You are on page 1of 99

INSTITUTO POLITÉCNICO NACIONAL

ESCUELA SUPERIOR DE INGENIERIA MECANICA Y ELECTRICA


UNIDAD PROFESIONAL “ADOLFO LÓPEZ MATEOS”

“ANÁLISIS PARA COMPENSAR


EL FACTOR DE POTENCIA.”

T E S I S

QUE PARA OBTENER EL TÍTULO DE:

INGENIERO ELECTRICISTA

PRESENTAN:
VÍCTOR MANUEL ESPINOSA RIVERO
ALBERTO IVÁN MAYORAL ISLAS
ERNESTO CARLOS PÉREZ GARCÍA

ASESORES:

ING. JOSÉ ANTONIO MARTÍNEZ HERNÁNDEZ


M. EN C. RUBEN ORTIZ YAÑEZ

MÉXICO, D.F. 2013


INSTITUTO POLITECNICO NACIONAL

ESCUELA SUPERIOR DE INGENIERIA MECANICA y ELECTRICA


UNIDAD PROFESIONAL "ADOLFO LOPEZ MATEOS"
TEMA DE TESIS
QUE PARA OBTENER EL TITULO DE INGENIERO ELECTRICISTA
POR LA OPCION DE TITULACION TESIS COLECTIVA y EXAMEN ORAL INDIVIDUAL
DEBERA(N) DESARROLLAR C. VÍCTOR MANUEL ESPINOSA RIVERO
C. ALBERTO IVÁN MAYORAL ISLAS
C. ERNESTO CARLOS PÉREZ GARCÍA

"ANÁLISIS PARA COMPENSAR EL FACTOR DE POTENCIA."

ESTABLECER CRITERIOS ANALÍTICOS Y TÉGNICOS PARA CORREGIR y COMPENSAR EL


FACTOR DE POLENCIA BAJO LA PERSPECTIVA DE LA APLICACIÓN INDUSTRIAL PARA
EVIT AR PENALIZACIONES Y EFICIENTAR lEb USO DE LA ENERGÍA ELÉCTRICA.

>- INTRODUCCIÓN.

>- MARCO TEÓRICO.

>- CORRECCIÓN DEL FACTOR DE POTENCIA.

>- COMPENSACIÓN DE LA POTENCIA REACTNA (FP).

>- BENEFICIOS TÉCNICO - EeONÓMICO.

>- CONCLUSIONES.

·M ÉXICO D.F., 21 DE FEBRERO DEL 2013

ASES ORE S

JEFE DE LA CARRERA
Análisis para Compensar el Factor de Potencia.

AGRADECIMIENTOS

Una destacada participación con este equipo de trabajo que hemos formado y fortalecido
con el paso del tiempo, ideas, sugerencias, altas y bajas pero apoyandonos a menudo,
obteniendo buenos resultados, un trabajo final en el cual se demuestra que este equipo de
trabajo desarrolla sus mejores habilidades y aptitudes para entregarse al 100%, un trabajo
arduo lleno de dificultades como lo es la tesis destacando nuestra capacidad de
concentración para aportar lo mejor de nosotros.

Cabe mencionar que este equipo no solo de trabajo si no tambien grandes amigos, nos
complace mencionar que esto no hubiese sido posible sin la destacada participación de
personas y de este nuestra alma mater el Instituto Politécnico Nacional la orgullosa Escuela
Superior de Ingeniería Mecánica y Eléctrica para que lleguemos a un exitoso termino de
este nuestro trabajo, para ello nos es grato aprovechar este espacio para expresar nuestros
sinceros agradecimientos.

Al C. Ingeniero José Antonio Martínez Hernández y al C. M. en C. Rubén Ortiz Yañez


quienes con su amplio conocimiento y experiencia aceptaron realizar esta tesis bajo su
dirección y sincero apoyo, guiando nuestras ideas y enriqueciendo nuestros conocimientos,
sus ideas aportadas que nos fueron de inigualable ayuda, les agradecemos el habernos
facilitado los medios suficientes para llevar a cabo las mejores propuestas durante el
desarrollo de la tesis.

Cabe resaltar de forma individual a nuestros familiares y amigos que nos brindan ese
entusiasmo y apoyo con grata energía para concluir satisfactoriamente nuestros estudios y
tema de tesis.

Victor

A mi familia: Ma. Elena Rivero Aguilar, Francisco Alfredo Espinosa Rivero, Carlos Daniel
Espinosa Rivero, Norman Eduardo Espinosa Rivero, Helen Consuelo Espinosa Rivero por
todo el amor y cariño que me brindan día a día, por su apoyo incondicional y por darme la
fuerza necesaria para conseguir esta meta. ¡GRACIAS POR TANTO!
Análisis para Compensar el Factor de Potencia.

Alberto

A mi familia: María Antonieta Islas Gómez, Estela Elizabeth Mayoral Islas, Cecia Kerem
Luna Sánchez, por la comprensión brindada a lo largo de todos estos años llenos de
altibajos en donde este gran sueño llego a ser realidad, no me queda más que decirles
MUCHAS GRACIAS por estar siempre a mi lado y por su apoyo incondicional.

Ernesto

A ti mamá Gloria Pérez García te agradezco que con el sudor de tu frente y apreciado
apoyo hemos llegado a esta meta a mi hermana Alma Delia Pérez García quien con sus
sabios consejos logre este gran éxito, a mis tios primos, amigos como Miguel A. Vera,
Gabriel de la “O” que con incondicional apoyo me dieron fuerzas para no decaer y seguir
adelante, y con especial dedicación y agradecimiento nuevamente a ti mamá y hermana,
abuelita Lourdes García Torres y abuelito Miguel Pérez Lopez, papá (tio) Luis Rey Pérez
García (finado) quienes al igual que todos han sido parte de esta gran motivación a no
rendirme y ser más de lo que deseo, ¡GRACÍAS INTERMINABLES!
Análisis para Compensar el Factor de Potencia.

ÍNDICE

Contenido

Índice de figuras 1

Índice de tablas 3

Magnitudes y unidades eléctricas de uso frecuente (SI) 4

Objetivo general 5
Objetivos específicos 5
Introducción 6
Estado del arte 8

CAPÍTULO 1: MARCO TEÓRICO 10


1.1 Introducción 10
1.2 Tipos de potencia 10
1.2.1 Potencia activa y potencia instantánea 10
1.2.2 Potencia reactiva 14
1.2.3 Potencia aparente 15
1.3 Tipos de cargas 16
1.3.1 Potencia en circuitos con carga resistiva pura 16
1.3.2 Potencia en circuitos con carga inductiva pura 19
1.3.3 Potencia en circuitos con carga capacitiva pura 22
1.3.4 Potencia media o activa en circuitos con cualquier carga: | | 25

1.4 Potencia en sistemas trifásicos 27

1.4.1 Potencia en cargas balanceadas en estrella (Y) 27

1.4.2 Potencia en cargas balanceadas en delta (Δ) 29

1.4.3 Potencia en cargas trifásicas desbalanceadas 30

1.5 Tri de potencias 33


Análisis para Compensar el Factor de Potencia.

CAPÍTULO 2: CORRECCIÓN DEL FACTOR DE POTENCIA 35


2.1 Introducción 35
2.2 Factor de potencia 35
2.3 Metodología para la corrección del factor de potencia 36
2.4 Uso de Tablas para corregir el factor de potencia 38
2.5 Selección del banco de capacitores 40
2.6 Planteamiento analítico para la corrección del factor de potencia 44
2.6.1 Método analítico para corregir el factor de potencia 44
2.6.2 Uso de tablas para corregir el factor de potencia 47
2.6.3 Corrección del factor de potencia en sistemas con armónicas 49

CAPÍTULO 3: COMPENSACIÓN DE LA POTENCIA REACTIVA (FP) 57


3.1 Introducción 57
3.1.1 Compensación de potencia reactiva mediante maquinas síncronas 58
3.1.2 Compensación de potencia reactiva mediante compensador
estático de VAr´s (CEV) 59
3.1.3 Compensación de potencia reactiva mediante bancos de capacitores 59
3.2 Tipos de compensación 59
3.2.1 Compensación individual 60
3.2.2 Compensación en grupo 61
3.2.3 Compensación central con banco automático 63

3.3 Conexión de los bancos de capacitores 64

3.3.1 Conexión estrella a tierra con neutro sólidamente aterrizado 65

3.3.2 Conexión estrella con neutro flotante 66

3.3.3 Conexión delta 66

3.4 Componentes armónicas 67

3.5 Instalación real 70


Análisis para Compensar el Factor de Potencia.

CAPÍTULO 4: BENEFICIOS TÉCNICO-ECONÓMICOS 75


4.1 Introducción 75
4.2 Aumento en la capacidad del sistema 75
4.3 Disminución de caídas de tensión 77
4.4 Reducción de pérdidas 77
4.5 Penalización y bonificación 78
4.6 Ejemplo numérico de los beneficios de la corrección del factor de potencia 79
4.7 Análisis Económico por medio de la corrección del factor de potencia 83

CONCLUSIONES 89

BIBLIOGRAFÍA 91
Análisis para Compensar el Factor de Potencia.

ÍNDICE DE FIGURAS

Figura Nombre Pagina

1 Sistema monofásico. 12

2 Potencia activa. 14

3 Potencia reactiva. 15

4 Fasor resultante de sumar las potencias activa y reactiva. 16

5 Circuito equivalente de Thévenin con carga resistiva. 16

6 V, I, P para un circuito con carga resistiva. 17

7 Circuito equivalente de Thévenin con carga inductiva. 19

8 V, I, P para un circuito con carga inductiva. 20

9 Circuito capacitivo puro. 22

10 Espectro de señales V, I, P para una carga capacitiva pura. 23

11 Circuito equivalente de una red eléctrica. 25

12 Triángulos de impedancia. (a) | | (b) | | . 25

13 Cargas balanceadas en estrella. 27

14 Cargas trifásicas balanceadas conectadas en delta 29

15 Cargas trifásicas desbalanceadas conectadas en estrella de 4H. 31

16 (a) Triangulo de potencias con predominio del efecto inductivo. 33


(b) Triangulo de potencias con predominio del efecto capacitivo.
17 Diagrama unifilar de cargas inductivas. 36

18 Triangulo de potencias. 37

19 Corrección de L a S, manteniendo el suministro de carga constante. 48


20 Diagrama unifilar para compensación en sistema con armónicas. 49

21 Diagrama unifilar con filtro para armónicas. 56

22 Compensación mediante maquinas síncronas. 58

23 Compensación individual. 61

1
Análisis para Compensar el Factor de Potencia.

24 El capacitor se conecta en paralelo al equipo. 61

25 Compensación en grupo. 62

26 El capacitor se conecta en paralelo a los equipos. 63

27 Compensación central. 64

28 Capacitor en paralelo a la línea. 64

29 Conexión estrella a tierra con neutro sólidamente aterrizado. 65

30 Conexión delta con neutro flotante con protección en el neutro. 66

31 Conexión delta para motores en baja tensión. 67

32 Onda fundamental (60 Hz) y componentes armónicos: 5º (300 Hz), 7º 68


(420 Hz) y 11º (660 Hz).
33 Circuitos que ejemplifican: a) resonancia paralelo, b) resonancia 70
serie.
34 Demanda en kW en un día. 71

35 Demanda en kVAr en un día. 72

36 Diagrama que muestra la colocación de los bancos de capacitores. 74

37 Caso de estudio de los beneficios. 79

38 Recibo de consumo de energía con bajo factor de potencia. 83

39 Recibo de consumo de energía con factor de potencia corregido a 84


0.95

2
Análisis para Compensar el Factor de Potencia.

ÍNDICE DE TABLAS.

Tabla. Nombre Página

1 Factor K para el cálculo de la potencia del banco de capacitores. 39

1a Intersección de valores del factor de potencia inicial y deseado. 48


2 Valores para bancos de capacitores monofásicos de baja tensión. 41

3 Valores para los bancos de capacitores trifásicos en baja tensión. 42

3a Especificaciones de bancos de capacitores. 48

4 Mínimo número de unidades recomendadas en paralelo por 43


grupo serie para limitar la tensión a un máximo del 10% sobre la
nominal, cuando falla una unidad.

5 Límites para bancos de capacitores. 49

5a Comparación de resultados obtenidos con los límites 55


establecidos.

6 Medición de consumo de energía en una industria. 71

7 Lecturas mensuales en la industria. 72

8 Costos de la tarifa OM en los meses de Julio, Agosto y


Septiembre del 2012. 85

9 Cálculo de la factura eléctrica con penalización por FP. 86

10 Cálculo de la factura eléctrica con bonificación por FP. 87

11 Lista de precios de bancos de capacitores de la marca “Arteche”. 88

3
Análisis para Compensar el Factor de Potencia.

MAGNITUDES Y UNIDADES ELÉCTRICAS DE USO FRECUENTE (SI)

SIMBOLO
MAGNITUD SIMBOLO NOMBRE DE LA UNIDAD INTERNACIONAL
DE LA UNIDAD
corriente eléctrica I Ampere A
carga eléctrica Q Coulomb C
potencial eléctrico V
diferencia de potencial, tensión V (U) volt V
fuerza electromotriz E
capacitancia C Farad F
intensidad de campo magnético H ampere por metro A/m
densidad de flujo magnético, inducción B Tesla T
magnética
flujo magnético ɸ Weber Wb
autoinductancia, inductancia mutua L, M (Lmm) Henry H
coeficiente de acoplamiento K
resistividad Ρ Ohm metro Ω. m
número de vueltas en un devanado N
número de fases M
frecuencia F Hertz Hz
periodo T segundos-1 s-1
frecuencia angular Ω radián por segundo rad/s
diferencia de fase Φ Radian Rad
impedancia compleja Z
módulo de impedancia (magnitud) |Z| ohm Ω
resistencia R
reactancia X
admitancia compleja Y
módulo de admitancia |Y| Siemens S
conductancia G
cusceptancia B
factor de calidad Q
potencia activa P Watt W
potencia aparente S, (Ps) volt ampere VA
potencia reactiva Q, (PQ) volt ampere reactivos VAr
factor de potencia Λ
energía activa W, (Wp) joule, watthora J, W.h
corriente instantánea i(t) ó i
corriente pico Ip ampere A
corriente eficaz I
fasor de corriente I, Ī
tensión instantánea v(t) ó v
tensión pico Vp
tensión eficaz V volt V
fasor de tensión V, , Ū
fasor de fuerza electromotriz Ē

4
Análisis para Compensar el Factor de Potencia.

OBJETIVO GENERAL

Establecer criterios analíticos y técnicos para corregir y compensar el factor de


potencia bajo la perspectiva de aplicación industrial para evitar penalizaciones y
eficientar el uso de la energía eléctrica.

OBJETIVOS ESPECIFICOS

 Analizar la respuesta en el tiempo de la potencia eléctrica en redes en


estado estacionario, en cargas pasivas monofásicas R, L y C.

 Comparar la operación eléctrica de los sistemas monofásicos y trifásicos


con cargas pasivas RLC.

 Establecer la representación y relación geométricas de las potencias


eléctricas en sistemas monofásicos y trifásicos.

 Establecer el procedimiento analítico para corregir el factor de potencia.

 Compensar el factor de potencia con cargas de efecto eléctrico contrario.

5
Análisis para Compensar el Factor de Potencia.

INTRODUCCIÓN

En la actualidad se hace mucho más frecuente la necesidad de utilizar


compensadores de potencia reactiva en sistemas industriales debido a la
diversidad de cargas existentes como hornos de arco, molinos de acero y en
especial motores de gran capacidad, siendo estos últimos las más perjudiciales
puesto que son cargas del tipo inductivo y como consecuencia consumen gran
cantidad de potencia reactiva para su funcionamiento, ocasionando un bajo factor
de potencia, así como reducción de la capacidad, un incremento de pérdidas y
caída de tensión en el sistema, lo cual se refleja en pérdidas monetarias
considerables para el industrial.

Actualmente la penalización por bajo factor de potencia se ha incrementado y


como consecuencia las industrias afectadas pagan mucho más en su factura
eléctrica innecesariamente. Los bancos de capacitores ayudan a compensar y
estabilizar el factor de potencia, adaptándose a las variaciones de carga;
redundando en un beneficio inmediato al eliminar las causas de penalización. Este
ahorro nos permite recuperar la inversión de los equipos en un mediano plazo.

Los sistemas de compensación de potencia reactiva tienen la finalidad de aportar


energía reactiva para que el conjunto de la instalación presente un factor de
potencia que este dentro de la norma, obteniendo así una bonificación en la
factura de consumo eléctrico y evitar las penalizaciones en la factura eléctrica.

La mejora del factor de potencia ayuda a disminuir las capacidades térmicas de


los transformadores y conductores, reduce las pérdidas de la línea y las caídas de
tensión. No obstante las compañías suministradoras de energía eléctrica alientan
este esfuerzo debido que al mejorar el factor de potencia no solo reduce la
demanda de energía eléctrica, sino que también ayuda a postergar grandes
inversiones en subestaciones y centrales de generación.

6
Análisis para Compensar el Factor de Potencia.

En este contexto, en la primera parte de esta tesis, se describen los tipos de


potencia así como su comportamiento en las diferentes cargas pasivas,
posteriormente se hace el análisis en sistemas trifásicos de acuedo a su tipo de
conexión y se describe el triángulo de potencias.

En el capítulo 2 se presentan, en forma resumida, los diferentes métodos para la


corrección del factor de potencia respaldados por ejemplos prácticos.

En el capítulo 3 se presentan los métodos de compensación de potencia reactiva


resaltando la utilización de bancos de capacitores, tipos de compensación y las
conexiones más utilizadas.

El capítulo 4, se mencionan los beneficios que se obtienen a partir de la corrección


del factor de potencia y se realiza un análisis de costo beneficio para respaldar la
implementación de los bancos de capacitores.

Por último se presentarán las conclusiones generales de la tesis.

7
Análisis para Compensar el Factor de Potencia.

ESTADO DEL ARTE

Siendo el factor de potencia (FP) un parámetro normalizado, existen múltiples


estudios y diseños de cargas eléctricas que incorporan bancos de capacitores o
sistemas de filtros que dichos sistemas operen de manera optimizada con FP
normalizado para el rango óptimo de operación de los sistemas eléctricos es con
un 0.9 ≤FP ≤1. Sin embargo, hablar de un FP=1, es hablar de un sistema ideal.

Como se ha mencionado, Cada sistema de cargas eléctricas requieren de un


levantamiento de las condiciones de operación para que en base a ello se
establezca la necesidad o no de corregir el FP., por lo que los ingenieros
diseñadores de las instalaciones eléctricas deben de realizar el proyecto
específico para operar su sistema en términos de calidad de la energía.

A modo de referenciar algunas investigaciones y diseños al respecto, se


presentan los casos relacionados, cada caso de estudio donde se requiera
corregir el FP es puntual a la utilización de la energía que se requiera, por lo que
enfatizamos solo casos referenciales que nos representan a totalidad de los
estudios que existen al respecto:

Las aportaciones al estudio de los motores de inducción magneto hidrodinámica


realizada por Lluís Massagués i Vidal Engyner industrial con un contenido sobre
maquinas eléctricas lineales aplicadas a la impulsión de fluidos

En enero de 2005 Josue Elias Obregon Lozano realizo el estudio de la medicion


de la eficiencia a motores de induccion utilizando el metodo de deslizamiento en
San Nicolas de los Garza, N.L.

En Mayo de 1994 el Ing. Tomas Morales Quiñones presenta tesis acerca de el


motor de induccion con factor de potencia unitario en San Nicolas de los Garza,
N.L.

8
Análisis para Compensar el Factor de Potencia.

En el 2008 el Ing. Juan Pablo Serrano Rubio realizo una Tesis de Maestría 2008
(Maestría en Sistemas Inteligentes) acerca de Sistema Inteligente Aplicado al
Mantenimiento de Condición en Motores de Inducción en el Instituto Tecnológico
de León.

9
Análisis para Compensar el Factor de Potencia.

CAPÍTULO 1
MARCO TEÓRICO
1.1 Introducción

En las redes y los circuitos eléctricos de Corriente Alterna (CA) que operan en
estado estacionario, se buscan que las señales de tensión y corriente senoidales
tengan desfasamientos inferiores a 25.8° para que la potencia aparente S,
proporcionada a la carga sea mejor aprovechada, se eviten perdidas de energía y
los equipos tengan mayor durabilidad.

En este capítulo, se hace un análisis trigonométrico de la respuesta de la potencia


eléctrica en cargas monofásicas R, L y C, en estado estacionario. Esto para
sustentar el estudio espectral y fasorial de la potencia en sistemas monofásicos y
trifásicos.

1.2 Tipos de potencias

En los sistemas eléctricos las potencias eléctricas, para su estudio y por los
efectos eléctricos que se producen, se describen como potencias instantáneas,
potencia activa y potencias reactivas en redes en estado permanente.

1.2.1 Potencia activa y potencia instantánea

Por definición la potencia es la variación de la cantidad de trabajo realizado en la


unidad de tiempo.
() (1.1)

Donde:
p (t) = potencia eléctrica (w)
ω = trabajo (J)
t = tiempo (s)

10
Análisis para Compensar el Factor de Potencia.

Asimismo, por definición la tensión eléctrica o diferencia de potencial (d.d.p) es el


trabajo realizado en la unidad de carga; es decir, para desplazar una carga de un
punto a otro requiere de un trabajo, por lo tanto:

(1.2)

Donde:
v= diferencia de potencial, d.d.p ó tensión eléctrica (V)
q=carga eléctrica (C)

Por lo tanto, de la ecuación 1.2, se desprende que:

(1.3)

Sustituyendo (1.3) en (1.1) queda,

( ) (1.4)

Como el incremento de la cantidad de carga que pasa a través de un conductor


en la unidad de tiempo es igual a la intensidad de corriente; es decir,

(1.5)

Entonces, sustituyendo la ec. (1.5) en (1.4) la potencia instantánea es igual a:

(1.6)

De la ecuación (1.6) se desprende que para todo sistema eléctrico de potencia


entregada a una carga en cualquier instante de tiempo es igual al producto de la
tensión instantánea por la corriente instantánea, ecuación (1.6).

11
Análisis para Compensar el Factor de Potencia.

En la figura 1, se aprecia un sistema monofásico representado por un circuito


equivalente de Thévenin, que representa a la fuente de energía y una carga
eléctrica donde la fuente entrega una potencia instantánea a la carga

Figura 1. Sistema monofásico[1].

Para el sistema suponiendo que se le aplica una tensión ( ) a una


impedancia de carga | | produce una intensidad de corriente
( ), entonces, la tensión y la corriente instantáneas pueden
representarse por las ecuaciones:

( )

( )

Sustituyendo en la ecuación número (1.6) se tendrá una potencia instantánea p


igual a:
[ ( )][ ( )]

Realizando el producto de vi, aplicando identidades trigonométricas y reduciendo


se desprende que:

( ) ( )

12
Análisis para Compensar el Factor de Potencia.

( )[ ( ) ( )]

[ ( ) ( ) ( )]

[ ( ) ( ) ( )]

[ ( ) ( ) ]

[ ( ( ) ( ) ]

( ) ( )

( ( ) ( )

( ) (1.7)

Donde:

V= Tensión Eficaz = (volt).


I= Corriente Eficaz = (ampere).



= Desfasamiento entre v e i que produce la carga.
2
ω= Frecuencia Angular = 2 f  (radianes/s).
T
f = frecuencia (Hz).
t= Tiempo (s).
T= periodo (s).

Al primer término de la ecuación (1.7) se le conoce como potencia activa y el


segundo término corresponde a la potencia instantánea.

13
Análisis para Compensar el Factor de Potencia.

La potencia activa (P), es la que consumen realmente las cargas eléctricas, por lo
cual cuando se habla de demanda eléctrica, es esta potencia la que se utiliza para
determinar dicha demanda, su unidades el watt.

Esta potencia al originarse en la componente resistiva, se representa con un fasor


a cero grados, como se puede apreciar en la figura 2, considerando como
referencia la tensión V.

I P V

Figura 2. Potencia Activa (P).

1.2.2.-Potencia reactiva (Q)

Cuando un circuito contiene bobinas, capacitores, o ambos tipos de elementos,


una parte de la energía consumida durante un ciclo se almacena en ellos y
posteriormente regresa a la fuente. Durante este periodo de retorno de la energía,
la potencia es negativa, razón por la cual los motores y otras máquinas necesitan
esta potencia para su funcionamiento. La potencia reactiva tiene un valor medio
nulo, por lo que no produce trabajo útil y se designa con la letra Q.

A partir de su expresión

(1.8)

Donde:
S= Potencia aparente o total (VA).
Z=Impedancia

14
Análisis para Compensar el Factor de Potencia.

Su unidad corresponde a los volt-ampere-reactivos (VAR). Lo que reafirma en que


esta potencia se debe únicamente a los elementos reactivos, los cuales pueden
ser del tipo inductivo o capacitivo , como se observa en la figura 3.

Figura 3. Potencia reactiva

1.2.3 Potencia aparente (S)

La potencia aparente de un circuito eléctrico de corriente alterna es el vector


resultante de sumar la potencia activa y la potencia reactiva. La relación fasorial
entre los tres tipos de potencia P, Q y S de un sistema eléctrico, considerando
como referencia la tensión V y predominio del efecto inductivo, se muestra en la
figura 4.

Esta potencia es la potencia que el sistema entrega a la carga, cuando el factor de


potencia es igual a uno ( =1), en estas condiciones la potencia activa es igual
a la potencia aparente. Dicha potencia se denota con la letra S y su unidad es el
volt-ampere (VA).

La ecuación para calcular la potencia aparente es:

(1.9)

15
Análisis para Compensar el Factor de Potencia.

Figura 4. Relación fasorial entre potencias, con predominio inductivo.

1.3 Tipos de cargas

1.3.1 Potencia en circuitos con carga resistiva pura

En la figura 5. Se muestra la representación de un circuito con carga resistiva.

Figura 5. Circuito equivalente de Thévenin con carga resistiva[1].

Cuando se tienen cargas resistivas la tensión y la corriente están en fase; esto es


φ=0; por lo tanto, las ecuaciones de tensión y corriente son:

(1.10)

Bajo estas condiciones la ecuación (1.7) se convierten en:

(1.11)

16
Análisis para Compensar el Factor de Potencia.

Donde:

Potencia promedio entregada a la carga, P.

En la figura 6 se muestra el espectro de señales de de la respuesta en el


tiempo que producen cargas resistivas.

Figura 6.- V, I, P para un circuito con carga resistiva[1].

En conclusión la potencia activa o consumida para circuitos con carga resistiva es


igual a:

( ) (1.12)

La energía disipada para un periodo:

( ) (joule, J) (1.13)

También como puede observarse en la figura número 6, la señal de potencia es


positiva, en estas condiciones existe una transferencia de potencia únicamente de
la fuente hacia la carga, por lo que, toda la potencia S que recibe la carga se
consume o transforma.

17
Análisis para Compensar el Factor de Potencia.

Entonces, teniendo una carga resistiva no regresa potencia a la fuente; por lo


que, toda la potencia que la fuente le proporciona a la carga se consume.

Considerando que el FP es igual a la razón que existe entre la potencia activa P y


la potencia aparente S y dado que las cargas resistivas no produce
desfasamiento; ; por lo tanto en el factor de potencia (FP), para este tipo de
circuito es igual a 1; esto es:

( ) (1.14)

(VA) (1.15)

En síntesis, en una carga resistiva, donde la impedancia Z es igual a R y


considerando que:
e

Entonces, la potencia activa P es igual a la potencia aparente S, por lo tanto son


iguales a:

(1.16)

Ya que:
;

Este análisis también se demuestra considerando que:

(1.17)

(1.18)

Para este caso P=S, por lo tanto:


(1.19)

18
Análisis para Compensar el Factor de Potencia.

De lo anterior se desprende que el desfasamiento entre V e I resulta importante


ya que permite determinar qué tanta potencia se regresa de la carga hacia la
fuente, provocando pérdidas y mayor disipación de calor en la generación y
transmisión de la energía; si la carga es resistiva toda la potencia se consume; sin
embargo, sí entonces y como se aprecia en el siguiente
análisis.

1.3.2 Potencia en circuitos con carga inductiva pura

En un circuito ideal únicamente con carga inductiva, figura 7; esto es,


despreciando incluso la propia resistencia del conductor de la línea de
alimentación y de la bobina y considerando que una bobina atrasa la corriente
con respecto a la tensión ; entonces el desfasamiento .

Sustituyendo el ángulo =90°, en la ecuación (1.7) se obtiene que p en una


bobina es igual a lo establecido en la ecuación (1.20).

( )

( ) ( ) (1.20)

Figura 7. Circuito equivalente de Thévenin con carga inductiva[1].

19
Análisis para Compensar el Factor de Potencia.

, esto indica que una carga inductiva pura “no consume potencia” la misma
cantidad de potencia que recibe de la fuente la regresa. El flujo de potencia es
cero en un periodo.

( ), esto indica que es una onda senoidal de potencia tiene el doble


de la frecuencia de la señales de tensión y corriente.

El espectro de las señales de potencia P, tensión V y corriente I se muestran en la


figura 9 y corresponden a los modelos matemáticos.

( ) ( )

( )

De este espectro se desprende que la potencia p tiene igual número de valores


instantáneos positivos que negativos por lo que el promedio de valores es cero; es
decir P=0. En otras palabras la potencia positiva (valores instantáneos de potencia
positiva) es la potencia que la fuente transfiere a la carga y la potencia negativa
(valores instantáneos de potencia negativa) es la potencia que la carga transfiere
a la fuente.

Figura 8. V, I y P para un circuito con carga inductiva[1].

20
Análisis para Compensar el Factor de Potencia.

Otro tipo de potencia que se presenta en las cargas eléctricas es la potencia


reactiva Q y es igual a:
(1.21)

Su unidad (volt) (ampere) (reactivos), (VAr).

Para el inductor , entonces:

(VAr) (1.22)

De acuerdo a la Ley de Ohm


ó

Sustituyendo en la ecuación (1.22) se deduce que la potencia reactiva en una


bobina es:

(VA) (1.23)

Como ( ) ( ), entonces.

(1.24)

Considerando este análisis, se puede establecer de manera ideal, que como la


potencia, por el tiempo de consumo, es la energía que se paga como
consumidores; esto es:

(joule) (1.25)
Donde:
W=Energía (J).

21
Análisis para Compensar el Factor de Potencia.

1.3.3 Potencia en circuitos con carga capacitiva pura

En el circuito de la figura 9, se representa un circuito con una carga puramente


capacitiva, para circuitos capacitivos puros, la corriente esta adelantada
respecto a la tensión ; esto demuestra que el efecto es contrario al circuito
inductivo.

Figura 9. Circuito capacitivo puro[1].

Entonces, para este caso

Sustituyendo en la ecuación (1.20) la potencia queda:

( ) ( )

( ) ( ) (1.26)

Al igual que en el circuito inductivo la ecuación (1.26) indica que corresponde a


una onda senoidal que tiene el doble de frecuencia que V e I. El espectro de las
señales de potencia p, tensión v y corriente i, se muestra en la figura 10.

22
Análisis para Compensar el Factor de Potencia.

Figura 10. Espectro de señales de V, I y P para una carga capacitiva pura[1].

De la figura 10 se observa que el flujo neto de potencia a la carga capacitiva pura;


también como en el caso de los inductores, es cero para un ciclo completo.

La magnitud de potencia reactiva, para el capacitor es:

|( ( ))| | | (VAR)

Considerando la tensión en el capacitor Vc igual a, de acuerdo a la Ley de Ohm:

(1.27)

Entonces, la potencia reactiva en el capacitor Qc:

(VAr) (1.28)

La potencia aparente es igual a:

(VA) (1.29)

La potencia activa o promedio es cero:


23
Análisis para Compensar el Factor de Potencia.

( ) ( )

El Factor de Potencia por lo tanto también es cero:

La energía de un capacitor se determina a partir de la definición de potencia, esto


es:

( ) (1.30)

Por definición

Por lo tanto
(1.31)

Sustituyendo la ecuación (1.30) en la ecuación (1.31)

Integrando y resolviendo se obtiene la ecuación de la energía almacenada en un


capacitor en función del tiempo; es decir, a medida que se carga el capacitor C la
tensión cambia y cambia también la energía almacenada ( ).

() ( ) [ () ( )]

()

En términos de valores eficaces


(1.32)

24
Análisis para Compensar el Factor de Potencia.

1.3.4 Potencia media o activa en circuitos con cualquier tipo de carga


| | .

Dado el circuito representativo de una red eléctrica, figura 11, donde | |

Figura 11. Circuito equivalente de una red eléctrica[1].

Si predomina el efecto inductivo: X L  X C

| | (1.33)

Si predomina el efecto capacitivo: X L  X C

| | (1.34)

Los triángulos de impedancias de las ecuaciones (1.33) y (1.34) son los que se
muestran en la figura 12.

Figura12. Triángulos de impedancias. (a) | | (b) | | [1] .

25
Análisis para Compensar el Factor de Potencia.

El coseno de de cualquiera de los triángulos de la figura 12 es igual a:

| |
(1.35)

Entonces, la potencia media o activa es:

*| |+ (1.36)

Como la magnitud de la corriente eficaz es igual a:

| |

Entonces, sustituyendo dicha corriente en la ecuación (1.36) se obtiene que P


también es igual a las equivalencias mostradas en las ecuaciones (1.37) y (1.38).

*| |+ *| |+ [ ] (1.37)
| |

(1.38)

La ecuación (1.38) demuestra que la potencia media o activa es la potencia


consumida o disipada por los elementos resistivos de la carga. En un motor, por
ejemplo, R  l A que corresponde a la resistencia del conductor con que está
hecho el embobinado.

26
Análisis para Compensar el Factor de Potencia.

1.4.-Potencia en sistemas trifásicos

1.4.1 Potencia en cargas balanceadas en estrella (Y)

En la figura 13, se representa un sistema de cargas balanceadas cuya impedancia


por fase es Z= R j X.

Figura 13. Cargas balanceadas en estrella [2].

En este sistema la magnitud de la potencia total corresponde a la suma de las


potencias promedio o activa de cada fase (suma de potencias monofásicas) esto
es:

(1.39)

Donde:

PT = potencia total (W).


= potencia de cada fase (W)

La potencia de cada fase (potencia monofásica) es igual a:

(1.40)

27
Análisis para Compensar el Factor de Potencia.

Donde:

= desfasamiento entre V y I de cada fase.

Dado que EL = √ y que IL=If la PT también es igual a:

(1.41)

De manera análoga se deduce la potencia reactiva y potencia aparente del


sistema por lo tanto la potencia reactiva para cada fase total del sistema es:

√ (1.42)

También bajo el mismo esquema se deduce que las potencias aparentes


entregada a cada fase S y total ST son:

(1.43)

28
Análisis para Compensar el Factor de Potencia.

(1.44)

√ (1.45)

1.4.2 Potencia en cargas balanceadas conectadas en delta (∆)

En la figura 14 se muestra un sistema de cargas conectadas en delta.

Figura 14. Cargas trifásicas balanceadas conectadas en delta[2].

Potencia activa

( ) (1.46)

( ) (1.47)

√ (1.48)

29
Análisis para Compensar el Factor de Potencia.

Potencia reactiva

(1.49)

(1.50)

Potencia aparente

√ (1.51)

Factor de potencia
(1.52)

1.4.3 Potencia en cargas trifásicas desbalanceadas

Como se ha descrito en el punto anterior en los sistemas trifásicos balanceados en


delta y estrella prácticamente las potencias totales corresponden a tres veces la
potencia de fase.

Sin embargo dicho tipo de sistemas son ideales, en los sistemas de cargas
trifásicos reales, las impedancias por fase son diferentes o que origina que exista
corriente en el neutro, por lo que normalmente las cargas se conectan en estrella
con el hilo adicional que corresponde al hilo neutro.

30
Análisis para Compensar el Factor de Potencia.

En la figura 15 se muestra un sistema trifásico de 4 hilos de cargas


desbalanceadas conectadas en estrella.

Figura 15. Cargas trifásicas desbalanceadas conectadas en estrella de 4H[2].

Como se ha señalado en la industria la carga de cada fase cambia en forma


continua, el hilo neutro permite niveles de tensión uniformes y proporciona la
trayectoria de las corrientes de cada carga.

Aplicando ley de Kirchhoff de tensiones se obtienen las ecuaciones de tensión


siguientes:

(1.53)

Resolviendo el sistema de ecuaciones (1.51), las corrientes equivalen a:

(1.54)

31
Análisis para Compensar el Factor de Potencia.

(1.55)

(1.56)

La potencia activa por fase es:

(1.57)

(1.58)

La potencia reactiva total es:

(1.59)

Donde:

La potencia aparente total es:

(1.60)

32
Análisis para Compensar el Factor de Potencia.

1.5 Triángulo de potencias

De la potencia aparente S se desprende la relación de potencias establecida por el


diagrama fasorial de potencias conocido como triangulo de potencias; mismo que
teóricamente se establecen como se muestran en a figura 16 (a) y (b).

Figura 16. (a) triángulo de potencia con predominio del efecto inductivo. (b) triangulo de
potencias con predominio del efecto capacitivo[3].

Como se ha comentado a nivel industrial se desarrollan elevados niveles de


potencia reactiva, debido a que por lo general los procesos de producción utilizan
motores de inducción. La estadística de consumo energético nos dice que el 60%
de la facturación corresponde al consumo de los motores de inducción.

Entonces por lo general en el consumo predomina el efecto inductivo que tiene un


FP en adelanto y el triángulo de potencias más utilizado para establecer la relación
entre P, Q y S es el mostrado en la figura 16 (a).

Ambos triángulos indican que solo se requieren dos de las tres magnitudes de
potencias pues la tercera se puede obtener aplicando el teorema de Pitágoras o
relaciones trigonométricas algunas relaciones entre magnitudes son:

33
Análisis para Compensar el Factor de Potencia.

√ (1.61)

√ (1.62)

√ (1.63)

Los triángulos de potencia mostrados en la figura 16 indican también que


conforme aumenta el desfasamiento entre la corriente y la tensión, la potencia
reactiva aumenta. Por el contrario, si el desfasamiento entre la corriente y la
tensión disminuye entonces la Q disminuye. Por ejemplo si las cargas fuesen
resistivas no hay efector reactivo entonces FP=1.

34
Análisis para Compensar el Factor de Potencia.

CAPÍTULO 2
CORRECCIÓN DEL FACTOR DE
POTENCIA
2.1 Introducción

La corrección del factor de potencia presenta algunos beneficios como son:

 Disminución de pérdidas en los conductores.


 Reducción de las pérdidas de las caídas de tensión.
 Aumento de la disponibilidad de potencia de transformadores y líneas.
 Incremento de la vida útil de las instalaciones eléctricas.

 Reducción del costo de su facturación de energía eléctrica.

En el presente capitulo se establece el procedimiento para corregir el FP de


manera analítica y usando tablas preestablecidas.

2.2 Factor de potencia

En un sistema monofásico se define como la relación de la potencia activa entre


la potencia aparente como se muestra en la formula (2.1).

(2.1)

Al igual que en un sistema monofásico el factor de potencia en un sistema trifásico


se define como la relación de la potencia activa ( √ ) entre la
potencia aparente ( √ ) por lo tanto el factor de potencia sistema trifásico
se calcula:

35
Análisis para Compensar el Factor de Potencia.


(2.2)

El factor de potencia también es un indicador sobre el correcto aprovechamiento


de la energía, de forma general es la cantidad de energía que se ha convertido en
trabajo. Este puede tomar valores entre 0 y 1, siendo la unidad el valor ideal, lo
cual indicaría que toda la energía consumida por los aparatos ha sido
transformada en trabajo.

2.3 Metodología para la corrección del factor de potencia

Generalmente un FP bajo se debe a un exceso de cargas inductivas (motores);


por ejemplo, considerando un motor con una potencia P, por su efecto inductivo
provoca un FP en retraso; en la figura 17 se muestra un diagrama unifilar que
alimenta cinco motores.

Figura 17. Diagrama unifilar de cargas inductivas

( ) (2.3)

36
Análisis para Compensar el Factor de Potencia.

El triángulo de potencias de los motores se muestra en la figura 18.

Figura 18. Triangulo de potencias[1].

(2.4)

(2.5)

Considerando que el motor provoca un FP bajo (desfasamiento entre v e i superior


a 25.85º), para corregirlo se fija el FP deseado que este dentro de la norma
0.9≤FP≤1.

Con el nuevo ángulo s se calcula Qs:

( ) (2.6)

(2.7)

(2.8)

De donde se obtiene que:

ó ( ) (2.9)

37
Análisis para Compensar el Factor de Potencia.

Dado que la potencia activa P no varía, se pueden construir dos triángulos


proporcionales montados en el mismo plano y considerando a dicha potencia
como referencia la figura 19. El triángulo SL, QL y P, corresponde al triángulo con el
FP sin corregir y el triángulo SS, QS y P de potencias que muestra un FP corregido.
QC corresponde a la potencia reactiva capacitiva agregada, misma que permitió
disminuir el efecto reactivo de la potencia reactiva inductiva.

Figura 19.Corrección de L a S, manteniendo el suministro de carga constante[1].

Se determina el valor de C que se debe conectar para corregir el FP, de la


siguiente manera:

Entonces;

Por lo tanto;

(2.10)

Es importante considerar que en los sistemas reales el capacitor debe tener la


potencia QC y la capacidad C determinada, parámetros mínimos que deben ser
requeridos a los proveedores.

38
Análisis para Compensar el Factor de Potencia.

2.4.-Uso de tablas para corregir el factor de potencia

Otra forma de corregir el factor de potencia es utilizando la tabla 1. En este caso


se hace un cruzamiento entre el factor de potencia inicial, normalmente en atraso
y un factor K que corresponde al factor de potencia deseado; Q c se obtiene de la
siguiente manera:
(2.11)

Factor de FACTOR K
Potencia Factor de Potencia Deseado
Inicial 0.86 0.87 0.88 0.89 0.9 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1
0.66 0.545 0.572 0.599 0.625 0.654 0.683 0.712 0.743 0.775 0.81 0.847 0.888 0.935 0.996 1.138
0.67 0.515 0.541 0.568 0.596 0.624 0.652 0.682 0.713 0.745 0.779 0.816 0.857 0.905 0.966 1.103
0.68 0.485 0.512 0.539 0.566 0.594 0.623 0.652 0.683 0.715 0.75 0.787 0.828 0.875 0.936 1.078
0.69 0.456 0.482 0.509 0.537 0.565 0.593 0.623 0.654 0.686 0.72 0.757 0.798 0.846 0.907 1.049
0.70 0.427 0.453 0.48 0.508 0.536 0.565 0.594 0.625 0.657 0.692 0.729 0.77 0.817 0.878 1.02
0.71 0.398 0.425 0.452 0.48 0.508 0.536 0.566 0.597 0.629 0.663 0.7 0.741 0.789 0.849 0.992
0.72 0.37 0.397 0.424 0.452 0.48 0.508 0.538 0.569 0.601 0.635 0.672 0.713 0.761 0.821 0.964
0.73 0.343 0.37 0.396 0.424 0.452 0.481 0.51 0.541 0.573 0.608 0.645 0.686 0.733 0.794 0.936
0.74 0.316 0.342 0.369 0.397 0.425 0.453 0.483 0.514 0.546 0.58 0.617 0.658 0.706 0.766 0.909
0.75 0.289 0.315 0.342 0.37 0.398 0.426 0.456 0.487 0.519 0.533 0.59 0.631 0.679 0.739 0.882
0.76 0.262 0.288 0.315 0.343 0.371 0.4 0.429 0.45 0.492 0.526 0.563 0.605 0.652 0.713 0.855
0.77 0.235 0.262 0.289 0.316 0.344 0.373 0.403 0.433 0.466 0.5 0.537 0.578 0.626 0.686 0.829
0.78 0.209 0.236 0.263 0.29 0.318 0.347 0.376 0.407 0.439 0.474 0.511 0.552 0.599 0.66 0.802
0.79 0.183 0.209 0.236 0.264 0.292 0.32 0.35 0.381 0.413 0.447 0.484 0.525 0.573 0.634 0.776
0.80 0.157 0.183 0.21 0.238 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499 0.547 0.608 0.75
0.81 0.131 0.157 0.184 0.212 0.24 0.268 0.298 0.329 0.361 0.395 0.432 0.473 0.521 0.581 0.724
0.82 0.105 0.131 0.158 0.186 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.447 0.495 0.556 0.698
0.83 0.079 0.105 0.132 0.16 0.188 0.216 0.246 0.277 0.309 0.343 0.38 0.421 0.469 0.53 0.672
0.84 0.053 0.079 0.106 0.134 0.162 0.19 0.22 0.251 0.283 0.317 0.354 0.395 0.443 0.503 0.646
0.85 0.026 0.053 0.08 0.107 0.135 0.164 0.194 0.225 0.257 0.291 0.328 0.369 0.417 0.477 0.62
0.86 - 0.027 0.054 0.081 0.109 0.138 0.167 0.198 0.23 0.265 0.302 0.343 0.39 0.451 0.593
0.87 - - 0.027 0.054 0.082 0.111 0.141 0.172 0.204 0.238 0.275 0.316 0.364 0.424 0.567
0.88 - - - 0.027 0.055 0.084 0.114 0.145 0.177 0.211 0.248 0.289 0.337 0.397 0.54
0.89 - - - - 0.028 0.057 0.086 0.117 0.149 0.184 0.221 0.262 0.309 0.37 0.512
0.90 - - - - - 0.029 0.058 0.089 0.121 0.156 0.193 0.234 0.281 0.342 0.484
0.91 - - - - - - 0.03 0.06 0.093 0.127 0.164 0.205 0.253 0.313 0.456
0.92 - - - - - - - 0.031 0.063 0.097 0.134 0.175 0.223 0.284 0.426
0.93 - - - - - - - - 0.032 0.067 0.104 0.145 0.192 0.253 0.395
0.94 - - - - - - - - - 0.034 0.071 0.112 0.16 0.22 0.363
0.95 - - - - - - - - - - 0.037 0.078 0.126 0.186 0.329
0.96 - - - - - - - - - - - 0.041 0.089 0.149 0.292
0.97 - - - - - - - - - - - - 0.048 0.108 0.251
0.98 - - - - - - - - - - - - - 0.061 0.203
0.99 - - - - - - - - - - - - - - 0.142
Tabla 1. Factor K para el cálculo de la potencia del banco de capacitores[4].

39
Análisis para Compensar el Factor de Potencia.

2.5 Selección del banco de capacitores

Para realizar la selección de un banco de capacitores se deben elegir los


capacitores en los rangos existentes normalizados. En las tablas 2 y 3 se
presentan una lista de los valores de los bancos de capacitores más comunes
existentes en el mercado de acuerdo a su tensión, cabe resaltar que en
relación a las tensiones y tamaños de los capacitores, los diferentes
fabricantes producen equipos para tensiones normalizados más utilizados por
las empresas de electricidad, aunque también los fabrican para tensiones y
tamaños especiales bajo especificación del cliente.

Sin embargo, los tamaños existentes en el mercado son muy numerosos y


generalmente se fabrican tanto condensadores monofásicos como trifásicos en
incrementos de 5 kVAr hasta 50 kVAr, de 10 kVAr hasta 100 kVAr y en saldos
de 50 kVAr hasta 300 kVAr. Tamaños mayores requieren pedidos especiales,
en todo caso es importante destacar que la frecuencia de operación de los
condensadores debe ser 60 Hz.

40
Análisis para Compensar el Factor de Potencia.

Tensión de Potencia (kVAr) Capacitanci Corriente Fusible Conducto


a nominal NH ó Dz r
línea (V) nominal de
(A) (A)
(μF) conexión
50H 60H 50H 60H
z z z z mm2
2.1 2.5 137.0 9.5 11.4 20.0 2.5
2.5 3.0 165.0 11.4 13.6 25.0 2.5
4.2 5.0 274.0 19.1 22.7 32.0 6.0
5.0 6.0 329.0 22.7 27.3 50.0 10.0
220V 6.3 7.5 411.0 28.6 34.1 63.0 10.0
8.3 10.0 548.0 37.7 45.5 80.0 16.0
10.0 12.0 657.0 45.5 54.5 100.0 25.0
12.5 15.0 822.0 56.8 68.2 125.0 35.0
16.6 20.0 1096.0 75.5 90.1 160.0 70.0
2.1 2.5 46.0 5.5 6.6 10.0 2.5
2.5 3.0 55.0 6.6 7.9 16.0 2.5
4.2 5.0 92.0 11.1 13.2 25.0 2.5
5.0 6.0 110.0 13.2 15.8 32.0 4.0
6.3 10.0 184.0 21.8 26.3 50.0 10.0
8.3 12.0 220.0 26.3 31.6 50.0 10.0
380V
10.0 15.0 276.0 32.9 39.5 63.0 16.0
12.5 18.0 330.0 39.5 47.4 80.0 25.0
16.6 20.0 367.0 43.7 52.6 100.0 25.00
20.0 24.0 440.0 52.6 63.2 100.0 35
20.8 25.0 460.0 54.7 65.8 125.0 35.0
25.0 30.0 551.0 65.8 78.9 160.0 50.0
4.2 5.0 68.0 9.5 11.4 20.0 2.5
5.0 6.0 82.0 11.4 13.6 25.0 2.5
8.3 10.0 137.0 18.9 22.7 32.0 6.0
10.0 12.0 164.0 22.7 27.3 50.0 10.0
440V
12.5 15.0 206.0 28.4 34.1 63.0 10.0
16.6 20.0 274.0 37.7 45.5 80.0 16.0
20.8 25.0 343.0 47.3 56.8 100.0 25.0
25.0 30.0 411.0 56.8 68.2 125.0 35.0
4.2 5.0 58.0 8.7 10.4 20.0 2.5
5.0 6.0 69.0 10.4 12.5 20.0 2.5
8.3 10.0 115.0 17.3 20.8 32.0 6.0
10.0 12.0 138.0 20.8 25.0 50.0 6.0
480V
12.5 15.0 173.0 26.0 31.3 50.0 10.0
16.6 20.0 230.0 34.6 41.7 80.0 16.0
20.8 25.0 288.0 43.3 52.1 100.0 25.0
25.0 30.0 345.0 52.1 62.5 100.0 36.0
Tabla 2. Valores para bancos de capacitores monofásicos de baja tensión[6].

41
Análisis para Compensar el Factor de Potencia.

Tensión Potencia (kVAr) Capacitancia Corriente Fusible NH


Conductor
de nominal ó Dz
línea (V) nominal (μF) de
(A) (A)
conexión
50Hz 60Hz 50Hz 60Hz mm2
2.1 2.5 137.01 5.5 6.6 10.0 2.5
4.2 5.0 274.03 10.9 13.1 25.0 2.5
6.3 7.5 411.04 16.4 19.7 32.0 6.0
8.3 10.0 548.05 21.8 26.2 50.0 10.0
10.4 12.5 685.07 27.3 32.8 63.0 16.0
220V
12.5 15.0 822.08 32.8 39.4 63.0 16.0
14.6 17.5 959.09 38.2 45.9 80.0 25.0
16.6 20.0 1096.12 43.7 52.5 100.0 25.0
18.7 22.5 1233.12 49.1 59.0 100.0 35.0
20.8 25.0 1370.14 54.6 65.6 125.0 35.0
2.1 2.5 45.92 3.2 3.8 10.0 2.5
4.2 5.0 91.85 6.3 7.6 16.0 2.5
6.3 7.5 137.77 9.5 11.4 20.0 2.5
8.3 10.0 183.7 12.7 15.2 25.0 4.0
10.4 12.5 229.62 15.8 19.0 32.0 6.0
12.5 15.0 275.55 19.6 22.8 32.0 6.0
14.6 17.5 321.47 22.2 26.6 50.0 10.0
380V 16.6 20.0 367.39 25.3 30.4 50.0 10.0
18.7 22.5 413.32 28.5 34.2 63.0 16.0
20.8 25.0 458.24 31.7 38.0 63.0 16.0
25.0 30.0 551.09 38.0 45.6 80.0 25.0
29.2 35.0 642.94 44.3 53.2 100.0 25.0
33.3 40.0 734.79 50.6 60.8 100.0 35.0
37.5 45.0 826.64 57.0 68.4 125.0 50.0
41.6 50.0 918.48 63.3 76.0 125.0 50.0
2.1 2.5 34.25 2.7 3.3 6.0 2.5
4.2 5.0 68.51 5.5 6.6 10.0 2.5
6.3 7.5 102.76 8.2 9.8 16.0 2.5
8.3 10.0 137.01 10.9 13.1 25.0 2.5
10.4 12.5 171.26 11.7 16.4 32.0 4.0
12.5 15.0 205.52 16.4 19.7 32.0 6.0
14.6 17.5 239.77 19.2 23.0 50.0 6.0
440V 16.6 20.0 274.003 21.8 26.2 50.0 10.0
18.7 22.5 308.28 24.6 29.5 50.0 10.0
20.8 25.0 342.53 27.3 32.8 63.0 16.0
25.0 30.0 411.04 32.8 39.4 63.0 16.0
29.2 35.0 479.54 38.2 45.9 80.0 25.0
33.3 40.0 548.05 41.7 52.5 100.0 25.0
37.5 45.0 616.56 49.1 59.0 100.0 35.0
41.6 50.0 685.07 54.6 65.6 125.0 35.0
4.2 5.0 57.56 5.1 6.0 10.0 2.5
8.3 10.0 115.13 10.0 12.0 20.0 2.5
12.5 15.0 172.69 15.0 18.0 32.0 4.0
16.6 20.0 230.26 20.1 24.1 50.0 6.0
20.8 25.0 287.82 25.1 30.1 50.0 10.0
480V
25.9 30.0 346.39 30.1 36.1 63.0 16.0
29.2 35.0 402.95 35.1 42.1 80.0 16.0
33.3 40.0 460.52 40.1 48.1 80.0 25.0
37.5 45.0 518.08 45.1 54.1 100.0 25.0
41.6 50.0 575.65 50.1 60.1 100.0 35.0
Tabla 3. Valores para los bancos de capacitores trifásicos en baja tensión[6].

42
Análisis para Compensar el Factor de Potencia.

De acuerdo con el tipo de conexión y con los valores conocidos para las unidades
capacitivas, los fabricantes de capacitores recomiendan la formación de grupos de
serie, de acuerdo a la tabla 4.

Número Conexión estrella con Conexión delta o


de neutro flotante estrella aterrizada
grupos Mínimo Mínimo Mínimo Mínimo
en serie número número número número
de
de unidades de de unidades
unidades por unidades por
banco por
por grupo trifásico grupo banco trifásico
1 4 12 1 3
2 8 48 6 36
3 9 81 8 72
4 9 108 9 108
5 10 150 9 135
6 10 180 9 162
7 10 210 10 210
8 10 240 10 240
9 11 297 11 297
10 11 303 11 330
11 11 330 11 363
12 11 396 11 396
13 11 429 11 429
14 11 462 11 462
15 11 495 11 495
Tabla 4. Mínimo número de unidades recomendadas en paralelo por grupo serie para
limitar la tensión a un máximo del 10% sobre la nominal, cuando falla una unidad[6].

43
Análisis para Compensar el Factor de Potencia.

2.6 Planteamiento analítico para la corrección del factor de potencia

2.6.1 Método analítico para corregir el factor de potencia

Considerando usar un banco de capacitores para contrarrestar el efecto inductivo


de un motor. El diseño inicia estableciendo el triángulo de potencias
correspondientes a los datos de placa; a partir de estos datos se hace el cálculo
del valor de los capacitores (valor de la capacitancia) y su respectiva potencia para
corregir el FP a 0.95.

Diseño

Motor trifásico tipo jaula de ardilla de 75 HP (56kW), Factor de servicio 1.15,


Corriente nominal de 188 ampere, eficiencia de 92.8 %, Factor de Potencia 0.84 a
plena carga, velocidad nominal de 3540 rpm, torque nominal de 150.93, torque de
arranque de 1,8, corriente de arranque de 6.8 ampere, peso 320 kilos, dos polos,
60 Hz, tensión de operación 220 volt.

Datos nominales:

P= 56kW
P=56kW (0.928)=51.96kW
FP= 0.84
Desfasamiento
1= cos-1(0.84)
1= 32.85

( )

44
Análisis para Compensar el Factor de Potencia.

Triangulo de potencias

P= potencia activa (W), S= potencia aparente (VA), Q= potencia reactiva (VAr)

Por lo tanto

Dado que: ( )

Tenemos:

Cálculos de parámetros propuestos (deseados).

45
Análisis para Compensar el Factor de Potencia.

( ) ( )

( )

( )

Como la potencia reactiva es igual a:

Despejando se obtiene la reactancia del banco de capacitores, además como


el capacitor se conecta en paralelo opera a una misma tensión, 220V, entonces la
reactancia capacitiva es:

( )

Dado que la reactancia en fin de la frecuencia es:

Se deduce que la capacitancia que permite la corrección del FP/fase es:

( )( )( )

46
Análisis para Compensar el Factor de Potencia.

Finalmente haciendo uso de la tabla 3, se seleccionan las especificaciones para el


banco de capacitores trifásico en baja tensión con los valores calculados en el
punto anterior, los cuales se muestran en la tabla 3a:

Tensión Potencia (kVAr) Capacitancia Fusible


de Corriente nominal NH ó Dz Conductor
línea (V) nominal (μF) de
(A) (A) conexión
50Hz 60Hz 50Hz 60Hz mm2
2.1 2.5 137.01 5.5 6.6 10 2.5
4.2 5 274.03 10.9 13.1 25 2.5
6.3 7.5 411.04 16.4 19.7 32 6
8.3 10 548.05 21.8 26.2 50 10
10.4 12.5 685.07 27.3 32.8 63 16
220V
12.5 15 822.08 32.8 39.4 63 16
14.6 17.5 959.09 38.2 45.9 80 25
16.6 20 1096.12 43.7 52.5 100 25
18.7 22.5 1233.12 49.1 59 100 35
20.8 25 1370.14 54.6 65.6 125 35

Tabla 3a. Especificaciones del banco de capacitores.

2.6.2 Uso de tablas para corregir el factor de potencia

El uso de tablas es una forma más sencilla y rápida ya que a diferencia del método
tradicional en este casose hace uso de la tabla 1, que como se mencionó
anteriormente es útil para obtener el valor del factor K, el cual se debe seleccionar
en función del cosφ inicial (sin compensación) y el deseado. El valor de la
constante es aquel donde se intersectan los valores del factor de potencia inicial y
deseado.

Retomando los valores del factor de potencia tanto inicial como deseado los
cuales tienen una intersección en el valor que se utiliza en el cálculo de la potencia
reactiva necesaria para corregir el factor de potencia a un valor normalizado como
se muestra en la tabla 1a:

47
Análisis para Compensar el Factor de Potencia.

Factor de Factor K
potencia Factor de potencia deseado
Inicial 0.9 0.91 0.92 0.93 0.94 0.95 0.96 0.97
0.76 0.371 0.4 0.429 0.46 0.492 0.526 0.563 0.605
0.77 0.344 0.373 0.403 0.433 0.466 0.5 0.537 0.578
0.78 0.318 0.347 0.376 0.407 0.439 0.474 0.511 0.552
0.79 0.292 0.43 0.35 0.381 0.413 0.447 0.484 0.525
0.8 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499
0.81 0.24 0.268 0.298 0.329 0.361 0.395 0.432 0.473
0.82 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.447
0.83 0.188 0.216 0.246 0.277 0.309 0.343 0.38 0.421
0.84 0.162 0.19 0.22 0.251 0.283 0.317 0.354 0.395
0.85 0.135 0.169 0.194 0.225 0.257 0.291 0.328 0.369
Tabla 1a. Intersección de valores del factor de potencia inicial y deseado.

Una vez localizado el valor se sustituye en la ecuación (2.11) para calcular la


potencia reactiva del capacitor.

( )

Una vez que se calculó la potencia reactiva se hace uso de la tabla 3, para
seleccionar las especificaciones del banco de capacitores que se utilizara para la
corrección del factor de potencia lo cual se muestra en la tabla 3a:

Tensión Potencia (kVAr) Capacitancia Fusible


de Corriente nominal NH ó Dz Conductor
línea (V) nominal (μF) de
(A) (A) conexión
50Hz 60Hz 50Hz 60Hz mm2
2.1 2.5 137.01 5.5 6.6 10 2.5
4.2 5 274.03 10.9 13.1 25 2.5
6.3 7.5 411.04 16.4 19.7 32 6
8.3 10 548.05 21.8 26.2 50 10
10.4 12.5 685.07 27.3 32.8 63 16
220V
12.5 15 822.08 32.8 39.4 63 16
14.6 17.5 959.09 38.2 45.9 80 25
16.6 20 1096.12 43.7 52.5 100 25
18.7 22.5 1233.12 49.1 59 100 35
20.8 25 1370.14 54.6 65.6 125 35
Tabla 3a. Especificaciones del banco de capacitores.

48
Análisis para Compensar el Factor de Potencia.

Como se puede notar el cálculo de la potencia reactiva se puede realizar de


distintas maneras como se desarrolló en el ejemplo anterior, donde en primer
instante se utilizó la metodología tradicional y en segundo plano haciendo uso del
método tablas para el cálculo de la potencia reactiva, se tiene que la variación en
el resultado no resulta significativa, por lo cual se puede decir que es viable hacer
uso de cualquiera de los dos métodos.

2.6.3Corrección del factor de potencia en sistemas con armónicas

Para éste caso es necesario tomar en cuenta las consideraciones establecidas en


la tabla 5 donde se muestran los límites para bancos de capacitores.

Valores incluyendo Límite en % del


Armónicas valor nominal
IRMS 180
VRMS 110
VPICO 120
KVAr 135
Tabla 5. Límites para bancos de capacitores[10].

Como se puede apreciar en el diagrama unifilar de la figura 20.

Figura 20. Diagrama unifilar para compensación en sistemas con armónicas.

49
Análisis para Compensar el Factor de Potencia.

Si el horno entra en operación durante las tardes:

 Verificar si existe un problema de resonancia al entrar en operación el


horno.
 Si se requiere tener un factor de potencia de 0.95 durante la tarde ¿Cuál
sería la capacidad del banco de capacitores adicional?
 Si el banco de capacitores adicional debe ser usado como filtro para así no
dañar al de 50kVAr que se encuentra instalado, ¿A qué frecuencia se
sintonizaría?

Principalmente debemos calcular la frecuencia de resonancia:

Donde:

( )( ) ( )( )

( ) ( )

Por lo tanto la frecuencia de resonancia es:

Posteriormente se hace el cálculo del banco de capacitores, tomando en cuenta


que se pretende corregir el factor de potencia a 0.95, para ello se calculará la
potencia total de la planta.

50
Análisis para Compensar el Factor de Potencia.

Horno de inducción:

√ √( ) ( )

Motor de inducción de 100HP:

( )( )

√( ) ( )

Motor de inducción de 50HP.

( )( )

√( ) ( )

Motor de inducción de 70HP:

( )( )

√( ) ( )

51
Análisis para Compensar el Factor de Potencia.

Tablero de 50kW:

√( ) ( )

Por lo tanto las potencias totales de la carga son:

De tal manera que el factor de potencia actual es:

; ( )

Para corregir el factor de potencia a 0.95 tenemos:

( )

Por lo tanto el banco de capacitores requerido es de:

( ) ( ( ) ( ))

Si se tiene un banco de 50kVAr instalado en la planta y para compensar el factor


de potencia a 0.95 se necesitan 63.8kVAr más, por conveniencia se utiliza un
banco de 65kVAr, el cual eleva el factor de potencia a 0.951 que es muy cercano
al deseado.

52
Análisis para Compensar el Factor de Potencia.

Así se tendría:

√( ) ( )

Verificando la resonancia de la nueva condición tenemos:

( )

Por lo tanto la frecuencia de resonancia está dada por:

Por lo que se puede usar un banco de 65kVAr para formar un filtro de 7aarmónica.

Y el valor del reactor para el filtro de 7a esta dado por:

El valor de la resistencia está dado por:

53
Análisis para Compensar el Factor de Potencia.

Posteriormente se deben calcular los límites tanto para el banco como para el
filtro, teniendo así:

Valores nominales para el banco de capacitores de 65kVAr:

La corriente a frecuencia nominal que circula por banco de capacitores como parte
del filtro es:

√ √

Suponiendo que la corriente de 7a armónica es 1/7 de la fundamental del horno,


entonces se tiene que la corriente fundamental del horno de inducción está dada
por:

√ √

Como la corriente armónica fluirá por el banco como parte del filtro, entonces la
corriente rms (Irms) por el banco de capacitores es:

√ √( ) ( )

54
Análisis para Compensar el Factor de Potencia.

El voltaje a frecuencia fundamental en el banco de capacitores es:

√ √

Y el voltaje en el banco de capacitores debido a la 7ª armónica es:

√ √

Por lo tanto el voltaje rms y voltaje pico en el banco de capacitores son:

√ ( ) √ ( )

La potencia entregada por el banco de capacitores es:

√ √

En la tabla 5a se demuestra que los cálculos anteriores no rebasan los límites


mencionados en la tabla 5.

Calculo % Límite % Excede límite?


Irms 105.79 180 NO
Vrms 102.36 110 NO
Vpico 105.98 120 NO
kVAr 108.29 135 NO
Tabla 5a. Comparación de resultados obtenidos con los límites establecidos

55
Análisis para Compensar el Factor de Potencia.

De esta manera se tiene que el banco de capacitores de 65kVAr soportara ser


parte de un filtro para la 7ª armónica y al mismo tiempo nos ayuda a mejorar el
factor de potencia a 0.95, este se conecta como se muestra en la figura 21.

Figura 21. Diagrama unifilar con filtro para armónicas.

56
Análisis para Compensar el Factor de Potencia.

CAPÍTULO 3
COMPENSACÍON DE LA POTENCIA
REACTIVA (FP)

3.1 Introducción

En la operación de los sistemas eléctricos de potencia se presentan, de vez en


cuando, situaciones tales como una demanda anormal de reactivos, esto es, que
dicha demanda sobrepasa la aportación que de ellos hacen algunos elementos de
la red, obligando a los generadores a bajar su factor de potencia para suministrar
los reactivos complementarios. El objetivo de la compensación reactiva es que la
potencia aparente sea lo más parecida posible a la potencia activa.

El costo de generar, transmitir y transformar los reactivos, en el camino a su


consumo, invita a realizar algunas consideraciones con respecto a los elementos
que consumen estos reactivos, imponiendo la necesidad de localizar, operar y
proyectar los equipos compensadores, de tal forma que estos no alteren el
funcionamiento normal del sistema al cual se conecta.

En el presente capitulo se describen los métodos prácticos más comunes para


compensar el factor de potencia que son:

 Máquinas síncronas.
 Compensador Estático de VARS (CEV).
 Bancos de Capacitores.

57
Análisis para Compensar el Factor de Potencia.

3.1.1 Compensación de potencia reactiva mediante maquinas síncronas

Las máquinas sincrónicas pueden funcionar como aportadores de potencia


reactiva funcionando en vacío, siendo en este caso conocidos como capacitores
sincrónicos. La generación de potencia reactiva depende de la excitación,
necesitando ser sobreexcitados para poder satisfacer sus propias necesidades de
energía reactiva y entregar a su vez energía reactiva al sistema, es decir un motor
síncrono diseñado para trabajar en vacío y con un amplio rango de regulación,
estas máquinas síncronas son susceptibles de trabajar con potencia reactiva
inductiva o capacitiva según el grado de excitación del campo. Si están sobre
excitadas se comportan como condensadores. Por el contrario si están sub-
excitadas se comportan como inductancias.

La potencia de un condensador sincrónico en condiciones de sobre-excitación


está limitada por la temperatura, en condiciones de sub-excitación, la potencia
queda limitada por la estabilidad de la máquina. Este tipo de compensación no es
muy utilizada, se utiliza sólo en el caso de que existan en la instalación motores
sincrónicos de gran potencia (mayores a 200 HP) que funcionan por largos
períodos de tiempo.

Figura 22. Compensación mediante maquinas síncronas[8].

58
Análisis para Compensar el Factor de Potencia.

3.1.2 Compensación de potencia reactiva mediante compensador estático de


VAr`s (CEV)

Un CEV puede aportar la potencia reactiva necesaria para el control dinámico del
voltaje, compensando así los desvíos de potencia reactiva de la red, provocados
por grandes variaciones de carga, que podrían provocar variaciones inaceptables
de voltaje, inestabilidades o hasta colapso del sistema. El CEV también es usado
para amortiguar las oscilaciones de potencia, mejorar la estabilidad transitoria y
reducir las pérdidas en el sistema por medio del control de la potencia reactiva.

3.1.3 Compensación de potencia reactiva mediante bancos de capacitores

Este método es el que se utiliza en la actualidad en la mayoría de las instalaciones


industriales dado que es más económico y permite una mayor flexibilidad. Se
pueden fabricar en configuraciones distintas. Sin embargo son muy sensibles a las
armónicas presentes en la red, los bancos de capacitores elevan el factor de
potencia, con lo cual aumenta la potencia transmitida por la línea porque no
necesita conducir la potencia reactiva.

3.2 Tipos de compensación

Una compensación de la potencia reactiva para la corrección del factor de


potencia se puede instalar de diferentes maneras tomando en cuenta factores que
intervienen en la instalación como: tipos de cargas eléctricas, variación y
distribución de las cargas, factor de carga y tensión de las líneas. Los tipos de
compensación pueden ser:

 Compensación individual
 Compensación en grupo
 Compensación central

59
Análisis para Compensar el Factor de Potencia.

3.2.1 Compensación individual

La compensación individual es utilizada principalmente en instalaciones donde sus


equipos en operación tienen un consumo de carga inductiva considerable.

El método de la compensación individual es el tipo de compensación más efectivo


debido a que la potencia reactiva circula por los conductores cortos entre el motor
y el banco de capacitores, la compensación individual presenta las siguientes
ventajas y desventajas:

Ventajas:

 Los capacitores son instalados cerca de la carga inductiva, la potencia


reactiva es confinada al segmento más pequeño posible de la red.
 Los capacitores son puestos en servicio solo cuando el motor está
trabajando.
 Todas las líneas quedan descargadas de la potencia reactiva.

Desventaja:

 El costo de varios capacitores por separado es mayor que el de un


capacitor individual de potencia equivalente.

Es importante mencionar que para no incurrir en una sobre compensación en la


carga inductiva que provoque alteraciones en la tensión que puedan dañar la
instalación eléctrica, la potencia del banco deberá limitarse al 90% de la potencia
reactiva del motor en vacío.

60
Análisis para Compensar el Factor de Potencia.

Figura 23. Compensación individual[4].

Figura 24. El capacitor se conecta en paralelo al equipo[4].

3.2.2 Compensación en grupo

Este tipo de compensación es muy común utilizarla cuando se tienen diversas


cargas inductivas las cuales consumen la misma cantidad de potencia reactiva y
dichas cargas trabajan de manera simultánea. La compensación en grupo
presenta las siguientes ventajas y desventajas.

61
Análisis para Compensar el Factor de Potencia.

Ventajas:

 Se conforman grupos de cargas de diferente potencia pero con un tiempo


de operación similar, para que la compensación se realice por medio de un
banco de capacitores común con su propio interruptor.
 Se reducen costos de inversión para la adquisición de bancos de
capacitores.
 Los bancos de capacitores pueden ser instalados en el centro de control de
motores.

Desventajas:

 La sobrecarga no se reduce en las líneas de alimentación principales, es


decir seguirá circulando potencia reactiva entre el centro de control de
motores y los motores.

Figura 25.Compensación en grupo[4].

62
Análisis para Compensar el Factor de Potencia.

Figura 26. El capacitor se conecta en paralelo a los equipos[4].

3.2.3 Compensación central con banco automático

La compensación central es el método más completo para corregir el factor de


potencia ya que esta se basa en instalar la potencia total del banco de capacitores
en la acometida, esta potencia se divide en varios bloques según sea el caso de
las cargas instaladas, estos bloques se desconecta y se conectan por medio de un
regulador automático el cual ya está programado para el factor de potencia el cual
se desea obtener. Las ventajas y desventajas que este arreglo presenta son:

Ventajas:

 Mejor utilización de la capacidad de los bancos de capacitores.


 Se tiene una mejora en la regulación de tensión en el sistema.
 El suministro de potencia reactiva es conforme se requiera en ese instante.

Desventajas:

 Se requiere de un regulador automático del banco para compensar según


las necesidades de cada momento.
 La sobrecarga no se reduce en la fuente principal ni en las líneas de
distribución.

63
Análisis para Compensar el Factor de Potencia.

Figura 27. Compensación central[4].

Figura 28. Capacitor en paralelo a la línea[4].

3.3 Conexión de los bancos de capacitores

Los capacitores instalados, se pueden conectar en cualquiera de las conexiones


trifásicas clásicas que son: Estrella sólidamente aterrizada, estrella con neutro
flotante y conexión delta.

64
Análisis para Compensar el Factor de Potencia.

3.3.1 Conexión estrella a tierra con neutro sólidamente aterrizado

En esta conexión, el voltaje de las unidades capacitivas debe ser igual o mayor
que el voltaje de fase a neutro del sistema al cual se van a conectar. Normalmente
esta conexión se usa en sistemas de distribución, en rangos de tensiones hasta
34.5 kV. La capacidad del banco en kVAr se selecciona de manera que
proporcione la potencia reactiva deseada en el sistema.

Cada fase en este tipo de conexión está formada por grupos de unidades
capacitivas conectadas en serie paralelo para dar el valor de potencia deseado tal
como se muestra en la figura 29 a), en este tipo de arreglos generalmente se
adopta una protección por fusibles para cada unidad capacitiva, sin embargo
existe también la posibilidad de proteger a las unidades capacitivas por grupo,
esta opción se usa generalmente en sistemas de distribución con compensación
de baja capacidad, esto se muestra en la figura 29 b).

Figura 29. Conexión estrella a tierra con neutro sólidamente aterrizado.

65
Análisis para Compensar el Factor de Potencia.

La conexión estrella con neutro sólidamente aterrizado, tiene la ventaja de permitir


un balanceo de fases más fácil que en otras conexiones, sin embargo en estos
arreglos, se presenta el problema de que la falla en una unidad capacitiva
presenta una sobretensión en el resto de las unidades del arreglo, sometiéndolas
a mayores esfuerzos dieléctricos.

3.3.2 Conexión estrella con neutro flotante

Este tipo de conexión se usa es sistemas de media tensión o mayores, presenta la


ventaja de evitar en forma importante la presencia de transitorios de sobretensión
y permite también una mejor protección contra sobrecorriente; en cambio, tiene el
problema de desbalance de voltaje, que hace que aparezcan tensiones al neutro,
por lo que es necesario incorporar una protección contra sobretensiones al neutro.
En la figura 30, se muestra la protección para este tipo de arreglo.

Figura 30.Conexión estrella con neutro flotante con protección en el neutro.

3.3.3 Conexión delta

En esta conexión se usa generalmente en baja tensión (600 Volts o menos) en


motores eléctricos ó cargas de valor similar, tiene la ventaja sobre las conexiones
en estrella de que no presenta problemas de desbalance y también aísla las
corrientes armónicas.

66
Análisis para Compensar el Factor de Potencia.

Figura 31. Conexión delta para motores en baja tensión.

3.4 Componentes armónicas

Las armónicas son corrientes y/o voltajes presentes en un sistema eléctrico, con
una frecuencia múltiplo de la frecuencia fundamental. Así, en sistemas con
frecuencia de 60 Hz y cargas monofásicas, las armónicas características son la
tercera (180 Hz), quinta (300 Hz), y séptima (420 Hz) por ejemplo. Con el
creciente aumento en el uso de cargas no lineales (procedentes de la electrónica
de potencia), se han empezado a tener algunos problemas en las instalaciones
eléctricas debido a los efectos de las componentes armónicas de corrientes y
voltajes en el sistema eléctrico, que no se contemplaban anteriormente. Entre
estos están el calentamiento en cables, en los devanados de transformadores y
motores, el disparo repentino de interruptores, el sobrecalentamiento (y posible
explosión) de capacitores, y también el mal funcionamiento de equipos de control
y medición en general.

67
Análisis para Compensar el Factor de Potencia.

Figura 32. Onda fundamental (60 Hz) y componentes armónicas: 5º (300 Hz), 7º (420 Hz)
y 11º (660 Hz)[10].

En particular, al incorporar un banco de capacitores en una instalación con


equipos productores de armónicas, se debe tener en cuenta que aunque los
capacitores son cargas lineales, y por lo tanto no crean armónicas por sí mismos,
pueden contribuir a producir una amplificación importante de las armónicas
existentes al entrar en combinación con las mismas.

Al respecto hay que considerar que la impedancia de un capacitor se reduce


cuando crece la frecuencia, presentando así un camino de baja impedancia para
las corrientes de las armónicas superiores. Por su parte, los capacitores de
corrección del factor de potencia forman un circuito paralelo con la inductancia de
la red de distribución y con la del transformador. Así las corrientes armónicas
generadas por los elementos no lineales se dividen entre las dos ramas de este
circuito paralelo, dependiendo de la impedancia presentada por el circuito para
cada armónica.

68
Análisis para Compensar el Factor de Potencia.

Esto puede provocar una sobrecorriente muy perjudicial para el capacitor. En el


peor de los casos, cuando la frecuencia de alguna corriente armónica coincide, o
está próxima, con la frecuencia de resonancia del circuito paralelo, la corriente que
circula por cada rama del banco puede llegar a ser tan grande que los capacitores
se degraden aceleradamente, o eventualmente exploten. Asimismo, estas
corrientes armónicas también producen sobretensiones que se suman a la tensión
total aplicada al capacitor y pueden dañar al dieléctrico del mismo.

Al energizar un banco de capacitores esta toma corrientes transitorias, cuya


magnitud puede llegar a alcanzar valores elevados en el momento de cerrar el
circuito. Un banco de capacitores descargado, hace bajar momentáneamente a
cero la tensión de la línea en el lugar de su instalación, y para el sistema esto
representa un corto circuito aparente. Si los capacitores se encontraban cargados
antes de conectarse a la línea y si la polaridad de tensión era distinta a la de la
línea en el momento de la conexión, se producen corrientes todavía más altas.

Existen dos razones que se deben considerar cuando se instalen capacitores para
corregir el factor de potencia. La primera razón, es como ya se había mencionado
anteriormente es que los capacitores son por naturaleza un camino de baja
impedancia para las corrientes armónicas, esto es, absorben la energía a las altas
frecuencias. Este aumento en las corrientes, incrementa la temperatura del
capacitor y por consiguiente reduce su vida útil. La segunda razón, y
potencialmente más peligrosos, es el efecto de resonancia.

Cuando los capacitores son conectados al sistema eléctrico, ellos forman un


circuito de resonancia en paralelo junto con las inductancias del sistema
(transformador). Si llegase a existir una corriente armónica cercana al punto de
resonancia formado, entonces el efecto se magnifica. Este efecto amplificado,
puede causar serios problemas tales como un exceso en la distorsión de tensión,
disparos por sobretensiones en los controladores, niveles de aislamiento
estresados de transformadores y conductores.

69
Análisis para Compensar el Factor de Potencia.

Se recomienda que para evitar que la distorsión armónica no afecte el


funcionamiento adecuado de un capacitor, su corriente eficaz no debe sobrepasar
un 115% de su valor a plena carga.

Figura 33. Circuitos que ejemplifican a) resonancia paralelo, b) resonancia serie[11].

La resonancia paralela es una impedancia alta para el flujo de corriente armónica,


mientras la resonancia serie es una impedancia baja para el flujo de corriente
armónica.

La resonancia en paralelo ocurre cuando la reactancia inductiva del sistema y las


reactancias capacitivas son iguales a la misma frecuencia.

La resonancia serie es el resultado de series de combinaciones de bancos de


capacitores y líneas ó inductancias de transformadores.

3.5 Instalación real

En una instalación industrial se requiere corregir el factor de potencia a un valor


normalizado. En la cual del medidor instalado, se tomaron las siguientes lecturas
durante las 24 hrs. Del día, los datos se muestran en la tabla 6.

70
Análisis para Compensar el Factor de Potencia.

Periodo
Horas kW kVAr kWH kVArH
En Horas
de 0 a 8 8 20 70 160 560
de 8 a 10 2 300 240 600 480
de 10 a 12 2 320 220 640 440
de 12 a 14 2 80 120 160 240
de 14 a 15 1 280 200 280 200
de 15 a 18 3 300 280 900 840
de 18 a 24 6 20 70 120 420
Total 24 - - 2860 3180
Tabla 6. Medición de consumo de energía en una industria.

Suponiendo que el trabajo en la industria es constante durante los 26 días que


opera al mes, probablemente las lecturas de la compañía suministradora serian:

De la tabla 6 se representan en forma gráfica, las demandas que se tienen dentro


de la industria, los cual se muestra en las figuras 34 y 35.

Figura 34. Demanda de kW en un día.

71
Análisis para Compensar el Factor de Potencia.

Figura 35. Demanda de kVAr en un día.

Posteriormente se realizó un análisis similar para los siguientes meses, los


resultados se muestran en la tabla 7.

LECTURAS
MES kWH kVArH Demanda Máxima
Marzo 2012 74360 82680 320 kW
Abril 2012 52500 64300 290 kW
Mayo 2012 85240 102300 380 kW
Promedios 70700 83093 330 kW
Tabla 7. Lecturas mensuales en la industria.

Si la industria trabaja 208 horas al mes tenemos:

Teniendo estos valores calculamos el factor de potencia actual de la industria.

72
Análisis para Compensar el Factor de Potencia.

√ √( ) ( )

Si se quiere corregir el factor de potencia a 0.90, haciendo uso de la tabla 1


tenemos que el factor K para calcular el banco de capacitores será 0.72, teniendo
así:

( )

Si la corrección debe hacerse en el lado de baja tensión del sistema y este trabaja
a 220V, 60Hz, de la tabla 3 se seleccionan los bancos para cubrir los 244kVAr
que se necesitan para corregir el FP.

De lo cual tenemos que los bancos de capacitores y lugares de colocación serán:

3 de 50 kVAr para la subestación de 450 kVA.


1 de 20 kVAr para el motor de 75 H.P.
3 de 25kVAr para el alimentador de soldadoras.

La colocación de los bancos se muestra en la figura 36.

73
Análisis para Compensar el Factor de Potencia.

Figura 36. Diagramar que muestra la colocación de los bancos de capacitores.

74
Análisis para Compensar el Factor de Potencia.

CAPÍTULO 4
BENEFICIOS TÉCNICO-ECONÓMICOS

4.1 Introducción

En este capítulo se analizan los diferentes beneficios que se obtiene al corregir el


factor de potencia como consecuencia de compensar potencia reactiva en un
sistema eléctrico, estos beneficios son los que se consideran a continuación:

 Aumento en la capacidad del sistema.


 Disminución en la caída tensión.
 Reducción de pérdidas.
 Reducción de cargos en la factura.

4.2 Aumento en la capacidad del sistema

El aumento en la capacidad del sistema eléctrico, es un beneficio muy importante


el cual justifica la implementación de bancos de capacitores en los sistemas de
distribución. Esto es particularmente significativo cuando las cargas alimentadas
por el sistema eléctrico aumentan rápidamente. El uso de bancos de capacitores
reduce la carga en kVA del sistema, de esta forma se libera capacidad (kVA) que
puede usarse para alimentar cargas futuras, dicha potencia liberada se deduce de
la ecuación (4.1).

(4.1)

75
Análisis para Compensar el Factor de Potencia.

4.3 Disminución de caídas de tensión

Al conectar un capacitor en paralelo, no solo se incrementa el factor de potencia


de la fuente que entrega potencia a la carga, sino que también disminuye la
corriente de la fuente, considerando una impedancia de la línea entre la fuente y la
carga, la disminución en la corriente de la fuente da por resultado que se tengan
menos pérdidas en la línea y menos caídas de tensión en la misma.

El tener un bajo factor de potencia trae como consecuencias caídas de tensión en


la planta cuando los kVAr del sistema de distribución son exigidos. Cuando el
factor de potencia disminuye, la corriente total dela línea se incrementa
(principalmente corriente reactiva) causando grandes caídas de tensión a través
de la impedancia de línea. Esto se debe a que la caída de tensión en una línea es
igual a la corriente que fluya multiplicada por la impedancia de la línea. Entre
mayor sea corriente mayor será la caída de tensión.

La implementación de capacitores produce un incremento de tensión en el


sistema, desde el punto de la instalación hacia la generación. En un sistema con
factor de potencia (FP) atrasado, esto se presenta debido a que los capacitores
pueden reducir la cantidad de corriente reactiva que se transporta en el sistema,
de esta forma se reduce la caída de tensión resistiva y reactiva en el mismo. Para
estimar el porcentaje de la disminución de la caída de tensión esta dado por la
ecuación (4.2):

(4.2)

76
Análisis para Compensar el Factor de Potencia.

4.4 Reducción de pérdidas

La potencia que se pierde por calentamiento está dada por la expresión I2R donde
I es la corriente total y R es la resistencia eléctrica de los equipos (conductores,
bobinas de generadores y transformadores).

Las pérdidas por efecto Joule se manifestarán en:

 Calentamiento de cables
 Calentamiento de las bobinas del transformador
 Disparo sin causa aparente de los dispositivos de protección

Uno de los mayores problemas que causa el sobrecalentamiento es el deterioro


irreversible del aislamiento de los conductores, que además de reducir la vida útil
de los equipos, puede provocar cortos circuitos.

El bajo factor de potencia también puede causar pérdidas de potencia en el


sistema de distribución interno de la planta. La corriente en los alimentadores es
alta debido a la presencia de la corriente reactiva. Cualquier reducción en esta
corriente disminuye los kW de perdida en la línea.

Al pasar de un factor de potencia bajo (FP<0.9) a un factor de potencia alto


(FP>0.9), la corriente se reduce cierto porcentaje y por consiguiente las pérdidas
también se reducen, dichos porcentajes se calculan con la ayuda de las
ecuaciones 4.3 y 4.4 respectivamente.

(4.3)

(4.4)

77
Análisis para Compensar el Factor de Potencia.

4.5 Penalización y bonificación

En México de acuerdo a la tarifa y Diario Oficial de la Federación del día 10 de


Noviembre de 1991, cuando el factor de potencia tenga un valor inferior a 0.9, el
suministrador de energía eléctrica tendrá derecho a cobrar al usuario una
penalización o cargo por la cantidad que resulte de aplicar al monto de la
facturación el porcentaje de recargo que se determine según la siguiente fórmula:

*( ) + (Cuando ) (4.5)

Importe del cargo = Factor de cargo x Costos Energéticos

En el caso de que el factor de potencia tenga un valor superior de 90%, el


suministrador tendrá la obligación de bonificar al usuario la cantidad que resulte de
aplicar a la factura el porcentaje de bonificación según la ecuación (2.4).

* ( )+ (Cuando ) (4.6)

Importe del cargo = Factor de Bonificación x Costos Energéticos

Los valores resultantes de la aplicación de estas fórmulas se redondearán a un


solo decimal, por defecto o por exceso, según sea o no menor que 5 el segundo
decimal. En ningún caso se aplicaran porcentajes de penalización superiores a
120%, ni porcentajes de bonificación superiores a 2.5%.

78
Análisis para Compensar el Factor de Potencia.

4.6 Ejemplo numérico de los beneficios de la corrección del factor de


potencia

Figura 37. Caso de estudio de los beneficios.

DATOS:
S=500kVA.
Factor de potencia actual=0.7
Factor de potencia deseado=0.95
Conductor 600KCM a 100 metros de distancia
6 conductores 2/fase
220 volts
350 kW

79
Análisis para Compensar el Factor de Potencia.

Para el cálculo del banco de capacitores tenemos:

( )

( )

La potencia reactiva necesaria para la corrección del factor de potencia es:

( ( ) ( ))

La potencia liberada en el sistema se obtiene a partir de:

Potencia en el transformador con FP=0.7

Potencia en el transformador con FP=0.95

La potencia liberada al corregir el factor de potencia en el transformador es:

La reducción de pérdidas se obtiene de:

Corriente con factor de potencia de 0.7

√ √

80
Análisis para Compensar el Factor de Potencia.

Corriente con factor de potencia de 0.95

√ √

Por lo tanto:

La corriente se reduce en un 26.37%

Calculo de la corriente en los conductores de fase sin corregir el FP.

Calculo de la corriente en los conductores de fase al corregir el FP.

Resistencia de un conductor de 600 KCM a 100 metros de distancia.

( ) ⁄

Pérdidas en el alimentador considerando la corriente de conductor sin corregir el


FP.

81
Análisis para Compensar el Factor de Potencia.

Pérdidas en el alimentador considerando la corriente de conductor al corregir el


FP.

Por lo tanto:

Las pérdidas se reducen en un 46.87%.

Para determinar la reducción en la caída de tensión tenemos:

Cálculo de la caída de tensión antes de corregir el FP.

Cálculo de la caída de tensión después de corregir el FP.

Por lo tanto el porcentaje de la disminución de la caída de tensión es:

82
Análisis para Compensar el Factor de Potencia.

4.7 Análisis económico por medio de la corrección del factor de potencia

Anteriormente se mostro el análisis de los beneficios que se tienen al corregir el


factor de potencia, sin mencionar el más representativo y el que justifica el uso de
bancos de capacitores, como lo es la reducción de cargos en la factura; por lo cual
en este punto se llevará a cabo un análisis económico a través de las facturas
eléctricas mostradas en las figuras 38 y 39, las cuales especifican la penalización
y/o bonificación que se tiene de acuerdo al FP.

Figura 38. Recibo de consumo de energía con bajo factor de potencia.

83
Análisis para Compensar el Factor de Potencia.

Figura 39. Recibo de consumo de energía con factor de potencia corregido a 0.95.

De la ecuación 4.5 tenemos que:

[( ) ] [( ) ]

Tenemos que la penalización que se aplica por tener un factor de potencia de


0.86resulta de un 2.8%

84
Análisis para Compensar el Factor de Potencia.

En la tabla 8, se muestran los costos de la tarifa OM de consumo y venta de


energía de la CFE para los meses de Julio, Agosto y Septiembre del año 2012:

REGIÓN CARGO POR KILOWATT DE CARGO POR KILOWATT-HORA


DEMANDA MÁXIMA MEDIDA DE ENERGÍA CONSUMIDA
MES DE JULIO 2012
BAJA CALIFORNIA $145.65 $1.389
BAJA CALIFORNIA SUR $161.29 $1.877
CENTRAL $164.77 $1.389
NORESTE $151.51 $1.298
NOROESTE $154.67 $1.289
NORTE $152.14 $1.298
PENINSULAR $170.11 $1.327
SUR $164.77 $1.342
MES DE AGOSTO 2012
BAJA CALIFORNIA $146.41 $1.393
BAJA CALIFORNIA SUR $162.13 $1.882
CENTRAL $165.63 $1.393
NORESTE $152.30 $1.302
NOROESTE $155.47 $1.292
NORTE $152.93 $1.302
PENINSULAR $170.99 $1.331
SUR $165.63 $1.346
MES DE SEPTIEMBRE 2012
BAJA CALIFORNIA $144.86 $1.340
BAJA CALIFORNIA SUR $160.41 $1.810
CENTRAL $163.87 $1.340
NORESTE $150.69 $1.252
NOROESTE $153.82 $1.243
NORTE $151.31 $1.252
PENINSULAR $169.18 $1.280
SUR $163.87 $1.295
Tabla 8. Costos de la tarifa OM en los meses de Julio, Agosto y Septiembre del
2012[3].

De la tabla 8, tenemos que el cargo por kilowatt de demanda máxima medida es


de $164.77 y $165.63 para los meses de Julio y Agosto respectivamente, mientras
que el cargo por kilowatt-hora de energía consumida es de $1.389 para el mes de
Julio mientras que para Agosto se tiene que es de $1.393. Con lo cual podemos
realizar el cálculo de la factura:

85
Análisis para Compensar el Factor de Potencia.

Cargos Valor Cargo Total ($)


Julio 7,672 kWh 1.389 10,656.40
Consumo de energía Agosto 548 kWh 1.393 763.36
Consumo total 11,419.78

Demanda máxima Julio 33 kW 164.77 4,910.52


Agosto 33 kW 165.63 352.54
Demanda total 5,263.61
Total consumo
16,683.39
y demanda

Penalización por FP 16,683.39 2.80% 459.46


menor de 0.90 Subtotal 17,476.44

IVA (15%) 17,476.44 15% 2,796.24

Total 20,273.00
Tabla 9. Cálculo de la factura eléctrica con penalización por FP.

Si se corrige el factor de potencia de 0.86 a 0.95 podemos calcular la bonificación


que se tiene mediante la ecuación 4.6, teniendo así:

[ ( )] [ ( )]

Podemos observar que si se eleva el factor de potencia a un valor normalizado en


este caso 0.95 nos resulta en una bonificación de 1.31% el cual se refleja en la
factura eléctrica; de la tabla 8 obtenemos los cargos por kilowatt de demanda
máxima medidos para los meses de Agosto y Septiembre los cuales son $165.63
y $163.87 respectivamente, mientras que los cargos por kilowatt-hora de energía
consumida en Agosto son de $1,393 y en Septiembre de $1.340; podemos
calcular la factura eléctrica:

86
Análisis para Compensar el Factor de Potencia.

Cargos Valor Cargo Total ($)


Agosto 7,280 kWh 1.393 10,141.04
Consumo de energía Septiembre 520 kWh 1.340 696.80
Consumo total 10,837.84

Demanda máxima Agosto 33 kW 165.63 4,936.15


Septiembre 33 kW 163.87 348.79
Demanda total 5,284.94
Total consumo
16,122.78
y demanda

Bonificación por FP 16,122.78 -1.31% 211.20


mayor de 0.90 Subtotal 16,245.70

IVA (15%) 16,245.70 15% 2,436.85

Total 18,682.00
Tabla 10. Cálculo de la factura eléctrica con bonificación por FP.

Una vez realizados los cálculos de las facturas podemos saber cuánto es el ahorro
mensual que se tiene al corregir el factor de potencia el cual está dado por el total
de la factura sin corregir el FP menos el total de la factura después de corregir el
FP:

Si para corregir el factor de potencia de 0.86 a 0.95 se necesita un capacitor de 10


kVAr a 240V, de la tabla 11 vemos que tiene un precio de $7,200.00

87
Análisis para Compensar el Factor de Potencia.

Tabla 11. Lista de precios de bancos de capacitores de la marca “Arteche”[14].

Con estos datos podemos hacer un aproximado de la recuperación de la inversión


la cual sería:

( )
( )

La inversión se recupera en aproximadamente 5 meses y el capacitor aún tiene 7


años de garantía y seguirá produciendo ahorros durante toda su vida útil. Es
importante mencionar que también se cuenta con los beneficios de reducción de
pérdidas en el alimentador, disminución de la caída de tensión y aumento en la
capacidad de algunos equipos como el transformador.

88
Análisis para Compensar el Factor de Potencia.

CONCLUSIONES

Como se ha mencionado, en el cuerpo de esta tesis, el mayor monto de


facturación de energía, alrededor del 60%, se debe al uso de los motores de
inducción utilizados en los procesos de producción, bandas de transportación de
materiales, cementeras, minas y sistemas de bombeo, entre otros. Estas cargas
inductivas provocan un defasamiento φ, entre la tensión y la corriente, superior a
25.8°, dando lugar a un Factor de Potencia en retraso, menor a 0.9; ya que, el
Factor de Potencia , y el coseno de cualquier ángulo mayor a 25.8°

es menor a 0.9. En estas condiciones, a partir de una demanda de energía de 25


kW, que pueden incluir los servicios domésticos como los molinos de nixtamal, se
penaliza, en los términos señalados en la ecuación 4.5. Sin embargo, si se corrige
el defasamiento para tener un FP mayor a 0.9; entonces se otorga una
bonificación igual a la determinada por la ecuación 4.6, bonificación que puede ser
de hasta del 2.5%, cuando dicho FP es muy próximo a uno.

Para el análisis de corrección del FP, se realiza una breve descripción del
comportamiento en el tiempo de las señales de tensión, corriente y potencia de las
cargas pasivas: resistivas, inductivas y capacitivas, de donde se observa que el
efecto contrario al inductivo es el efecto capacitivo; entonces, los capacitores
corrigen el FP compensando la potencia reactiva inductiva, minimizando pérdidas
de energía en los propios motores, conductores y transformadores.

En general el método analítico permite determinar el valor de la capacitancia de


los capacitores, para corregir el FP para tener valores de entre 0.9 y 1, como lo
establece la norma, y así compensar la potencia reactiva inductiva, para este
caso, se parte de la relación fasorial de potencias S, P y Q, representados
mediante un triángulo rectángulo de potencias, denominado triángulo de
potencias, de donde se derivan las expresiones matemáticas descritas en las
ecuaciones 2.4-2.10 que permiten determinar la potencia y capacidad de los
capacitores requeridos paras la corrección del FP.

89
Análisis para Compensar el Factor de Potencia.

El uso de tablas, para determinar la capacitancia y potencia de capacitores, es un


recurso práctico para corregir el FP, ya que permite relacionarlos con valores
comerciales; sin embargo la construcción de dichas tablas se realiza a partir de
relacionar las identidades de P, Q, S y φ de un tri ngulo de potencias.

Asimismo, se describen las formas más convenientes de conectar los capacitores


para compensar el FP y finalmente se presentan los beneficios técnicos y
económicos que se tienen cuando se opera un sistema dentro de la norma, que en
síntesis son:
 Mejor operación eléctrica de un sistema.
 Estabilidad en la tensión, disminución en las caídas de tensión.
 Reducción de pérdidas por efecto joule.
 Reducción de penalizaciones, en la facturación.

90
Análisis para Compensar el Factor de Potencia.

BIBLIOGRAFÍA

[1] Notas académicas del curso de análisis de circuitos eléctricos II, Ing. José
Antonio Martínez Hernández

[2]Instituto Politécnico Nacional. Apuntes de Electrotecnia III, Ing. Benjamín


Cedeño Aguilar, 2003.

[3]http://www.cfe.gob.mx.

[4]Compendio de información de la Comisión Nacional para el Ahorro de Energía:


http://www.conae.gob.mx.

[5] I. Grainger John, D. Stevenson Jr. William. Análisis de Sistemas de Potencia,


2008.

[6]Norma NMX-J-203-ANCE. Especificaciones y Requerimientos para Bancos de


Capacitores en Baja y Media Tensión, Julio 2008.

[7] Comisión Federal de Electricidad, “Relación de Compensadores Estáticos de


VARS”, Subdirección de Transmisión, Coordinación de Protecciones,
Comunicaciones y Control, 2010.
.
[8]Capacitores para la Corrección del Factor de Potencia. Ing. Jesús Garduño,
Fernández. México 12, D.F.

[9] GÔNEN, Turan; Electic Power Distribution System Engineering. McGraw-Gil.


1986.

[10]IEEE-519, "IEEE Recomendó Prácticas y Requerimientos para el Control


armónica en Sistemas Eléctricos de Potencia".

91
Análisis para Compensar el Factor de Potencia.

[11] G. Lemieux, "Power System Harmonic Resonance - A Documented


Case"IEEE Transactionson Industry Applications, vol. 26, NO. 3, May/June, 1990.

[12] Administración de la Demanda Eléctrica, Medición de Energía y Corrección


del Factor de Potencia, Ing. Jesús A. Báez Moreno, Departamento de Ingeniería
Eléctrica/Centro de Estudios de Energía, Marzo 2008.

[13] Compensación por Bancos de Capacitores en un Sistemas Eléctricos de


Potencia. Artículo, IEEE, Septiembre 2008

[14] Catálogo de precios de bancos de capacitores Arteche, pag. 3, Enero 2012.

[15] Enríquez Harper Gilberto. El libro practico de los generadores,


transformadores y motores, Septiembre 2008.

92