Professional Documents
Culture Documents
Paper 47-144, recommended by the AIEE commit- must be kept in mind. Under present cir- high voltage winding, corresponding to a
tee on electric machinery for presentation at the cumstances the desirability of full voltage stated shape of applied wave, is specified to
AIEE summer general meeting, Montreal, Quebec, impulse testing of commercial transformers the purchaser by actual figures. Thus, the
Canada, June 9-i3, i947. Manuscript submitted is questioned. The desirability to the trans- degree of control of impulse voltage distri-
Marh8,1 14;9aeavialefrprnig.pi former manufacturer of a continuous -im- bution is predefined. When the machine is
assembled the distribution of voltage is
M. B. MALLETT is transformer engineer in the pulse voltage research program, together
English Electric Company of Canada, Ltd., St. with full voltage laboratory facilities, is not measured and the results compared with the
Catherines, Ontario, Canada. questioned. specified maximum values in the contract.
- ,| B $ * $ @ i 5 * 0
: U : i
t g | %
age testing, the commercial distribution
test completely eliminates the serious
hazard of undetected damage. Also,
0
o
0 t " > t g @g 5*3° .. 6.0% the distribution test is inherently a simple
||| '3 i 8 86.0% and practical test which lends itself
a1 -- 3 , 4 70.7% I readily to routine production work.
Such testing can be conducted quickly
5
2 38.7% O
L 20. 9 TURNS FROM NEUTRAL and at reasonable expense.
0% The testing procedure as just outlined
t ~~~~~HIGH
HIGH VOLTAGE NEUTRAL
steers a middle course between the ex-
tremes of no commercial impulse testing
WINDING CONNECTIONS FOR TEST and full voltage commercial impulse
testing. The procedure has been adopted
w9 L_- - n -N4 - - - - - - - - - for the present as a practical compromise
|n cu |N co t N
2 - w1which best meets the conflicting factors
> U) z z z z z z z z z z z z z oa z z z as they now exist.
o100 F Figure 1 shows the results of a dis-
-' 90u - - tribution test s take n a ommercial
QL.L distributed concentric type transformer.
< 80 F
The measured voltages were scaled from
° 70
EL
I I I L I I I I I I I __oLI I theoscillograms shown inFigure2.
z
> In practice it is to take
only necessarymeasure-
u a l .a relatively small number of
50 ---t-I ments in order to establish the ruling
Z 40 m- ____ stress picture in the distributed con-
| 1 l < { | _ H 1 1 1
centric winding structure. Typical meas-
v 3o | < l
s 30 ci urements ordinarily required are as
0 0) co rQ ~ ~ ~ ~ ~ ~ ~ tabulatedin Figure 1, excepting that
10 | __ o | o o F_ voltages involving tap leads are included
< 0
2 ) co|~~ C1- .-.. °. an
(D -. __ )c - PO r- 0 The meas-
only for one tap connection.ruligsrse
5 0
BETWEEN COILS
n
-
BETWEEN TAPS
~
-~~~~~~~~~~~urements sondtrmine
sshowndete lingstresses
TO GROUND i
MEASURED VOLTAGES to ground, between coils, and between
taps. Excepting for tap portions, all
ruling stresses for this type of winding
Figure 1. Measured distribution of impulse held at the winding terminals. The low structure ordinarily are located at or near
voltage in a 230-kv winding frequency test checks the strength versus the coil ends. See discussion of voltage
stress relationship for each part under distribution in part I of this paper.
low frequency conditions, that is, with The ruling stresses between turns are
2. No full voltage impulse tests are made uniform voltage distribution. The im- substantially less than five per cent of
on commercial transformers. pulse distribution test checks the stress applied voltage. It is not practical to
3. A continuous impulse voltage research only as imposed on the parts under im- measure such small voltages and therefore
program is carried on in order that the basic pulse
design can be improved continuously. All
onls vose on thats wim- turn voltages a
voltage conditions, that is, with turn voltages are not included in Figure
nd inrFore
testing in connection with this program is nonuniform voltage distribution. How- 1. If desired, however, turm to turn
carried out on experimental structures. The ever, by demonstrating the actual dis- taps can be built into a critical portion
program includes low voltage distribution tribution of impulse voltage, the dis- of the winding, such as adjacent to the
testing, as carried out on commercial ma- tribution test considerably increases the line. While it is not practical to scale
chines. These tests provide basic stress
data. The program also includes full voltage significance of the low frequency test. these turn voltages on the oscillograms,
testing to destruction of complete winding The more closely the distribution of the pictures will demonstrate that the
structures as well as component parts impulse voltage approaches ulniformity, maximum amplitudes are less than five
thereof. These tests provide basic insulation the more nearly the low frequency test per cent.
strength data. becomes a valid means of judging the Figure 3 was taken when the test
Insulation testing of a transformer impulse voltage strength.3 Tests dem- actulally was being conducted. The
winding can be considered as a demon- onstrate that, for all practical pulrposes, permanent winding connections are not
stration that the strength of each part is the impulse distribution in the distributed completed and all coil ends and tap leads
sufficient to withstand the stress imposed concentric winding does not deviate are available for testing. The test is
thereon with specified voltage conditions unduly from uniformnity. Thus the low made conveniently with the transformer