ATS-63A1&ATS-63A2&ATS-63T1

User Manual

Issue 01

Date 2014-10-30

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2014. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com
Email: support@huawei.com

Huawei Proprietary and Confidential


Issue 01 (2014-10-30) i
Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual About This Document

About This Document

Purpose
This document describes the ATS-63A1, ATS-63A2, and ATS-63T1 (ATS for short) in terms
of their application scenarios, panels, ports, working principles, installation, and cable
connections.
The figures provided in this document are for reference only.

Intended Audience
This document is intended for:
 Hardware installation engineers
 Installation and commissioning engineers
 Field maintenance engineers
 System maintenance engineers
 Sales engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, may result in minor or moderate injury.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential ii


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual About This Document

Symbol Description
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue 01 (2014-10-30)
This issue is the first official release.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential iii


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Model Number Description .......................................................................................................................................... 1
1.2 Introduction .................................................................................................................................................................. 1
1.3 Application Scenario ..................................................................................................................................................... 3
1.4 Panel and Ports ............................................................................................................................................................. 4
1.5 Working Principles........................................................................................................................................................ 8

2 Installation and Cable Connection .......................................................................................... 10


2.1 Installation .................................................................................................................................................................. 10
2.2 Cable Connections to the ATS-63A1 or ATS-63A2 .................................................................................................... 11
2.3 Cable Connections to the ATS-63T1........................................................................................................................... 13

3 Power-on and Maintenance ...................................................................................................... 16


3.1 Power-on ..................................................................................................................................................................... 16
3.2 Troubleshooting .......................................................................................................................................................... 17
3.2.1 ATS Hardware Fault ................................................................................................................................................ 17
3.2.2 ATS Communication Failure ................................................................................................................................... 17
3.2.3 ATS AC Surge Protector Fault ................................................................................................................................. 18
3.2.4 ATS Closing Failure ................................................................................................................................................. 19

4 Parts Replacement ....................................................................................................................... 21


4.1 Replacing an AC SPD ................................................................................................................................................. 21
4.2 Replacing an ATS Main Control Box ......................................................................................................................... 23

5 FAQ ................................................................................................................................................ 26
A Appendix ..................................................................................................................................... 28
A.1 Technical Specifications ............................................................................................................................................ 28
A.2 Monitoring Parameters............................................................................................................................................... 29

Issue 01 (2014-10-30) Huawei Proprietary and Confidential iv


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

1 Overview

1.1 Model Number Description


The following figure shows the ATS model number description.

Figure 1-1 ATS model number description

1.2 Introduction
The ATS is an automatic AC switching system that integrates control and power distribution
modules. Three ATS models are available, namely, ATS-63A1, ATS-63A2, and ATS-63T1. In
the description of common features, a simplified name ATS is used. In the description of their
differences, a full ATS model is used.
The following table describes the differences among the ATS-63A1, ATS-63A2, and
ATS-63T1.

Table 1-1 ATS differences

Model Supported AC Input Rated Capacity Mains Input Surge


Protection

ATS-63A1 Three-phase+three-phase Three-phase: 63 A x 380 V 20 kA (nominal); 40 kA


(maximum)
ATS-63A2 Three-phase+three-phase Three-phase: 63 A x 380 V 30 kA (nominal); 60 kA
(maximum)
ATS-63T1 Three-phase/Dual–live Three-phase: 63 A x 380 V 30 kA (nominal); 60 kA
wire+three-phase/dual–live Dual–live wire: 63 A x 220 V (maximum)
wire

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

The following figure shows an ATS-63A1 or ATS-63A2.

Figure 1-2 ATS-63A1 or ATS-63A2

The following figure shows an ATS-63T1.

Figure 1-3 ATS-63T1

The ATS supports and detects the inputs from two power sources (DG 1 and mains or DG 1
and DG 2) and switches between the two power inputs. The power source can switch to DG 1
by turning the bypass switch. The ATS has the following functions:
 Provides one AC distribution, one 10 A AC output, and one maintenance socket output
(optional) for loads.
 Provides a bypass switch, by using which power source can switch to DG 1.
 Monitors the voltage, current, frequency, and power factor of three-phase outputs.
 Protects mains and DG against overvoltage and undervoltage.
 Generates alarms for mains open phase and DG open phase.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

1.3 Application Scenario


The ATS is applicable to scenarios of DG 1+mains or DG 1+DG 2. The following figure
shows the typical ATS network diagram.

Figure 1-4 Typical ATS network diagram

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

1.4 Panel and Ports


Panel

Figure 1-5 ATS-63A1 or ATS-63A2 interior

(1) Space reserved for (2) 10 A AC output circuit (3) Three-phase AC output
a residual current breaker terminals
device
(4) ATS main control (5) Transfer switch (6) Space reserved for a
box maintenance socket
(7) SPD (8) DG 1 input circuit (9) Mains/DG 2 input circuit
breaker breaker

Figure 1-6 ATS-63T1 interior

(1) Space reserved for (2) 10 A AC output circuit (3) Three-phase AC output
a residual current breaker terminals
device
(4) ATS main control (5) Transfer switch (6) Space reserved for a
box maintenance socket
(7) SPD (8) DG 1 input circuit breaker (9) Mains/DG 2 input circuit

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

breaker

ATS Main Control Box

Figure 1-7 ATS main control box (front and side views)

(1) COM_IN port (2) COM_OUT port (3) RS232 port


(4) Indicators (5) AMF (6) DG RUN
(7) ALM (8) AC FAULT (9) NO1/COM1/NC1
(10) NO2/COM2/NC2 (11) Dual in-line package (DIP) switch

Table 1-2 Indicator description


Silk
Screen Color Status Meaning
RUN Green Blinking at 4 Hz (on for The communication is
0.125s and then off for abnormal.
0.125s)
Blinking at 0.5 Hz (on for 1s The ATS runs properly.
and then off for 1s)
ALM Red Steady on A fault occurs.
Off The fault is rectified.
DG1 Green Steady on DG 1 supplies power.
Off DG 1 supplies no power.
MAIN Green Steady on The mains or DG 2 supplies
(DG2) power.
Off The mains or DG 2 supplies no
power.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

Silk
Screen Color Status Meaning

BYPASS Green Steady on The transfer switch is BYPASS.


Off The transfer switch is AUTO.

Table 1-3 Communications port description

Silk Screen Port Definition Function


COM_IN Master/slave protocol port. The Communicates with the
COM_IN and COM_OUT ports are components such as the energy
COM_OUT internally cascaded. control center 500 (ECC500) and
DC transfer switch (DTS) over
CAN.
RS232 Communications port Communicates with a PC for
maintenance and local upgrade.

Table 1-4 Dry contact description

Silk Screen Meaning Dry Contact Type Remarks

NO1/COM1/NC1 Controls DG 1 Normally open (NO) The DG connects to


startup and or normally closed COM1 and NC1 by
shutdown. (NC) contact default.
NO2/COM2/NC2 Controls DG 2
startup and
shutdown.
AC_FAULT Monitors the AC NO contact Open: The ATS has
input. no AC input.
Closed: The ATS
has AC input.
DG_Run Monitors the DG NO contact Open: The DG is not
status. running.
Closed: The DG is
running.
ALM Reports ATS fault NO contact Open: No alarm is
alarms. generated.
Closed: An alarm is
generated.
AMF Reports mains NC contact Open: The mains is
failure alarms. normal.
Closed: The mains
fails.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

Silk Screen Meaning Dry Contact Type Remarks


Note:
 If the ATS detects that the voltage of any DG is normal, dry contact DG_Run is closed.
 If both the ECC500 and ATS are configured, connect the DG startup/shutdown signal
cable to the DG1_CTL and RST1 ports on the ECC500 panel, rather than the
NO1/COM1/NC1 and NO2/COM2/NC2 ports on the ATS.

Figure 1-8 DIP switch

Table 1-5 DIP switch description

Silk Screen Description


ADD DIP1 indicates a working scenario.
OFF (upwards): Mains+DG (default status)
ON (downwards): DG+DG
DIP2 indicates a hardware address.
OFF (upwards): ATS 1
ON (downwards): ATS 2
CAN 1 and 2 indicate the build-out resistor for the CAN
communications hardware.
OFF (upwards): 0 ohms
ON (downwards): 120 ohms
Note:
 After the ATS main control box is powered on (including hot and cold resetting), the
working scenario is controlled by the DIP switch. After the ATS main control box is
connected to the host, the working scenario is controlled by the host, and the DIP switch
becomes invalid.
 If the ATS is at the end of CAN cascading, set a build-out resistor by setting CAN 1 and
CAN 2 both to ON.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

1.5 Working Principles


Figure 1-9 ATS-63A1 or ATS-63A2 conceptual diagram

Figure 1-10 ATS-63T1 conceptual diagram

The ATS working principles are as follows:


 Set the ATS to work in DG 1+mains or DG 1+DG 2 mode by using the DIP switch on
the side of the ATS main control box. The ATS works in DG 1+mains mode by default.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 1 Overview

After the ATS main control box is powered on (including hot and cold resetting), the working scenario is
controlled by the DIP switch. After the ATS main control box is connected to the host, the working
scenario is controlled by the host, and the DIP switch becomes invalid.
 DG 1+mains mode
− If the mains is normal, the ATS switches to the mains. Then the loads are powered by
the mains.
− If the mains is faulty, the ATS sends a startup signal to the DG. The DG connects to
the loads for power supply.
− If the mains recovers, the ATS switches to the mains after a delay check and shuts
down the DG.
− The cycle continues based on actual situations.
 DG 1+DG 2 mode
− During initial operation, the ATS checks DG 1 contactor. If the contactor is in good
condition, the ATS sends a startup signal to DG 1. After the DG 1 output reaches the
specified value, DG 1 returns a control signal to the ATS. Then the ATS connects DG
1 to the loads for power supply.
− When the DG 1 operating period expires or DG 1 experiences a fault (for example,
contactor fault, overvoltage, or no voltage), the ATS sends a startup signal to DG 2.
After the DG 2 output reaches the specified value, DG 2 returns a control signal to
the ATS. Then the ATS connects DG 2 to the loads for power supply.

If the contactor of a route is faulty, no power is supplied over this route.


 If DG 1 and DG 2 work in active/standby mode, the ATS switches to DG 2 if DG 1 is faulty, or to
DG 1 if DG 2 is faulty.
 If DG 1 and DG 2 work in mutual backup mode, the ATS switches between DG 1 and DG 2 every 8
hours by default.
− When the DG 2 operating period expires or DG 2 experiences a fault (for example,
contactor fault, overvoltage, or no voltage), the ATS sends a startup signal to DG 1.
After the DG 1 output reaches the specified value, DG 1 returns a control signal to
the ATS. Then the ATS connects DG 1 to the loads for power supply.
 The ATS provides one 10 A single-phase AC output.
 (Optional) The ATS provides one maintenance socket output.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

2 Installation and Cable Connection

 When operating Huawei equipment, you must follow the local laws and regulations.
 Installation and maintenance personnel must be trained to perform operations correctly
and safely.
 To prevent electric shocks, get the tool insulated and wear insulation gloves when
connecting cables.

2.1 Installation
Procedure
Step 1 Install slide rails on the rack, as shown in the following figure.

Figure 2-1 Installing slide rails

Step 2 If there are no floating nuts on both sides of the rack, install the floating nuts delivered with
the cabinet.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

Step 3 Push the ATS into the cabinet and tighten the four M6 screws on the left and right mounting
ears using a screwdriver to a torque of 2 N.m, as shown in the following figure.

Figure 2-2 Installing an ATS

----End

2.2 Cable Connections to the ATS-63A1 or ATS-63A2


Prerequisites
You have prepared an electrostatic discharge (ESD) wrist strap or a pair of ESD gloves, a
Phillips screwdriver, a flat-head screwdriver, an ESD box or bag, and the cabinet door key.

Procedure
Step 1 Put on an ESD wrist strap or a pair of ESD gloves.
Step 2 Install the ATS ground cable, as shown in the following figure.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

Figure 2-3 Installing an ATS ground cable

Step 3 Set the CAN communications DIP switch on the ATS.

When the ATS serves as the last level on the CAN communications circuit, switch the toggle switches 1
and 2 of the DIP switch corresponding to the CAN_R port both to 1. Otherwise, signal transmission may
be unreliable.

Step 4 Connect two communications cables respectively to the COM_IN and COM_OUT ports on
the ATS.
Step 5 Install dry contact communications cables for the ATS based on site requirements.
Step 6 Install AC output power cables for the ATS, as shown in the following figure.

Figure 2-4 Installing AC output power cables for the ATS

Step 7 Install AC input power cables for the ATS, as shown in the following figure.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

Figure 2-5 Installing AC input power cables for the ATS

----End

2.3 Cable Connections to the ATS-63T1


Prerequisites
You have prepared an ESD wrist strap or a pair of ESD gloves, a Phillips screwdriver, a
flat-head screwdriver, an ESD box or bag, and the cabinet door key.

Context
The ATS-63T1 fittings contain two short-circuit copper bars, which will be used only for
dual–live wire input.

Procedure
Step 1 Put on an ESD wrist strap or a pair of ESD gloves.
Step 2 Install the ATS ground cable, as shown in the following figure.

Figure 2-6 Installing an ATS ground cable

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

Step 3 Set the CAN communications DIP switch on the ATS.

When the ATS serves as the last level on the CAN communications circuit, switch the toggle
switches 1 and 2 of the DIP switch corresponding to the CAN_R port both to 1. Otherwise,
signal transmission may be unreliable.

Step 4 Connect two communications cables respectively to the COM_IN and COM_OUT ports on
the ATS.
Step 5 Install dry contact communications cables for the ATS based on site requirements.
Step 6 Install AC output power cables for the ATS, as shown in the following figure.

Figure 2-7 Installing AC output power cables for the ATS

Step 7 Install AC input power cables for the ATS.


 Three-phase scenario

Figure 2-8 Installing AC input power cables for the ATS

 Dual–live wire scenario

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 2 Installation and Cable Connection

Figure 2-9 Installing AC input short-circuit copper bars for the ATS

Figure 2-10 Installing AC input power cables for the ATS

----End

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 3 Power-on and Maintenance

3 Power-on and Maintenance

Prerequisites
 The following steps may result in power failures or alarm generation. Before and after
operations, inform the alarm center.
 The commissioning involves various technologies. Only trained personnel are allowed to
perform commissioning. Perform operations strictly in compliance with commissioning
instructions.
 The commissioning is performed with power on. During commissioning, stand on dry
insulating objects, and remove conductive articles such as watches and bracelets. Use
insulated tools.
 During operations, do not contact two electric bodies with different currents.
 When you are performing operations, attach the label "Currently being serviced. Do not
switch on." to the power distribution device to prevent others from performing
operations.
 During commissioning, shut down the device immediately if any fault is detected.
Rectify the fault and proceed with the commissioning.

3.1 Power-on
Procedure
Step 1 Check that power cables, communications cables, signal cables, and ground cables are
correctly and securely connected.
Step 2 Measure the DG or mains input circuit breaker on the ATS using a multimeter and ensure that
at least one AC input is available.
Step 3 Check that the transfer switch is AUTO.
Step 4 Switch the DG 1 input circuit breaker and mains/DG 2 input circuit breaker to ON.
Step 5 Check that the ATS AC output is normal.
Step 6 Check that the ATS communicates with peripheral equipment properly.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 3 Power-on and Maintenance

In scenarios with an ECC500 and ATS-63T1, the setting value of System AC Type on the LCD of
ECC500 must be set to Three Phase regardless of the ATS-63T1 AC input type is three-phase, dual–live
wire or single-phase.

----End

3.2 Troubleshooting
3.2.1 ATS Hardware Fault
Description
This alarm is generated when the ATS or ATS subrack is faulty.

Attribute
Alarm ID Alarm Severity Alarm Type
- Major -

Impact on the System


AC power cannot be switched.

Possible Causes
 The ATS main control box is faulty.
 The ATS subrack is faulty.

Procedure
Step 1 Replace the ATS main control box and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, go to Step 2.
Step 2 Replace the ATS subrack and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, contact Huawei technical support.
----End

3.2.2 ATS Communication Failure


Description
This alarm is generated when the ATS does not respond to the command from the host for 1
minute.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 3 Power-on and Maintenance

Attribute
Alarm ID Alarm Severity Alarm Type
- Major -

Impact on the System


The ATS fails to be monitored and AC power information fails to be obtained.

Possible Causes
 The communications cable is faulty.
 The ATS main control box is faulty.

Procedure
Step 1 Rectify the faults on the communications cable, such as cable damage, loose connectors, bent
pins, or misplaced pins. Then check whether the alarm is cleared.
 If yes, no further action is required.
 If no, go to Step 2.
Step 2 Replace the ATS main control box and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, contact Huawei technical support.
----End

3.2.3 ATS AC Surge Protector Fault


Description
This alarm is generated when the AC SPD on the ATS is faulty.

Attribute
Alarm ID Alarm Severity Alarm Type

- Major -

Impact on the System


The system does not protect against surge and may be damaged.

Possible Causes
 The ATS AC SPD is faulty.
 The ATS main control box is faulty.
 The ATS subrack is faulty.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 3 Power-on and Maintenance

Procedure
Step 1 Check whether the indication window on the SPD is red.
1. If the indication window is red, replace the SPD and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, go to Step 2.
2. If the indication window is green, go to Step 2.
Step 2 Replace the ATS main control box and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, go to Step 3.
Step 3 Replace the ATS subrack and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, contact Huawei technical support.
----End

3.2.4 ATS Closing Failure


Description
This alarm is generated when no feedback signal is received after the ATS control contactor is
closed.

Attribute
Alarm ID Alarm Severity Alarm Type
- Major -

Impact on the System


The AC input becomes abnormal.

Possible Causes
 The ATS main control board is loose.
 The ATS main control box is faulty.
 The ATS subrack is faulty.

Procedure
Step 1 Disconnect the AC loop, reseat the ATS main control box, and close the AC loop. Then check
whether the alarm is cleared.
 If yes, no further action is required.
 If no, go to Step 2.
Step 2 Replace the ATS main control box and check whether the alarm is cleared.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 3 Power-on and Maintenance

 If yes, no further action is required.


 If no, go to Step 3.
Step 3 Replace the ATS subrack and check whether the alarm is cleared.
 If yes, no further action is required.
 If no, contact Huawei technical support.
----End

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 4 Parts Replacement

4 Parts Replacement

4.1 Replacing an AC SPD


An AC SPD needs to be replaced if its indication window turns from green to red, indicating
that the SPD has failed.

Prerequisites
 You have prepared an ESD wrist strap or a pair of ESD gloves, a flat-head screwdriver, a
cable cutter, cable ties, an ESD box or bag, and the cabinet door key.
 You have confirmed the model of the AC SPD to be replaced and prepared a replacement
AC SPD.
 You are authorized to enter the site.

Context
An AC SPD protects all circuits following it by suppressing power surges.

Procedure
Step 1 Put on an ESD wrist strap or a pair of ESD gloves.
Step 2 Disconnect the AC power supply.

An AC SPD can be replaced only when the AC power is off. Otherwise, personal injury will
be caused.

Step 3 Replace the AC SPD.

If... Then...

If only one or more modules in the AC SPD are damaged Perform Step 3.1.

If all modules and the base of the AC SPD are damaged Perform Step 3.2.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 4 Parts Replacement

1. Replace a module in the AC SPD, as shown in the following figure.


a. Hold the faulty module and pull it out.
b. Install a new module in the AC SPD.

Figure 4-1 Replacing a module in the AC SPD

2. Replace the AC SPD.


a. Disconnect cables from the faulty AC SPD. Insulate each cable and label it
immediately after disconnecting it.
b. Push the contact plate on the top of the AC SPD upwards using a flat-head
screwdriver and remove the SPD, as shown in the following figure.

The SPDs of different appearances are removed in similar ways. Remove an SPD based on its actual
appearance.

Figure 4-2 Removing an AC SPD (appearance 1)

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 4 Parts Replacement

Figure 4-3 Removing an AC SPD (appearance 2)

c. Place the replacement AC SPD on the corresponding guide rail, push the contact
plate on the top of the AC SPD upwards using a flat-head screwdriver, and push the
AC SPD inwards to secure it.
d. Reconnect the cables to the AC SPD based on the cable labels.
Step 4 Connect the AC power supply and check that the AC SPD alarm has been cleared.
Step 5 Check whether the AC SPD is running properly by viewing the indication window color. If
the indication window is green, the AC SPD is running properly.
Step 6 Remove the ESD wrist strap or gloves and put all the tools away.
----End

Follow-up Procedure
 Place the faulty component into the ESD box or bag. Then place the ESD box or bag into
a carton padded with foam or into the packing box or bag of the replacement component.
 Fill in the fault card with the information regarding the faulty component.
 Contact your local Huawei office to handle the faulty component.

4.2 Replacing an ATS Main Control Box


The ATS main control box needs to be replaced if it is faulty and cannot be repaired
immediately.

Prerequisites
 You have prepared an ESD wrist strap or a pair of ESD gloves, a Phillips screwdriver, a
flat-head screwdriver, a cable cutter, cable ties, an ESD box or bag, and the cabinet door
key.
 You have confirmed the model of the ATS main control box to be replaced and prepared
a replacement main control box.
 You are authorized to enter the site.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 4 Parts Replacement

Context
 The ATS main control box is not hot-swappable.
 The ATS main control box replacement may cause system power failures. To prevent
power failures, ensure that other power systems, such as the battery, provide continuous
power supply.

Procedure
Step 1 Put on an ESD wrist strap or a pair of ESD gloves.
Step 2 Switch all AC input circuit breakers on the ATS to OFF.

To avoid personal injury, ensure that AC power is off before replacing an ATS main control
box.

Step 3 Disconnect cables from the faulty ATS main control box. Insulate each cable and label it
immediately after disconnecting it.
Step 4 Remove the faulty ATS main control box and install the replacement main control box, as
shown in the following figure.

If the ATS is at the end of CAN cascading, set a build-out resistor before installing the
replacement main control box.

1. Loosen the two captive screws on the panel of the faulty ATS main control box using a
screwdriver. Hold the ejector lever and pull out the faulty main control box.
2. Hold the ejector lever of the replacement ATS main control box and insert the main
control box into the ATS subrack until its front panel aligns with that of the ATS
subrack.
3. Close the ejector lever.
4. Tighten the captive screws using a screwdriver.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 4 Parts Replacement

Figure 4-4 Replacing an ATS-63A1 main control box

(1) Faulty ATS main control box (2) Replacement ATS main control box

Step 5 Reconnect the cables to the replacement ATS main control box based on the cable labels.
Step 6 Set parameters again according to the appropriate installation guide.
Step 7 Remove the ESD wrist strap or gloves and put all the tools away.
----End

Follow-up Procedure
 Place the replaced component into the ESD box or bag and then place the ESD box or
bag into the carbon box with foams or the bag of a new component.
 Fill in the fault card with the information regarding the faulty component.
 Contact your local Huawei office to handle the faulty component.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 5 FAQ

5 FAQ

Symptom
The ATS has no AC output in Bypass mode because the DG shuts down.

Cause
In Bypass mode, the mains/DG 2 AC input circuit breaker is ON. If the mains resumes, the
ATS generates a DG 1 shutdown signal because it determines that the mains is preferred. As a
result, DG 1 shuts down and the ATS has not input.

Solution
Step 1 Disconnect the communications cable between the ATS and DG 1, and restart DG 1.
Step 2 After DG 1 starts, switch the mains/DG 2 AC input circuit breaker to OFF.
Step 3 Check whether the ATS generates AC signals.
Step 4 If no, check the cable connections or contact the maintenance personnel.

After the Bypass mode becomes normal, perform other maintenance tasks.

----End

Using the Bypass Switch


If the ATS main control box is faulty, turn the Bypass switch to Bypass to connect DG 1 and
the ATS by performing the following steps to ensure continuous AC output from the ATS.
Step 1 In the DG 1+mains or DG 1+DG 2 scenario, switch the ATS to the Bypass mode if you
ensure that DG 1 has AC input.
Step 2 Switch the mains circuit breaker (in the DG 1+mains scenario) or DG 2 AC input circuit
breaker (in the DG 1+DG 2 scenario) to OFF.
Step 3 Replace the main control box and connect the cable to the new box.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 26


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual 5 FAQ

Step 4 Switch the mains circuit breaker (in the DG 1+mains scenario) or DG 2 AC input circuit
breaker (in the DG 1+DG 2 scenario) to ON.
Step 5 Turn the Bypass switch to AUTO.
----End

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 27


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual A Appendix

A Appendix

A.1 Technical Specifications


Table A-1 ATS technical specifications

Category Item Specifications


Environment Operating temperature –20°C to +65°C
Storage temperature –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m (When the altitude is between 2000 m and
4000 m, the temperature decreases by 1ºC for each
additional 200 m.)
Structure Dimensions (H x W x D) 175 mm x 442 mm x 310 mm
Weight 17 kg
Installation mode Installed in a standard 19-inch rack
Protection level IP20 (front side)
Maintenance mode All external ports and connected cables can be
maintained from the front.
Electromagnetic Class A (6 dB margin)
compatibility
(EMC)
Safety and Passes the certification of the Conformite Europeenne (CE) and Standards Organization of
regulatory Nigeria Conformity Assessment Programme (SONCAP).
Surge protection AC mains input ATS-63A1: 20 kA in common mode; 20 kA in
differential mode; 40 kA in maximum
ATS-63A2: 30 kA in common mode; 30 kA in
differential mode; 60 kA in maximum
ATS-63T1: 30 kA in common mode; 30 kA in
differential mode; 60 kA in maximum

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 28


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual A Appendix

Category Item Specifications


Surge protection for signal 5 kA in common mode and 3 kA in differential mode
ports
Reliability Mean time between failures ≥ 100,000 hours
(MTBF)
Annual repair rate < 1%
Service Life ≥ 10 years

A.2 Monitoring Parameters


ATS parameters can be configured remotely. The following table describes the parameters.

Table A-2 Parameter settings

Parameter Value Range Default Value Remarks


Lower mains 90–220 V AC 90 V AC Lower voltage switch-off threshold = Voltage
voltage of L1, L2, L3 lower than setting value
switch-on (Switch-on voltage of lower voltage recovery
threshold – 5 V)
Default value: 85 V AC
Upper mains 220–350 V AC 310 V AC Switch-on voltage of upper voltage recovery =
voltage Upper voltage switch-off threshold – 5 V
switch-off
threshold
DG delay load 0–600s 30s -
Lower DG 150–220 V AC 198 V AC Lower voltage switch-off threshold = Voltage
voltage of L1, L2, L3 lower than setting value
switch-on (Switch-on voltage of lower voltage recovery
threshold – 5 V)
Default value: 193 V AC
Upper DG 220–265 V AC 253 V AC Switch-on voltage of upper voltage recovery =
voltage Upper voltage switch-off threshold – 5 V
switch-off
threshold
DG shutdown 0–600s 10s The interval between the time for DG
cool duration generator circuit breaker (GCB) switch-off
and the time when the DG sends shutdown
signals.

The ATS generates real-time monitoring data and reports the data over protocols. The
following table describes the data.

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 29


Copyright © Huawei Technologies Co., Ltd.
ATS-63A1&ATS-63A2&ATS-63T1
User Manual A Appendix

Table A-3 Real-time data

Real-time Data Value Range Precision Requirement


Mains voltage 0–300 V Voltage range: 90–300 V AC
Precision: ±5 V AC
Output current 0–63 A Current range: 0–63 A, THD < 5%
Precision: 1 A
Output frequency 0–65 Hz Frequency range: 40–65 Hz
Precision: 0.1 Hz
DG voltage 0–300 V AC Voltage range: 198–253 V AC
Precision: ±5 V AC
DG current 0–75 A Current range: 0–75 A
THD < 5%
Precision: 1 A
DG frequency 0–65 Hz Frequency range: 40–65 Hz
Precision: 0.1 Hz
Active power 0–30 kW -
Power factor 0–1 -
Electric energy - Level 1 (tolerance ±1%)

Issue 01 (2014-10-30) Huawei Proprietary and Confidential 30


Copyright © Huawei Technologies Co., Ltd.