You are on page 1of 7

voltage incipient

High- oltage rower- ransrormer


2. Full tests may cause
failures which cannot be detected by any
of the standard American Standards Associ-
ation methods.2 An additional method has
been proposed involving pictures of the
esign4~ neutral impulse current.2 At the present
time there is no positive assurance that this
new method is infallible. The importance of
M. B. MALLETT detecting failure in commercial testing is
MEMBER AIEE paramount. Any testing procedure of com-
mercial transformers which may result in
undetected damage is difficult, if not impos-
Synopsis: The previous part of this paper tributed concentric type of transformer sible, to justify. This inescapable point has
covered the initial development and appli- and its application to the Ship been raised many times. It must be faced
cation of the distributed concentric type of design, squarely. Of secondary importance is the
power transformer design. This type of shaw transformers, were covered in 1943 fact that full voltage commercial testing,
design is chiefly suited for the larger sizes of by an Institute paper.i The basic design conducted in accordance with present meth-
power transformers in voltage classes of is also covered and described in British ods, is complicated and of the nature of a
138kv and up. This part deals further with patent number 581506. highly specialized laboratory procedure.
the distributed concentric type transformer. T t o d Such testing does not lend itself readily to
Principal points covered are This type of design is suited chieflY routine production work. Undue expense
for the larger sizes of power transformers and loss of time are incurred.
1. Commercial impulse voltage testing is discussed.
Impulse distribution tests made at low voltage have in voltage classes of 138 kv and up. 3.the Ithigh of
is no doubt safe to say that most as
been adopted as standard commercial tests for dis- Essentially the design comprises a series voltage power transformers,
tributed concentric type transformers. These tests
determine the distribution of impulse voltage in the of cylindrical high-voltage coils which are now installed in any particular country
transformer winding for any specified shape of ap- distributed concentrically between a throughout the world, have not been impulse
plied wave. Typical distrihution tests are reported tested. Also, that high voltage power trans-
as taken on a commercial transformer. cylindrical shield and the low voltage formers have a remarkably good over-all
2. A new form of insulating cylinder has been de-
veloped for application in the major insulation struc-
winding. See Figure 1. service record in any particular country,
ture. The cylinder wall is unique in that it is Since 1943 further development and including South Africa where lightning con-
porous and contains no bonding agent. This re- application of the basic design have been ditions in general are more severe than in
sults in improved characteristics as compared to desin
carried out. This further work, together
geera
North America. Viewed in proper perspec-
conventional type composition cylinders. The por-
ous cylinder is made by a novel process which is with field experience on the Shipshaw tive then, it would seem that the question of
illustrated and described,
3. Application of the basic design has been ex-
we rienheiprs
transformers, forms the basis of the pres-
commercial impulse testing is actually not
as critical as we often are led to believe.
tended now to include transformers in the 138-kv, ent paper. However, most operators on this continent
161-ky, and 230-kv voltage classes. A particularly are concerned deeply over the hazard of
large transformer, weighing 250 tons complete, has
been manufactured. Shipment was made to the Commercial Impulse lightning failure. Also, many operators
Pacific Coast with the transformer proper assembled. t t believe that the low frequency test alone
The shipping clearance problem was met with a
novel tank construction which is illustrated and
Voltage Testing does not prove the high voltage transformer
described. to a sufficient degree in respect to service
4. Field experience is reported with transformers Full voltage impulse testinga of com- voltage conditions.
subjected to short circuit while in service, and also mercial transformers is a controversial
with a transformer involved in a railway wreck dur- an cmlxsubject. The followin h Careful consideration of these points
ing transportation. and complex subject. The following
analytical points are submitted on this f p i r
y d
ely debated subject.
d s .following procedre in respect to dis-
N THE WINTER of 1942-43 three tributed concentric type transforners.
* 90,000-kva banks of single-phase dis- 1. The specific subject of commercial im-
tributed-concentric-type transformers pulse voltage testing is often confused with 1. Impulse voltage distribution tests are
the general subject of impulse voltage re- made on the high voltage windings of all
were installed at the famous war-built search and experimentation. In the trans- commercial transformers for which such tests
Shipshaw powerhouse in upper Quebec, former shop, the primary function of com- are specified by the purchaser. These tests
Canada. Each bank steps up the output mercial testing is to prove the product to the are made at low voltage (about one kilovolt).
Of one generator to- the transmission greatest degree practical; the primary func- They determine the distribution of impulse
volageof154kv
of kv
voltage154
The initial development of the dis-
~~tion
prove oftheimpulse voltage
product greatestis to
to theresearch im- shape
degree voltageof in
applied windingInfor
the wave.
practical. These fundamental concepts the distribution of impulse voltage in the
any specified
contract tenders,

Paper 47-144, recommended by the AIEE commit- must be kept in mind. Under present cir- high voltage winding, corresponding to a
tee on electric machinery for presentation at the cumstances the desirability of full voltage stated shape of applied wave, is specified to
AIEE summer general meeting, Montreal, Quebec, impulse testing of commercial transformers the purchaser by actual figures. Thus, the
Canada, June 9-i3, i947. Manuscript submitted is questioned. The desirability to the trans- degree of control of impulse voltage distri-
Marh8,1 14;9aeavialefrprnig.pi former manufacturer of a continuous -im- bution is predefined. When the machine is
assembled the distribution of voltage is
M. B. MALLETT is transformer engineer in the pulse voltage research program, together
English Electric Company of Canada, Ltd., St. with full voltage laboratory facilities, is not measured and the results compared with the
Catherines, Ontario, Canada. questioned. specified maximum values in the contract.

1086 Mallett-Power Transfformer Design AIEE TRANSACTIONS


HIGH VOLTAGE LINE frequency test becomes a criterion of
2-X 3 !2x40 FULL impulse voltage strength to a consider-
3-|4 B|
FU

WAVE | able degree. While the combination of


and low frequency test
! -1
tI T- g I I 10lo(l9APPLIED.
100%)
distribution test
a
zg ' e , ,does not prove directly the impulse
z
a1 lZ$ 0
t
' 68.l°z
6. %0 | . 0 | B| strength, it does provide the purchaser
with considerably more evidence and data
j: I
o than the low frequency test alone.
| Z Z z Z 63.2%:: z z L i As contrasted to commercial full volt-
o
84, 6
q 1F-
>8 v
-
' a~~~~~~~~~
a, ° ' '

- ,| B $ * $ @ i 5 * 0
: U : i
t g | %
age testing, the commercial distribution
test completely eliminates the serious
hazard of undetected damage. Also,
0
o
0 t " > t g @g 5*3° .. 6.0% the distribution test is inherently a simple
||| '3 i 8 86.0% and practical test which lends itself
a1 -- 3 , 4 70.7% I readily to routine production work.
Such testing can be conducted quickly
5

2 38.7% O
L 20. 9 TURNS FROM NEUTRAL and at reasonable expense.
0% The testing procedure as just outlined
t ~~~~~HIGH
HIGH VOLTAGE NEUTRAL
steers a middle course between the ex-
tremes of no commercial impulse testing
WINDING CONNECTIONS FOR TEST and full voltage commercial impulse
testing. The procedure has been adopted
w9 L_- - n -N4 - - - - - - - - - for the present as a practical compromise
|n cu |N co t N
2 - w1which best meets the conflicting factors
> U) z z z z z z z z z z z z z oa z z z as they now exist.
o100 F Figure 1 shows the results of a dis-
-' 90u - - tribution test s take n a ommercial
QL.L distributed concentric type transformer.
< 80 F
The measured voltages were scaled from
° 70
EL
I I I L I I I I I I I __oLI I theoscillograms shown inFigure2.
z
> In practice it is to take
only necessarymeasure-
u a l .a relatively small number of
50 ---t-I ments in order to establish the ruling
Z 40 m- ____ stress picture in the distributed con-
| 1 l < { | _ H 1 1 1
centric winding structure. Typical meas-
v 3o | < l
s 30 ci urements ordinarily required are as
0 0) co rQ ~ ~ ~ ~ ~ ~ ~ tabulatedin Figure 1, excepting that
10 | __ o | o o F_ voltages involving tap leads are included
< 0
2 ) co|~~ C1- .-.. °. an
(D -. __ )c - PO r- 0 The meas-
only for one tap connection.ruligsrse
5 0
BETWEEN COILS
n
-
BETWEEN TAPS
~
-~~~~~~~~~~~urements sondtrmine
sshowndete lingstresses
TO GROUND i
MEASURED VOLTAGES to ground, between coils, and between
taps. Excepting for tap portions, all
ruling stresses for this type of winding
Figure 1. Measured distribution of impulse held at the winding terminals. The low structure ordinarily are located at or near
voltage in a 230-kv winding frequency test checks the strength versus the coil ends. See discussion of voltage
stress relationship for each part under distribution in part I of this paper.
low frequency conditions, that is, with The ruling stresses between turns are
2. No full voltage impulse tests are made uniform voltage distribution. The im- substantially less than five per cent of
on commercial transformers. pulse distribution test checks the stress applied voltage. It is not practical to
3. A continuous impulse voltage research only as imposed on the parts under im- measure such small voltages and therefore
program is carried on in order that the basic pulse
design can be improved continuously. All
onls vose on thats wim- turn voltages a
voltage conditions, that is, with turn voltages are not included in Figure
nd inrFore
testing in connection with this program is nonuniform voltage distribution. How- 1. If desired, however, turm to turn
carried out on experimental structures. The ever, by demonstrating the actual dis- taps can be built into a critical portion
program includes low voltage distribution tribution of impulse voltage, the dis- of the winding, such as adjacent to the
testing, as carried out on commercial ma- tribution test considerably increases the line. While it is not practical to scale
chines. These tests provide basic stress
data. The program also includes full voltage significance of the low frequency test. these turn voltages on the oscillograms,
testing to destruction of complete winding The more closely the distribution of the pictures will demonstrate that the
structures as well as component parts impulse voltage approaches ulniformity, maximum amplitudes are less than five
thereof. These tests provide basic insulation the more nearly the low frequency test per cent.
strength data. becomes a valid means of judging the Figure 3 was taken when the test
Insulation testing of a transformer impulse voltage strength.3 Tests dem- actulally was being conducted. The
winding can be considered as a demon- onstrate that, for all practical pulrposes, permanent winding connections are not
stration that the strength of each part is the impulse distribution in the distributed completed and all coil ends and tap leads
sufficient to withstand the stress imposed concentric winding does not deviate are available for testing. The test is
thereon with specified voltage conditions unduly from uniformnity. Thus the low made conveniently with the transformer

1947, VIOLUME3 66 Mallett-Power Transformer Design 1087


on the shop floor and out of oil, the stress
distribution with air immersion being sub-
stantially the same as that with oil im-
mersion.
Equipment used for the test includes
a low voltage impulse generator, cathode
ray oscillograph, wave meter, and camera.
The generator is arranged to discharge
repetitively. By repetitive sweeps the
oscillograph records the voltage-time
picture as a standing image on a fluores-
cent screen. Thus photographic records
can be made quickly and conveniently
with an ordinary camera.___
In commercial testing, photographs are,
taken of the applied wave and of all _
the measured voltages. A permanent
commercial test record is made up which
includes data as shown in Figure 1, to-
gether with prints of all the films as
shown in Figure 2.

Porous Insulating Cylinders


Insulating cylinders are a vital part of
the core type transformer. In the dis-
tributed concentric structure, a number of -
spaced concentric cylinders function di-
electricallyas the primarysolidcomponent
of the major insulation. At the same
time the cylinders function mechanically
as a supporting frame work for the entire
high voltage winding and shield structure. -
Thus the dielectric and mechanical char- - -
acteristics of these cylinders are of first
importance.
Conventional insulating cylinders, as
heretofore used in power transformers,
are of composition type. They com-
prise wound paper strip plus a binder such
as shellac or bakelite. The wall structure
is impregnated completely with the
binder. Such a cylinder structure has
the following limitations:
1. Thin fissures are commonly present in Figure 2. Typical oscillograms included in In the manufacture of fiberlock cylin-
the wall structure. These may develop commercial test report ders, wet fibrous stock is first built up
during manufacture of the cylinder or sub- on a mandrel. The raw material is
sequently, and are difficult to dete^t. Since brought in from a board-making mill.
impregnation with the binder makes the
cylinder wall impermeable, it is ordinarily comprises a dense felted mat of inter- It comprises felted rolls or sheets of rag
impossible to fill these fissures with he trans- locked cellulose fibers, and contains no fibers which have been maintained in the
former immersing oil. Accordingly, com- cement or bonding agent of any kind. original wet state as first taken from the
position cylinders containing fissures present Because of their nature the cylinders pulp solution.
a serious breakdown hazard, particularly have been called "fiberlock cylinders. The wet stock then is kneaded and
under conditions of high axial stress.
2.dAs comparedit tofhighlaxin unregnatd
2. As compared to plain unimpregnated
fibrous material, the presence of the binder
.
Since the wall structure contains no
binder it..is porous. Any fissures which
compacted by the unique method il-
lustrated in Figure 4. In this method an
tends to reduce the axial creepa3ge strength may exist are filled readily with the endless steel cable loop is wrapped spirally
along the cylinder. Also, the binder pro- transformer oil and the hazard of break- about the cylinder, the cable being held
motes tracking under conditions of excessive down caused by sealed-in voids is elimi- in tension by an overhead traveling air
stress. nated. Also, the fiberlock cylinder pos- cylinder. The mandrel is then revolved,
3. Composition cylinders are brittle. They sesses superior creepage and antitracking with the result that the cable helix travels
tend to crack when subjected to deformation chrceitc.Mcaialthcyn- aealyb srwaton coste
or a sharp blow. hrcestc.Mcaialthcyi-ltrlyb sce acon coste
der wall is a unitary and homogeneous cylinder surface. Pressures up to 1,000
A new type of insulating cylinder has structure which is hard, strong, and tough. pounds per square inch thus are applied
been developed in which these deficiencies At the same time the cylinder is not progressively and repetitively to the
are eliminated. The cylinder structure brittle. entire fibrous mass. This simple method

1088 Mallett-Power Transformer Design AIBE TRANSACTIONS


effectively works the wet material into a
unitary mat having a high degree of
compactness.
Finally the remaining water is ex-
tracted from the structure by the ap-
plication of heat and vacuum. This
produces a further increase in density,
due to the powerful natural shrinkage
action of the now compact and unitary
fibrous mat about the supporting man-
drel. The dcnsity of the finished dry
cylinder thus produced exceeds 1.1 grams
per cubic centimeter.
Changes in dimension of the finished
cylinder due to reabsorption of moisture
are relatively small. Moisture reabsorp-
tion and dimensional changes are elimi-
nated, however, by impregnating the A typical application is illustrated in Figure 4. Processing fbrous insulating
cylinder with hot paraffin when it is drY Figure 5i cylinders
and still on the mandrel. When the
transformer is oil immersed, the paraffin is Application of Design
leached out of the cylinder structure and tapped off the B3onneville svste,in
is replaced by the transformer oil. The Since completion of the 154-kv Ship- with the 69-ky primary distribution
small percentage of wax thus added to shaw transformers in 1943, application of system of the British Columbia Electric
the oil volume of the transformer does the basic design has been widened to Railway Conmpany. The chief function
not affect materially any of the char- include transformers in the 138-ky and of the tie is to provide 2-way stand-by
acteristics of the oil. 230-kv voltage classes. The 1i38-k trais- service between the two systems.
In general the electrical and mechanical foriners were all single-phase units with An on-load tap gear is connected di-
characteristics of the fiberlock cylinder typical power transformer ratings. rectly in the 230-ky winding to provide
are similar to those of calendered rag A particularly large 230-ky trans- tie-in flexibility. In addition, a third
stock pressboard-a material universally formner of the distributed concentric winding of the transformer provides for
considered as one of the best transformner type has been mnanufactured and shipped synchronous condenser regulation at the
insulations available. to tile Pacific Coast. A sister unit is tie point.
Fiberlock cylinders have been applied now under construction in the shop. The machine has an equivalent physical
over the past three years to more than a The transformer is three phase and capacity of 50,000 kva and weighs 250
million kilovolt-amperes of transformers. is for tying a 230-kv transmission circuit, tons complete. It has banked radiators
and occupies a floor space of 34 by 29
feet.
Shipment was made with the trans-
former assembled, including core and
coils, tank proper in one piece, tank-
cover proper, and on-load tap gear.
Thus maximum protection of the trans-
former was assured, together with mini-
mum installation work.
Shipment of so large a transformer in
this manner was made possible by a
unique tank construction. All three
shipping dimensions-height, length, and
width-required special consideration.
The problem of shipping height was
met by a novel well type of tank con-
struction. See Figure 6. In this con-
struction the core and coils are slung
between the side walls of a well at the
bottom of the tank. The core and coils
rest directly on the bed plate of the well
and the lower cad of the core is only one
inch above the car loading platform.
The sub-base structure, required for
horizontal transfer of jacking force, is
built around the well and made integral
Figure 3. Conducting with the side and end walls of the well.
a commefcial distribu. Thus, the shipping height is reduced by
tion test an amount approximately equal to the

1947, VOLumE 66 MalleU-Power Transformer Design 1089


Figure 5 (left). "Fiber-
lock" cylinder founda-
tion for paper shield
structure

depth of sub-base structture, as compared


to conventional construction where the
sul)-base is underneath the core.
The available length of car loading
platform imposed another problem. This
was imiet by extending the tank cantilever
fashion up) over the car deck. See
Figure 7. This extension supports the
tap gear and houses the tap gear reactor.
In order to meet the limiting shipping
width it was necessary to detach the side-
wall reinforcing beams required for
vacuum oil filling. These beams were
then bolted on at the site. See vertical
rows of bolt holes, Figure 7.
Structural Stability
Manv breakdowns of power trans--
formers are due to mechanical failure of
the winding under conditions of short
circuit. Also, the winding structure Figure 6. Well-type
mtiust be of rugged construction to with- tank construction
stand transportation shocks.
The importance of structural stability
was stressed in part I of this paper. wreck. According to a writteni report from standing. The locomotive, which was
an eye witness, the transformer was being ahead of the transformer car, threw the
Also, the specific means provided to moved down grade on a rail spur by iiieanis of parked flat car to one side an(i climbed the
ensure stability in the distributed con- a switching locomotive coupled to the rock pile. The transformer car left the
centric winding structure were described. transformer car. Because of ice on the rails track completely and stove in the tender of
The following experience in the field the locomotive was unable to hold back the the locomotive. The transformer was re-
tends to confiri the design in this respect: transformer car, with the result that it rani turned to the shop and completely dis-
away over one-eighth mile of rough track, assembled. No parts were misplaced anid
1. I)istributed concentric transformers at attaining an estimated speed of 4(0 miles no parts were damaged. The machine was
the Shipshaw powerhouse were subjected to per hour at the end of the spur. The spur then reassembled, retested, and reshipped.
short circuit in July of 1943. The fault was ended at a rock dump where a flat car was It has been in service ever sinee.
a 3-phase arc on the generator side of the
transformer bank. Power was fed to the
fault through the transformers from the high -- ____r __ , .
voltage system. Duration of the fault was l--
estimated at 10 cycles and the voltage main- CANA\L A- 'ACIFC TAPR
nE
tained on the high voltage teriminals of the CAR r.c.30991o |l !l~t6
transformers calculated at 73 per cent of MAX. LOAD lTAP GEAR
normal. After the fault was cleared the 226000 LBS MFACTOR
P
transformer.F were put back in service andfl., i:_rrl L ; t
have been operating satisfactorily ever since. ________-_______)
'. In February of 1943 one of the Shipshaw Figure 7. Cantilever 2 2 r,
transformers was involved in a railway tank construction L ot i'LA iOJV

1090 Mallett-Power Transformer Design AIEE TRANSACTIONS


Summary compared to conventional type composition past four years indicates that the distributed
cylinders. This type of cylinder has been concentric winding structure is of rugged
1. Impulse distribution tests made at low applied to more than 1,000,000 kva of trans- and stable construction.
voltage have been adopted as standard com- formers.
mercial tests for distributed concentric type 3. Application of the distributed concen- References
power transformers. These tests determine tric type design has been extended to now
the distribution of impulse voltage in the include transformers in the 138-kv, 161-kv,
transformer winding for any ,, specified
4. . shape .and 230-kv M. B. Mallett. ALEE-TRANSAONS,
.IGNMBMltt.
4o^ . voltage,* classes., A rparticularly ~~~~~~~~~~~~~SIGN, AIEE TRANSACTIONS, vvolume
E
of applied wave. large 230-kv transformer has been manu- 62, 1943, August section, pages 526-31.
2. A new type of insulating cylinder has factured. The machine weighs 250 tons 2. PROGRESS IN IMPULSE TESTING OF TRANS-
been developed for application in the major complete and occupies a floor space of 34 by FORMERS, J. H. Hagenguth. AIEE TRANSACTIONS,
insulation structure of the distributed con- 29 feet. volume 63, 1944, pages 999-1005.
centric type transformer. The cylinder wall 4. Mechanical stability of the power trans- 3. LIGHTNING STUDIES OF TRANSFORMERS BY
THE CATHODE RAY OSCILLOGRAPH, F. F. Brand,
is porousis and
prousand ontans
contains n bonding
no bodingagen.
agent. fomer indig structure
former winding sructre iis of paramount
aramunt K. K. Palueff. AIEE TRANSACTIONS, volume 48,
This results in improved characteristics as importance. Field experience during the 1929, pages 998-1008.

Discussion former than for the conventional ones. The


difference between the types seems to be
method involved. In general, fiberlock
cylinders have mechanical characteristics
about 10 degrees centigrade, probably indi- closely approaching those of calendered rag
F. L. Lawton (Aluminum Company of cating slightly better oil circulation in the stock pressboard. As is well known, such
Canada, Ltd., Montreal, Quebec, Canada): distributed concentric coil type. material is exceedingly tough and nonbrittle,
The author has presented a refreshingly The fiberlock insulation is an interesting as contrasted to the marked brittleness of
candid analysis of commercial impulse- development and we would be very much composition cylinders. In this regard we
voltage testing. The combination of the interested in some figures showing the me- have experienced considerable trouble in
usual low-frequency voltage tests with low- chanical strength of this insulation compared the past with composition cylinders breaking
voltage impulse voltage distribution tests to the conventional types now used. as a result of severe transportation shocks.
on commercial transformers plus a continu- Floyd stresses that the impulse voltage
ous impulse voltage research program on distribution test does not prove the impulse
experimental structures is basically sound. G. D. Floyd (Hydro-Electric Power Com- voltage strength of the transformer and is
There appears to be little sound justification mission of Ontario, Toronto, Ontario, therefore limited in value as an acceptance
for expensive full-voltage impulse tests on Canada): The author proposes use of a volt- test. The author agrees entirely with this
commercial units, with acceptance by the age distribution impulse test in place of the conclusion. As specifically stated in the
purchaser of undetectable damage which presently accepted impulse test to prove the paper, the impulse distribution test in com-
may lead to failure in service. impulse strength of transformer insulation. bination with the low frequency test is a
The distributed concentric type of design This test, which is at best a compromise, compromise procedure and does not directly
results in a structurally rugged transformer. would have its chief value as a design test, prove the transformer impulse strength.
However, there is one question which comes for improvement in the design of the insula- Floyd states, however, that the full volt-
to the fore with this particular design, as tion structure. As an acceptance test, it age impulse testing of commercial trans-
inferred indirectly by the author in dis- proves nothing except the distribution of the formers is an accepted test. To this the
cussing the inherent % eaknesses of insulating impulse voltage through the winding at a author takes excep'tion. Full voltage im-
cylinders of the composition type, and the number of selected points, To be an ac- pulse testing of commercial transformers
use of the new "fiberlock" design. This ceptance test in the strict sense of the word, never has been accepted at all by the elec-
question is: What is the likelihood of the the adequacy of the insulation to withstand trical industry in Canada and only to a
formation of chains of minute particles of the stress also should be proved. There is limited extent in the United States. The
water between coils of the concentric high- always the possibility that the points question as to whether such tests should be-
voltage windings, under certain conditions? selected for measurement of distribution come routine standard tests in the industry
Would the porous fiberlock cylinders be as may not include the place where the ratio of has been debated many times before the
effective as cylinders of the composition impulse insulation strength to impulse test Institute over the past ten years. The
type? voltage is the least. Impulse failures in question has never been settled and such
The reference to formation of chains of transformer insulation often occur in unex- testing has never been generally accepted
minute particles of water in insulating oils pected places, and the unexpected place is by the industry. This nonacceptance results
is to a phenomenon observed in circuit the one most likely to be overlooked in the directly from the inescapable point that to
breaker oil containing some moisture. voltage distribution test. To make this type date no positive and infallible means has
Under certain temperature conditions, of test the basis for acceptance as to im- been devised which will detect damage
widely dispersed water molecules appear to pulse strength is questionable, although it is from incipient impulse voltage failure.
coalesce into visible drops and move in such recognized that information of considerable Because full voltage impulse testing of
a fashion between electrodes with a high po- value to the designer can be obtained in this commercial transformers has not been
tential difference that the chain of droplets way. accepted generally by the industry, it would
constitutes a breakdown path, with break- seem that the procedure proposed by the
down likely to occur at relatively low volt- author, specifically the combination of low
age. . M. B. Mallett: The author wishes to thank frequency test and impulse distribution test,
contributors of discussion for their interest should be compared to the existing practice
and comments. of making the low frequency test only. Cer-
J. T. Madill (Aluminum Company of It is particularly gratifying to hear of the tainly any compromise procedure which pro-
Canada, Ltd., Shipshaw, Quebec, Canada): good service which the nine 30,000-kva dis- vides any information whatsoevrer in re-
In regard to the nine 30,000-kva distributed tributed concentric type transformers are spect to the impulse voltage strength of the
concentric coil type power transformers at giving at Shipshaw, as reported by Madill. transformer, is an addition and an improve-
Shipshaw it can be reported that they all are He asks for figures showing the relative meat over providing the purchaser with no
operating very satisfactorily with almost no mechanical strength of fiberlock cylinders impulse test data at all.
maintenance. In the case of one of these as compared to conventional composition Lawton's comments in respect to com-
transformers installed as one phase of a type cylinders. It is hardly feasible to mercial impulse voltage testing are particu-
3-phase bank with two conventional trans- answer this request, in that both the com- larly significant, since the company with
formers as the other two phases, the winding pression strength and tensile strength of which he is associated has an unusually large
and coil temperatures seem to indicate that composition materials vary widely (as much number of high voltage power transformers
there is less difference between the winding as three to one), depending on the type of on the system.
and oil temperature for this type of trans- bonding agent used and the processing Lawton has raised the point as to whether

1947, VOLUME 66 Mallett-Power Transformer Design 1091


the porous fiberlock cylinder is effective in barrier the same as conventional type com- insulation structure of the transformer, and
preventing lining up of minute water par- position cylinders. It seems to the author the use of pressboard collars between sec-
ticles. The density of the cylinder is such that this point has been confirmed over a tions of disk coils. Calendered press-
that it certainly should preclude the con- period of many years by the use of press- board stock as thus used for many years is
tinuous line-up of water particles from coil board casings between tank and coil struc- porous and practically identical physically
to coil, and effectively function as a solid ture, the use of pressboard collars for the end with the newly developed fiberlock cylinder.

almost directly proportional to the annual


conomics ol Long-L istance )6= charge.
2. Line compensation by either series
capacitors or special intermediate syn-
rower | ransmission chronous condensers becomes desirable for
straightaway transmission distances exceed-
ing 200 to 300 miles. Below these distances,
S. B. CRARY 1. B. JOHNSON line compensation does not appear to be
FELLOW AIEE MEMBER AIEE
3. The 287-kv voltage level is about the
most economical for power transfers of 200,-
THIS paper summarizes the results of 360 and 450 kv, are not necessarily stand- 000 kw per circuit for straightaway distances
economic*studies of 300 miles and for higher loadings cir- at
economic studies of of a-c power trans-
a-c power
trans- ard
ard voltages, as tthis study was made
voltages, as
shorter distances up to 350,000 kw per
mission for distances from 100 to 600 before standardization of the higher volt- cuit for 100 miles.
miles. Particular emphasis is placed on age steps has been realized. 4. The 360-kv voltage level is about the
the economics of higher voltages. Con- Several of the important possible varia- most economic voltage for distances in the
clusions have been drawn as to the effect tions in cost were carefully studied and range from 300 to 600 miles when line com-
of voltage, distance, and loading. Sev- considered in order to test the validity 00nsatio350issedforpowertransfersoft300,
eral papers have been presented dealing of the conclusions which were being
drawn during the course of the study.
0 ,kwiper
5. The difference
cinrcit.
in energy transmission
with the technical problems' - involved in costs for any two voltage levels near the the
transmitting power long distances, where- The effect of these variations have tem- optimum is relatively small even for
as comparatively few have dealt with the pered the conclusions, which are pre- same power transfer and becomes practically
economic problem.5-8 This is quite sented here. Therefore, the results of inconsequential when the optimum eco-
understandable. The economic problem this study as summarized in the con- nomic loadings for each of the voltages are
depends to a considerable extent upon clusions are believed to give a fair ap- sed.
conditions surrounding the particular praisal of the present economic problem. 6. The terminal transformer costs approach
* that of the transmission line when the line
considleration,
underunder
case case consideration,
may be altered by new developments
and
and inin time
time
Conclusions length is in the range of 100 miles.
and change in costs. 7. Transformer costs limit the use of
higher voltages than 360 to 400 kv for the
theof widespread
of the
However, in view However,inview Based on the results of this study, ~~~~~~~~~~~~shorter
distances whereas for the longer dis-
attention now being given to longer the following conclusions have been tances up to 600 miles circuit breaker costs
distance and higher voltage transmission drawn: also limit the use of higher voltages when
and the comparisons currently being intermediate stations are used.
made with other methods of transporting 1: Theby cost
given
of a-c energy transmission
Figure 1 may be attained by ra- g8. Operation of high-voltage systems with
energy, it is considered worthwhile to tional transmission system design for power grounsio costs bymaterially
nded netrals allowingufor thethe
reduces
show for assumed costs and conditions transfers of 200,000 to 350,000 kw per cir- thernextlower levelof transformer insulation
some of the important economic factors cuit, for a load factor of 50 per cent and an as well as reducing the transmission line
and the conclusions resulting therefrom. annual charge on investment of 11.5 per csts.
cent. Higher load factors or lower annual
The costs used in this study are be- charges will reduce the transmission costs. 9. The lower resistance conductors result
lieved to be representative although they As energy transmission costs are chiefly in generally lower transmission costs over a
are necessarily averaged values. In this those of investment, the cost is almost in- greater range of loads even for load factors
paper, the costs correspond to averages versely proportional to the load factor and as low as 50 per cent. Also, since the larger
considered to be representative in 1945,
and no attempt has been made to adjust
them for recent changes. The higher
voltage levels selected for parameters, Figr 1. Cost oF elec- /
Paper 47-163, recommended by the AIEE corn- trcenergy transmission _____ 2________ _________
mittee on power transmission and distribution for at 50 per cent load fac- cr
presentation at the AJEEsummer general meeting, tor based on 11.5 perX
Montreal, Qutebdc, Canada, June 9-13, 1947.*
Manuscript submitted March 26, 1947; made cent annual charge on in- e _
available for printing May 7, 1947. vestmentE /.
S. B. CRARY and I. B. JOHNSON are both with the
central station engineering divisions, General At 200,000 to 350,000
Electric Company, Schenectady, N. Y. kilowatts per circuit.
The authors wish to acknowledge the assistance ate odiin nd dS- °
given to them by Mrs. Doris Stupp and Miss Doris . . .O 10 20 30 40 55 0
Bryant for making the calculations. Sunptiofls gilven In paper MILES

1092 Crary, Johnson-A-C Power Transmission AJEE TRANSACTIONS

You might also like