CIGRE‐IEC 2016 Colloquium on EHV and UHV 

FREQUENCY STABILIZER IN 
Montréal, QC, Canada, May 9‐11, 2016

TRANSMISSION SYSTEMS
E. SPAHIC, S. LETZGUS, G. BECK, G. KUHN, 
V. HILD
SIEMENS GERMANY

Paper ID112
1
New Energy mix ‐> Grid stability jeopardized
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

• Current situation:
Montréal, QC, Canada, May 9‐11, 2016

– Conventional power plants delivering energy & system 
requirements
• Future development:
– Significant increase of energy from renewables
– Thermal and nuclear power plants retirements and shut down 
due to new environmental policies
• Transmission system stability requirements: 
– Frequency control i.e. inertia
– Voltage control i.e. reactive power
– Short circuit power

• Renewables do not provide the necessary inertia and short


circuit power to the power system
2
Stored kinetic energy i.e. inertia – key for frequency stability
CIGRE‐IEC 2016 Colloquium on EHV and UHV 
Montréal, QC, Canada, May 9‐11, 2016

50,1 50,2
Initial response
Hsys = 36 s
Primary reserve 50,0 Hsys = 21 s
50,0
Secondary reserve Hsys = 16 s
Frequency [Hz]

49,8 Hsys = 11 s

Frequency [Hz]
49,9
49,6
49,8
49,4

49,7 49,2
ROCOF
49,6 49,0
0 5 Time [s] 10 15
‐15 0 15 30 45 60 75 90 105 120
Time [s]

• High frequency drop in case of generation outage today
• In future the ROCOF (df/dt) will be higher and frequency deviation 
also (df) since inertia reduced.
• Increase of inertia one of the key issues for the future

3
Future development of inertia – critical!
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

• Strong increase of renewables and phase out of classical power 
Montréal, QC, Canada, May 9‐11, 2016

generators:

• Significant decrease of system inertia, especially in times with high 
renewable penetration
• Similar results for short circuit current and voltage conditions
• Actions necessary!

4
SVC PLUS Frequency Stabilizer ‐> Frequency and voltage stability 
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

improvement
Montréal, QC, Canada, May 9‐11, 2016

• STATCOM with power intensive storage for short time

• Operations in 4 PQ‐quadrants +/‐50 Mvar and +/‐50 MW for app. 8s
• Significantly smaller footprint (app. 3000 m2 for 50 MVA)
• Significantly lower costs comparing with other technologies

5
SVC PLUS Frequency Stabilizer ‐> significant frequency 
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

performance improvement
Montréal, QC, Canada, May 9‐11, 2016

• Use Case United Kingdom Summer 2024 “Go Green”, Outage of 
HVDC interconnector with France.
50,2
50,0
With SVC PLUS Frequency Stabilizer 
49,8
Frequency [Hz]

@500 MW
49,6 With SVC PLUS Frequency Stabilizer 
@250 MW
49,4
49,2
Without SVC PLUS 
49,0
Frequency Stabilizer
48,8
0 5 10 15 20 25 30 35 40
Time [s]

• Flexible application of the SVC PLUS Frequency Stabilizer ‐> operation 
at full power or at e.g. 50%. Different impacts. “Smart” application. 

6
SVC PLUS Frequency Stabilizer and Power Oscillation Damping
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

• STATCOM can impact (reduce) the POD by changing the reactive 
Montréal, QC, Canada, May 9‐11, 2016

power at one of the grid points
• With active power injection/storage the impact on the POD much 
higher.
2,5

2,0

1,5
Power [GW]

Without SVC PLUS Frequency Stabilizer
1,0 With SVC PLUS Frequency Stabilizer
Active power from/into SVC PLUS Frequency Stabilizer
0,5

0,0

‐0,5
0 1 2 3 4 5 6 7 8 9 10
Time [s]

• Lower POD and faster dampening with SVC PLUS Frequency Stabilizer

7
SVC PLUS Frequency Stabilizer – Test facility and results
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

• Two towers with 1,65 MW total power
Montréal, QC, Canada, May 9‐11, 2016

• Measurement results for active/reactive power

Active power (pu) Reactive power (pu) Time (s)


STATCOM operation 0.00 - 0.24 0–2
STATCOM operation 0.00 1.00 2–3
STATCOM operation 0.00 0.48 3–4
Frequency & voltage support 0.48 0.24 4–5
Full frequency support 1.00 0.00 5–6
STATCOM operation 0.00 - 0.24 6–9

1,2
1,0 Active power
0,8 Reactive power
Power [pu]

0,6
0,4
0,2
0,0
‐0,2
‐0,4
0 1 2 3 4 5 6 7 8 9
Time [s]

8
Conclusions
CIGRE‐IEC 2016 Colloquium on EHV and UHV 

• Future networks with increased renewables are facing challenges like 
Montréal, QC, Canada, May 9‐11, 2016

lack of inertia
• MMC STATCOM with power intensive energy storage (also called SVC 
PLUS Frequency Stabilizer) can actively support the grid
• Based on the proven technologies SVC PLUS and supercaps
• Frequency support is being  50,0

made by releasing active  49,8

power into the grid (for 
49,6
frequency dips) or by taking 

Frequency (Hz)
active power from the grid  49,4

SVC PLUS FS for 
(frequency rise). 49,2
frequency suppport

• Voltage support in steady state  49,0

and during disturbance 48,8
0 10 20 30 40

• Successful lab‐tests with  Time (s)

1,65 MW
9