Job

Name: SQ-100-A Cut Sheet


Tag: MK-1
Quantity: 1
Printed Date: December 14, 2018

Model: SQ-100-A
Direct Drive Centrifugal Inline Fan
Standard Construction Features: Galvanized steel housing (optional aluminum) with duct collars.
Centrifugal backward inclined aluminum wheel. Direct driven motor in the air stream.

1.2 0.3
Fan Configuration 1,7 2
F

5
Drive type Direct 1 RP 0.25
M

Brake Horsepower (BHP)


Static Pressure (in. wg)
0.8 0.2

rea
Performance

d a
Requested Volume (CFM) 1,000 0.6 0.15

de a
Actual Volume (CFM) 1,140

sh
i n
Total External SP (in. wg) 0.65 0.4 0.1

te em
Fan RPM 1,725 ra
st
pe

Operating Power (bhp) 0.25 0.2 Sy 0.05


t o

o
Startup Power (bhp) 0.25
n

Do
Air Stream Temp (F) 70 0 0
Start-up Temp (F) 70 0 3 6 9 12 15
Air Density (lbs/ft^3) 0.075 Volume (CFM) x 100
Elevation (ft) 100 Static Pressure Calculations
Fan curve
Static Efficiency (%) 47 External SP 0.5 in. wg
Brake horsepower curve
Outlet Velocity (ft/min) 870 Direct Drive RPM Adjustment 0.15 in. wg
Operating Point SP Total External SP 0.65 in. wg
Operating Bhp point
Motor Max system curve
System curve
Enclosure ODP
Size (hp) 1/4
V/C/P 115/60/1
NEC FLA (Amps) 5.8

Sound
Octave Bands (hz) LwA dBA Sones
62.5 125 250 500 1000 2000 4000 8000
Inlet 69 74 74 72 66 64 59 54 73 62 10.6

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures performed in
accordance with AMCA Publication 211 and AMCA Publication 311 and comply with
the requirements of the AMCA Certified Ratings Program.Performance certified is for
installation type B: Free inlet, Ducted outlet.Power rating (BHP/kW) does not include
transmission losses.Performance ratings do not include the effects of
appurtenances (accessories).The inlet sound ratings shown are loudness values in
fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard
301. Values shown are for installation type B: free inlet hemispherical sone levels.
dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal
for Sound applies to inlet sone ratings only. Radiated (casing) sound data is the
sound generated through the fan housing when the fan is ducted on both the inlet
and outlet.
FLA - based on tables 150 or 148 of National Electric Code 2002. Actual
motor FLA may vary, for sizing thermal overload, consult factory.

Page 1 of 2 Version 2.0.0, December 2018


Job Name: SQ-100-A Cut Sheet
Tag: MK-1
Quantity: 1
Printed Date: December 14, 2018

Dimensions and Weights

Label Value Description


- 56 Weight w/o accessories (lbs)
A 17 Overall Height (in)
B 17 Overall Width (in)
C 21 Overall Length (in)
- 14 Inlet Width (in)
- 14 Inlet Height (in)
- 14 Outlet Width (in)
- 14 Outlet Height (in)

*All dimensions are in inches.


Page 2 of 2 Version 2.0.0, December 2018