Chapter – 2
Controllers used in process control

1 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Basic control modes
 Proportional-integral-derivative (PID) control and on-off control
are the predominant types of feedback controllers used in the
process industries.
 The operation of the controller may be
vDiscontinuous (e.g. ON/OFF) Modes
vContinuous Modes (Smooth variation)
 Proportional Control Mode
 Integral Control Mode
 Derivative Control Mode

2 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
vComposite Control Modes
 Proportional-Integral Mode (PI)
 Proportional-Derivative Mode (PD)
 Proportional- Integral-Derivative Mode (PID)
vON/OFF controller
Ø Is the simplest and cheapest control mode.
Ø on-off controllers are less widely used than PID
Ø it can be said that the output is either 0% or 100% for errors
less than zero or more than zero.

3 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Continuous modes
 The output of the controller changes smoothly in response to the
error or rate of change of error.
Ø Proportional Control Mode
Ø Integral control Mode
Ø Derivative control mode
Ø A combination of one or more of the above modes.
vProportional control mode
 In feedback control, the objective is to reduce the error signal
to zero where
e (t ) = Ysp ( t) -Ym (t )

4 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont..
For proportional control, the controller output is proportional
to the error signal. This mode can be expressed by the equation

Where
P = Controller output
Kp = Proportional gain between error & controller output
e(t) = process error
Po = controller output with no error(%)

5 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont.…
q The key concepts behind proportional control are that
Ø The controller gain can be adjusted to make the controller output
changes as sensitive as desired to deviations between set point and
controlled variable.
Ø The sign of Kp can be chosen to make the controller output increase
(or decrease) as the error signal increases
An inherent disadvantage of proportional-only control is that a
steady-state error (or offset) occurs after a set-point change or a
sustained disturbance.

6 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont.…
 As the gain of the proportional gain is increased the system
responds faster to changes in set-point but becomes progressively
under damped and eventually unstable.
v Integral control mode
 The offset error of the proportional mode occurs because the
controller cannot adapt to process load changes.
 In other words, the zero-error output is a fixed value.
 The integral mode eliminates this problem by allowing the
controller to adapt to changing external conditions by changing
the zero-error output.

7 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333

 For integral control action, the controller output depends on the


integral of the error signal over time.
 If the error makes random oscillations above and below zero, the
net sum will be zero.
v Integral mode has the following characteristics
 The rate of change of controller output depends error and the size
of the gain.
 If the error is zero, the output stays fixed at a value equal to what it
was when the error went to zero.
 If the error is not zero, the output will begin to increase or
decrease at a rate of KI
8 Process control fundamentals: by Fekadu G. 11/14/2017
ADU ECEg 4333
Cont.…
Ø the integral controller is seldom used by itself, because little
control action takes place until the error signal has persisted for
some time.
Ø In contrast, proportional control action takes immediate corrective
action as soon as an error is detected.
Ø Consequently, integral control action is normally used in
conjunction with proportional control as the proportional-integral
(PI) controller:

9 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v Derivative control mode
Ø The function of derivative control action is to anticipate the future
behavior of the error signal by considering its rate of change.

Ø Derivative controller action responds to the rate at which the error


is changing.
Ø Derivative action is not used alone because it provides no output
when the error is constant.

10 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont..
q Derivative mode has the following characteristics
Ø If the error is zero & constant in time, the mode provides no output.
Ø If the error is changing in time, the mode contributes an output of
“Kd” percent for every 1%-per-second rate of change of error.
Ø By providing anticipatory control action, the derivative mode tends to
stabilize the controlled process.
Ø Thus, it is often used to counteract the destabilizing tendency of the
integral mode
Ø Derivative control action also tends to improve the dynamic response
of the controlled variable by the settling time, reducing the time it
takes to reach steady state.

11 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v Composite control modes
 In industrial processes it is expedient to combine several basic
modes of control to gain the advantages of the modes and eliminate
the limitations of the modes.
q The various composite modes are:
 Proportional-Integral Mode (PI)
 Proportional-Derivative Mode (PD)
 Three-Mode controller (PID)

12 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v PI controller

 The lack of derivative action may make the system steadier in the
steady state in the case of noisy data.
 This is because derivative action is more sensitive to higher-
frequency terms in the inputs.

13 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v PI controller mode has the following characteristics
 one-to-one correspondence of the proportional mode is available
 The integral mode eliminates the inherent offset.
 If the error is not zero, the proportional term contributes a
correction, and the integral term begins to increase or decrease the
accumulated value
 This mode can be used in systems with frequent or large load
changes.
 During the start of a batch process, the integral action causes
considerable overshoot of the error and output before settling to
the operation point.

14 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v PD controller
Ø The stability and overshoot problems that arise when a
proportional controller is used at high gain can be mitigated.

qPD controller mode has the following characteristics


 The system cannot eliminate the offset of proportional controllers.
 It can, however, handle fast process load changes as long as the
offset error is acceptable.

15 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
v PID controller
Ø PD control deals neatly with the overshoot and ringing problems
associated with proportional control it does not cure the problem
with the steady-state error.

Ø P depends on the present error, I on the accumulation of past errors,


and D is a prediction of future errors, based on current rate of
change.

16 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333

17 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont..

18 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q Features of PID controllers
Reset Windup
Ø An inherent disadvantage of integral control action is a
phenomenon known as reset windup.
Ø When a sustained error occurs, the integral term becomes quite
large and the controller output eventually saturates.
Ø Further buildup of the integral term while the controller is
saturated is referred to as reset windup or integral windup.

19 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q Derivative Kick
 One disadvantage of the previous derivative controller is that a
sudden change in set point (and hence the error) will cause the
derivative term momentarily to become very large and thus
provide a derivative kick to the final control element.
q Reverse or Direct Action
Ø A controller operates with direct action when an increasing value
of the controlled variable causes an increasing value of the
controller output.
Ø A controller operates with reverse action when an increase in
controlled variable causes a decrease in controller output.

20 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Importance of manual controller mode
Ø Controllers are designed to operate in automatic mode, however,
in certain situations, the plant operator may decide to override the
automatic mode and adjust the controller output manually.
Ø This manual mode of controller operation is very useful during a
plant start-up, shutdown, or emergency situation.
Ø A manual/automatic switch

21 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q 2.2 PID controller design, tuning and troubleshooting
2.2.1 PID controller design
Performance criteria for Closed-loop systems
Ø The function of a feedback control system is to ensure that the
closed-loop system has desirable dynamic and Steady-state
response characteristics.

22 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q closed-loop system to satisfy the following performance criteria:
 The closed-loop system must be stable
 The effects of disturbances are minimized, providing good
disturbance rejection
 Rapid, smooth responses to set-point changes are obtained, that is,
good set-point tracking
 Steady-state error (offset) is eliminated
 Excessive control action is avoided

23 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q Model Based controller design
 If it is possible to design a satisfactory mathematical model of a
process, then it is possible to design a controller based on the
model.
q Direct Synthesis Method
 The controller design is based on a process model and a desired
closed loop transfer function.

24 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
q 2.2.2 PID controller tuning
v PID tuning is the process of finding the values of proportional,
integral, and derivative gains of a PID controller to achieve desired
performance and meet design requirements.
 During control system design, the initial controller settings are
calculated based on process knowledge and control objectives.
on-site adjustment is referred
Ø on-line tuning
Ø field tuning
Ø controller tuning.

25 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333

q Continuous Cycling Method (Ziegler and Nichols)


The tuning technique is based on the following trial-and-error procedures:
I. After the process has reached steady state, eliminate the I & D control
action
II. Set Kc equal to a small value (e.g 0.5) and place the controller in the
automatic mode.
III. Introduce a small, momentary set-point change so that the controlled
variable moves away from the set point.
IV. Then Calculate the PID controller settings using the Ziegler-Nichols
(Z-N) tuning relations using the relations as shown in the table below.
V. Evaluate the Z-N controller settings by introducing a small set-point
change and observing the closed-loop response.

26 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
Cont.

27 Process control fundamentals: by Fekadu G. 11/14/2017


ADU ECEg 4333
qcontinuous cycling method has several major disadvantages:
 It can be quite time-consuming . The long experimental tests
may result in reduced production or poor product quality.
 In many applications, continuous cycling is objectionable,
because the process is pushed to the stability limits.
 This tuning procedure is not applicable to integrating or open-
loop unstable processes, because their control loops typically
are unstable at both high and low values of Kc, while being
stable for intermediate values.

28 Process control fundamentals: by Fekadu G. 11/14/2017