Use of DANGER, WARNING, CAUTION, and NOTE
This publication includes, DANGER, WARNING, CAUTION, and NOTE information where appropriate to point out safety
related or other important information.
DANGER Hazards which could result in severe personal injury or death
WARNING Hazards which could result in personal injury
CAUTION Hazards which could result in equipment or property damage
NOTE Alerts user to pertinent facts and conditions
Although DANGER and WARNING hazards are related to personal injury, and CAUTION hazards are associated with
equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational
conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all
DANGER, WARNING, and CAUTION notices.

TRADEMARKS
Advant and Advant Controller are registered trademarks of ABB Asea Brown Boveri Ltd. Switzerland
ABB Master is a registered trademark of ABB Brown Boveri Ltd. Switzerland
HART is a registered trademark of the HART Communication Foundation of Austin, Texas, USA
Windows is a registered trademark of Microsoft Corporation

NOTICE
The information in this document is subject to change without notice and should not be construed as a commitment by ABB
Automation Products AB. ABB Automation Products AB assumes no responsibility for any errors that may appear in this
document.
In no event shall ABB Automation Products AB be liable for direct, indirect, special, incidental or consequential damages of
any nature or kind arising from the use of this document, nor shall ABB Automation Products AB be liable for incidental or
consequential damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without ABB Automation Products AB’s written permission,
and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose.
The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance
with the terms of such license.

3BSE018751D1
Advant Controller 450 – Release Notes
Table of Contents

TABLE OF CONTENTS
Chapter 1 - Introduction
1.1 Executive Summary................................................................................................. 1-1
1.2 How to Use This Document..................................................................................... 1-1
1.3 Version Designation................................................................................................. 1-1
1.4 Revision Record....................................................................................................... 1-2
1.5 Compatibility ........................................................................................................... 1-2
1.6 Restrictions .............................................................................................................. 1-2
1.7 Related Documentation............................................................................................ 1-4

Chapter 2 - Functionality
2.1 Brief Revision Description ...................................................................................... 2-1
2.2 Product Notes........................................................................................................... 2-1

Chapter 3 - Installation
3.1 Installation of Hardware .......................................................................................... 3-1
3.2 Initial Installation of System Software .................................................................... 3-1
3.3 Installation of Revised System Software ................................................................. 3-1
3.4 Upgrading of System Software................................................................................ 3-1
3.5 Transferring of Application Program....................................................................... 3-1
3.5.1 Between Revisions of System Software ................................................. 3-1
3.5.2 Between Versions of System Software ................................................... 3-2
3.5.3 Between MasterPiece 200/1 and Advant Controller 450........................ 3-2

Chapter 4 - Miscellaneous
4.1 Valid User Documentation for Advant Controller 450 *2.2.................................... 4-1

3BSE018751D1 i
Advant Controller 450 – Release Notes
Section 1.1 Executive Summary

Chapter 1 Introduction

1.1 Executive Summary


This document covers program modules QC07 version 3.0 for Advant Controller 450.

1.2 How to Use This Document


The Release Notes provides information not included in the ordinary documentation.
Please read it briefly before any use of the delivered equipment. Study the referred documents in
chapter 3 before installation and start-up of the controller.

1.3 Version Designation


Release date: 1999-04-23
The version designations are:
Program Module Family QC07*3.0/0
Program Modules QC07-BOB41*3.0/0
QC07-BAS41*3.0/0
QC07-LIB41*3.0/0
QC07-LIB42*3.0/0
QC07-FUZ41*3.0/0
QC07-OPF41*3.0/0
QC07-LOS41*3.0/0
QC07-BAT41*3.0/0
QC07-UDP41*3.0/0
QC07-COM41*3.0/0

The program modules are used in


the following products: Advant Controller 450 *2.2/0

3BSE018751D1 1-1
Advant Controller 450 – Release Notes
Section 1.4 Revision Record

1.4 Revision Record

1999-
Release Date
04-23
Advant Controller 450* 2.2/0
Program Module Family
3.0/0
QC07*
QC07-BOB41* 3.0/0
QC07-BAS41* 3.0/0
QC07-LIB41* 3.0/0
Program Modules

QC07-LIB42* 3.0/0
QC07-FUZ41* 3.0/0
QC07-OPF41* 3.0/0
QC07-LOS41* 3.0/0
QC07-BAT41* 3.0/0
QC07-UDP41* 3.0/0
QC07-COM41* 3.0/0
abcdef......* (1) x.y/z
(1) Program modules for specific applications can be loaded on the same program card as
the standard system software. These program modules are not documented in the
standard documentation for the controller, see chapter 4.

1.5 Compatibility

1.6 Restrictions
Software QC07*3.0
Software QC07*3.0 can only be used with CPU PM511V. It can not be used with PM510V.

Advant Station 500 Series OS


Advant Controller 450 with software QC07*3.0 can be used with Advant Station 500 Series OS
with software (AdvaCommand) version 1.4 or later (except for On-line Builder, see below).
AdvaCommand version 1.8 supports all functions in Advant Controller 450 with software
QC07*3.0.

3BSE018751D1 1-2
Advant Controller 450 – Release Notes
Section 1.6 Restrictions

NOTE
On-line Builder must be of version *2.6 or later.

For further information please refer to the AdvaCommand documentation.

MasterView 800/1

MasterView 800/1 supports the Advant Controller 450 with software QC07*3.0 (limited to the
same functionality as found in MasterPiece 200/1*4.0).
NOTE! The adaptive PID controller, PIDCONA, is not supported by MasterView 800/1.

Advant Station 500 Series IMS


Advant Station 500 Series IMS with software version 1.1/1 or later can be used.

Advant Station 100 Series ES


The following software are required:
Windows NT: AMPL Control Configuration*1.6 (or later versions)

Advant Station 500 Series ES


Advant Station 500 Series ES can not be used as engineering station for the Advant Controller
450 with software QC07*3.0.

Advant Station 500 Series OS with option On-line Builder


AdvaCommand version 1.7 or 1.8 can be used as engineering station for the Advant Controller
450 with software QC07*3.0 if the On-line Builder is of version 2.6 or later.

MasterAid 111, 213, 214, 215, 220, 720


These tools can not be used with Advant Controller 450 with software QC07*3.0.

3BSE018751D1 1-3
Advant Controller 450 – Release Notes
Section 1.7 Related Documentation

1.7 Related Documentation


ABB Master Product Guides
- Overview 3BSE 016 140R101
- Advant Controller 450 3BSE 015 953R101
- S100 I/O 3BSE 015 967R101
- S800 I/O 3BSE 015 969R101
Price List, Advant Controller 450 with S100 I/O 3BSE 014 364
Price List, S100 I/O 3BSE 007 519
Price List, S100 I/O with OOCU 3BSE 007 520
Price List, S800 I/O 3BSE 014 365
User documentation is found in Chapter 4.

3BSE018751D1 1-4
Advant Controller 450 – Release Notes
Section 2.1 Brief Revision Description

Chapter 2 Functionality

2.1 Brief Revision Description


Compared to the Advant Controller 450*2.1/3 (system software QC07*2.0/3) corrections in the
system software have been made of problems/errors in the following functions:
• Process Data Communication
Further information is available at Your local ABB representative.

2.2 Product Notes


Start-up of the Controller
During most of the initiation phase (from the ENTER button on the CPU is pressed to controller
is running) the indication “P –” is shown on the CPU displays (on the primary CPU of a
redundant pair). After the initiation phase is passed, the indication on the CPU displays are
changing to “P 1” (or “P 2”). As long as the indication on the CPU is “P –” the engineering
station must not be used since the internal structures of the controller has not yet been fully
established.
The elapsed time between ENTER is pushed and the controller is running (“P 1” or “P 2”) can
vary depending on the I/O configuration.
System without S800 I/O starts normally up within 1 - 2 minutes.
System with S800 I/O can take several minutes more to start-up. The more S800 I/O, the longer
time it takes.

S800 I/O
To keep the total memory consumption in the controller at a low level, the reserved memory
area in the database for S800 I/O modules (after the command DIMDB), is smaller than needed
when the database is fully filled in.
It is therefore recommended to dimension for 1 extra module of each S800 I/O module type (AI,
AO, DI and DO) that are used. If the memory still is too small, it must be redimensioned
(DIMDB) and some more modules added.

Advant Fieldbus 100


For cable redundancy on the twisted pair or optical media, the following rules apply to the
communication interfaces:
– With CI520, CI810 or PM810 cable redundancy is not possible.
– With CI520V1, CI810V1 (with software: CI810SW*1.2/1 or later) or PM810V1
cable redundancy can be used.

3BSE018751D1 2-1
Advant Controller 450 – Release Notes
Section 2.2 Product Notes

Data Set Peripheral


Short cycle times for Data Set Peripheral (DSP) communication (on Advant Fieldbus 100) in
combination with MasterBus 300 communication via SC510 or high load in the main CPU can
influence the DSP communication and cause missing updates of the data base in the Advant
Controller 450.
During these conditions, cycle times for Data Set Peripheral (DSP) communication less than
100 milliseconds are not recommended to use in Advant Controller 450.
If PC elements are used for communication on Advant Fieldbus 100 there is no influence from
MasterBus 300 communication or high load in the main CPU.

PROFIBUS DP
The controller module for PROFIBUS DP, CI541V1, must not be inserted live in a running
submodule carrier (SC510 or SC520). The Advant Controller 450 may stall.
A live insertion can be done if the following sequence is performed:
1. Pull out the submodule carrier from the subrack
2. Placed the CI541V1 on the submodule carrier
3. Then make a live insertion of the submodule carrier with the CI541V1

Program card and redundant CPUs


In an Advant Controller 450 with single CPU it is recommended but not necessary to have the
program card with system software placed at its location in the subrack.
In an Advant Controller 450 with redundant CPUs the situation is different. If the Advant
Controller 450 is configurated for an automatic start-up after a power failure the program card
must be situated in the subrack. At such a start-up the back-up CPU reloads both the system
software (from the program card) and the AMPL application (from the primary CPU). Without
the program card the back-up CPU will not start-up and the redundancy is lost (the primary
CPU starts-up normally).

Submodules
A submodule (for example CI522A, CI543V01, CS513) can be moved on-line from one
position on a carrier to another position (on the same or another carrier), configured in the new
position and started. But it is not possible to move the submodule back to its original position
and start it up again. To use the original position a restart of the controller must be done.

3BSE018751D1 2-2
Advant Controller 450 – Release Notes
Section 3.1 Installation of Hardware

Chapter 3 Installation

3.1 Installation of Hardware


Delivery Binder, tab 11 – Installation Procedures, contains valid installation information for the
delivered equipment.
Please also refer to Advant Controller 450, User’s Guide and if applicable to HART Protocol
Interface, User’s Guide and Intrinsic Safety Support S100 I/O, User’s Guide.

3.2 Initial Installation of System Software


Please refer to Advant Controller 450, User’s Guide.

3.3 Installation of Revised System Software


Please refer to Advant Controller 450, User’s Guide.

3.4 Upgrading of System Software


Upgrade of the system software from a previous version (program modules QC02*7.0/x *8.0/x
or *9.0/x) to this version (program modules QC07*3.0) is done by installing the new system
software according to Advant Controller 450, User’s Guide and by transferring the application
program as described below.

NOTE
It is necessary to change the CPU module to PM511V. Depending on which
function to be used after upgrading, also other hardware modules must be
exchanged. Further information is available at Your local ABB representative.

3.5 Transferring of Application Program

3.5.1 Between Revisions of System Software


Transfer of application program between different revisions of the system software (for
example from program modules QC07*3.0/x to program modules QC07*3.0/y) requires
normally Source Code Handling.
Please refer to Advant Controller 450, User’s Guide.

3BSE018751D1 3-1
Advant Controller 450 – Release Notes
Section 3.5.2 Between Versions of System Software

3.5.2 Between Versions of System Software


Transfer of application program between different version of the system software (for example
from program modules QC02*8.0/x to program modules QC07*3.0/y) requires Source Code
Handling.

NOTE
Some DB elements have been changed between the QC02 and the QC07 versions of the system
software. Corresponding corrections must be done in the source code before the application can
be loaded.
Please refer to Advant Controller 450, User’s Guide.

3.5.3 Between MasterPiece 200/1 and Advant Controller 450


Please refer to Upgrading the MasterPiece 200/1, User’s Guide
or to Your local ABB representative.

3BSE018751D1 3-2
Advant Controller 450 – Release Notes
Section 4.1 Valid User Documentation for Advant Controller 450 *2.2

Chapter 4 Miscellaneous

4.1 Valid User Documentation for Advant Controller 450 *2.2

Table 4-1. Manuals for Configuration/Application Building

Document Ordering No. Actual revision


Advant Controller 450, User’s Guide 3BSE 002 415R601 –
PC Elements AC 400 Series, Reference Manual 3BSE 002 418R501 –
Fuzzy Control with FUZZYCON, User’s Guide 3BSE 012 693R0001 –
User Defined PC Elements, User’s Guide (1) 3BSE 009 739R0001 –
Object Support via Advant Fieldbus 100 3BSE 014 762R0001 –
Data Base Elements AC 400 Series Reference Manual 3BSE 014 819R201 –
AMPL Application Building, Reference Manual 3BSE 003 841R0001 –
AMPL Configuration AC 400 Series, Reference Manual 3BSE 002 417R0501 –
Functional Units Part 1, Summary and Common Properties, 3BSE 003 849R0001 –
User’s Guide
Functional Units Part 2, AI, AO, DI, DO, User’s Guide 3BSE 003 850R0001 –
Functional Units Part 3, SEQ, GROUP, User’s Guide 3BSE 003 851R0001 –
Functional Units Part 4, PIDCON, RATIOSTN, MANSTN, 3BSE 003 852R0001 –
User’s Guide
Functional Units Part 5, GENCON, GENBIN, GENUSD, 3BSE 003 853R0001 –
User’s Guide
Functional Units Part 6, MOTCON, VALVECON, 3BSE 003 854R0001 –
User’s Guide
Functional Units Part 7, PIDCONA, User’ Guide 3BSE 002 433R0101 –
Functional Units Part 8, DRICONS, User’s Guide 3BSE 012 570R0101 –
Function Units Part 9, DRICONE, User’s Guide 3BSE 013 947R0001 –
MP 280 Application Notes 7650 060-201 2
(1) Software on a DDS Cassette

3BSE018751D1 4-1
Advant Controller 450 – Release Notes
Section 4.1 Valid User Documentation for Advant Controller 450 *2.2

Table 4-2. Manuals for Installation

Document Ordering No. Actual revision


Elektroniska apparater (in Swedish only) 3BSE 002 428R0002 –
Interference-Free Electronics, Design and applications 3BSE 000 877R0001 –
Advant OCS, Installation Rules, Reference Manual 3BSE 009 178R0001 –
Terminal Diagram Forms 3BSE 014 083R0001 –

Table 4-3. Manuals for Optional Functions

Document Ordering No. Actual revision


S100 I/O Hardware, Reference Manual 3BSE 002 413R0201 –
S800 I/O, User’s Guide 3BSE 008 878R0201 –
HART Protocol Interface, User’s Guide 3BSE 008 619R0001 –
Intrinsic Safety Support S100 I/O, User’s Guide 3BSE 008 431R0001 –
Weighing, User’s Manual 7650 141-201 1
EXCOM, User’s Guide 3BSE 003 835R0001 –
MasterView 320, User’ Guide 3BSE 003 836R0001 A
MasterFieldbus and S400 I/O, User’s Guide 3BSE 003 837R0001 –
MasterNet, User’s Guide 3BSE 003 839R0101 –
GCOM Multidrop, User’s Guide 3BSE 000 165R0001 –
RCOM, AC 400 Series, User’s Guide 3BSE 000 532R0001 A
MultiVendor Interface with CI532V02, Modbus, 3BSE 000 533R0001 –
AC 400 Series, User’s Guide
MultiVendor Interface with MVB+CI534V02, Modbus, 3BSE 010 719R0001 –
AC 400 Series, User’s Guide
MultiVendor Interface, Siemens 3964(R), AC 400 Series, 3BSE 000 535R0001 –
User’s Guide
MultiVendor Interface, Allen-Bradley DF1, AC 400 Series, 3BSE 013 712R0001 –
User’s Guide
Advant Fieldbus 100, User’s Guide 3BSE 000 506R701 –
PROFIBUS-DP, User’s guide 3BSE 016 040R0001

3BSE018751D1 4-2
Advant Controller 450 – Release Notes
Section 4.1 Valid User Documentation for Advant Controller 450 *2.2

Table 4-3. Manuals for Optional Functions (Continued)

Document Ordering No. Actual revision


Positioning System, User’s Manual 7650 069-201 0
FCB Type Circuits Drives Objects 3BSE 013 131R0101 –

Table 4-4. Special Manuals

Document Ordering No. Actual revision


Upgrading the MasterPiece 200/1, User’s Guide 3BSE 006 727R0101 –

3BSE018751D1 4-3