4 − (T f + 273) 4 )
y = ly
Wc = 2.17. f . pb (Tw − T f )1.25 (9)
q′′ = h.(Tw − T f ) (10)
—4—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007
varying heat loss/unit volume. The method suggested by The time constant of the transformer winding can be
the authors gives due representation for this omission and, determined. The thermal time constant of winding is
hence, is believed to give more accurate estimates. around 4.5–5 min. These values have been expressly
It may be observed that the maximum temperature calculated (and not assumed as was done earlier) using
occurs in the neighborhood of 80–95% of the axial and the thermal parameters of the winding.
50% of the radial thickness of the disc. It is illustrated in
table I. Fig. 3 and figures 5 shows the spatial temperature Table I: HST Magnitude and Location in ONAN
distribution in a disc-type Hv winding. It may be 250KVA Transformer , Amb. Temp. =33 c , on humidity=60%
observed that the HST would occur around the location of detail description HST HST cal
the second or the third disc from the top as surmised. But pu load winding type HST local local R/L IEC M1
this position would change if there is oil stagnancy in the 1 hvd 91 88/53 113 97
cooling ducts. In a layer winding, the HST occurs at lvd 94 85/43
around 80 to 95% of winding from the bottom. The 1.25 hvd 116 84/47 140 123
spatial temperature distribution for a layer winding in, lvd 120 82/57
plane has been shown in Fig. 4. Under OFAF modes of 1.5 hvd 142 86/48 172 148
cooling, the magnitude and location of the HST at lvd 147 81/44
different loading have been shown in Tables I. The 1.8 hvd 182 81/43 215 182
lvd 185 81/43
computed value of the HST, arrived at the estimated
2* hvd 205 89/39 245 221
temperature of the hot spot and its location seem to be in
lvd 214 82/44
line with the field measurements. However, there appears
2.2* hvd …. 83/46 280 245
to be no published literature giving this information lvd 244 85/48
against which comparisons can be made.
*There are instances [16] in which large power transformer are
However it is obviously necessary to limit the core loaded to as high as 2.5 pu although the limit there-on is 1.5 pu
temperature to values that cause no damage to the core as per the IEEE guide
itself, adjacent materials, or the oil. It has been shown in
figures 3, 4, 5 and table 1 and 2that core temperatures as Table II: variation of viscosity and density with
low as 110 C–120 C may degrade oil. This has led experts temperature in oil of the transformer
in the field to suggest that 130 C with 0.08m/s for oil Velocity Temperature Temperature
speed would be a reasonable limit for the core Density Viscosity
m/s in bottom (oc) in top(oc)
temperature. 0.001 40.063 302.66 684.92 0.226
VIS,D,TOT,BOT versus V 0.002 40.033 199.48 685 0.226
0.003 40.025 155.32 688 0.226
900
800 0.004 40.021 131.18 685.5 0.226
700
VIS,D,TOT,BOT
—5—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007
2) Velocity, density and viscosity [10] , “Predicting liquid filled transformer loading
On the table II and figure 6 shows that with increasing capability,” IEEE Trans. Ind. Applicat., vol. 30, pp. 170–
of oil velocity will be decrease top oil temperature and 178, Jan./Feb. 1994.
density and viscosity will be increase in oil and so [11] “IEEE Loading Guide for Mineral Oil Immersed
temperature will be constant in bottom oil. That means Transformer, C57.91/Corrigenda,”, Draft Corrigenda to
with increasing of velocity could improve the condition of C57.91-1995, 2001.
cooling and decreasing the TOT and HST. Of course the [12] IEEE Guide for Determination of Maximum Winding
medium of core and winding temperature would be more Temperature Rise in Liquid-Filled Transformers, IEEE
than TOT while oil velocity is over of 0.08m/s. Std. 1538-2000, Aug. 2000.
[13] G. Swift, T. S. Molinski, and W. Lehn, “A
4. Conclusions fundamental approach to transformer thermal modeling.
The heat source function has been taken as Part-I: Theory and equivalent circuit,”
temperature dependent. The thermal model presented here IEEE Trans. Power Delivery, vol. 16, pp. 171–175, Apr.
can predict the hotspot location, with a higher degree of 2001.
accuracy than was hither to possible. The result of the [14] S. A. Ryder, “A simple method for calculating
study on the rate of convergence indicates that the winding temperature gradient in power transformers,”
convergence is indeed quite rapid and nearly monotonic. IEEE Trans. Power Delivery, vol. 17, pp. 977–982, Oct.
Also, suggestions have been made as to the optimum 2002.
numbers of terms to be considered to obtain sufficient [15] M. N. Ozisik, Boundary Value Problem of Heat
accuracy. It has been shown that core temperatures as low conduction. Scranton, PA: International Textbook, 1968,
as 110 C–120 C may degrade oil. This has led experts in pp. 467–475.
the field to suggest that 130 C with 0.08m/s for oil speed [16] H. Nordman and M. Lahtinen, “Thermal overload
would be a reasonable limit for the core temperature. tests on a 400 MVA power transformer with a special 2.5
p.u. short time loading capability,” IEEE Trans. Power
References Delivery, vol. 18, pp. 107
[1] M. K. Pradhan and T. S. Ramu, “Prediction of hottest
spot temperature (HST) in power and station
transformers,” IEEE Trans. Power Delivery, vol. 18, pp.
1275–1283, Oct. 2003.
[2] R. Hurter and F. Viale, “Thermal aspects of large
transformers, test procedures hot spot identification,
permissible limits, their assessment in factory tests and
service, overload limitations, effect of cooling system:-
Presented in the name of study committee-12,” in Proc.
CIGRE.12–13 30th Session, vol. 1, 1984.
[3] J. Aubin, “Thermal aspects of transformers:-Presented
in the name of study committee 12,” in Proc. CIGRE
Paper, 12-1073 1990, vol. 1, Aug./Sept. 1990.
[4] “Loading Guide for Mineral Oil-Immersed Power
Transformer,”, IEC- 354, 1991.
[5] M. V. Thaden, S. P. Meheta, S. C. Tuli, and R. L.
Grubb, “Temperature rise test on a OFAF core-form
transformer, including loading beyond name plate,” IEEE
Trans. Power Delivery, vol. 10, pp. 913–919, Apr. 1995.
[6] W. Lampe, L. Pettersson, C. Ovren, and B.
Wahlstrom, “Hot spot measurement in power
transformers,” in Proc. CIGRE Paper, 12—02 30th
Session, vol. 1, 1984.
[7] W. J. Mcnutt, J. C. McIver, R. V. Snow, and D. J.
Fallon, “Transformer loading capability information
derived from winding hot spot measurements,”
in Proc. Int. Conf. Large High Voltage Electrical System,
30th Session, vol. 1, CIGRE, Paris, France, 1984, Paper,
12-08.
[8] “IEEE Loading Guide for Mineral Oil Immersed
Transformer,”, C57.91.1995, 1996.
[9] L. W. Pierce, “An investigation of the thermal
performance of an oil filled transformer winding,” IEEE
Trans. Power Delivery, vol. 7, pp. 1347–1358, July 1992.
—6—
8th. Int. Conf. on Thermal, Mechanical and Multiphysics Simulation and Experiments in Micro-Electronics and Micro-Systems, EuroSimE 2007